PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.
INSTALLATION MUST COMPLY WITH ALL LOCAL CODES.
IMPORTANT: Save these Instructions for the Local Electrical Inspector’s use.
INSTALLER: Please leave these Instructions with this unit for the owner.
OWNER: Please retain these instructions for future reference.
Safety Warning: Turn off power circuit at service panel and lock out panel, before wiring this appliance.
Requirement: 120 V AC, 60 Hz. 15 or 20 A Branch Circuit
2
IMPORTANT SAFETY INSTRUCTIONS
Read All Instructions Before Using the Appliance.
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE
THE FOLLOWING:
A. Use this unit only in the manner intended by the
manufacturer. If you have questions, contact
the manufacturer.
B. Before servicing or cleaning the unit, switch
power off at service panel and lock service
panel disconnecting means to prevent power
from being switched on accidentally. When the
service disconnecting means cannot be locked,
securely fasten a prominent warning device,
such as a tag, to the service panel.
C. Installation Work and Electrical Wiring Must Be
Done By Qualified Person(s) In Accordance
With All Applicable Codes & Standards,
Including Fire-rated Construction.
D. Sufficient air is needed for proper combustion
and exhausting of gases through the flue
(chimney) of fuel burning equipment to prevent
back- drafting. Follow the heating equipment
manufacturers guideline and safety standards
such as those published by the National Fire
Protection Association (NFPA), the American
Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and the
local code authorities.
E. When cutting or drilling into wall or ceiling, do
not damage electrical wiring and other hidden
utilities.
F. Ducted systems must always be vented to the
outdoors.
WARNING
CAUTION
FOR GENERAL VENTILATING USE ONLY.
NOT USE TO EXHAUST HAZARDOUS OR
EXPLOSIVE MATERIALS OR VAPORS.
CAUTION
To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent
exhaust air into spaces within walls, ceilings,
attics, crawl spaces, or garages.
WARNING
TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCT WORK.
Install this hood in accordance with all
requirements specified.
WARNING
To Reduce The Risk Of Fire Or Electric Shock,
Do Not Use This Hood With Any External Solid
State Speed Control Device.
OPERATION
a. Always leave safety grills and filters in place.
Without these components, operating blowers
could catch onto hair, fingers and loose clothing.
The manufacturer declines all responsibility in the
event of failure to observe the instructions given
here for installation, maintenance and suitable use
of the product. The manufacturer further declines
all responsibility for injury due to negligence and
the warranty of the unit automatically expires due to
improper maintenance.
DO
This unit is manufactured for indoor use only. Do not use this unit outdoors.
3
IMPORTANT SAFETY INSTRUCTIONS
Read All Instructions Before Using the Appliance.
READ AND SAVE THESE INSTRUCTIONS
Electrical requirements
IMPORTANT
Observe all governing codes and ordinances.
It is the customer’s responsibility:
To contact a qualified electrical installer.
To assure that the electrical installation is adequate
and in conformance with National Electrical Code,
ANSI/NFPA 70 — latest edition*, or CSA Standards
C22.1-94, Canadian Electrical Code, Part 1 and
C22.2 No.0-M91 - latest edition** and all local
codes and ordinances.
If codes permit and a separate ground wire is used,
it is recommended that a qualified electrician
determine that the ground path is adequate.
Do not ground to a gas pipe.
Check with a qualified electrician if you are not sure
range hood is properly grounded.
Do not have a fuse in the neutral or ground circuit.
IMPORTANT
Save Installation Instructions for electrical
inspector’s use.
The range hood must be connected with copper
wire only.
The range hood should be connected directly to the
fused disconnect (or circuit breaker) box through
metal electrical conduit.
Wire sizes must conform to the requirements of the
National Electrical Code ANSI/NFPA 70 — latest
edition*, or CSA Standards C22.1-94, Canadian
Electrical Code Part 1 and C22.2 No. 0-M91 - latest
edition** and all local codes and ordinances.
A U.L.- or C.S.A.-listed conduit connector must be
provided at each end of the power supply conduit
(at the range hood and at the junction box).
Copies of the standards listed may be obtained from:
* National Fire Protection Association Batterymarch Park
Quincy, Massachusetts 02269
** CSA International 8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
4
Parts Included with your Hood
•Hood Canopy Assembly with Round Metal
Transition installed.
•Rectangular Metal Transition with Back draft
dampers.
•Care & Use /Installation Instructions
•2 Filters
•Fitting Screws.
Parts Not Included with your
Hood
•Duct Tape
•1/2" Conduit
•Wire Nuts
•Round or Rectangular Duct.
•Charcoal filters
•Round back draft damper
•Wiring clamp
•Models DUH30252UC and DUH36252UCOnly:
CAUTION! Lamps are not supplied, use
ONLY 120 Volt, 50 Watt (maximum) 50°
halogen light made or a GU10 base.
Tools required
Flat blade and Phillips screwdrivers
Pencil
Metal snips (in some applications)
Electric drill
Saw (saber or keyhole)
Duct tape
Pliers
Level
Caulking
Tape measure
1/4.pivoting hex socket
Flashlight
Wire stripper
1/4. Nutdriver
Small hammer
INSTALLING THE HOOD
•For the most efficient air flow exhaust, use a
straight run or as few elbows as possible.
CAUTION: Vent unit to outside of
building, only.
•One person is necessary for installation.
On avarage 2 hours are necessary to complete
installation (without considering cut to be done
on wall and or on cabinet, installation of ducts ,
conduit and electrical connections to the mains).
16 installation steps are required.
•The hood is fitted with Screws and Drywall
Anchors suitable for most surfaces, consult a
Qualified Installer, check if they perfectly fit with
your cabinet/wall.
•Do not use flex ducting.
•COLD WEATHER installations should have an
additional backdraft damper installed to
minimize backward cold air flow and a
nonmetallic thermal break to minimize
conduction of outside temperatures as part of
the ductwork. The damper should be on the
cold air side of the thermal break.
The break should be as close as possible to
where the ducting enters the heated portion of
the house.
•Remote blowers require a five wire installation.
•Make up air: Local building codes may require
the use of Make-Up Air Systems when using
Ducted Ventilation Systems greater than
specified CFM of air movement.
The specified CFM varies from locale to locale.
Consult your HVAC professional for specific
requirements in your area.
•Typical installation
Min installation height from the countertop to the
bottom of the hood is 24” to 30“.These hoods
are not recommended to be used over indoor
grills.
5
1. Choose vent options
Vent Exhaust Option
The hood is designed for vertical or horizontal
discharge or can be installed in a recirculating
ductless version:
For safety reasons, ducting should vent directly
outdoors (not into an attic, underneath the
house, into the garage or into any enclosed
space).
Keep duct runs as short and straight as
possible.
Duct fittings (elbows and transitions) reduce air
flow efficiency.
Back to back elbows and „S“ turns give very
poor delivery and are not recommended.
A short straight length of duct at the inlet of the
remote blower gives the best delivery.
Transition to duct from the integral blower or
remote duct transition as close to the downdraft
as is pos-sible.
In order of preference, use
1st. 10" round duct
2nd. 8" round duct
3rd. 3-1/4" x 14" duct
4th. 7" round duct
5th. 3-1/4" x l0" duct
6th. 6" round duct
The use of flexible metal round duct should
only be used when no other duct fitting exists.
Limit use to short lengths and do not crush
when making corners.
After having choosen the vent option, proceed
as follows:
2. Remove the round transition from its seat by
unscrewing the its fixing screws (save the
screws).
7" Round
Transition
4. Remove the junction box cover.
J-Box
Cover
Remove either the top or the back wiring knockout
according the preference and install an approved
wiring clamp
wiring
clamp
5. Remove the duct knockouts using a flat blade
screwdriver
and a small hammer.
Use the screwdriver by knocking out the pannel in
similar fashion to a scalpel.
Take care of sharp edges.
Attention!
If is intended to use the hood in recirculating version do
not remove any duct knockouts and order the necessary
charcoal filter from your supplier.
Round
vertical
R2
discharge
R1
Rectangular
vertical
discharge
3. Remove the grease filters.
Rectangular
horizontal
R1
discharge
R1= Remove rectangular duct knockout only.
R2 = Remove semicircular and rectangular duct
knockouts.
8
6. For rectangular ducted discharge installations
only (otherwise skip to next step)
Attach exhaust adaptor/damper over knockout
opening with two exhaust adaptor screws. Make sure
damper pivot is nearest to top/back edge of hood.
Remove tape from damper flap.
Pivot
Top/back
edge
Exhaust
transition/damper
NOTE: The exhaust adaptor/damper can be
installed up to 1 inch on either side of the hood
center to accommodate off-center ductwork. In
extreme off-center installations, one end of the duct
connector may need to be trimmed to clear the
electrical cable clamp.
7. For round ducted discharge installations only
Re-install the round transition with its screws.
7" Round
Transition
NOTE: The round transition can be installed up to 1
inch on either side of the hood center to
accommodate off-center ductwork. In extreme offcenter installations, one end of the duct connector
may need to be trimmed to clear the electrical cable
clamp.
9
8. Mark holes
Select the vent option that your installation will
require and proceed to that section:
Outside top exhaust
(Vertical duct– 3 1/4”x 10” Rectangular)
Use the diagram or the hood as a template and
mark the locations on the cabinet for ductwork,
electrical wiring and keyhole screw slots.
Outside top exhaust
(Vertical duct–7” Round)
Use the diagram or the hood as a template and
mark the locations on the cabinet for ductwork,
electrical wiring and keyhole screw slots.
Hood mounting screws (4)
13 15/16" (30" Hood)
16 15/16" (36" Hood)
Cabinet front
Cabinet Bottom
"
5"
"
1 1/4"
Wood shims (recessed
bottom cabinets only)
Hood mounting screws (4)
13 15/16" (30" Hood)
16 15/16" (36" Hood)
Cabinet front
Cabinet Bottom
Access
hole for 7"
round duct
Wood shims (recessed
bottom cabinets only)
5 1/4"
Vertical duct
access hole
8" DIA.
HOLE
13 15/16" (30" Hood)
16 15/16" (36" Hood)
12 9/16"
5 1/4"
Electrical access hole
Center
line
Center
line
Electrical access hole
(in cabinet bottom)
(in cabinet bottom)
13 15/16" (30" Hood)
16 15/16" (36" Hood)
12 1/2"
5"
Electrical access hole
Electrical access hole
(in cabinet bottom)
(in cabinet bottom)
"
2"
"
2 1/4"
10 1/2"
1 1/4"
10 1/2"
1 1/2"
Outside rear exhaust
(Horizontal duct– 3 1/4”x 10” Rectangular)
•Use the diagram or the hood as a template and
mark the locations on the cabinet for ductwork,
electrical wiring and keyhole screw slots.
Recirculating
Use the hood as a template and mark the locations
on the cabinet for the electrical wiring and keyhole
screw slots.
Since the hood is to be recirculated (not to be
vented outside), do not cut out any vent openings in
the wall or cabinet bottom.
Wood shims (recessed
bottom cabinets only)
3 3/4"
Cabinet
bottom
13 15/16" (30" Hood)
16 15/16" (36" Hood)
Hood mounting screws (4)
Cabinet front
Horizontal duct
access hole
5 1/4"5 1/4"
Center line
12 7/16"
13 15/16" (30" Hood)
16 15/16" (36" Hood)
1/8"
7/16"
Electrical access hole
(in wall)
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.