Fire Alarm Systems | FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module
FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module
www.boschsecurity.com
u Signaling Line Circuit (SLC) is power-limited and
supervised
The FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module provides a Signaling Line Circuit (SLC) for connection of analog devices to the FPA‑1000 Analog Addressable Fire Panels. It is mandatory equipment which installs at the top position on the main board in the fire panel. A second FPE-1000-SLC Plug-in Module can be installed as an option in the position below the first SLC board. The bottom position can be equipped with an optional FPE‑1000‑CITY City Tie Plug‑in Module. The plug‑in modules connect directly to the main board. Signaling Line Circuits can be wired as Class A Style 6 or 7 or Class B Style 4 circuits. Class A configuration is recommended because this allows the system to poll the circuit in both directions, ensuring circuit operation in the event of a single break in the wiring. Each SLC is power‑limited and supervised.
Class B Style 4 circuits
u Up to 254 detectors and modules, or 127 analog
sounder bases in combination with suitable detectors
Functions
Sounder base addressing
For addressing a detector/ sounder base combination, addresses 1 through 127 are available for the detector and 128 through 254 for the sounder base. The sounder base will automatically be addressed based on the detector’s address (detector’s address + 127)
Certifications and approvals
Region Certification
USA UL FSZI: Emergency Alarm System Control
CSFM see our website
FDNY­CoA
Units (ANSI/UL 2017) and UOJZ: Con­trol Units, System (ANSI/UL 864)
#6101
2 | FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice 2690605707 | en, V6, 24. Jul 2014
Installation/configuration notes
Wiring Considerations
Use plain wire. Twisted pair or shielded wire can be used in harsh environments, but overall wire length must be reduced. Observe maximum circuit resistance of 50 Ω.
Parts included
Quant. Component
1 FPE‑1000‑SLC module
1 Literature – Installation Guide
Technical specifications
Electrical
Line Voltage: Nominal: 39 VDC
Range: 29 VDC to 40 VDC)
Line Current: 204 mA (per FPE-1000-SLC):
Circuit Resistance: < 50 Ω
Circuit Capacitance: < 1 μF
Circuit Inductance: < 1 mH
Configuration (per FPE-1000-SLC):
One or two Class B Style 4, or one Class A Style 6 or 7
Wire Gauge: 12 AWG to 18 AWG (ISO 4 mm2 to
0.75 mm2)
Environmental
Environment Friendly: RoHS compliant
Relative Humidity: Up to 95%, non-condensing
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Temperature (storage): -4°F to +140°F (-20°C to +60°C)
Ordering information
FPE‑1000‑SLC Signaling Line Circuit Plug‑in Module
Provides a Signaling Line Circuit (SLC) for connection of analog devices to the FPA‑1000 Analog Addressable Fire Panels
Order number FPE-1000-SLC
Loading...