Fire Alarm Systems | FPE-7039 MUX expansion module
FPE-7039 MUX expansion module
www.boschsecurity.com
u Provides two Class B multiplex buses (supports
addresses 9 to 128, 129 to 255)
u Provides one Class A multiplex bus (supports
addresses 9 to 128)
The FPE‑7039 MUX expansion module is designed to
enhance the conventional features of the FPD‑7024,
D7024 or DS9400 FACPs. The module connects
directly to the FACP and results in a total of up to 255
addressable points. The module also increases the
number of relay outputs (to 58 on the D7024 control
panels and 59 on FPD 7024 control panels). It adds an
additional 400 events to the history buffer for a total
of 499 non volatile events. It also allows for up to 100
system users (an addition of 84 PINs from the base
system).
The module can be programmed remotely from a PC
using the RPS Remote programming software.
Notice
The D7024 and DS9400 panels are listed to
UL864, 8th edition.
u Allows system to support conventional and
addressable devices at the same time
u Scales from a conventional to an addressable
system without changing the control panel
u Increases event history buffer to 499 events
Installation/configuration notes
Compatible Products
The following products are compatible with the
FPE‑7039 MUX expansion module:
Category Product ID Product Description
Control
Panels
FPD-7024 Addressable and conventional FACPs
D7024* Addressable and conventional FACPs
DS9400* Control panels
Modules D343* MUX duct detector housing with
auxiliary relay
D7042 MUX remote module, 8-input class B
D7042B MUX module w/ metal enclosure, 8-
input
Certifications and approvals
Region Certification
USA UL UOJZ: Control Units, System (ANSI/UL
864)
CSFM see our website
D7044 MUX single-input module, 12V
D7044M MUX mini single-input module, 12V
D7050 MUX smoke head
D7050DH MUX duct smoke head
2 | FPE-7039 MUX expansion module
D7050TH MUX smoke head w/ fixed heat
(135°F)
D7050-B6 MUX base, 2-wire
D7052 MUX dual-input module, 12V
D7053 MUX input/output module, 12V
FLM-7024-ISO MUX bus expansion module
FMM-7045 MUX manual station, single-action, red
FMM-7045-D MUX manual station, double-action,
red
*Legacy product not available for purchase. Legacy products were
investigated to comply only to UL864 8th edition or earlier.
Mounting Considerations
The module mounts onto the control panel board
inside of the control panel's enclosure using connector
pins. The Input\Output board mounts to the inside
wall of the enclosure for field wiring.
Wiring Considerations
Refer to control panel’s installation guide for
additional wiring requirements.
Notice
If used in fire applications, a minimum of 18 AWG
(ISO 0.75 mm2) is required.
Technical specifications
Environmental
Environment Indoor, dry
Power
Current Draw
Alarm
Load, Class A
Load, Class B
Standby
Bus Voltage 8.5 V to 13 V
Wire Resistance (maximum) 50 Ω at +20°C (+68°F), depends
190 mA maximum
100 mA maximum
100 mA maximum for each bus
190 mA maximum
on method and wire sized used
Ordering information
FPE-7039 MUX expansion module
It enhances the features of the FACPs. It increases the
number of addressable points to 247. It increases the
number of relay outputs to 58 on the D7024/DS9400
or 59 on the FPD‑7024. It increases number of events
on the history buffer to 499.
Order number FPE-7039
Wire
resistance
Wire length 5950 ft (1810 m) , depends on wire size and number
Wire
capacitance
Notice
Do not use shielded wire. Twisted-pair wire is not
recommended, but is acceptable if wire length is
reduced by 50%.
50 Ω at +20°C (+68°F), depends on method and wire
sized used
of devices
< 0.12 μF (max per bus)
Parts included
Quantity Component
1 FPE‑7039 board
1 FPE‑7039 Input/output board
3 Standoffs for Input/output board
4 Standoffs for FPE‑7039 board
1 Literature pack