Fire Alarm Systems | FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module
FPE‑1000‑SLC Signaling Line Circuit
Plug‑in Module
www.boschsecurity.com
u Signaling Line Circuit (SLC) is power-limited and
supervised
The FPE‑1000‑SLC Signaling Line Circuit Plug‑in
Module provides a Signaling Line Circuit (SLC) for
connection of analog devices to the FPA‑1000 Analog
Addressable Fire Panels. It is mandatory equipment
which installs at the top position on the main board in
the fire panel. A second FPE-1000-SLC Plug-in Module
can be installed as an option in the position below the
first SLC board. The bottom position can be equipped
with an optional FPE‑1000‑CITY City Tie Plug‑in
Module. The plug‑in modules connect directly to the
main board.
Signaling Line Circuits can be wired as Class A Style 6
or 7 or Class B Style 4 circuits. Class A configuration is
recommended because this allows the system to poll
the circuit in both directions, ensuring circuit
operation in the event of a single break in the wiring.
Each SLC is power‑limited and supervised.
u Configurable as one Class A Style 6 or 7 or two
Class B Style 4 circuits
u Up to 254 detectors and modules, or 127 analog
sounder bases in combination with suitable
detectors
Functions
Sounder base addressing
For addressing a detector/ sounder base combination,
addresses 1 through 127 are available for the detector
and 128 through 254 for the sounder base. The
sounder base will automatically be addressed based
on the detector’s address (detector’s address + 127)
Certifications and approvals
Region Certification
USA UL FSZI: Emergency Alarm System Control
CSFM see our website
FDNYCoA
Units (ANSI/UL 2017) and UOJZ: Control Units, System (ANSI/UL 864)
#6101
2 | FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398
www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
latam.boschsecurity@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice
2690605707 | en, V6, 24. Jul 2014
Installation/configuration notes
Wiring Considerations
Use plain wire. Twisted pair or shielded wire can be
used in harsh environments, but overall wire length
must be reduced. Observe maximum circuit resistance
of 50 Ω.
Parts included
Quant. Component
1 FPE‑1000‑SLC module
1 Literature – Installation Guide
Technical specifications
Electrical
Line Voltage: Nominal: 39 VDC
Range: 29 VDC to 40 VDC)
Line Current: 204 mA (per FPE-1000-SLC):
Circuit Resistance: < 50 Ω
Circuit Capacitance: < 1 μF
Circuit Inductance: < 1 mH
Configuration (per
FPE-1000-SLC):
One or two Class B Style 4, or one
Class A Style 6 or 7
Wire Gauge: 12 AWG to 18 AWG (ISO 4 mm2 to
0.75 mm2)
Environmental
Environment Friendly: RoHS compliant
Relative Humidity: Up to 95%, non-condensing
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Temperature (storage): -4°F to +140°F (-20°C to +60°C)
Ordering information
FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module
Provides a Signaling Line Circuit (SLC) for connection
of analog devices to the FPA‑1000 Analog Addressable
Fire Panels
Order number FPE-1000-SLC