Fire Alarm Systems | FPD‑7024 Fire Alarm Control Panels
FPD‑7024 Fire Alarm Control Panels
www.boschsecurity.com
u Four initiating zones (expandable to eight); up to 20
two‑wire smoke detectors per zone
u Programmable through keypads or remote
programming software (RPS) through a Conettix
interface module
The FPD‑7024 Fire Alarm Control Panels (FACPs) can
be used in commercial and public building
applications such as schools, universities,
manufacturing plants, and health care facilities. They
are listed by UL for central station, local, auxiliary, and
remote station systems.
The FPD‑7024 FACPs support four on‑board initiating
zones that can be expanded to eight using the
FPC-7034. Each initiating zone supports two‑wire and
four‑wire detectors configurable as Class A , Style D or
Class B, Style B loops. Each zone can support up to 20
two‑wire detectors, or any number of four‑wire
detectors depending on available power. Each FACP
has a built‑in digital fire alarm communicator
transmitter (DACT).
Enhance the FPD‑7024 conventional system features
by adding a D7039 Multiplex Expansion Module.
Adding a D7039 Multiplex Expansion Module to the
FPD‑7024 turns the conventional FACP into an
addressable FACP. The D7039 adds up to 247
addressable points to the base system and adds an
additional 400 events to the history buffer for a total
of 499 events. The D7039 also increases the number
of programmable relay outputs from 19 to 59 and
expands system users to 100.
u Two notification appliance circuits (NACs) on board
with a shared internal regulated 24 VFWR, 4 A NAC
power supply
u Easily converts to addressable with the addition of a
D7039 Multiplex Expansion Module
Functions
Notification Appliance Circuits (NACs)
Two Class A, Style Z or Class B, Style Y NACs provide
up to 4 A of regulated 24 VFWR power to operate
horns, strobes, bells, and other notification
appliances. Each NAC can be programmed to provide
Temporal Code 3, California March, steady, pulsed,
and synchronized output for Wheelock, Gentex, or
System Sensor notification appliances.
User Interface
A viewing port in the locked control panel enclosure
door shows the system status light‑emitting diodes
(LEDs) and liquid‑crystal display (LCD) while
maintaining system keypad security. Unlocking the
enclosure door provides access to the system controls
for silencing off‑normal conditions, zone bypassing,
detector resetting, testing, other fire functions, and
programming. These functions are also available on all
FMR‑7033 LCD Keypads connected to the system.
Organized Event Display
Sorts alarm, trouble, and supervisory events into
categories and allows scrolling through specific
events.
2 | FPD‑7024 Fire Alarm Control Panels
History Buffer
The system stores events in a 99‑event history buffer.
Notice
The number of events that can be stored in the
history buffer increases to 499 with the addition
of a D7039 Multiplex Expansion Module.
Central Station Reporting
The FPD-7024 FACPs send reports to two telephone
numbers (or, if a Conettix interface module is
installed, IP addresses) to an appropriate Conettix
receiver at the central station with full single, double,
and backup reporting. The panel supports
communication in BFSK, SIA, Contact ID, Modem IIIa2,
and 4/2 or 3/1 Tone Bursts.
Dirty Smoke Detector Monitoring
All on‑board zones and FPC‑7034 zones are
continuously monitored for smoke detectors signaling
a dirty condition using the Bosch Chamber Check
feature and CleanMe protocol. If a detector's smoke
chamber is dirty, the detector sends a CleanMe signal
on the two‑wire loop or a dirty detector signal on the
addressable loop. The control panel annunciates that
there is a dirty detector on the loop or the address.
The Chamber Check feature signals a dirty smoke
chamber using the LED on the detector head.
Accessories
The FPD‑7024 enclosure has space for additional
accessory modules and two D1218 (18 Ah) batteries
or two D126 (7 Ah) batteries.
Certifications and approvals
RegionCertification
USAULUOJZ: Control Units, System (ANSI/UL
FMFPD-7024
CSFMsee our website
FCCESVAL04B7024
FDNYCoA
864)
#6173
Installation/configuration notes
Compatible Products
The following products are compatible (refer to the
product datasheet for country‑specific certifications/
approvals) with the FPD‑7024 FACP:
CategoryProduct ID and Description
Batteries and
Power Supplies
D126 12 V, 7 Ah battery
D1218 12 V, 18 Ah battery
FPP‑RNAC‑8A‑4C Remote NAC power supply
DetectorsFor two‑wire detector compatibility, refer to
Dimensions (HxWxD):20.8 in. x 15 in. x 4.3 in. (52.8 cm x
38.1 cm x 10.9 cm)
Material:Cold-rolled steel
Base: 18 gauge (1.2 mm)
Cover: 19 gauge (1.1 mm)
Indicating Device Circuits (IDC)
Current:44 mA maximum per loop
Line resistance:150 Ω
Voltage:24 VDC nominal
Outputs
NAC:24 VDC nominal, 4 A maximum
On-board Relays:Three Form C contacts rated at 5 A, 28 VDC
Off-board Relays:Up to two D7035 Octal Relay Modules with each
providing eight Form C relay outputs; contacts
rated at 5 A, 28 VDC
In an addressable system, up to 20 D7053
Multiplex Input-Output Modules are allowed per
bus for a total of 40
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398
www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
latam.boschsecurity@bosch.com
www.boschsecurity.com
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.
Ordering information
FPD-7024 FACP
Four detector zones (expandable to eight); up to 20
two wire smoke detectors per zone
Order number FPD-7024
FPD-7024-LC FACP without Enclosure and Transformer
Four detector zones (expandable to eight); up to 20
two wire smoke detectors per zone
Order number FPD-7024-LC
FPD-7024-LT FACP without Transformer
Four detector zones (expandable to eight); up to 20
two wire smoke detectors per zone. Available only in
Latin America.
Order number FPD-7024-LT
Accessories
FPC-7024-FK1 Basic Fire Panel Kit
Four-zone FACP with one four-wire photoelectric
smoke detector and base with EOL relay, one two‑wire
horn/strobe, one manual station, and two RJ31X
phone jacks with dual modular phone cords.
Order number FPC-7024-FK1
D102 Replacement Key
Replacement key (#1358) for the D101 lock.
Order number D102