Fire Alarm Systems | FPC‑7034 Four-Point Expander
FPC‑7034 Four-Point Expander
www.boschsecurity.com
u Adds four Class B (Style B) or Class A (Style D)
initiating circuits to the FPD‑7024 FACP
u For use with normally‑open (NO) or normally‑closed
(NC) alarm contacts
The FPC‑7034 Four-point Expander doubles the
number of alarm initiating device circuits on the
FPD‑7024 Fire Alarm Control Panel (FACP). These
circuits are identical to the circuits on the FACP.
This plug‑in module is automatically recognized by the
control panel's firmware when power is restored to
the system.
Certifications and approvals
Region Certification
USA UL UOJZ: Control Units, System (ANSI/UL
864)
FM FPC-7034
CSFM see our website
FDNY-
#6173
CoA
Installation/configuration notes
Compatible Products
The following products are compatible with the
FPC‑7034 Four-point Expander:
u Compatible with two‑wire or four‑wire smoke
detectors
u Up to 20 two‑wire smoke detectors per circuit
u Easy installation due to plug‑in design and screw
terminal circuit connections
Category Product ID Product Description
Control
FPD‑7024 Addressable or conventional FACP
Panels
Detectors For a list of compatible smoke detectors, see the
FPD‑7024 Smoke Detector Compatibility List
Technogram.
Notice
When four‑wire smoke detectors are used, power
must be supplied to the detectors from either the
control panel or an external power source.
Mounting Considerations
The FPC‑7034 mounts on the FPD‑7024 control board,
just to the right of the keypad. Use the four nylon
stand‑offs supplied with the expander.
Initiating Circuit Wiring
Circuit connection for the expansion initiating circuits
is identical to the on‑board circuit configuration. For
wiring details, see the FPD‑7024 Installation Guide .
Install a supplied EOL resistor at the end of each
wiring run.

2 | FPC‑7034 Four-Point Expander
Parts included
Quant. Component
1 Four-loop expander board
4 2.21 kΩ End‑of‑Line (EOL) Resistors (P/N: 25899)
4 Stand‑offs (P/N: 26510)
1 Literature pack
Technical specifications
Environmental Considerations
Environment: Indoor, dry
Relative Humidity: Up to 95%, non‑condensing
Temperature (operating): +32°F to +122°F (0°C to +50°C)
Mechanical Properties
Dimensions
(HxWxD):
2.0 in. x 4.5 in. x 1.3 in.
(5.1 cm x 11.4 cm x 3.3 cm)
Response Time: Choice of fast (500 ms) or programmable from
1 sec to 89 sec
Power Requirements
per initiating circuit:
Alarm Current (short circuit): 40 mA maximum
Alarm Current (threshold): >25 mA
Detector Standby Current (total): 3 mA maximum
Loop Supervision Current: 8.0 mA to 15.0 mA
Trouble Current Threshold: <7 mA
Voltage (supply): 18.0 VDC to 25.5 VDC
per FPC‑7034 module:
Current (standby): 60 mA maximum
Current (alarm): 160 mA maximum
Ordering information
FPC‑7034 Four-Point Expander
The FPC‑7034 adds four Class B (Style B) or two
Class A (Style D) initiating circuits to the FPD‑7024
FACP. This plug‑in module is automatically recognized
by the control panel's firmware when power is
restored to the system.
Order number FPC-7034

3 | FPC‑7034 Four-Point Expander
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398
www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
latam.boschsecurity@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice
2692182923 | en, V6, 19. Dec 2014