Bosch CF36-1D, CF80-1D, CF112-1D, CF71-1D, CF140-1D Installation Manual

...
Page 1
6720874436(2017/04)ZA
Installation manual CF36-1D CF80-1D CF45-1D CF90-1D CF56-1D CF112-1D CF71-1D CF140-1D
Thank you very much for purchasing our air conditioner, Before using your air conditioner, please read this manual carefully and keep it for future reference.
Climate 5000 VRF
CF Series - DC Fan Motor
Page 2
2 | NOTES
6720874436 (2017/04)
Ceiling-Floor Type Indoor Unit
Page 3
1. PRECAUTIONS
■ Ensure that you are in conformity with the local, national and international laws and regulations.
■ Read "PRECAUTIONS" carefully before installation.
■ The following precautions include important safty items. Observe them and apply accordingly.
■ Keep this manual with the owner's manual in a handy place for future reference.
The safty precautions listed here are divided into two categories. In either case, important safty information is listed which must be read carefully.
WARNING
Failure to observe a warning may result in death.
CAUTION
Failure to observe a caution may result in injury or damage to the equipment.
After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Also, inform cus­tomers that they should store this installation manual along with the owner's manual for future reference.
WARNING
Be sure only trained and qualified service personnel to install, repair or service the equipment.
Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
CONTENTS PAGE Install according to these installation instructions strictly.
If installation is defective, it will cause water leakage, electrical shock and fire.
When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.
Contact your installer for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
Use the attached accessories parts and specified parts for instal­lation.
Failure to do so could lead to the system failing, water leakage, electri­cal shock and fire.
Unit should only be mounted on a suitable load bearing ceiling and surface.
Not enough or installation is not properly done, the set will drop to cause injury.
The appliance shall not be installed in the laundry room.
Before obtaining access to terminals, all supply circuits must be disconnected.
The appliance must be positioned so that the plug is accessible.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in electrical work, it will cause electrical shock fire.
Use only the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal.
If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
Wiring routing must be properly arranged so that control board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
If the supply cable is damaged, it must be replaced by the manu­facture or its service agent or a similarly qualified person in order to avoid a hazard.
An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.
When carrying out piping connection, take care not to let air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cable or use of extension cable, and do not share the single outlet with other electrical appliances.
Otherwise, it will cause fire or electrical shock.
Carry out the specified installation work after taking into account strong winds.
Improper installation work may result in the equipment falling and causing accidents
1. PRECAUTIONS ................................. 3
2. INSTALLATION INFORMATION .................... 4
3. ATTACHED FITTINGS ............................ 4
4. INDOOR UNIT INSTALLATION ..................... 5
5. INSTALL THE CONNECTING PIPE .................. 7
6. CONNECT THE DRAIN PIPE ....................... 8
7. WIRING ........................................ 9
8. CONTROL OPERATION ........................... 10
9. TEST OPERATION ............................... 13
Ceiling-Floor Type Indoor Unit
6720874436 (2017/04)
PRECAUTIONS | 3
Page 4
If the refrigerant leaks during installation, ventilate the area im­mediately.
Toxic gas may be produced if the refrigerant comes into the place contacting with fire.
The temperature of refrigerant circuit will be high, please keep the communication cable away from the copper tube.
After completing the installation work, check that the refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
CAUTION
Ground the air conditioner.
Do not connect the ground wire to gas or water pipes, light­ning rod or a telephone ground wire. Incomplete grounding may result in electric shocks.
Ensure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks.
Connect the outdoor unit first and then the indoor unit cables.
You are not allow to connect the air conditioner with the power source until wiring and pipework for the air condi­tioner is complete.
While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent con­densation.
Incorrect drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 metre away from televisions or radios in order to prevent image interfer­ence or noise.
Depending on the radio waves, a distance of 1 metre may not be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children or infirm persons without supervision.
Do not install the air conditioner in the following loca­tions:
There is petrolatum existing.
Salty atmosphere (near the coast). If this can't be
avoided, choose a anticorrosive model.
There is caustic gas (the sulfide, for example) existing
in the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
The appliance shall not be installed in the laundr y room.
2. INSTALLATION INFORMATION
To install properly, please read this "installation manual" at
first.
The air conditioner must be installed by only competent persons.
When installing the indoor unit or its pipe work and cabling,
please follow this manual.
If the air conditioner is installed on a metal part of the
building, it must be electrically insulated according to the relevant standards to electrical appliances.
When all the installation work is finished, please turn on the
power only after a thorough check.
Regret for no further announcement if there is any change of
this manual caused by product improvement.
INSTALLATION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
3. ATTACHED FITTINGS
Please check whether the following fittings are supplied. You may find there are extra parts supplied.
Name of Accessories Qty Outline Usage
Installation manual 1
(This manual)
Hook
2
Hang­ing arm
model 36~140
2
model 160 4
Network matching cable 1
The indoor unit which at the terminal of com­munication system should connect a impedance between port P and port Q.
Drainage pipe 1
Drainage
Thermal insulation pipe (160model)
1
Keep the drainage pipe temperature
Bolt assembly 4
Copper 1
Use for pipe connec­tion of engineering installation
Snapring 1
Use for fastening the drainage pipe
4 | INSTALLATION INFORMATION
6720874436 (2017/04)
Ceiling-Floor Type Indoor Unit
Page 5
Remote controller & Its Frame
1. Remote controller ....................1
2. Remote controller holder. . . . . . . . . . . . . . . 1
3. Mounting screw (ST2.9x10-C-H) ........ 2
4. Alkaline dry battery (AM4) ............. 2
Fig.3-1
Remote
controller
Remote controlle
r
holder
Mounting screw B
ST2.9x10-C-H
Remote controller
Remote controller holder
Mounting screw B ST2.9x10-C-H
CAUTION
Do not damage the controller.
Before installation, operate the remote controller to
determine its location in a reception range.
Keep the remote controller at least 1m apart from the
nearest TV set or stereo equipment. (It is necessary to prevent image disturbances or noise interferences.)
Do not install the remote controller in a place exposed
to direct sunlight or close to a heating source, such as a stove.
Ensure that the batteries are fitted the correct way round.
NOTE
This manual is subject to changes due to technological improvement without further notices.
4. INDOOR UNIT INSTALLATION
4.1 The units may be mounted vertically, provided that the correct clearances for positioning are maintained.
4.2. Wall Mounting Installation
Fig.4-1
J. Connectingpoint of
refrigerant pipe
(I.gas side)
I. Connectingpointof
refrigerant pipe
(J.Liquid side)
Drainpoint
I. Connection point of refrigerant pipe (I. gas side)
J. Connection point of refrigerant pipe (J. Liquid side)
Drain point
A
B
Fig.4-2
Fig.4-3
Hook
Hook
Ceiling-Floor Type Indoor Unit
6720874436 (2017/04)
INDOOR UNIT INSTALLATION | 5
Page 6
4.3. Ceiling Installation
Fig.4-5
Hanging ar
m
Hanging arm
Remove the side board and the grill. (Refer to Fig. 4-6)
Fig.4-6
Side boar
d
Grille
Side board
Grille
Locate the hanging arm on the hanging screw bolt.
(Refer to Fig. 4-7)
Prepare the mounting bolts on the unit.( Refer to Fig. 4-8)
Fig.4-7
Fig.4-8
Screw nut
Washer
Hanging
screw bolt
Hanging arm
2025mm
Mounting bolt(max.40mm
)
813mm
INDOOR UNIT
Screw nut
20~25 mm
8~13 mm
Mounting bolt (max. 40 mm)
INDOOR UNIT
Washer
Hanging screw bolt
Hanging arm
Hang the unit on the hanging arm by sliding backward. Securely
tighten the mounting bolts on both sides.(Refer to Fig. 4-9)
1. Connect the hook with self tapping screw onto the wall.
(Refer to Fig. 4-4)
Fig.4-4
Washer
Tapping scre
w
<6mm
Hook
Hook
Tapping screw
Washer
< 6 mm
2. Hang the indoor unit on the hook.
6 | INDOOR UNIT INSTALLATION
6720874436 (2017/04)
Ceiling-Floor Type Indoor Unit
Page 7
3. Hang the unit on the hanging arm by sliding backward. Securely tighten the mounting bolts on both sides.
Hanging arm
Mounting bolt
Hanging screw bolt
D. Connecting point of
refrigerant pipe
(D.gas side)
Drain point
E. Connecting point of
refrigerant pipe (E. Liquid side)
20mm
G
C
Fig. 4-9
Hanging screw bolt
Hanging arm
Mounting bolt
D. Connecting point of
refrigerant pipe
(D.gas side)
> 20 mm
E. Connecting point of
refrigerant pipe
(E.Liquid side)
Drain point
CAUTION
The above dimensions are based on model 36 as rated capacity,which may differ from the unit you purchased.
4.4. The dimension of the unit (Unit: mm)
Table 4-1
MODEL
A B C D E F G
36~71 990 660 203 505 506 907 200
80~90 1280 660 203 795 506 1195 200
112~140
1670 680 244 1070 450 1542 200
4.5. Material and size of the piping
Table 4-2
Pipe Material
Copper Pipe for Air Conditioner
Mode(R410A) 36~45 56~140
Size(mm)
I(Liquid side) Ø 6.4 Ø 9.5
J(Gas side)
Ø 12.7 Ø 15.9
5. INSTALL THE CONNECTING PIPE
CAUTION
Do not let air, dust, or other impurities fall in the pipe system during the time of installation.
The connecting pipe should not be installed until the indoor and outdoor units have been together.
Keep the connecting pipe dry, and do not let moisture in during installation.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
5.1. The Procedure of Connecting Pipes
5.1.1 Measure the necessary length of the connecting pipe, and use the following process.
1) Connect the indoor unit at first, then the outdoor unit. a. Use a pipe
bender to form the radius of the pipework.
CAUTION
1. Cover the surfaces of the flare pipe and the joint nuts
with oil, and tighten it for 3~4 turns with hands before fasten the flare nuts.
2. Be sure to use two wrenches simultaneously when you
connect or disconnect the pipes
2) The stop valve of the outdoor unit should be closed tightly (as
original supplied). Every time you operate it, first loosen the nuts at the part of stop valve, then connect the flare pipe immediately (within 5minutes). If the nuts have been loosened for a long time, dust and other impurities may enter the pipe system and may cause malfunction later. Ensure that air is expelled from out of the pipe with refrigerant before connection.
3) Remove the air (refer to the “Expel The Air”) after connecting the
refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the service-points.
Notices For Benable pipe.
• The bending angle should not exceed 90°.
• Bending position is preferably in the bendable pipe. The larger the better it is.
• Do not bend the pipe more than three times.
Ceiling-Floor Type Indoor Unit
6720874436 (2017/04)
INSTALL THE CONNECTING PIPE | 7
Page 8
Bend the connecting pipe of small wall thickness.
Cut out a desired concave at the bending part of the insulating pipe.
Then expose the pipe(cover it with tapes after bending).
To prevent collapsing of deforming, please bend the pipe at its biggest
radius.
Use a pipe bender to get a small radius pipes.
Use only refrigeration copper pipe.
Use the same insulating materials. (More than 9mm thick)
Fig.5-1
Fig.5-2
Fig.5-3
Use frozen oil
Bend the pipe with thumb
Min-radius 100mm
Mak
e the ends straight
Use frozen oil
Bend the pipe with thumb
Min-radius 100 mm
Make the ends straight
2. Locate The Pipe
1) Drill a hole in the wall (suitable just for the size of the wall conduit, 90mm in general), then set on the fittings such as the wall conduit and its cover.
2) Wrap the connecting pipe and the cables together tightly with tapes. Do not let air in, which will cause water leakage by condensation.
3) Pass the bound connecting pipes through the wall conduit from outside. Be careful of the pipe allocation not to do any damage to thetubing.
3. Connect the pipes.
4. Then, open the top of stop valves of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor equal fluently flow.
5. Ensure there is no leakage by checking it with leak detector or soapy water.
6. Cover the joint of the connecting pipe to the indoor unit with the soundproof/insulating sheath (fittings), and tape it well to prevent leakage.
6. CONNECT THE DRAIN PIPE
6.1. Install the drainpipe of the indoor unit
The outlet has PTI screw bread, Please use sealing materials and pipe sheath(fitting) when connecting PVC pipes.
CAUTION
The drain pipe of the indoor unit must be heat insulated, or it will produce condensation, as well as the connections of the indoor unit.
Hard PVC tape must be used for pipe connection, and
ensure sure there is no leakage.
With the connection part to the indoor unit, please
note not to apply pressure on the side of indoor unit pipes.
Ensue the drain pipe faces downwards is more than
1/100, there should not be any kinks in the pipe work.
The total length of the drain pipe when pulled out
shall not exceed 20m, when the pipe is that long, supporting brackets should be used to ensure straightness of the pipe.
Refer to the Fig.8-1 for the installation of the pipes
Fig.6-1
1.5m~2 m
Insulating
material
Downward de cliv ity
lower t han 1/100
Bend
S shap e
VP30
Downward de cliv ity
lower than 1/100
Put as deep as possible
(about 10cm)
1.5~2 m
Insulating material
Downward decline lower than 1/100
Downward decliviry lower than 1/100
VP 30
Bend
Shape
The bend should be (about 10 cm)
6.2. Drainage test
Check whether the drainpipe is not blocked.
New built house should have this test done before the ceiling is
covered.
8 | CONNECT THE DRAIN PIPE
6720874436 (2017/04)
Ceiling-Floor Type Indoor Unit
Page 9
7. WIRING
Specified power cables should be used. Do not apply any
pressure on the terminals used to connect.
Incorrect connection may cause fire.
Grounding must be properly done.
The grounding cable should be kept away from gas pipes, water pipes, telephone, lightening rods or other grounding cables. Improper grounding may cause electric shock.
Electric Wiring must only be done by qualified professionals.
Use aseparate circuit according to national regulations.
If the wiring capacity is not enough, electric shock or fire may occur.
CAUTION
1. Be sure to Install Current Leakage Protection Switch, Or electric shock may occur.
2. Power cable used is to be selected according to national regulations.
3. An all-pole disconnection device which has at least 3 mm separation distance in all pole and a residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed cable shall be installed in accordance to national wiring regulations.
4. Outdoor unit power cable should be selected and connected according to the outdoor unit installation manual.
5. Cabling should be away from high temperature components, or the insulation layer of the cable may be damaged.
6. Use wire clamp to fix the cables and terminal block after connection.
7. Communication cables should be wrapped together with heat insulated refrigerant pipes.
8. Connect the indoor unit to power only after the refrigerant has been vacuumed.
9. Ensure the communication cable is not connected the mains power cable.
7.1. The specification of power
Table 7-1
TYPE (W) 3600-14000W
Phase 1-PHASE
Power
Frequency
& volt
220-240V~ 50Hz 208-230V~ 60Hz
Circuit breaker/fuse (a) 5/3
Indoor unit power cable (mm
2
) 1.0
Indoor/outdoor
connecting
cable
(mm
2
)
Cable size
(mm
2
)
1.0
Electric signal 0.75
CAUTION
A disconnection device having an air gap contact separa­tion in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation.
Fig.7-1
CENTRAL CONT ROL MONITO R(CCM)
INDOOR UNIT
OUTDOOR UNIT
COMPUTER
INDOOR UNIT
INDOOR UNIT
The shield twisted-pair wire
Power (220-240V~ 50Hz/208-230V~ 60Hz)
The shield twisted-pair wire
INDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
CENTRAL CONTROL MONITOR (CCM)
COMPUTER
Power (220-240V~ 50Hz/208-230V~ 60Hz)
INDOOR UNIT
CAUTION
The reserved function is indicated in broken line table,users can select it when necessary
7.2. Indoor/outdoor unit signal wire
• Connect the cable according to their numbers.
• Wrong connection may cause malfunction .
7.3. Cable connection
• Ensure that the cables are protected with insulation material to reduce condensation damage.
7.4. Panel Wiring
Connect the Swing Motor terminal block according to the Panel Installation Manual.
7.5. Terminal Board Diagram
Please refer to the indoor unit wiring diagram for the wiring. Note: The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring correctly and set system address and network address of indoor units.
Signal-phase powern supply model
Fig.7-2
To indoor power
220-240V~ 50Hz
(208-230V
~
60Hz)
To indoor power
220-240V~ 50Hz
(208-230V
~
60Hz)
L
N
To indoor power
220-240V~ 50Hz
(208-230V~ 60Hz)
To indoor power
220-240V~ 50Hz
(208-230V~ 60Hz)
Ceiling-Floor Type Indoor Unit
6720874436 (2017/04)
WIRING | 9
Page 10
Please adopt the shielded twist
ed-pair wire,
and connect the shielded layed to (E)
2800~14000W
TO CCM
COMM.BUS
TO
INDOOR&OUTDOOR
COMM.BUS
Fig.7-3
Fig.7-4
Display
board
Wire controller
To wire controller
The r
eserved wire control
function is indicat
ed in broken
table, user can pur
chase the
wire controller when necessary.
TO CCM COMM.BUS
TO INDOOR&OUTDOOR COMM.BUS
2800~14000W
Please connect the shielded twisted-pair wire, and connect the shielded layed to (E)
Display board
Wire controller
To wire controller
The reserved wire control function is indicated in broken table, user can purchase the wired controller when necessary.
8. CONTROL OPERATION
8.1. Horsepower set
Horsepower code
POWER_S
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
ENC1
Base on different purposes to setting the switch cords on PC panel of indoor electrical control box. Once finish the setting, please cut off the main power, and then input power again, otherwise, setting function could not work.
Table 8-1
ENC1
Switch For setting the cooling output
Switch cord Setting the cooling output
Note: No one are permitted to alter the cooling
output which be set before
shipping from
factory, except
licensed maintain
personnel.
2 3600 W 3 4500 W 4 5600 W 5 7100 W 6 8000 W 7 9000 W 8 11200 W
9 14000 W
CAUTION
The system together can have 64 units (0-63),everyone has only system address code. If two addresses are the same in one system, a abnormal operation will occur.
Please switch off the power before setting,otherwise the unexpected error will occur.
8.2. Network address set
1. Network address is set by communication of indoor and outdoor unit; the address is the same as indoor address, there is no need to set separately.
2. The central control of indoor units can be done on outdoor unit, there is no need to control indoor unit separately, for details please refer to V4+ outdoor unit manual.
3. For previous control of indoor units, the network can be set by connecting (X,Y,E) terminals, there is no need to set network address. The network can also be set by outer network module and main board (CN20).
8.3. TROUBLE SHOOTING
OPERATION
TIMER
DEF/FAN
ALARM
MANUAL
Run lamp
Timer lamp
Defrost lamp
Alarm lamp
Manual switc
h
Run lamp
Timer lamp
Defrost lamp
Alarm lamp
Manual switch
OPERATION
TIMER
DEF/FAN
ALARM
MANUAL
10 | CONTROL OPERATION
6720874436 (2017/04)
Ceiling-Floor Type Indoor Unit
Page 11
Table 8-2
No. Type Contents LED lamp flash Remarks
1 Malfunction
The evaporator sensor check point is adnormal or room temp. sensor is abnormal.
Run lamp flashes quickly.
After the malfunctions disappear, it restores automatically.
2 Malfunction Indoor/outdoor unit communication is abnormal. The timer lamp flashes quickly
After the malfunctions disappear, it restores automatically.
3 Malfunction
Condenser sensor check point is abnormal or outdoor temp. Sensor is abnormal.
All the indoor alarm lamps flash slowly.
After the malfunctions disappear, it restores automatically.
4 Malfunction Water level switch is abnormal Alarm lamp flashes quickly
If the malfunctions can't be solved in three minute all the indoor alarm lamps flash at 0.5Hz. Turn off the power to restore.
8.4. Main board Code designation
SW1 definition
1234
SW1
ON
1 means factory test mode
0 means add. auto searching
mode (default setting)
1234
SW1
ON
01 means DC fan static pressure
is 1 (reserved)
1234
SW1
ON
1 means DC fan Is chosen
0 means AC fan Is chosen
1234
SW1
ON
10 means DC fan static pressure
is 2 (reserved)
1234
SW1
ON
00 means DC fan static pressure
is 0 (reserved)
1234
SW1
ON
11 means DC fan static pressure
is 3 (reserved)
SW2 definition
1234
SW2
ON
00 means the temperature is
15 degrees when shutting down the unit for cold wind proof.
1234
SW2
ON
00 means the time of stopping
indoor fan is 4 minutes
1234
SW2
ON
01 means the temperature is
20 degrees when shutting down the unit for cold wind proof.
1234
SW2
ON
01 means the time of stopping
indoor fan is 8 minutes
1234
SW2
ON
10 means the temperature is
24 degrees when shutting down the unit for cold wind proof.
1234
SW2
ON
10 means the time of stopping
indoor fan is 12 minutes
1234
SW2
ON
11 means the temperature is
26 degrees when shutting down the unit for cold wind proof.
1234
SW2
ON
11 means the time of stopping
indoor fan is 16 minutes
Ceiling-Floor Type Indoor Unit
6720874436 (2017/04)
CONTROL OPERATION | 11
Page 12
SW5 definition
1 2
SW5
ON
00 means temperature
compensation is 6 degrees under heating mode
1 2
SW5
ON
10 means temperature
compensation is 4 degrees under heating mode
1 2
SW5
ON
01 means temperature
compensation is 2 degrees under heating mode
1 2
SW5
ON
11 means temperature
compensation is 8 degrees under heating mode
SW6 definition
1 2 3
SW6
ON
1 means old display panel
0 means new display panel
1 2 3
SW6
ON
1 means auto wind under auto
mode
0 means auto wind under non
auto mode
1 2 3
SW6
ON
reserved
SW7 definition
1 2
SW7
ON
Standard configure
1 2
SW7
ON
Last one in the network
J1,J2 definition
J1
J1 no Jumpers means power off memory function
J1
J1 Jumpers means no power off memory function
J2
reserved
0/1 definition
ON
Means 0
ON
Means 1
12 | CONTROL OPERATION
6720874436 (2017/04)
Ceiling-Floor Type Indoor Unit
Page 13
9. TEST OPERATION
1. The test operation must be carried out after the entire installation has been completed.
2. Please confirm the following points before the test operation:
• The indoor unit and outdoor unit are installed properly.
• Pipe work and wiring are correctly installed.
• The refrigerant pipe system is leakage-checked.
• The drainage is not blocked.
• The heating insulation works well.
• The ground wiring is connected correctly.
• The additional amount of refrigeration pipe work and addi-
tional refrigerant has been recorded.
• The power voltage fits the rated voltage of the air conditioner.
• There are no obstacle at the outlet and inlet of the outdoor and
indoor units.
• The gas-side and liquid-side stop valves are both opened.
• The air conditioner is pre-heated by turning on the power.
3. According to the user's requirement, install the remote controller holder where the remote controller's signal can reach the indoor unit smoothly.
4. Test operation
Set the air conditioner under the mode of "COOLING" with
the remote controller, and check the following points. If there is any malfunction, please resolve it according to the chapter "Troubleshooting" in the "Owner's Manual".
• 1) The indoor unit
a. Whether the switch on the remote controller works well.
b. Whether the buttons on the remote controller works
well.
c. Whether the air flow Louvre moves normally.
d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
f. Whether the temporary buttons works well.
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during
operation.
I. Whether the air conditioner heats well in the case of the
HEATING/COOLING type.
• 2) The outdoor unit
a. Whether there is vibration or abnormal noise during
operation.
b. Whether the generated wind, noise, or condensed of by
the air conditioner have influenced your neighbourhood.
c. Whether any of the refrigerant has leaked.
CAUTION
A protection feature prevents the air conditioner from being activated for approximately 3 minutes when it is restarted immediately after shut off.
Ceiling-Floor Type Indoor Unit
6720874436 (2017/04)
TEST OPERATION | 13
Page 14
14 | NOTES
6720874436 (2017/04)
Ceiling-Floor Type Indoor Unit
Page 15
Ceiling-Floor Type Indoor Unit
6720874436 (2017/04)
NOTES | 15
Page 16
Robert Bosch (Pty) Ltd., 15th Road, Randjespark 1685 Midrand SOUTH AFRICA
Loading...