EVX-25E / EVX-50E / EVX-100E
EXPANDER
INSTALLATION INSTRUCTIONS
The EVX-25E/ EVX-50E / EVX-100E is a self contained amplifier, tone generator, power supply and supervisory interface. It is designed to be used in conjunction with the EVAX 25/
50 /100 to provide additional speaker output power. It may also be used stand-alone in conjunction with a Fire Alarm Control Panel to provide voice evacuation where an automatic message is not desired.
Installation and operation is identical to the EVAX 25/ 50 /100 (see Installation Instructions P/N 1-5001 Rev. D). With the exception that no digital message is present. When used in conjunction with the EVAX 25/ 50/100 the Expander will act as a slave reproducing the tone and message generated by the master. When used as a stand-alone, the Expander will connect to the FACP exactly as the EVAX 25/ 50/100 does to provide automatic tone in alarm and voice override capability.
All terminal designations and volume controls are identical to the EVAX 25/ 50/ 100. One exception is that on the Expander SN1 determines Tone, Master/Slave, Battery and
Microphone supervision. There is no SN2.
Factory defaults are: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
Expander as Slave |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
1 |
= OFF |
Temporal Whoop Signal |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
2 |
= OFF |
|
|
|
|
|
|
|
|
Switch Network Detail |
|||||||
3 |
= OFF |
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
1 |
8 |
|
OFF = 0 (UP) |
||||||||||
|
|
|
|
|
|
|
|||||||||||
4 |
= OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON = 1 (DOWN) |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
5 |
= OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
6 |
= OFF |
Slave |
(ON = Master setting) |
SN1 |
Tone Selection |
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||||
7 |
= ON |
Battery connected |
(OFF = No Batteries) |
|
|
|
|
|
|
|
|
|
|||||
8 |
= OFF |
No Mic |
|
|
|
SW 1/2/3 Sets the tone generated by the amplifier |
|||||||||||
(ON = Mic connected) |
when it is operating in Master mode. |
||||||||||||||||
|
Expander as Master / Stand-Alone |
|
7 Settings: |
0/0/0 |
|
Temporal Whoop |
|||||||||||
1 |
= OFF |
Temporal Whoop Signal |
|
|
|
|
1/0/0 |
|
Hi / Lo Tone |
||||||||
2 |
= OFF |
|
|
|
|
|
|
|
|
|
|
0/1/0 Sine Wave |
|||||
|
|
|
|
|
|
|
|
|
|
0/0/1 1 kHz Sine Wave |
|||||||
3 |
= OFF |
|
|
|
|
|
|
|
|
|
|
1/1/0 March Time Beep (880 Hz) |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
1/0/1 Slow Whoop |
|||||
4 |
= OFF |
|
|
|
|
|
|
|
|
|
|
0/1/1 Code 3 Beep |
|||||
5 |
= OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
= ON |
Master setting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7 |
= ON |
Battery connected |
(OFF = No Batteries) |
|
|
|
|
|
|
|
|
|
|||||
8 |
= ON |
Mic connected |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
For ratings and specifications see Evax 25/50/100 Installation Instructions P/N 1-5001 Rev. F |
|||||||||||||||||
|
|
|
|
|
P/N B-5002 Rev. E |
130 Perinton Parkway, Fairport, NY 11450 |
|||||||||||
|
|
|
|
|
|
Page 1 of 2 |
|||||||||||
|
|
|
|
|
|
|
|
|
Customer Service: (800) 289-0096 |
||||||||
|
|
|
|
|
|
|
|
|
Technical Support: (888) 886-6189 |
FIRE ALARM CONTROL PANEL
_
SIGNAL
CIRCUIT
ALARM POLARITY +
INPUT POWER
XFMR
120 VAC
Supervised
Non-Power Limited
EVX-25E / 50E / 100E
EVAX 25E / 50E / 100E
TYPICAL INSTALLATION
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E |
Supervised - Power Limited |
|
Supervised - Power Limited |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
O EOLR |
|
|
CLASS “B” (Style “Y”) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L |
|
|
|
|
F |
|
|
|
|
F |
|
|
|
|
F |
|
|
|
|
|
|
WIRING |
|
|
I |
|
|
|
|
I |
|
|
|
|
I |
|
|
|
|
|
|
|
R |
|
|
|
|
R |
|
|
|
|
R |
|
|
|
|
|
|
|
|
|
E |
|
|
|
|
E |
|
|
|
|
E |
|
|
|
|
|
Standard Life Safety Speakers, Strobes connected and powered separately |
||||||||||||||||
|
|
Break wire to maintain supervision. Do not loop wire around speaker terminals |
Supervised - Power Limited
|
|
|
|
|
|
|
|
|
|
|
|
CLASS “A” (Style “Z”) |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
WIRING |
||
|
|
TB1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
|
F |
|
|
F |
|
|
|
|
|
|
|
|
|
|
TB2 |
|
I |
|
|
I |
|
|
|
|
|
|
|
|
|
|
|
R |
|
|
R |
|
|
|
|
|
|
|
|
|
|
|
11 |
|
E |
|
|
E |
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10 |
|
|
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
9 |
|
|
|
|
EOL |
|
|
1 |
TB3 |
J1 |
|
|
|
|
8 |
|
|
|
|
|
|
|
|
|
|
|
|
J2 |
7 |
|
TB1 |
|
|
|
|||
FACP |
|
2 |
|
|
|
|
|
|
6 |
|
|
|
|
||
EOLR |
E |
3 |
|
|
|
|
|
|
|
5 |
|
5 |
6 |
7 |
8 |
O |
|
|
|
|
|
|
|
|
|||||||
|
L |
4 |
YEL |
|
FAULT |
|
|
|
|
4 |
|
|
|
|
|
|
E |
5 |
|
|
|
1 |
2 3 |
3 |
|
Supervised - Power Limited |
|||||
MATCHING |
O |
6 |
|
|
|
|
|
|
|
2 |
|
|
|
|
|
L |
GRN |
|
NORMAL |
|
|
|
|
|
|
|
|
||||
EOLR |
|
7 |
|
|
|
|
1 |
|
|
|
|
|
|||
(SPEAKER |
|
8 |
RED |
|
ALARM |
|
|
|
|
|
|
|
|
|
|
CIRCUIT) |
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
MESSAGE |
MIC |
|
|
|
|
|
P2 |
For Fire Emergency Use Only |
|
|
|||
|
|
|
|
|
|
|
|
|
|
||||||
|
|
GAIN |
GAIN |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
Field wiring connections: |
|||
|
|
|
|
|
|
|
|
|
|
|
|
#6-32 wire clamp screw 14-18 AWG |
|||
|
|
|
|
|
|
|
|
|
|
|
|
#8-32 wire clamp screw 12-18 AWG |
|||
|
|
|
|
|
|
|
|
|
|
|
Horizontal wire entry terminal 18-26 AWG |
||||
|
|
|
|
|
|
|
|
|
|
|
|
Wire gauge determined by circuit load |
|||
|
|
|
S1 |
|
SN1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Battery Wire Harness |
- |
|
- |
|
|
||||
|
|
|
|
|
|
|
12V |
|
|
12V |
|||||
|
|
|
|
|
|
Supervised - Non Power Limited |
|
Battery |
|
Battery |
|||||
|
|
|
|
|
|
Charging Current 1A max. |
+ |
|
+ |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
Jumper Wire is Provided |
FIRE ALARM CONTROL PANEL |
EVAX 25E / 50E / 100E |
|
|
|
|
|
||||||||||
|
|
- |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|||||||
|
SIGNAL |
|
|
|
Master / Slave Connection Detail |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
||||||||
|
CIRCUIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ALARM |
+ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
POLARITY |
|
|
|
|
|
|
|
|
|
|
Non-Supervised - Power Limited |
||||
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Non-Supervised wiring |
Field wiring connections: |
|
|
|
|
|
|
|
|
|
|
must be only run in the |
|||||
TO |
|
|
|
|
same cabinet or between |
|||||||||||
#6-32 wire clamp screw 14-18 AWG |
ADDITIONAL |
|
|
|
|
|
|
cabinets which are piped |
||||||||
EXPANDERS |
|
|
|
|
||||||||||||
#8-32 wire clamp screw 12-18 AWG |
|
|
|
|
|
|
|
|
|
|
together within the same |
|||||
Horizontal wire entry terminal 18-26 AWG |
|
|
|
|
|
|
|
|
|
|
room at a maximum of |
|||||
Wire gauge determined by circuit load |
|
|
|
|
|
|
|
|
|
|
20’. |
|||||
|
|
|
|
|
|
|
|
TB1 |
|
|
|
|
|
|
|
|
TB1 |
|
|
|
|
|
|
|
||
|
|
1 |
2 |
3 |
4 |
5 |
6 |
|
7 |
8 |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
|
|
|
|
|
|
|
|
|
|
TB2 |
|
|
|
|
|
|
|
|
TB2 |
|
|
|
1 |
|
|
|
|
|
|
11 |
|
|
1 |
|
|
|
|
|
11 |
|
|
|
|
|
|
|
|
|
10 |
|
|
|
|
|
|
|
10 |
||
|
|
|
2 |
|
|
|
|
|
|
9 |
|
|
2 |
|
|
|
|
|
9 |
|
1 |
TB3 |
J1 |
|
|
|
|
|
8 |
1 |
TB3 |
J1 |
|
|
|
|
8 |
||
|
|
|
|
|
J2 |
|
7 |
|
|
|
J2 |
|
7 |
||||||
E |
2 |
|
|
|
|
|
|
|
6 |
2 |
|
|
|
|
|
|
6 |
||
O |
3 |
|
|
|
|
|
|
|
|
5 |
3 |
|
|
|
|
|
|
|
5 |
L |
4 |
|
|
|
|
|
|
|
|
4 |
4 |
|
|
|
|
|
|
|
4 |
FACP |
5 |
YEL |
|
FAULT |
|
|
1 |
2 |
3 |
3 |
5 |
YEL |
|
FAULT |
|
|
1 2 |
3 |
3 |
EOLR |
6 |
GRN |
|
NORMAL |
|
|
|
|
2 |
6 |
GRN |
|
NORMAL |
|
|
|
2 |
||
7 |
|
|
|
|
|
1 |
7 |
|
|
|
|
1 |
|||||||
|
8 |
RED |
|
ALARM |
|
|
|
|
|
8 |
RED |
|
ALARM |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
MESSAGE |
MIC |
|
|
|
|
|
|
P2 |
MESSAGE |
MIC |
|
|
|
|
|
P2 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
GAIN |
GAIN |
|
|
|
|
|
|
GAIN |
GAIN |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
14 pin ribbon cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(factory supplied) may be used |
|
|
|
|
|
|
|
|
|
|
|
SLAVE |
|
|
|
|
in place of hard wired connections |
|
MASTER |
|
|
||||||||
|
|
|
|
|
|
on TB2-11,5,3,1 |
|
|
|
||||||||||
|
|
EVX-25E / 50E/ 100E |
|
EVX-25E / 50E/ 100E |
|||||||||||||||
|
|
S1 |
|
SN1 |
|
|
|
|
|
Supervised - |
|
S1 |
|
SN1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power Limited |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Master |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*NOTE: Switch SN1-6, SN1-8 must be in OFF position for all Slave modules. |
All Power and Speaker connections remain unchanged. |
J1 Shorting blocks removed from slave units for pass-through supervision.
P/N B-5002 Rev. E |
130 Perinton Parkway, Fairport, NY 11450 |
Page 2 of 2 |
|
|
Customer Service: (800) 289-0096 |
|
Technical Support: (888) 886-6189 |