Bosch CH70-24MCW-FR, CH70-24MCW-FW Specsheet

Page 1
Fire Alarm Systems | CH70 Multi‑candela Chime Strobes
CH70 Multi‑candela Chime Strobes
www.boschsecurity.com
u Low current draw with temperature compensation
to reduce power consumption and wiring costs
u 24 VDC, filtered or FWR
These Wheelock CH70 Multi‑candela, Wall‑mount Chime Strobes provide a low current draw, a choice of single‑stroke or vibrating operation, an adjustable sound level, a chime tone adjustable from 800 Hz to 1200 Hz, and a choice of four light output intensities (15 cd, 30 cd, 75 cd, or 110 cd) in one unit. The strobes can be synchronized using SM (single) or DSM (dual) modules. They also have an attached mounting plate for easy indoor installation on a variety of electrical boxes.
Functions
Sound Mode Settings
The chimes are factory set in single‑stroke mode. They can be changed to vibrating mode before wiring by moving a jumper. Single‑Stroke Mode The minimum input pulse duration must be at least 160 ms on and 160 ms off. The chime only operates once each time it is pulsed. Use this mode for coded systems. Vibrating Mode Continuous input voltage must be applied to the chime to activate the chime at 1 sec intervals.
u Single‑stroke or vibrating tone
u Selectable strobe intensities of 15 cd, 30 cd, 75 cd,
or 110 cd
Strobe Settings
The unit comes set at 15 cd. Change the setting using a screwdriver in the slot in the unit's base (setting is visible on indicator plate within the lens).
Volume and Tone Settings
The volume and tone controls are factory set to ensure maximum dBA output. The volume and tone can be tuned to suit a particular application, but appropriate measurements must be taken to ensure the volume meets the listing requirements for private mode fire protective service per UL464.
Certifications and approvals
Cooper Wheelock, Inc. holds these Listings and Approvals:
Region
USA UL UCST: Audible Signal Appliances, Gener-
Certification
al Siganal (UL464), ULSZ: Audible Sig­nal Appliances (UL464), UUKC: Signal­ing Appliances and Equipment for the Hearing Impaired (UL1971)
CSFM see our website
Page 2
2 | CH70 Multi‑candela Chime Strobes
Installation/configuration notes
Compatible Products
The following products are compatible with the CH70 Chime Strobes:
Category Product ID Product Description
Control
D7022
1
Conventional FACP
Panels
D7024
2
Addressable FACP
D7024 Conventional FACP
D8024
D9124
D10024A
FPD-7024
1
1
1
2
Analog FACP
Addressable FACP
Analog FACP
Addressable FACP
FPD-7024 Conventional FACP
FPA-1000 Analog Addressable FACPs
Modules SM‑12/24‑R Synchronization module (red)
DSM‑12/24‑R Dual synchronization module (red)
1
For synchronization, use the SM or DSM modules with these control panels. The synchronization module must be set for 24 V operation. When used, the D7022 must be set for 24 VDC operation.
2
When used with a D7039 Multiplex Expansion Module, the FPD-7024 and D7024 become addressable fire alarm control panels (FACPs).
Mounting Considerations
Mount these chime strobes on the indicated back boxes for the indicated applications:
Conduit
Applications
Surface Mounted
Flush Mounted
Four‑inch square*
SBB Back Box
* Requires a four‑inch square back box that is 2.125 in (5.4 cm) deep with a 1.5 in. (3.8 cm) deep extension ring.
Wiring
The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).
Parts included
Quant. Component
1 Chime strobe
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
Chime Current (maximum): 22 mA
Voltage (input) 24 VDC nominal, filtered or FWR
Strobe Current (maximum):
15 cd: VDC: 60 mA
FWR: 102 mA
30 cd: VDC: 92 mA
FWR: 155 mA
75 cd: VDC: 165 mA
FWR: 253 mA
110 cd: VDC: 220 mA
FWR: 347 mA
Environmental
Relative Humidity: Up to 85%, non‑condensing
Temperature (Operating): +32°F to +120°F (0°C to +49°C)
Mechanical
Candela Ratings: 15 cd, 30 cd, 75 cd, or 110 cd
Dimensions (H x W x D): 5.1 in. x 5.1 in. x 5.2 in.
(13 cm x 13 cm x 13.3 cm)
Material: Molded plastic enclosure with Xenon
flashtube and Lexan lens
Chime Ratings at 24 VDC
Reverberant dBA at 10 ft (3 m) per UL464:
Maximum: 58 dBA Minimum: 52 dBA
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Ordering information
CH70‑24MCW‑FR Multi‑candela Chime Strobe (red)
Red, wall‑mount chime with adjustable volume and single‑stroke or vibrating tone; strobe intensities of 15 cd, 30 cd, 75 cd, or 110 cd
Order number CH70-24MCW-FR
CH70‑24MCW‑FW Multi‑candela Chime Strobe (white)
White, wall‑mount chime with adjustable volume and single‑stroke or vibrating tone; strobe intensities of 15 cd, 30 cd, 75 cd, or 110 cd
Order number CH70-24MCW-FW
Accessories
ISP2‑R Surface Adapter (red)
13.3 cm (5.25 in.) square, 3 cm (1.1875 in.) deep
Order number ISP2-R
Page 3
3 | CH70 Multi‑candela Chime Strobes
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice 2711139211 | en, V4, 13. Aug 2014
ISP2‑W Surface Adapter (white)
13.3 cm (5.25 in.) square, 3 cm (1.1875 in.) deep
Order number ISP2-W
RP‑R Retrofit Plate (red)
20.3 cm (8 in.) high, 14.9 cm (5.875 in.) wide
Order number RP-R
SBB‑R Surface‑mount Back Box (red)
14 cm (5.5 in.) x 14.2 cm (5.6 in.) x 9.1 cm (3.6 in.)
Order number SBB-R
SBB‑W Surface‑mount Back Box (white)
14 cm (5.5 in.) x 14.2 cm (5.6 in.) x 9.1 cm (3.6 in.)
Order number SBB-W
SBL2‑R Retrofit Device Back Box (red)
dimensions 27.8 cm (10.9 in.) x 15.5 cm (6.1 in.) x
4.3 cm (1.7 in.)
Order number SBL2-R
SER‑R Square Semi‑flush Extension Ring (red)
12.7 cm (5 in.) square by 4 cm (1.5625 in.) deep
Order number SER-R
SER‑W Square Semi‑flush Extension Ring (white)
12.7 cm (5 in.) square by 4 cm (1.5625 in.) deep
Order number SER-W
SFP‑R Semi‑flush Plate (red)
15.2 cm (6 in.) square by 0.8 cm (0.3125 in.) thick
Order number SFP-R
Loading...