Bosch 24I RSF User Manual

Bosch Group
24i RSF
WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING
AND MAINS FED DOMESTIC HOT WATER
INSTALLATION AND
SERVICING INSTRUCTIONS
N.G. 47 311 37 L.P.G. 47 311 38
BOILER OUTPUT
To Domestic Hot Water – Modulated Control
Minimum 7.5 kW (25,600 Btu/h)
Maximum 23.4 kW (80,000 Btu/h)
To Central Heating – Modulated Control\
Auto Range Rated
Minimum 7.5 kW (25,600 Btu/h)
Maximum 23.4 kW (80,000 Btu/h)
THESE INSTRUCTIONS APPLY IN THE UK ONLY
THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE GAS METER
This appliance must be installed by a competent person in accordance
with the Gas Safety (Installation and Use) Regulations 1994
1.1 Gas Safety (Installation and Use) Regulations, October 1994
all gas appliances must be installed by a competent person in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution.
1.2 The manufacturers notes must not be taken, in any way, as overriding statutory obligations.
1.3 The compliance with a British Standard does not, of itself, confer immunity from legal obligations. In particular the installation of this appliance must be in accordance with the relevant requirements of the following; Gas Safety (Installation and Use) Regulations 1994 as amended. Current IEE Wiring Regulations BS 7671. Local Building Regulations. Building Standards (Scotland)(Consolidation). Bylaws of the local Water Company. Health and Safety Document No. 635 (Electricity at Work Regulations). The British Gas Material and Installation Specification for central heating and hot water It should be in accordance with the relevant recommendations of the following British Standards. BS6798:1987 Specification for installation of gas fired hot water boilers of rated input not exceeding 60 kW. BS5449:1990 Central Heating for Domestic Premises. BS5546:1990 Installation of gas hot water supplies for domestic purposes. BS5440:1:1990 Flues and Ventilation for gas appliances of rated input not exceeding 60 kW: Flues. BS5440:2:1989 Flues and Ventilation for gas appliances of rated input not exceeding 60kW: Air Supply. BS6891:1988 Installation of low pressure gas pipework installations up to 28mm (R1). BS7593:1993 Central Heating system cleansing and flushing. BS5482:PART 1 Domestic Butane and Propane gas burning installations in permanent dwellings.
1.4 To ensure that the installation will perform to the highest standards, the system and components should conform to any other relevant British Standards in addition to those mentioned in the instructions.
1.5 The appliance complies with the Essential Requirements of the Gas Appliance Directive and other Directives currently applicable.
1.6 This appliance contains no asbestos products. There is no potential hazard due to the appliance being electrically unsafe. There are no substances used that are a potential hazard in relation to the COSHH Regulations 1988.
1.7 The advice and instructions given in this document covers, as far as possible, the foreseeable situations which may arise. Contact Worcester Heat Systems Technical Helpline for advice on specific installations.
2.1 This appliance is not suitable for external installation.
2.2 The appliance controls are set to provide a maximum output
of 23.4 kW for the domestic hot water and central heating load.
2.3 The control circuit provides direct burner ignition. A pilot is not used.
2.4 PRINCIPAL APPLIANCE COMPONENTS.
See Fig. 1. A low thermal capacity Gas to Water heat exchanger incorporating an integral Hot Water heat exchanger to provide domestic hot water. Fully modulating controls in the central heating and domestic hot water modes of operation. An expansion vessel, pressure gauge and pressure relief valve. A fixed by-pass for the central heating system. A Temperature safety cut-out control. A water flow regulator. A standard telescopic horizontal flue assembly giving flue lengths from 127mm to 350mm. Optional extra extension flue kits to provide for flue lengths up to 2500mm. An optional vertical flue kit to provide for flue lengths up to 3000mm including vertical flue terminal. Optional facia mounted mechanical programmer.
2. General Information1. Installation Regulations
2
1. Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 10. Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9
2. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 11. Installing the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11
3. Data Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4 12. Commissioning the Appliance . . . . . . . . . . . . . . . . . . . . Page 16
4. Siting the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 13. Instructions to the User . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
5. Siting the Flue. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 14. Inspection and Service. . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
6. Air Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 15. Replacement of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20
7. Sealed System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 16. Conversion Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . Page 23
8. Open Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 17. Operational Flow Diagrams. . . . . . . . . . . . . . . . . . . . . . . Page 24
9. Hot Water Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 18. Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19. Component Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 34
Contents
Fig. 1. Water flow diagram.
Bi-thermal gas to water heat exchanger
Automatic air vent
Domestic water flow switch
Pressure relief valve
Safety
discharge
Domestic hot water
out
Domestic
cold
supply
C.H.
return
Sealed system expansion vessel
Circulating pump
Fixed by-pass
C.H.
flow
2.5 ELECTRICAL SUPPLY
Mains supply: 230V ~, 50 Hz, 180 watts. External fuse: 3A., Internal fuses: 2AT HRC(F1), and 1 AF (F2).
2.6 GAS SUPPLY
The boiler requires 2.76 m3/h (97.5 ft3/hr) of natural gas with a calorific value of 37.78 MJ/m
3
(1014 Btu/ft3) or 1.07 m3/h (37.8
ft
3
/hr) of propane with a calorific value of 95.65 MJ/m3(2568
Btu/ft
3
). The meter governor should deliver a dynamic pressure of 20 mbar (8in w.g.) at the appliance, equivalent to a pressure of about 19-19.5 mbar at the gas valve on natural gas or 37.0 mbar (14.8in w.g.) at the appliance for propane. The gas meter and supply pipes must be capable of supplying this quantity of gas in addition to the demand from any other appliances being served. The table below gives an indication of limiting gas pipe lengths and the allowance to be made for fittings. Refer to BS6891 for further information. The complete installation, including the gas meter, must be tested for soundness and purged. Refer to BS 6891.
Note: Each fitting used in the gas line from the meter is equivalent to a length of straight pipe which must be added to the straight pipe length to give the total length. i.e.: Bend = 0.5 metres, Tee = 0.5 metres, 90° Bend = 0.3 metres.
2.7 PACKING
The appliance and flue components are packaged separately.
2.8 GENERAL INSTALLATION
The appliance is for connection to a sealed system only. The specified ventilation openings made into a wall or compartment door must not be obstructed. If the appliance is to be fitted into a compartment then the compartment must conform to the requirements of BS 6798: 1987: Section 7. Do not place anything on top of the appliance. The clearances specified for servicing must be maintained.
2.9 FLUE
The appliance has a multi-directional fanned flue system. The standard telescopic flue assembly length is from 127mm to 350mm. Extension flue lengths available are from 350mm to 2500mm. An optional vertical flue kit to provide for flue lengths up to 3000mm including vertical flue terminal. A terminal guard, Type K2, GC 393 553, is available from Tower Flue Components, Vale Rise, Tonbridge, TN9 1TB. Do not allow the flue terminal fitted to the outside wall to become obstructed or damaged. A kit for internal fixing of the flue is available separately.
2.10 CONTROLS
The electronic control system and gas valve modulate the heat input in response to the domestic hot water temperature and central heating setting between minimum and maximum. The Central Heating Temperature control knob provides for the selection of domestic hot water only (Turned fully anti-clockwise) or central heating and domestic hot water (Turned clockwise). A facia mounted programmer is available as an optional extra. A remote mounted programmer may be connected to the appliance. There is provision for the connection of a mains voltage room thermostat and/or a frost thermostat. The electronic controls prevent rapid cycling of the appliance in the central heating mode.
2.11 SYSTEM NOTES IMPORTANT
Check that no dirt is left in either the gas or water pipework as this could cause damage to the appliance. The heating system should be flushed and treated in accordance with the recommendations of BS 7593:1992. Thoroughly flush cold water mains supply and purge the gas supply before finally connecting the appliance. The water pipe connections throughout a sealed system must be capable of sustaining a pressure of up to 3 bar. Radiator valves must conform to the requirements of BS 2767:1991. The relief valve discharge must be directed away from any electrical components or where it would cause a hazard to the user. A drain cock to BS 2879 must be fitted to the lowest point of the system. For circuit design purposes it is important that due note is taken of the information given in Table 3, section 3 relating to the available pump head.
2.12 SHOWERS, BIDETS, TAPS AND MIXING VALVES
Hot and cold taps and mixing valves used in the system must be suitable for operating at mains pressure. Thermostatically controlled shower valves will guard against the flow of water at too high a temperature. Hot and cold mains fed water can be supplied direct to an over­rim flushing bidet subject to local Water Company requirements. With all mains fed systems the flow of water from the individual taps will vary with the number of outlets operated simultaneously and the cold water mains supply pressure to the property. Flow balancing using “Ball-o-Fix” type valves is recommended to avoid an excessive reduction in flow to individual outlets.
2.13 SAFETY CONSIDERATIONS
The appliance must not be operated in a waterless condition. The appliance must not be operated with the boiler inner casing cover removed. Work must not be carried out on the appliance without the gas and electricity supplies being switched off. Checks must be made to ensure that the ventilation openings made into walls and partitions are unobstructed and the correct size.
2.14 OPERATION Domestic Hot Water:
With a demand for hot water the burner will light at its maximum setting and then automatically adjust its output to maintain the temperature of the delivered water. When hot water is no longer required, the burner will extinguish. The fan and pump may continue to run for a short period to dissipate the residual heat from the appliance. Central Heating: With a demand for heating the burner will light at its minimum setting and gradually increase to give a controlled temperature rise. When the required heating temperature is achieved the output of the appliance is then automatically adjusted to maintain the temperature of the system. The output can reduce down to a minimum of 7.5 kW. If the system no longer requires even the minimum output to maintain the desired room temperature the burner will extinguish. The fan and pump may continue to run to dissipate the residual heat from the appliance. The appliance will remain off for a fixed period before re-lighting to automatically meet the system requirements. Domestic Hot Water and Central Heating: The appliance will supply heat to the central heating system as required. A demand for domestic hot water at a tap or shower will override the central heating requirement for the period of the domestic hot water demand. When hot water is no longer required the appliance will return to the central heating state and its normal mode of operation. The fan may continue to run to dissipate the residual heat from the appliance as necessary.
2.15 DOMESTIC SUPPLY
Devices capable of preventing the flow of expansion water must not be fitted unless separate arrangements have been made.
3
Total length of gas supply pipe Pipe size
(metres) (Ømm)
36912
Propane
Gas Discharge
1.5 15
Rate
8.0 5.2 4.2 3.6 22
(m
3
/hr)
15.9 8.8 8.5 7.2 28
Natural Gas
8.7 5.8 4.6 22
18.0 12.0 9.4 28
Gas
Discharge
Rate
(m3/hr)
The data plate is fixed to the inner casing cover.
3. Data Tables
4
NOMINAL BOILER RATINGS
OUTPUT INPUT (Net).
BURNER SETTING
GAS RATE
PRESSURE
kW Btu/h kW Btu/h m bar. in. wg. m
3
/h ft3/h
NATURAL GAS
7.5 (25,600) 9.60 (32,750) 1.0 0.4 1.01 35.7
23.4 (80,000) 26.05 (88,890) 13.6 5.4 2.76 97.5
PROPANE
7.5 (25,600) 9.60 (32,750) 3.5 1.4 0.39 13.9
23.4 (80,000) 26.05 (88,890) 35.0 14.0 1.07 37.8
Table 1
AVAILABLE PUMP HEAD
BOILER OUTPUT HEAD MIN. FLOW RATE
TEMPERATURE RISE
ACROSS HEATING
kW Btu/h Metres Feet L/min. Gal/Min. FLOW AND RETURN
7.5 (25,600) 6.0 19.7 9.8 2.2 11°C (20°F)
23.4 (80,000) 2.6 8.5 30.5 6.7
Table 3
SPECIFICATIONS
CENTRAL HEATING FLOW FITTING 22mm Compression CENTRAL HEATING RETURN FITTING 22mm Compression COLD WATER MAINS INLET FITTING 15mm Compression DOMESTIC HOT WATER OUTLET FITTING 15mm Compression GAS INLET FITTING Rc
1
2inch PRESSURE RELIEF VALVE DISCHARGE FITTING 15 mm Copper Tube OVERALL HEIGHT (including flue turret) 960mm (37.8 inches) CASING HEIGHT 800mm (31.5 inches) CASING WIDTH 450mm (17.7 inches) CASING DEPTH 360mm (14.2 inches) WEIGHT(including water) 44 kg INSTALLATION WEIGHT 39 kg PACKAGED WEIGHT 44 kg PRIMARY WATER CAPACITY 3.0 litres MAXIMUM COLD SUPPLY PRESSURE 10 Bar (150 psi) MINIMUM COLD SUPPLY PRESSURE (working) for max. hot water flow 0.9 bar MINIMUM COLD SUPPLY PRESSURE (working) to operate appliance 0.1 bar MAXIMUM CENTRAL HEATING FLOW TEMPERATURE Nominally 82°C (180°F) OUTPUT TO DOMESTIC HOT WATER Modulating 7.5 to 23.4 kW OUTPUT TO CENTRAL HEATING Modulating 7.5 to 23.4 kW MAXIMUM DOMESTIC HOT WATER FLOW RATE (from the appliance) Nominally 8.0 ± 15% litres/min EQUIVALENT DOMESTIC HOT WATER FLOW RATE TO GIVE A TEMP RISE Nominally 11.2 litres/min
OF 30°C (SPECIFIC RATE)
Table 4
FLUE DETAILS
HORIZONTAL FLUE (Side or Rear) mm inches
FLUE DIAMETER 100 3.9 WALL HOLE DIAMETER 110 4.25 WALL HOLE DIAMETER (using internal flue fitting kit) 150 5.9 STANDARD FLUE – MINIMUM LENGTH 127 5.0 STANDARD FLUE – MAXIMUM LENGTH 350 14.0 EXTENDED FLUE – MAXIMUM LENGTH 2500 98.4
Table 2.
4.1 The appliance may be installed in any room although
particular attention is drawn to the requirements of the current IEE Wiring Regulations BS 7671 and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of appliances in rooms containing baths or showers. Where a room sealed appliance is installed in a room containing a bath or shower, any electrical switch or appliance control using mains electricity must not be able to be touched by a person using the bath or shower.
4.2 The appliance is not suitable for external installation.
4.3 The appliance does not require any special wall protection.
4.4 The wall must be capable of supporting the weight of the
appliance. See Table 4.
4.5 The following clearances must be available for installation and for servicing. See Fig. 2. (note the clearances at the front are for a removable panel e.g. a door).
4.6 The appliance can be installed in a cupboard used for airing clothes provided that the requirements of BS 6798 and BS 5440:2 are strictly followed.
Notwithstanding the instructions given in BS 5440:2, this appliance may be fitted in a compartment with no vents as long as the minimum clearances stated in Section 6: Air Supply, are maintained.
4.7 The airing space must be separated from the boiler space by a perforated non-combustible partition. Expanded metal or rigid wire mesh are acceptable provided that the major dimension is less than 13mm. See BS 6798:1987.
4.8 No combustible surface must be within 75mm of the casing. See BS476:4.
4.9 Always consider the possible need to disconnect the pipes from the appliance after installation.
4.10 LPG Installation: The appliance shall not be installed in a room or internal space below ground level when it is intended for use with LPG. This does not preclude the installation into rooms which are basements with respect to one side of the building but open to ground level on the opposite side.
4. Siting The Appliance
5
Above 180mm In front 0 mm In front to a fixed surface 600mm Below 200mm Right-hand side 10 mm Left-hand side 10 mm
Fig. 2. Appliance casing dimensions and
required clearances.
Side view
360mm 600mm*
20mm*
200mm* 10mm*
* Space required for installation and servicing
Front view
450mm
10mm*
225mm
180mm
800mm
See Fig. 3.
5.1 The flue must be installed as specified in BS 5440:Part 1.
5.2 The terminal must not cause an obstruction nor the
discharge cause a nuisance.
5.3 If the terminal is fitted within 850mm of a plastic or painted gutter or within 450mm of painted eaves then an aluminium shield at least 750mm long should be fitted to the underside of the gutter or painted surface.
5.4 If a terminal is fitted less than 2 metres above a surface to which people have access then a guard must be fitted. See Section 2.9.
5.5 The terminal guard must be evenly spaced about the flue terminal and fixed to the wall using plated screws.
5.6 In certain weather conditions a terminal may steam and siting where this could cause a nuisance should be avoided.
5.7 Take care to ensure that combustion products do not enter ventilated roof voids.
6.1 The appliance does not require a separate vent for combustion air.
6.2 The appliance can be fitted in a cupboard with no vents for cooling but the minimum clearances must be increased to those given below (note the clearances at the front are for a removable panel e.g. a door).
6.3 If the appliance is to be fitted in a cupboard or compartments with less clearance than those above (minimum clearances given in Section 4. Siting The Appliance) then permanent vents for cooling are required. One at high level and one at low level, either direct to outside air or to a room. Both vents must pass to the same room or be on the same wall to the outside air.
6.4 The minimum free areas required are given below.
6.5 Refer to BS 6798 and BS 5440:2 for additional information.
6. Air Supply5. Siting The Flue
6
L
L
K
K
F
F
G
A
M
EJF
HI
D
G
A
B,C
Fig. 3. Siting of the flue terminal.
TERMINAL POSITION MIN. DISTANCE TERMINAL POSITION MIN. DISTANCE
A– directly below an openable window or I– From a terminal facing a terminal 1200mm (47in.)
other opening e.g. air brick. 300mm (12in.) J– From an opening in a car port (e.g. door B– Below gutters, soil pipes or drain pipes. 75mm (3in.) window) into dwelling. 1200mm (47in.) C– Below eaves. 25mm (1in.) K– Vertically from a terminal on the same D– Below balconies or car port roof. 25mm (1in.) wall. 150mm (6in.) E– From vertical drain pipes and soil pipes. 25mm (1in.) L– Horizontally from a terminal on the same F– From internal or external corners. 25mm (1in.) wall. 300mm (12in.) G– Above ground, roof or balcony level. 300mm (12in.) M– From door, window or air vent (achieve H– From a surface facing a terminal. 600mm (24in.) where possible). 150mm (6in.)
Above the Turret 20mm In front 250mm Below 200mm Right-hand side 75mm Left-hand side 75mm
POSITION OF AIR FROM AIR DIRECT
AIR VENTS THE ROOM FROM OUTSIDE
HIGH LEVEL 270cm
2
135cm
2
LOW LEVEL 270cm
2
135cm
2
See Figs. 4.
7.1 The system must comply with the requirements of BS 6798 and BS 5449.
7.2 The appliance must not be operated without the system being full of water, properly vented and pressurised.
7.3 The pressure relief valve operates at 3 bar (45lb/in2). The discharge must be directed away from electrical components or where it might be a hazard to the user.
7.4 The pressure gauge indicates the system pressure which must be maintained.
7.5 The 8 litre expansion vessel is charged to 0.5 bar and is suitable for a static head of 5 metres (17.5ft). The pressure can be increased if the static head is greater than 5 metres (17.5ft).
7.6 With an initial system pressure of 0.5 bar, a system capacity of up to 100 litres can be accommodated. For system capacities greater than this an extra expansion vessel must be fitted. Refer to BS 7074 Pt. 1 for more information. The charge pressure can be increased but with a consequent decrease in system volume.
7.7 The filling point must be at low level. See Fig. 4.
7.8 Water loss must be replaced. See Fig 4. The connection
should be made in the central heating return as close to the appliance as possible.
7.9 Repeated venting loses water from the system. It is essential that this water is replaced and the system pressure maintained.
7.10 Connections to the mains water supply must not be made without the authority of the local Water Company.
7.11 The pump is set at maximum and must not be adjusted.
7.12 Connections in the system must sustain a pressure of up to
3 bar.
7.13 Radiator valves must conform to BS 2767:10.
7.14 Other valves used should conform to the requirements of
BS 1010.
7.15 The appliance is fitted with a fixed internal by-pass. But it is advisable to keeps one radiator permanently open.
The appliance is
NOT suitable for connection to an open vented
system.
8. Open Vent System
7. Sealed System
7
Fig. 4. Sealed primary water system.
Automatic air vent
Expansion vessel
Hot water out
Water main
Heating return Heating flow
Radiator valve
Lockshield valve
Mains cold
water
British Standard stop valve. Fixed spindle type
NOTE: A drain cock should be installed at the lowest point of the heating circuit and beneath the appliance.
Filling Loop Detail
Heating Return
Non-return
Valve
Non-return
Valve
Test cock
Hose union
Stop cock
Temporary Hose
9.1 The following are general requirements and, if necessary, reference should be made to the local Water Company before fitting the appliance.
9.2 MAINS COLD WATER INLET. Devices capable of preventing the flow of expansion water must not be fitted unless separate arrangements have been made. A mini expansion vessel kit is available which contains the necessary parts for fitting an internal expansion vessel to the appliance. See Section 19 COMPONENT PARTS LIST. A thread sealant compatible with potable water must be used. An external expansion vessel may be fitted on the mains cold water connection to the appliance.
9.3
The final 600mm of the mains cold water connection to the
appliance should be made in copper tube only.
9.4 The appliance is suitable for a mains pressure of up to 10 bar (150 lb/in
2
).
9.5 The appliance is fitted with a mains supply isolating valve.
9.6 The maximum domestic hot water flow rate is 8.0 litres/min
(±15%) (1.8 gallons/min).
9.7 In winter (when the mains inlet water temperature is lower) a reduced flow rate at the taps may be required to achieve the type of hot water delivery temperature available in warmer weather.
9.8 It is suggested that long pipe runs to the taps or shower should be insulated to prevent the rapid cooling of domestic hot water after a tap or shower has been turned off.
9.9 Hot and cold taps and mixing valves used with this appliance must be suitable for operating at mains pressure and temperatures of 65°C.
9.10 No anti-syphonage arrangements are necessary except for some loose head showers. See also Section 9.11 following.
9.11 Thermostatically controlled or pressure equalising shower valves will guard against the flow of water at too high a temperature.
9.12 The head of a loose head shower must not fall closer than 25mm (1in.) above the top edge of the bath to prevent its immersion in bath water. Alternatively the shower must be fitted with an anti-syphonage device at the point of the flexible hose connections.
9.13 The supply of hot and cold mains water direct to a bidet is permitted, (subject to local Water Company requirements), provided that the bidet is of the over-rim flushing type. The outlet(s) should be shrouded and unable to have any temporary hand held spray attached. No anti-syphonage arrangements are necessary.
9.14 LIME SCALE. In temporary hard water areas (more than 350mg/litre or 200ppm calcium bicarbonate) it is recommended that a proprietary scale reducer is fitted in the mains cold water connection to the appliance. Consult the local water company for additional advice. Installation of a scale inhibitor assembly should be in accordance with the requirements of the local Water Company. An isolating valve should be fitted to allow servicing. The water hardness can be determined by reference to the local Water Company.
9.15 NOTE: HOT WATER ONLY. If required the appliance may be used for Hot Water only before the Central Heating is connected. A 22mm copper by­pass pipe at least 4 meters long must be connected between the Central Heating Flow and Return, but it is advisable to connect a small radiator instead. IT IS NOT RECOMMENDED TO USE THE BOILER IN THIS CONDITION FOR EXTENDED PERIODS.
9. Hot Water Supply
8
Fig. 5. 230V room thermostat connections.
Fig. 6. 230V programmer connections.
RN RI
X2
Remove link
Neutral
Switched live
Live
RL
CN
Motor
CI
X2
Neutral
Switched live
Live
CL
Remove link
10.1 MAINS SUPPLY.
230 V ~, 50 Hz, 180 watts. External Fuse: 3A. Internal Fuses: 2AT HRC(F1), and 1.AF (F2).
10.2 It must be possible to completely isolate the appliance.
10.3 The following connection alternatives must be used:
A 3 amp fused three-pin plug and unswitched shuttered socket outlet (both complying with the requirements of BS 1363) or a double pole isolator with a contact separation of 3mm in all poles and supplying the appliance and controls only.
10.4 The appliance must be earthed.
10.5 Mains Cable. 0.75mm2(24 x 0.20mm) to BS 6500 Table 16.
The mains cable must be connected into the terminal
X1,
marked
L (Brown or Red lead), N (Blue or Black lead) and the earth stud and be held securely in the cable clamp. For access undo the three bottom screws and remove the facia access cover. See Fig. 7.
10.6 The wiring between the appliance and the electrical supply shall comply with current IEE Wiring Regulations and any local regulations which apply.
10.7 If a room thermostat and/or external programmer is to be fitted refer to Figs 5 and 6. The devices must be suitable for use with mains voltage.
10.8 A facia mounted mechanical programmer is available as an optional extra. Instructions are supplied with the programmer kits.
10.9 A time switch or programmer can be fitted externally to the appliance.
10.10 The boiler provides automatic frost protection, the use of a frost thermostat is not recommended. However if an external frost thermostat is considered necessary then it must be used in
conjunction with a programmer.
Important: To provide external frost protection the appliance must have the Central Heating Temperature Control Knob set to
supply heating (the appliance may then be left with the central heating turned off on the programmer). Connection must be made at
X2 terminals RI and CL. For advice on external frost thermostats contact Worcester Heat Systems Technical Helpline
10.11 SAFETY CHECK.
After installation or in the event of an electrical fault the electrical system shall be checked for short circuits, fuse failure, incorrect polarity of connections, earth continuity and resistance to earth.
10. Electrical
9
Fig. 7. Mains electricity connections.
Brown
Strain relief clamp
Blue
Brown
Green/yellow
Green/yellow
Programmer and room thermostat
strain relief clamps
230V
X1
X2
NL
Blue
Fig. 8. Wiring diagram.
Safety
limit stat
DHW sensor
CH
sensor
Gas valve
Pump
Main
Reg
Flow switch
Air
pressure
switch
Spark
transformer
Mains in
2 pink
2 Blue
2 Red
2 Yellow
2 Orange
Brown
Blue
Blue
Brown
Blue
Brown
Brown
Blue
Link Link
X1
X2
X3
X6
X5 X4
Flame sense electrode
Spark electrode
Fan
Brown
White
Green
3 COM
1 NC
2 NO
10
Fig. 9. Functional flow diagram.
F1 2ATHRC
F2 1.25AT
Optional links
SparkFlame sense
Outputs Inputs
Mains indicator
Modulating
valve
Overheat stat
X6 Pins 8 & 9
X6 Pins 15 & 16
X6 Pins 5,6 & 7
X6 Pins 1 & 2
X6 Pins 19 & 20
X6 Pins 3 & 4
Flow signal
CH temp. sensor
DHW temp. sensor
CH control POT
Air pressure switch
MAINS PROGRAMMER/CLOCK
FULL SEQUENCE
CONTROLLER
GAS VALVE
LOW VOLTAGE
ELECTRONICS
(Microcontroller)
ROOM STAT
X1
X2
321
1
2
3
4
6
5
RL1
X3
Pin 1 X3 Pin 2
X4 Pin 3
X5 Pin 3
X5 Pin 2X5 Pin 1
X4 Pin 1
FAN
PUMP
RL3
RL4
N
N
N
N
L
Technical Helpline.
The appliance is only suitable for fitting to a sealed system.
11.1 FLUE OPTIONS.
The standard flue length is from 127mm to 350mm measured from the appliance casing to the outer wall. Extension flue kits, a vertical take-off adapter, 45° and 90° flue bends are available to increase the length and redirect the flue as follows. Horizontal balanced flue:
a) From 127mm to 2500mm straight flue. b) From 127mm to 1750mm when a 90° flue bend is
required.
c) From 127mm to 1000mm when two 90° flue bends are
required. A 90° flue bend is equivalent to 750mm of straight flue. A 45° flue bend is equivalent to half a 90° bend. Refer to Figs. 21 and 22 to determine whether extension kits, 90° flue bend, 45° flue bend, or adapters are required. The maximum number of 90° flue bends allowed is two.
Flue components
1. Turret clamping ring.
2. Flue turret assembly
3. Flue terminal assembly
4. Extension air duct
5. Extension flue duct
6. In-line 90° flue bend
7. In-line 45° flue bend
8. Vertical flue adapter
The flue must be installed as specified in BS 5440 Part 1.
NOTE: READ THIS SECTION FULLY BEFORE COMMENCING INSTALLATION
11.2 GENERAL FITTING.
Check that the appliance carton contains:- Appliance, Installers Instruction Pack, Appliance Wall Plate, Users Information Pack, Installer Hardware Pack and an appliance template. Check that the position chosen for the appliance is in accordance with the instructions given in Sections 4 and 5. Hold the template to the wall. Check that the template is horizontal. See Fig. 10. Mark the position of the fixing holes and the position of the flue hole centre line onto the wall. See Fig. 10.
Side Flue – Extend the flue hole centre line from Fig. 11 along the appropriate wall. Check that it remains horizontal and mark a horizontal line. Measure 222mm from the junction of the walls and mark a vertical line which will then give the position of the flue hole. Drill the two fixing holes 60mm deep for No. 12 size plugs. Cut the flue duct hole at 110mm diameter (150mm dia. for internal fitting). Ensure that the hole is horizontal through the wall. Fit the wall mounting bracket.
Drill the two fixing holes 60mm deep for No. 12 size plugs. For the boiler retaining screws.
Fix the wall plate and check that it is horizontal before tightening the 2 screws.
Hang the appliance on the wall plate and screw the appliance to the wall using the screws provided.
11. Installing The Appliance
11
Fig. 10. Appliance mounting plate and flue position.
Fig. 11. Marking out the side flue position.
Mounting wall
Rear flue hole 110mm dia. (150mm dia. for internal fixing)
Side flue hole 110mm dia. (150mm dia. for internal fixing)
Appliance casing
Mounting plate
Fixing holes (alternatives)
Mounting wall
Mounting plate
222mm
Side wall
166mm
740mm
400mm
Rear flue position Side flue position
60mm
Appliance casing
Rear flue hole 110mm dia. (150mm dia. for internal fixing)
Mounting wall
Side wall
222mm
166mm
Loading...
+ 25 hidden pages