Bosch B308 Installation Manual

1 | Overview
The B308 Octo-output Module is a supervised device that provides 8 programmable outputs (Form C relays) and connects to control panels through the SDI2 bus. Each output provides dry contact switching rated for a maximum of 1.0 A at 24 VDC. The outputs are accessed through on-board screw terminal connections. The address switches are used to set the module’s SDI2 address. Control panel programming determines each output’s response to specifi c events. The B308 receives serial data from the control panel and activates outputs in response to control panel conditions and settings. Outputs can be programmed for remote control from a control panel keypad.
Figure 2.1: Address switches
= Outputs 11 to 18
= Outputs 111 to 118
3 | Installation
After you set the address switches for the proper address, install the module in the enclosure, and then wire it to the control panel.
CAUTION!
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
3.1 | Mount the module in the enclosure
Figure 1.1: Board overview
Callout ― Description
1 ― SDI2 interconnect wiring connectors (to control panel or additional modules)
2 ― SDI2 terminal strip (to control panel or additional modules)
3 ― Tamper switch connector
4 ― Terminal strip (outputs)
5 ― Heartbeat LED (blue)
6 ― Address switches
2 | SDI2 address settings
Two address switches determine the address for the B308 Octo-output Module. The control panel uses the address for communications. The address also determines the output numbers. Use a slotted screwdriver to set the two address switches.
NOTICE!
The module reads the address switch setting only during power up. If you change the switches after you apply power to the module, you must cycle the power to the module to enable the new setting.
Set the address switches per the control panel confi guration. If multiple B308 modules reside on the same system, each B308
module must have a unique address.
The module’s address switches provide a tens and ones value for the module’s address. For single-digit address numbers 1 through 9, set the tens switch to 0 and the ones digit to the appropriate number. Figure 2.1 shows the address switches setting for addresses 1 and 11.
2.1 | Valid addresses and output numbers per control panel
Valid B308 addresses are dependent on the number of outputs allowed by a particular control panel.
Control panel
B9512G 01 - 59 11 - 18, 21 - 28, 31 - 38, 41 -
B8512G 01 - 09 11 - 18, 21 - 28, 31 - 38, 41 -
B5512 01 - 05 11 - 18, 21 - 28, 31 - 38,
B4512 01 - 03 11 - 18, 21 - 28, 31 - 38
D9412GV4 01 - 12 11 - 18, 21 - 28, 31 - 38,
D7412GV4 01 - 06 11 - 18, 21 - 28, 31 - 38,
D7212GV4 01 - 02 11 - 18, 21 - 24
To determine the output numbers for each address, multiply the address number by 10 for the base number, and then use numbers 1 through 8 in the ones place for the output numbers. For examples, refer to Section 8.
Valid B308 addresses
Corresponding output numbers
48, 51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98, 101 - 108, 111 - 118, 121 - 128, 131 ­138, 141 - 148, 151 - 158, 161 - 168, 171 - 178, 181
- 188, 191 - 198, 201 - 208, 211 - 218, 221 - 228, 231 - 238, 241 - 248, 251 ­258, 261 - 268, 271 - 278, 281 - 288, 291 - 298, 301
- 308, 311 - 318, 321 - 328, 331 - 338, 341 - 348, 351 ­358, 361 - 368, 371 - 378, 381 - 388, 391 - 398, 401
- 408, 411 - 418, 421 - 428, 431 - 438, 441 - 448, 451 ­458, 461 - 468, 471 - 478, 481 - 488, 491 - 498, 501
- 508, 511 - 518, 521 - 528, 531 - 538, 541 - 548, 551 ­558, 561 - 568, 571 - 578, 581 - 588, 591 - 598
48, 51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98
41 - 48, 51 - 58
41 - 48, 51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98, 101 - 108, 111 - 118, 121 - 128
41 - 48, 51 - 58, 61 - 64
Mount the module into the enclosure’s 3-hole mounting pattern using the supplied mounting screws and mounting bracket. Refer to Figure 3.1.
Figure 3.1: Mounting the module in the enclosure
Callout ― Description
1 ― Module with mounting bracket installed
2 ― Enclosure
3 ― Mounting screws (3)
3.2 | Mount and wire the tamper switch
You can connect an optional enclosure door tamper switch for one module in an enclosure. Installing the optional tamper switch:
1. Mount the ICP-EZTS Tamper Switch (P/N: F01U009269) into the enclosure’s tamper switch mounting location. For complete instructions, refer to EZTS Cover and Wall Tamper Switch Installation Guide (P/N: F01U003734).
2. Plug the tamper switch wire onto the module’s tamper switch connector. Refer to Figure 1.1.
3.3 | Wire to the control panel
When you wire the module to a control panel, you can use either the module’s terminal strip labeled with PWR, A, B, and COM, or the module’s interconnect wiring connectors (wire included). Interconnect wiring parallels the PWR, A, B, and COM terminals on the terminal strip. Figure 1.1 indicates the location of both the terminal strip and the interconnect connectors on the module.
Refer to Figures 3.2, 3.3, and 3.4.
NOTICE!
Use either the terminal strip wiring or interconnect wiring connector to the control panel. Do not use both. When connecting multiple modules, you can combine terminal strip and interconnect wiring connectors in series.
Figure 3.2: Using terminal strip or interconnect cable wiring
D9412GV4 shown)
Callout ― Description
1 ― Terminal strip wiring (SDI2)
2 ― Interconnect cable (P/N: F01U079745) (included)
Figure 3.3: Installing multiple modules using the SDI2 terminal
strip (D9412GV4 shown)
Callout ― Description
1 ― Bosch control panel
2 ― B308 modules
Figure 3.4: Installing multiple modules using the SDI2 interconnect wiring connector (D9412GV4 shown)
Callout ― Description
1 ― Bosch control panel
2 ― B308 modules
3.4 | Relay output wiring
Each output provides a NO and a NC output. The NO, C (COMMON), and NC terminals are available in each terminal or connection output position. The silkscreen on the edge of the B308 circuit board clearly identifi es the function of each terminal and the relay output number. The middle terminal of each output position is the COMMON of the output and is labeled C. When the output is in an inactive state, the NC (Normally Closed) terminal has continuity with the C terminal. When the output is in an active (energized) state, the NO (Normally Opened) has continuity with the C terminal.
NOTICE!
Do not exceed relay contact ratings of 1.0 A, 24 VDC, resistive load.
4 | LED descriptions
The module includes one blue heartbeat LED to indicate that the module has power and to indicate the module’s current state. Refer to Table 4.1.
Flash Pattern Function
Flashes once every 1 second
3 quick fl ashes every 1 second
ON Steady LED trouble state: Module is not
OFF Steady
Table 4.1: LED descriptions
Normal state: Indicates normal operation state.
Communication error state: Indicates (the module is in a “no communication state”) resulting in an SDI2 communication error.
powered (for OFF Steady only), or some other trouble condition prohibits the module from controlling the heartbeat LED.
5 | Show the fi rmware version
To show the fi rmware version using an LED fl ash pattern:
- If the optional tamper switch is installed: With the enclosure door open, activate the tamper switch (push and release the switch).
- If the optional tamper switch is NOT installed: Momentarily short the tamper pins.
Refer to Figure 5.1 for an example of fl ash pattern
Figure 5.1: Firmware LED fl ash patterns
When the tamper switch is activated, the heartbeat LED stays OFF for 3 second before indicating the fi rmware version. The LED pulses the major, minor, and micro digits of the fi rmware version, with a 1 second pause after each digit.
In the following example, the version 1.4.3 shows as LED fl ashes: [3 second pause] *___****___*** [3 second pause, then normal operation].
s.
6 | Certifi cations
Region
US UL 365 - Police Station Connected Burglar Alarm
Units and Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 864 - Control Units and Accessories for Fire Alarm Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar-Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and Systems
UL 1610 - Central-Station Burglar-Alarm Units
CSFM - California Offi ce of The State Fire Marshal
FCC Part 15 Class B
FDNY - Fire Department of New York
FM Approval 3010
Canada CAN/ULC-S303 Local Burglar Alarm Units and
Systems
CAN/ULC-S304 Central and Monitoring Station Burglar Alarm Units
ICES-003 - Information Technology Equipment (ITE)
ULC/ORD-C1023 Household Burglar Alarm Sys­tem Units
ULC/ORD-C1076 Proprietary Burglar Alarm Units and Systems
7 | Specifi cations
Dimensions 2.9 in x 5.0 in x 0.6 in
(73.5 mm x 127 mm x 15.25 mm)
Voltage (operating)
Current (maximum)
Operating temperature
Relative humidity
Relay outputs
Terminal wire size
SDI2 wiring Maximum distance - Wire size (Unshielded
Compatibility B9512G/B9512G-E
12 V nominal
150 mA (22 mA for digital section + 16 mA per energized relay)
+32°F to +122°F (0°C to +50°C)
5% to 93% at +90°C (+32°C) non­condensing
Dry contacts rated for .001 to 1.0 A at 5 to 24 VDC (resistive load).
12 AWG to 22 AWG (2 mm to 0.65 mm)
wire only): 400 ft (122 m) - 22 AWG (0.65 mm) 1000 ft (305 m) - 18 AWG (1.02 mm)
B8512G/B8512G-E B5512/B5512E B4512/B4512E D9412GV4 D7412GV4 D7212GV4 (Refer to the control panel installation document for number of supported devices.)
8 | Point number examples
For B308 address 01 the output numbers for the output devices are 11 through 18:
Terminal no 12345 678
Output no 11 12 13 14 15 16 17 18
For B308 address 11 the output numbers for the output devices are 111 through 118:
Terminal no 12345 678
Output no 111 112 113 114 115 116 117 118
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
Octo-output Module
B308
en Installation Guide
Bosch Security Systems, Inc.
130 Perinton Parkway Fairport, NY 14450 USA
www.boschsecurity.com
Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 5 85630 Grasbrunn Germany
© 2015 Bosch Security Systems, Inc. F.01U.265.458 | 04 | 2015.06
Loading...