Bosch 24I RSF User Manual

Page 1
Bosch Group
24i RSF
WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING
AND MAINS FED DOMESTIC HOT WATER
INSTALLATION AND
SERVICING INSTRUCTIONS
N.G. 47 311 37 L.P.G. 47 311 38
BOILER OUTPUT
To Domestic Hot Water – Modulated Control
Minimum 7.5 kW (25,600 Btu/h)
Maximum 23.4 kW (80,000 Btu/h)
To Central Heating – Modulated Control\
Auto Range Rated
Minimum 7.5 kW (25,600 Btu/h)
Maximum 23.4 kW (80,000 Btu/h)
THESE INSTRUCTIONS APPLY IN THE UK ONLY
THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE GAS METER
This appliance must be installed by a competent person in accordance
with the Gas Safety (Installation and Use) Regulations 1994
Page 2
1.1 Gas Safety (Installation and Use) Regulations, October 1994
all gas appliances must be installed by a competent person in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution.
1.2 The manufacturers notes must not be taken, in any way, as overriding statutory obligations.
1.3 The compliance with a British Standard does not, of itself, confer immunity from legal obligations. In particular the installation of this appliance must be in accordance with the relevant requirements of the following; Gas Safety (Installation and Use) Regulations 1994 as amended. Current IEE Wiring Regulations BS 7671. Local Building Regulations. Building Standards (Scotland)(Consolidation). Bylaws of the local Water Company. Health and Safety Document No. 635 (Electricity at Work Regulations). The British Gas Material and Installation Specification for central heating and hot water It should be in accordance with the relevant recommendations of the following British Standards. BS6798:1987 Specification for installation of gas fired hot water boilers of rated input not exceeding 60 kW. BS5449:1990 Central Heating for Domestic Premises. BS5546:1990 Installation of gas hot water supplies for domestic purposes. BS5440:1:1990 Flues and Ventilation for gas appliances of rated input not exceeding 60 kW: Flues. BS5440:2:1989 Flues and Ventilation for gas appliances of rated input not exceeding 60kW: Air Supply. BS6891:1988 Installation of low pressure gas pipework installations up to 28mm (R1). BS7593:1993 Central Heating system cleansing and flushing. BS5482:PART 1 Domestic Butane and Propane gas burning installations in permanent dwellings.
1.4 To ensure that the installation will perform to the highest standards, the system and components should conform to any other relevant British Standards in addition to those mentioned in the instructions.
1.5 The appliance complies with the Essential Requirements of the Gas Appliance Directive and other Directives currently applicable.
1.6 This appliance contains no asbestos products. There is no potential hazard due to the appliance being electrically unsafe. There are no substances used that are a potential hazard in relation to the COSHH Regulations 1988.
1.7 The advice and instructions given in this document covers, as far as possible, the foreseeable situations which may arise. Contact Worcester Heat Systems Technical Helpline for advice on specific installations.
2.1 This appliance is not suitable for external installation.
2.2 The appliance controls are set to provide a maximum output
of 23.4 kW for the domestic hot water and central heating load.
2.3 The control circuit provides direct burner ignition. A pilot is not used.
2.4 PRINCIPAL APPLIANCE COMPONENTS.
See Fig. 1. A low thermal capacity Gas to Water heat exchanger incorporating an integral Hot Water heat exchanger to provide domestic hot water. Fully modulating controls in the central heating and domestic hot water modes of operation. An expansion vessel, pressure gauge and pressure relief valve. A fixed by-pass for the central heating system. A Temperature safety cut-out control. A water flow regulator. A standard telescopic horizontal flue assembly giving flue lengths from 127mm to 350mm. Optional extra extension flue kits to provide for flue lengths up to 2500mm. An optional vertical flue kit to provide for flue lengths up to 3000mm including vertical flue terminal. Optional facia mounted mechanical programmer.
2. General Information1. Installation Regulations
2
1. Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 10. Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9
2. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 11. Installing the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11
3. Data Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4 12. Commissioning the Appliance . . . . . . . . . . . . . . . . . . . . Page 16
4. Siting the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 13. Instructions to the User . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
5. Siting the Flue. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 14. Inspection and Service. . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
6. Air Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 15. Replacement of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20
7. Sealed System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 16. Conversion Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . Page 23
8. Open Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 17. Operational Flow Diagrams. . . . . . . . . . . . . . . . . . . . . . . Page 24
9. Hot Water Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 18. Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19. Component Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 34
Contents
Fig. 1. Water flow diagram.
Bi-thermal gas to water heat exchanger
Automatic air vent
Domestic water flow switch
Pressure relief valve
Safety
discharge
Domestic hot water
out
Domestic
cold
supply
C.H.
return
Sealed system expansion vessel
Circulating pump
Fixed by-pass
C.H.
flow
Page 3
2.5 ELECTRICAL SUPPLY
Mains supply: 230V ~, 50 Hz, 180 watts. External fuse: 3A., Internal fuses: 2AT HRC(F1), and 1 AF (F2).
2.6 GAS SUPPLY
The boiler requires 2.76 m3/h (97.5 ft3/hr) of natural gas with a calorific value of 37.78 MJ/m
3
(1014 Btu/ft3) or 1.07 m3/h (37.8
ft
3
/hr) of propane with a calorific value of 95.65 MJ/m3(2568
Btu/ft
3
). The meter governor should deliver a dynamic pressure of 20 mbar (8in w.g.) at the appliance, equivalent to a pressure of about 19-19.5 mbar at the gas valve on natural gas or 37.0 mbar (14.8in w.g.) at the appliance for propane. The gas meter and supply pipes must be capable of supplying this quantity of gas in addition to the demand from any other appliances being served. The table below gives an indication of limiting gas pipe lengths and the allowance to be made for fittings. Refer to BS6891 for further information. The complete installation, including the gas meter, must be tested for soundness and purged. Refer to BS 6891.
Note: Each fitting used in the gas line from the meter is equivalent to a length of straight pipe which must be added to the straight pipe length to give the total length. i.e.: Bend = 0.5 metres, Tee = 0.5 metres, 90° Bend = 0.3 metres.
2.7 PACKING
The appliance and flue components are packaged separately.
2.8 GENERAL INSTALLATION
The appliance is for connection to a sealed system only. The specified ventilation openings made into a wall or compartment door must not be obstructed. If the appliance is to be fitted into a compartment then the compartment must conform to the requirements of BS 6798: 1987: Section 7. Do not place anything on top of the appliance. The clearances specified for servicing must be maintained.
2.9 FLUE
The appliance has a multi-directional fanned flue system. The standard telescopic flue assembly length is from 127mm to 350mm. Extension flue lengths available are from 350mm to 2500mm. An optional vertical flue kit to provide for flue lengths up to 3000mm including vertical flue terminal. A terminal guard, Type K2, GC 393 553, is available from Tower Flue Components, Vale Rise, Tonbridge, TN9 1TB. Do not allow the flue terminal fitted to the outside wall to become obstructed or damaged. A kit for internal fixing of the flue is available separately.
2.10 CONTROLS
The electronic control system and gas valve modulate the heat input in response to the domestic hot water temperature and central heating setting between minimum and maximum. The Central Heating Temperature control knob provides for the selection of domestic hot water only (Turned fully anti-clockwise) or central heating and domestic hot water (Turned clockwise). A facia mounted programmer is available as an optional extra. A remote mounted programmer may be connected to the appliance. There is provision for the connection of a mains voltage room thermostat and/or a frost thermostat. The electronic controls prevent rapid cycling of the appliance in the central heating mode.
2.11 SYSTEM NOTES IMPORTANT
Check that no dirt is left in either the gas or water pipework as this could cause damage to the appliance. The heating system should be flushed and treated in accordance with the recommendations of BS 7593:1992. Thoroughly flush cold water mains supply and purge the gas supply before finally connecting the appliance. The water pipe connections throughout a sealed system must be capable of sustaining a pressure of up to 3 bar. Radiator valves must conform to the requirements of BS 2767:1991. The relief valve discharge must be directed away from any electrical components or where it would cause a hazard to the user. A drain cock to BS 2879 must be fitted to the lowest point of the system. For circuit design purposes it is important that due note is taken of the information given in Table 3, section 3 relating to the available pump head.
2.12 SHOWERS, BIDETS, TAPS AND MIXING VALVES
Hot and cold taps and mixing valves used in the system must be suitable for operating at mains pressure. Thermostatically controlled shower valves will guard against the flow of water at too high a temperature. Hot and cold mains fed water can be supplied direct to an over­rim flushing bidet subject to local Water Company requirements. With all mains fed systems the flow of water from the individual taps will vary with the number of outlets operated simultaneously and the cold water mains supply pressure to the property. Flow balancing using “Ball-o-Fix” type valves is recommended to avoid an excessive reduction in flow to individual outlets.
2.13 SAFETY CONSIDERATIONS
The appliance must not be operated in a waterless condition. The appliance must not be operated with the boiler inner casing cover removed. Work must not be carried out on the appliance without the gas and electricity supplies being switched off. Checks must be made to ensure that the ventilation openings made into walls and partitions are unobstructed and the correct size.
2.14 OPERATION Domestic Hot Water:
With a demand for hot water the burner will light at its maximum setting and then automatically adjust its output to maintain the temperature of the delivered water. When hot water is no longer required, the burner will extinguish. The fan and pump may continue to run for a short period to dissipate the residual heat from the appliance. Central Heating: With a demand for heating the burner will light at its minimum setting and gradually increase to give a controlled temperature rise. When the required heating temperature is achieved the output of the appliance is then automatically adjusted to maintain the temperature of the system. The output can reduce down to a minimum of 7.5 kW. If the system no longer requires even the minimum output to maintain the desired room temperature the burner will extinguish. The fan and pump may continue to run to dissipate the residual heat from the appliance. The appliance will remain off for a fixed period before re-lighting to automatically meet the system requirements. Domestic Hot Water and Central Heating: The appliance will supply heat to the central heating system as required. A demand for domestic hot water at a tap or shower will override the central heating requirement for the period of the domestic hot water demand. When hot water is no longer required the appliance will return to the central heating state and its normal mode of operation. The fan may continue to run to dissipate the residual heat from the appliance as necessary.
2.15 DOMESTIC SUPPLY
Devices capable of preventing the flow of expansion water must not be fitted unless separate arrangements have been made.
3
Total length of gas supply pipe Pipe size
(metres) (Ømm)
36912
Propane
Gas Discharge
1.5 15
Rate
8.0 5.2 4.2 3.6 22
(m
3
/hr)
15.9 8.8 8.5 7.2 28
Natural Gas
8.7 5.8 4.6 22
18.0 12.0 9.4 28
Gas
Discharge
Rate
(m3/hr)
Page 4
The data plate is fixed to the inner casing cover.
3. Data Tables
4
NOMINAL BOILER RATINGS
OUTPUT INPUT (Net).
BURNER SETTING
GAS RATE
PRESSURE
kW Btu/h kW Btu/h m bar. in. wg. m
3
/h ft3/h
NATURAL GAS
7.5 (25,600) 9.60 (32,750) 1.0 0.4 1.01 35.7
23.4 (80,000) 26.05 (88,890) 13.6 5.4 2.76 97.5
PROPANE
7.5 (25,600) 9.60 (32,750) 3.5 1.4 0.39 13.9
23.4 (80,000) 26.05 (88,890) 35.0 14.0 1.07 37.8
Table 1
AVAILABLE PUMP HEAD
BOILER OUTPUT HEAD MIN. FLOW RATE
TEMPERATURE RISE
ACROSS HEATING
kW Btu/h Metres Feet L/min. Gal/Min. FLOW AND RETURN
7.5 (25,600) 6.0 19.7 9.8 2.2 11°C (20°F)
23.4 (80,000) 2.6 8.5 30.5 6.7
Table 3
SPECIFICATIONS
CENTRAL HEATING FLOW FITTING 22mm Compression CENTRAL HEATING RETURN FITTING 22mm Compression COLD WATER MAINS INLET FITTING 15mm Compression DOMESTIC HOT WATER OUTLET FITTING 15mm Compression GAS INLET FITTING Rc
1
2inch PRESSURE RELIEF VALVE DISCHARGE FITTING 15 mm Copper Tube OVERALL HEIGHT (including flue turret) 960mm (37.8 inches) CASING HEIGHT 800mm (31.5 inches) CASING WIDTH 450mm (17.7 inches) CASING DEPTH 360mm (14.2 inches) WEIGHT(including water) 44 kg INSTALLATION WEIGHT 39 kg PACKAGED WEIGHT 44 kg PRIMARY WATER CAPACITY 3.0 litres MAXIMUM COLD SUPPLY PRESSURE 10 Bar (150 psi) MINIMUM COLD SUPPLY PRESSURE (working) for max. hot water flow 0.9 bar MINIMUM COLD SUPPLY PRESSURE (working) to operate appliance 0.1 bar MAXIMUM CENTRAL HEATING FLOW TEMPERATURE Nominally 82°C (180°F) OUTPUT TO DOMESTIC HOT WATER Modulating 7.5 to 23.4 kW OUTPUT TO CENTRAL HEATING Modulating 7.5 to 23.4 kW MAXIMUM DOMESTIC HOT WATER FLOW RATE (from the appliance) Nominally 8.0 ± 15% litres/min EQUIVALENT DOMESTIC HOT WATER FLOW RATE TO GIVE A TEMP RISE Nominally 11.2 litres/min
OF 30°C (SPECIFIC RATE)
Table 4
FLUE DETAILS
HORIZONTAL FLUE (Side or Rear) mm inches
FLUE DIAMETER 100 3.9 WALL HOLE DIAMETER 110 4.25 WALL HOLE DIAMETER (using internal flue fitting kit) 150 5.9 STANDARD FLUE – MINIMUM LENGTH 127 5.0 STANDARD FLUE – MAXIMUM LENGTH 350 14.0 EXTENDED FLUE – MAXIMUM LENGTH 2500 98.4
Table 2.
Page 5
4.1 The appliance may be installed in any room although
particular attention is drawn to the requirements of the current IEE Wiring Regulations BS 7671 and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of appliances in rooms containing baths or showers. Where a room sealed appliance is installed in a room containing a bath or shower, any electrical switch or appliance control using mains electricity must not be able to be touched by a person using the bath or shower.
4.2 The appliance is not suitable for external installation.
4.3 The appliance does not require any special wall protection.
4.4 The wall must be capable of supporting the weight of the
appliance. See Table 4.
4.5 The following clearances must be available for installation and for servicing. See Fig. 2. (note the clearances at the front are for a removable panel e.g. a door).
4.6 The appliance can be installed in a cupboard used for airing clothes provided that the requirements of BS 6798 and BS 5440:2 are strictly followed.
Notwithstanding the instructions given in BS 5440:2, this appliance may be fitted in a compartment with no vents as long as the minimum clearances stated in Section 6: Air Supply, are maintained.
4.7 The airing space must be separated from the boiler space by a perforated non-combustible partition. Expanded metal or rigid wire mesh are acceptable provided that the major dimension is less than 13mm. See BS 6798:1987.
4.8 No combustible surface must be within 75mm of the casing. See BS476:4.
4.9 Always consider the possible need to disconnect the pipes from the appliance after installation.
4.10 LPG Installation: The appliance shall not be installed in a room or internal space below ground level when it is intended for use with LPG. This does not preclude the installation into rooms which are basements with respect to one side of the building but open to ground level on the opposite side.
4. Siting The Appliance
5
Above 180mm In front 0 mm In front to a fixed surface 600mm Below 200mm Right-hand side 10 mm Left-hand side 10 mm
Fig. 2. Appliance casing dimensions and
required clearances.
Side view
360mm 600mm*
20mm*
200mm* 10mm*
* Space required for installation and servicing
Front view
450mm
10mm*
225mm
180mm
800mm
Page 6
See Fig. 3.
5.1 The flue must be installed as specified in BS 5440:Part 1.
5.2 The terminal must not cause an obstruction nor the
discharge cause a nuisance.
5.3 If the terminal is fitted within 850mm of a plastic or painted gutter or within 450mm of painted eaves then an aluminium shield at least 750mm long should be fitted to the underside of the gutter or painted surface.
5.4 If a terminal is fitted less than 2 metres above a surface to which people have access then a guard must be fitted. See Section 2.9.
5.5 The terminal guard must be evenly spaced about the flue terminal and fixed to the wall using plated screws.
5.6 In certain weather conditions a terminal may steam and siting where this could cause a nuisance should be avoided.
5.7 Take care to ensure that combustion products do not enter ventilated roof voids.
6.1 The appliance does not require a separate vent for combustion air.
6.2 The appliance can be fitted in a cupboard with no vents for cooling but the minimum clearances must be increased to those given below (note the clearances at the front are for a removable panel e.g. a door).
6.3 If the appliance is to be fitted in a cupboard or compartments with less clearance than those above (minimum clearances given in Section 4. Siting The Appliance) then permanent vents for cooling are required. One at high level and one at low level, either direct to outside air or to a room. Both vents must pass to the same room or be on the same wall to the outside air.
6.4 The minimum free areas required are given below.
6.5 Refer to BS 6798 and BS 5440:2 for additional information.
6. Air Supply5. Siting The Flue
6
L
L
K
K
F
F
G
A
M
EJF
HI
D
G
A
B,C
Fig. 3. Siting of the flue terminal.
TERMINAL POSITION MIN. DISTANCE TERMINAL POSITION MIN. DISTANCE
A– directly below an openable window or I– From a terminal facing a terminal 1200mm (47in.)
other opening e.g. air brick. 300mm (12in.) J– From an opening in a car port (e.g. door B– Below gutters, soil pipes or drain pipes. 75mm (3in.) window) into dwelling. 1200mm (47in.) C– Below eaves. 25mm (1in.) K– Vertically from a terminal on the same D– Below balconies or car port roof. 25mm (1in.) wall. 150mm (6in.) E– From vertical drain pipes and soil pipes. 25mm (1in.) L– Horizontally from a terminal on the same F– From internal or external corners. 25mm (1in.) wall. 300mm (12in.) G– Above ground, roof or balcony level. 300mm (12in.) M– From door, window or air vent (achieve H– From a surface facing a terminal. 600mm (24in.) where possible). 150mm (6in.)
Above the Turret 20mm In front 250mm Below 200mm Right-hand side 75mm Left-hand side 75mm
POSITION OF AIR FROM AIR DIRECT
AIR VENTS THE ROOM FROM OUTSIDE
HIGH LEVEL 270cm
2
135cm
2
LOW LEVEL 270cm
2
135cm
2
Page 7
See Figs. 4.
7.1 The system must comply with the requirements of BS 6798 and BS 5449.
7.2 The appliance must not be operated without the system being full of water, properly vented and pressurised.
7.3 The pressure relief valve operates at 3 bar (45lb/in2). The discharge must be directed away from electrical components or where it might be a hazard to the user.
7.4 The pressure gauge indicates the system pressure which must be maintained.
7.5 The 8 litre expansion vessel is charged to 0.5 bar and is suitable for a static head of 5 metres (17.5ft). The pressure can be increased if the static head is greater than 5 metres (17.5ft).
7.6 With an initial system pressure of 0.5 bar, a system capacity of up to 100 litres can be accommodated. For system capacities greater than this an extra expansion vessel must be fitted. Refer to BS 7074 Pt. 1 for more information. The charge pressure can be increased but with a consequent decrease in system volume.
7.7 The filling point must be at low level. See Fig. 4.
7.8 Water loss must be replaced. See Fig 4. The connection
should be made in the central heating return as close to the appliance as possible.
7.9 Repeated venting loses water from the system. It is essential that this water is replaced and the system pressure maintained.
7.10 Connections to the mains water supply must not be made without the authority of the local Water Company.
7.11 The pump is set at maximum and must not be adjusted.
7.12 Connections in the system must sustain a pressure of up to
3 bar.
7.13 Radiator valves must conform to BS 2767:10.
7.14 Other valves used should conform to the requirements of
BS 1010.
7.15 The appliance is fitted with a fixed internal by-pass. But it is advisable to keeps one radiator permanently open.
The appliance is
NOT suitable for connection to an open vented
system.
8. Open Vent System
7. Sealed System
7
Fig. 4. Sealed primary water system.
Automatic air vent
Expansion vessel
Hot water out
Water main
Heating return Heating flow
Radiator valve
Lockshield valve
Mains cold
water
British Standard stop valve. Fixed spindle type
NOTE: A drain cock should be installed at the lowest point of the heating circuit and beneath the appliance.
Filling Loop Detail
Heating Return
Non-return
Valve
Non-return
Valve
Test cock
Hose union
Stop cock
Temporary Hose
Page 8
9.1 The following are general requirements and, if necessary, reference should be made to the local Water Company before fitting the appliance.
9.2 MAINS COLD WATER INLET. Devices capable of preventing the flow of expansion water must not be fitted unless separate arrangements have been made. A mini expansion vessel kit is available which contains the necessary parts for fitting an internal expansion vessel to the appliance. See Section 19 COMPONENT PARTS LIST. A thread sealant compatible with potable water must be used. An external expansion vessel may be fitted on the mains cold water connection to the appliance.
9.3
The final 600mm of the mains cold water connection to the
appliance should be made in copper tube only.
9.4 The appliance is suitable for a mains pressure of up to 10 bar (150 lb/in
2
).
9.5 The appliance is fitted with a mains supply isolating valve.
9.6 The maximum domestic hot water flow rate is 8.0 litres/min
(±15%) (1.8 gallons/min).
9.7 In winter (when the mains inlet water temperature is lower) a reduced flow rate at the taps may be required to achieve the type of hot water delivery temperature available in warmer weather.
9.8 It is suggested that long pipe runs to the taps or shower should be insulated to prevent the rapid cooling of domestic hot water after a tap or shower has been turned off.
9.9 Hot and cold taps and mixing valves used with this appliance must be suitable for operating at mains pressure and temperatures of 65°C.
9.10 No anti-syphonage arrangements are necessary except for some loose head showers. See also Section 9.11 following.
9.11 Thermostatically controlled or pressure equalising shower valves will guard against the flow of water at too high a temperature.
9.12 The head of a loose head shower must not fall closer than 25mm (1in.) above the top edge of the bath to prevent its immersion in bath water. Alternatively the shower must be fitted with an anti-syphonage device at the point of the flexible hose connections.
9.13 The supply of hot and cold mains water direct to a bidet is permitted, (subject to local Water Company requirements), provided that the bidet is of the over-rim flushing type. The outlet(s) should be shrouded and unable to have any temporary hand held spray attached. No anti-syphonage arrangements are necessary.
9.14 LIME SCALE. In temporary hard water areas (more than 350mg/litre or 200ppm calcium bicarbonate) it is recommended that a proprietary scale reducer is fitted in the mains cold water connection to the appliance. Consult the local water company for additional advice. Installation of a scale inhibitor assembly should be in accordance with the requirements of the local Water Company. An isolating valve should be fitted to allow servicing. The water hardness can be determined by reference to the local Water Company.
9.15 NOTE: HOT WATER ONLY. If required the appliance may be used for Hot Water only before the Central Heating is connected. A 22mm copper by­pass pipe at least 4 meters long must be connected between the Central Heating Flow and Return, but it is advisable to connect a small radiator instead. IT IS NOT RECOMMENDED TO USE THE BOILER IN THIS CONDITION FOR EXTENDED PERIODS.
9. Hot Water Supply
8
Fig. 5. 230V room thermostat connections.
Fig. 6. 230V programmer connections.
RN RI
X2
Remove link
Neutral
Switched live
Live
RL
CN
Motor
CI
X2
Neutral
Switched live
Live
CL
Remove link
Page 9
10.1 MAINS SUPPLY.
230 V ~, 50 Hz, 180 watts. External Fuse: 3A. Internal Fuses: 2AT HRC(F1), and 1.AF (F2).
10.2 It must be possible to completely isolate the appliance.
10.3 The following connection alternatives must be used:
A 3 amp fused three-pin plug and unswitched shuttered socket outlet (both complying with the requirements of BS 1363) or a double pole isolator with a contact separation of 3mm in all poles and supplying the appliance and controls only.
10.4 The appliance must be earthed.
10.5 Mains Cable. 0.75mm2(24 x 0.20mm) to BS 6500 Table 16.
The mains cable must be connected into the terminal
X1,
marked
L (Brown or Red lead), N (Blue or Black lead) and the earth stud and be held securely in the cable clamp. For access undo the three bottom screws and remove the facia access cover. See Fig. 7.
10.6 The wiring between the appliance and the electrical supply shall comply with current IEE Wiring Regulations and any local regulations which apply.
10.7 If a room thermostat and/or external programmer is to be fitted refer to Figs 5 and 6. The devices must be suitable for use with mains voltage.
10.8 A facia mounted mechanical programmer is available as an optional extra. Instructions are supplied with the programmer kits.
10.9 A time switch or programmer can be fitted externally to the appliance.
10.10 The boiler provides automatic frost protection, the use of a frost thermostat is not recommended. However if an external frost thermostat is considered necessary then it must be used in
conjunction with a programmer.
Important: To provide external frost protection the appliance must have the Central Heating Temperature Control Knob set to
supply heating (the appliance may then be left with the central heating turned off on the programmer). Connection must be made at
X2 terminals RI and CL. For advice on external frost thermostats contact Worcester Heat Systems Technical Helpline
10.11 SAFETY CHECK.
After installation or in the event of an electrical fault the electrical system shall be checked for short circuits, fuse failure, incorrect polarity of connections, earth continuity and resistance to earth.
10. Electrical
9
Fig. 7. Mains electricity connections.
Brown
Strain relief clamp
Blue
Brown
Green/yellow
Green/yellow
Programmer and room thermostat
strain relief clamps
230V
X1
X2
NL
Blue
Fig. 8. Wiring diagram.
Safety
limit stat
DHW sensor
CH
sensor
Gas valve
Pump
Main
Reg
Flow switch
Air
pressure
switch
Spark
transformer
Mains in
2 pink
2 Blue
2 Red
2 Yellow
2 Orange
Brown
Blue
Blue
Brown
Blue
Brown
Brown
Blue
Link Link
X1
X2
X3
X6
X5 X4
Flame sense electrode
Spark electrode
Fan
Brown
White
Green
3 COM
1 NC
2 NO
Page 10
10
Fig. 9. Functional flow diagram.
F1 2ATHRC
F2 1.25AT
Optional links
SparkFlame sense
Outputs Inputs
Mains indicator
Modulating
valve
Overheat stat
X6 Pins 8 & 9
X6 Pins 15 & 16
X6 Pins 5,6 & 7
X6 Pins 1 & 2
X6 Pins 19 & 20
X6 Pins 3 & 4
Flow signal
CH temp. sensor
DHW temp. sensor
CH control POT
Air pressure switch
MAINS PROGRAMMER/CLOCK
FULL SEQUENCE
CONTROLLER
GAS VALVE
LOW VOLTAGE
ELECTRONICS
(Microcontroller)
ROOM STAT
X1
X2
321
1
2
3
4
6
5
RL1
X3
Pin 1 X3 Pin 2
X4 Pin 3
X5 Pin 3
X5 Pin 2X5 Pin 1
X4 Pin 1
FAN
PUMP
RL3
RL4
N
N
N
N
L
Page 11
Technical Helpline.
The appliance is only suitable for fitting to a sealed system.
11.1 FLUE OPTIONS.
The standard flue length is from 127mm to 350mm measured from the appliance casing to the outer wall. Extension flue kits, a vertical take-off adapter, 45° and 90° flue bends are available to increase the length and redirect the flue as follows. Horizontal balanced flue:
a) From 127mm to 2500mm straight flue. b) From 127mm to 1750mm when a 90° flue bend is
required.
c) From 127mm to 1000mm when two 90° flue bends are
required. A 90° flue bend is equivalent to 750mm of straight flue. A 45° flue bend is equivalent to half a 90° bend. Refer to Figs. 21 and 22 to determine whether extension kits, 90° flue bend, 45° flue bend, or adapters are required. The maximum number of 90° flue bends allowed is two.
Flue components
1. Turret clamping ring.
2. Flue turret assembly
3. Flue terminal assembly
4. Extension air duct
5. Extension flue duct
6. In-line 90° flue bend
7. In-line 45° flue bend
8. Vertical flue adapter
The flue must be installed as specified in BS 5440 Part 1.
NOTE: READ THIS SECTION FULLY BEFORE COMMENCING INSTALLATION
11.2 GENERAL FITTING.
Check that the appliance carton contains:- Appliance, Installers Instruction Pack, Appliance Wall Plate, Users Information Pack, Installer Hardware Pack and an appliance template. Check that the position chosen for the appliance is in accordance with the instructions given in Sections 4 and 5. Hold the template to the wall. Check that the template is horizontal. See Fig. 10. Mark the position of the fixing holes and the position of the flue hole centre line onto the wall. See Fig. 10.
Side Flue – Extend the flue hole centre line from Fig. 11 along the appropriate wall. Check that it remains horizontal and mark a horizontal line. Measure 222mm from the junction of the walls and mark a vertical line which will then give the position of the flue hole. Drill the two fixing holes 60mm deep for No. 12 size plugs. Cut the flue duct hole at 110mm diameter (150mm dia. for internal fitting). Ensure that the hole is horizontal through the wall. Fit the wall mounting bracket.
Drill the two fixing holes 60mm deep for No. 12 size plugs. For the boiler retaining screws.
Fix the wall plate and check that it is horizontal before tightening the 2 screws.
Hang the appliance on the wall plate and screw the appliance to the wall using the screws provided.
11. Installing The Appliance
11
Fig. 10. Appliance mounting plate and flue position.
Fig. 11. Marking out the side flue position.
Mounting wall
Rear flue hole 110mm dia. (150mm dia. for internal fixing)
Side flue hole 110mm dia. (150mm dia. for internal fixing)
Appliance casing
Mounting plate
Fixing holes (alternatives)
Mounting wall
Mounting plate
222mm
Side wall
166mm
740mm
400mm
Rear flue position Side flue position
60mm
Appliance casing
Rear flue hole 110mm dia. (150mm dia. for internal fixing)
Mounting wall
Side wall
222mm
166mm
Page 12
Connect the gas, water and pressure relief valve connections to the appliance. The primary system should be flushed and treated in accordance with the recommendations of BS7593:1992.
If the air and flue duct assembly is to be fitted from inside the room then the ducts must be adjusted to length, assembled and inserted through the wall at this stage before fitting the flue turret to the appliance. Refer to Section 11.3 following for the assembly of the air and flue ducts.
Remove the fan. See Section 14.3(e).
11.3 AIR AND FLUE DUCT PREPARATION AND ASSEMBLY
Check the contents of the standard flue kit against the packing list. Similarly check the extension kits if applicable. Remove all the packing from the flue and terminal assembly. The standard flue kit accommodates a flue assembly up to 350mm long measured from the appliance casing to the outer wall face. See dimension
L, Figs.13 and 14.
When dimension
L is greater than 350mm extension flue assemblies will be required. It will not be necessary to cut either the ducts attached to the turret or the terminal unless
L = 350 to 450mm.
Measure and cut the extension ducts to length ensuring that the cuts are square and free from burrs. Always check the dimensions before cutting the ducts. All extension duct dimensions refer to the straight lengths. The socketed ends must not be removed or included in any measurement.
11.4 EXTERNAL FITTING OF THE DUCT ASSEMBLY
Measure distance L. Side flue duct length =
L + 184mm. See Fig. 14.
Rear flue duct length =
L + 181mm. See Fig. 13. Do not cut either the turret or the terminal assembly ducts unless
L = 350 to 450mm.
1. Should L = 350 to 450mm then cut the terminal assembly
ducts reducing the length of the ducts to 200mm. Then cut each extension duct to 200mm (See Fig. 15). Assemble the flue as described below ensuring the correct length (
L+184mm for side
flues or
L+181mm for rear flues).
12
Fig. 13. Rear flue.
Fig. 14. Side flue.
Fig. 15. 350-450 Special.
Rear face of appliance and face of mounting wall
External wall face
40mm
Make good
L
Appliance casing
Fixing screws
Flue extension duct length 200mm
Air extension duct length 200mm
Terminal assembly reduced to 200mm
Turret assembly with full standard duct lengths
Rear flue
L + 181mm
Side flue L + 184mm
L = 350mm-450mm
Appliance side panel
External wall face
40mm
Make good
L
Fig. 12. Appliance pipework connections.
(A)
100mm
36.5mm
(B)
(C)
(D)
(E)
(F)
A Safety Relief = 50mm B CH Flow = 95mm C DHW Out = 160mm D Gas Inlet = 225mm E Mains Cold Water In = 290mm F CH Return = 355mm
Page 13
2. If L is within the range 127mm to 350mm then the flue can be telescopically adjusted to the correct length (
L+184mm for
side flues or
L+181mm for rear flues). The ducts are then fixed by drilling a pilot hole through the hole in the air duct and screwing the self tapping screw provided into the two ducts (See Fig. 16).
3. If L is within any of the following ranges it will not be necessary to cut the extension ducts:
0.88m to 1.10m, 1.63m to 1.85m or 2.38m to 2.50m. Each extension must be connected to the first section of flue or the previous extension by firstly fitting the inner flue ducts together and pilot drilling and fixing. (See Fig. 17). Then the outer air ducts can be similarly fixed using the pair of screws provided. The flue terminal section can then be telescopically adjusted and fixed as before (See Fig. 16) ensuring the correct length (
L+184mm for side flues or L+181mm for rear flues).
4. In the event of L not falling within any of the above ranges
it will be necessary to cut the FIRST extension length. The air and flue duct lengths should both be reduced to the same
length: L – 240mm where one extension is used; L – 990mm with two extensions and
L – 1,740mm with three. (See Fig. 17). The flue can then be assembled ensuring that the cut extension is fitted to the turret duct assembly first and that the flue is adjusted to the correct length of (
L+184mm for side flues or
L+181mm for rear flues) (See Fig. 16).
5. Finishing the flue
Apply the plastic tape provided to the last section of flue where it will be sealed to the external brickwork. From inside, push the assembly through the wall, align the flue turret with the socket on the appliance, push the turret down to fully engage it and clamp in place with the turret clamping ring. See Fig.
18. Make good the internal and external brickwork or rendering. Refit the fan and replace the inner casing cover.
13
Fig. 17. Extensions.
Fig. 18. Flue turret fixing.
Reset button
Flue Gas
Test Point
Flue turret
Turret clamping
ring
Rear flue L + 181mm
Side flue L + 184mm
Appliance casing
Fixing screws Fixing screw
Turret assembly
Terminal assembly
L = 450mm-2500mm
Extensions of equal length
Shorten first extension fitted
to the turret assembly
Fig. 16. Standard flue assembly.
Appliance casing
Fixing screw
Turret assembly
Terminal assembly
Rear flue
L + 181mm
Side flue L + 184mm
L
Page 14
11.5 INTERNAL FITTING OF THE DUCT ASSEMBLY
The rubber sealing gasket and the clamping ring are available from Worcester Heat Systems. Measure and cut the ducts as previously described for external fitting (Section 11.4). Fix the ducts to the terminal and fit the rubber sealing gasket and clamp to the terminal. Centralise the gasket and tighten the clamping ring. See Fig. 19. Slide the flue centering ring onto the air duct and tighten the screw. See Fig. 20. Fix the ducts and terminal assembly to the flue turret as described in Section 11.4 preceding.
Apply the plastic tape provided to the last section of flue where it will be sealed to the external brickwork. Push the assembly through the wall so that the gasket flange is against the outside face of the wall. See Fig. 20.
Align the flue turret with the socket on the appliance, push the turret down to fully engage it and clamp in place with the turret clamping ring. See Fig. 18. Refit the fan and replace the inner casing cover. Seal the gap around the duct with the flexible seal provided and make good. See Fig. 20.
11.6 FLUE BENDS
See Figs 21 and 22. Measure distances
X, Y and Z as appropriate.
Side flue duct length =
X + 63mm. See Fig. 21.
Rear flue duct length =
X + 60mm. See Fig. 21. Cut the flue and air ducts which are to make up the first section X such that both the assemblies are of equal length (either X + 63mm or
X + 60mm). Extensions will be necessary to allow X to be larger than 250mm. Any extension ducts are fixed by drilling a pilot hole through the hole in the duct or elbow and screwing the self tapping screw
provided into the two ducts. (See Fig. 21). The length
Y is the distance between bends the ducts must be
cut to
Y – 162mm. The swaged ends must be removed from the extension tube and only the air duct needs fixing. See Fig. 21. Z is the final flue length from the last elbow to the outside face of the external wall. The first duct sections fitted to the elbow must have unswaged ends. The length of the air ducts should be
Z – 196mm. The inner flue duct must be 30mm longer than the air duct. If
Z – 196mm is less than 160mm then the terminal section will need to be shortened to the same length as the extension flue section fitted to the elbow (length
Z – 100). If flue extensions are needed to attain the required length care must be taken to ensure that the last section of flue is longer than 260mm. Each extension must be connected to the previous section of flue or bend by firstly fitting the inner flue ducts together and pilot drilling and fixing as above (See Fig. 21). Then the outer air ducts can be similarly fixed using the pair of screws provided. The flue terminal section can then be telescopically adjusted and fixed as before (See Fig. 21), ensuring the correct length of
Z – 41. The silicon sealant supplied should be applied to the flue ducts which engage into elbows. See Fig. 21. From inside, push the assembly through the wall Align the flue turret with the socket on the appliance, push the turret down to fully engage it and clamp in place with the turret clamping ring. See Fig. 18. Make good the internal and external brickwork or rendering. Refit the fan. Do not use any sealant on the joint. Replace the inner casing cover.
14
Fig. 21. Flue bends.
56mm
Z Ð 41mm
56mm
Side flue
X + 63mm
Rear flue X + 60mm
Z
Y
X
Y
Ð 162mm
Fig. 19. Terminal assembly for internal
fitting of the flue.
Flue centring ring Flue terminal
Flue duct
Rubber sealing gasket
Air duct
Rubber sealing gasket
Clamping ring
Flue terminal
Fig. 20. Duct and terminal assembly for
internal fitting of the flue.
Page 15
11.7 VERTICAL ADAPTER
Measure and fit the flue as in Section 11.6 Flue bends except the first section length is measured from the case top and the ducts are cut to
X – 168mm. The minimum length for X is 190mm. See
Fig. 22.
11.8 FINAL INSTALLATION
Check that all the water and gas connections have been tightened. If a facia mounted programmer is to be fitted follow instructions with the programmer.. Remove the facia bottom panel as described in Section 14.3(c). Connect the mains electrical supply to the appliance at terminal X1. See Fig. 23. Connect any room and/or frost thermostats. The electrical leads must pass through the appropriate space in the control panel and be fixed with the cable clamps provided. Refit the facia panel. Test the gas supply pipework up to the appliance for soundness as indicated in BS 6891. Refer to Section 12 for a full description of the filling, venting and the pressurising of the system. If the appliance is not to be commissioned immediately, replace the cabinet front panel. Check that the gas supply, the electrical supply and the water connections are all turned off. If the premises are to be left unoccupied during frosty conditions, then drain the appliance and system. For short inoperative periods, leave the appliance under the control of the built in frost thermostat or the remote frost thermostat (if fitted) or leave operating continuously with the room thermostat set at 6°C.
15
Fig. 22. Vertical adaptor with
horizontal flue.
X-168
Y-162
90¡
90¡
Appliance
Vertical flue adaptor required for upwards section
TOTAL STRAIGHT FLUE LENGTH X + Y + Z or X + Z
2500mm with one bend 1750mm with two bends 1000mm with three bends
Z-41
Fig. 23. Mains electricity connections.
Brown
Strain relief clamp
Green/yellow
Programmer and room thermostat
strain relief clamps
230V
X1
X2
NL
Blue
Page 16
12.1 SUMMARY
The appliance is dispatched with the controls set to provide a maximum output for domestic hot water and central heating of
23.4 kW (80,000 Btu/h). The appliance automatically modulates to satisfy lower heat loads. Domestic Hot Water and Central Heating Systems. Check that both the mains water supply and central heating systems have been fully flushed out at installation. Gas Service. The complete system, including the meter, must be inspected and tested for soundness and purged as indicated in BS 6891.
12.2 APPLIANCE AND CENTRAL HEATING SYSTEM PREPARATION
Remove the cabinet front panel. Check that the electrical supply and the gas service to the appliance are off. Check that all the water connections throughout the system are tight. Open the system valves at the appliance. Open all the radiator valves, fill the system and vent each radiator in turn. Remove the inner casing cover as described in section 14.3(b). See Fig 24.
The automatic air vent will vent the appliance. Check that the air vent cap has been removed. See Fig. 25. Check that the pressure relief valve operates by turning the knob anti-clockwise until it releases. Water should be expelled from the discharge pipe. See Fig. 26. Lower the control box to gain access. Refer to Section 14.3(c).
Set the Expansion Vessel Pressure
The charge pressure of the expansion vessel as dispatched is 0.5 bar, which is equivalent to a static head of 5 metres (17ft). The charge pressure must not be less than the static head at the point of connection. A Schraider type tyre valve is fitted to the expansion vessel to allow the charge pressure to be increased if necessary.
Set the System Pressure
Fill the system until the pressure gauge shows 2.5 bar (37 lb/ins
2
) and check for water soundness. Release water from the system using the relief valve test knob until the initial System Design Pressure is obtained, up to a maximum of 1.5 bar. Initial System Design Pressure (bar) = Expansion Vessel Charge Pressure +0.3 (bar).
Note: 1 bar is equivalent to 10.2 metres (33.5 ft) of water. Set the movable pointer on the pressure gauge to coincide with the indicating pointer giving a permanent record of the set system pressure. If the pressure indicated on the pressure gauge is greater than
2.6 bar when operating at the maximum central heating temperature, an extra expansion vessel must be fitted to the system as close as possible to the appliance central heating return connection. The appliance (as dispatched) can accommodate a system volume of about 100 litres. Refer to BS 7074 Part 1. If the system volume is in excess of that accommodated by the expansion vessel fitted to the appliance then an extra vessel must be fitted as close as possible to the central heating return connection of the appliance. Any extra vessel fitted must be pressurised to the same figure as the integral vessel. If the expansion vessel fails then the specified replacement must be fitted.
12. Commissioning The Appliance
16
Fig. 25. Appliance components and fixings (upper assembly).
Flue hood
Overheat thermostat
Burner fixing screws (2)
Combustion chamber cover fixing clips (2)
Auto air vent
Fan assembly fixing screws (4)
Flue Gas Test Point
Fig. 24. Appliance casing and control equipment fixings.
Inner casing cover screws (4)
Side casing fixing screws (4)
Facia panel fixing screws (2)
Bottom facia panel fixing screws (3)
Fig. 26. Pressure relief valve.
Pressure relief valve. (Turn knob anti-clockwise to test).
Page 17
12.3 PROGRAMMER
Any programmer fitted on the appliance should be set up at this stage following the instructions sent with the programmer.
12.4 APPLIANCE OPERATION
Turn off the gas and electricity supplies to the appliance. Undo the two screws and hinge down the facia. Loosen the burner pressure test point screw and connect a pressure gauge. See Fig. 27.
Domestic Hot Water.
Set any Programmer to HEATING & WATER. Turn on the gas and electricity supplies. Set the Central Heating temperature control knob to Off. A tap should be opened to create a hot water demand then a continuous ignition spark will occur until the burner is alight and sensed by the control circuit. The burner will light and remain at its maximum setting. The burner pressure should be between
13.4 and 13.8 mbar on Natural gas (33.0 and 35.0 mbar on Propane). If the burner pressure is low, check that the supply pressure at the gas valve inlet is at least 19 mbar for Natural gas (37 mbar for Propane). Test for gas soundness at the joint between the burner and the gas valve with leak detection fluid. Note: The burner pressure is factory set and if (after checking that the supply pressure is sufficient) the correct pressure is not obtained then Worcester Heat Systems Service Department should be contacted. Gradually close the hot tap and check that the burner pressure drops. Fully open the tap and check that the burner pressure rises. Fully close the tap and check that the burner goes off. The fan may continue running until the appliance has cooled.
Central Heating
Check that all the radiator valves are open. Check that the system is pressurised and set to the required pressure as indicated on the gauge. Set any Programmer to HEATING & WATER. Turn on the gas and electricity supplies. Set the room thermostat and the Central Heating Temperature Control to maximum. The burner will light. The appliance will modulate its output between 7.5 and 23.4 kW over a period of about twenty minutes. Check the system to ensure that all the radiators are heating up evenly. Shut down all but one of the radiators and observe the burner pressure fall. Open all of the radiator valves and check that the burner pressure rises. Balance the system so that the required temperature difference across the central heating flow and return pipes is obtained. See Table 3, Section 3 Data Tables. Set the room thermostat to minimum and check that the burner goes out. Reset the room thermostat to maximum and the burner will re-light after a short anti-cycle delay and follow the normal operating procedure. Check for proper ignition of the burner after a break in the gas supply. Turn off the gas service cock and wait for 60 seconds. The burner will go out but sparking from the electrode will continue for 10 seconds when the appliance will enter a “lockout” state. Carefully open the gas service cock, interrupt the mains power supply to the appliance for a few seconds to reset the controls and observe the burner re-light and follow the normal sequence of operation. Turn off the gas service cock and the electrical supply to the appliance. Drain the system while the appliance is still hot. Refill, vent and re-pressurise as described in Section 12.2.
Domestic Hot Water and Central Heating
Turn on the electricity supply to the appliance and open the gas supply cock at the appliance. Set the Central Heating temperature control knob to demand and any programmer to HEATING & WATER. If a programmer is fitted, set the domestic hot water to Continuous or 24 Hrs and the central heating to ON. The burner will light and heat will pass into the system. Turn on a hot water tap and check that after a short delay fully heated hot water is discharged from the tap. Close the tap and the burner will go off. After a short time the appliance will then return to the central heating mode and automatically balance with the system requirements. Set the Central Heating Temperature Control Knob to OFF and the burner will go out.
12.5 COMPLETION OF COMMISSIONING
Disconnect the pressure gauge and tighten the test point screw. Restart the appliance and check for gas soundness around the test point screw. Refit the cabinet front panel. If the appliance is being passed over to the user immediately, refer to Section 13 - Instructions to the User and set the controls to the users requirements. If the appliance is to be left inoperative, check that the Central Heating Temperature Control is set to OFF. Turn off the gas service cock and switch off the electricity supply. If there is any possibility of the appliance and system being left inoperative during frosty conditions, drain the appliance and system. If the premises are to be left unoccupied during frosty conditions, then drain the appliance and system. For short inoperative periods, leave the appliance under the control of the built in frost thermostat or the remote frost thermostat (if fitted) or leave operating continuously with the room thermostat set at 6°C.
17
Fig. 27. Gas valve.
Main gas valve connections (Black : blue : brown : green/yellow)
Burner pressure test point
Inlet pressure test point
Electrical connections Ð modulator (Blue : Blue)
Modulating solenoid
Minimum pressure adjuster
Maximum pressure adjuster Note: Clockwise to increase and anti­clockwise to decrease the pressure
Page 18
13.1 Tell the user how to operate the appliance and hand over the Users Instructions leaflet.
13.2 Tell the user what to do if the heating system is not to be used in frosty weather.
13.3 Tell the user the sealed system set pressure.
13.4 Tell the user of the importance of regular servicing.
Worcester Heat Systems Ltd. offer a comprehensive maintenance contract.
13.5 Set the system controls to the user’s requirements.
13.6 If an external programmer has been fitted which has a
programmable domestic hot water facility then it is suggested that this be set to Continuous or the equivalent.
14.1 SERVICING
To ensure continued efficient operation of the appliance it must be checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but once per year should generally be adequate. The extent of the service required by the appliance is determined by the operating condition of the appliance when tested by fully qualified engineers. Any service work must be carried out by competent engineers such as British Gas or Corgi registered personnel.
14.2 PRE-SERVICE INSPECTION
Check that the flue terminal and the terminal guard, (if fitted), are clear. If the appliance is in a compartment, check that the ventilation openings in the compartment door or walls are clear. See Section 6 - Air Supply. Check the system and remake any joints or fittings which show signs of leakage. Refill, vent and re-pressurise as described in Section 12.2. Operate the appliance and the system taking note of any faults.
Measurement of the Flue Gases
For consistency of results of the flue gas measurements it is necessary to have a constant output and for the appliance to be at equilibrium. Turn on a tap to create a hot water demand. Wait until the appliance reaches thermal equilibrium (approx. 10 minutes). Remove the test point sealing screw on the appliance top panel. See Fig. 30. Connect to the test point with a piece of tubing. Expected measurements should be between:
For Natural Gas:
For Propane:
When calculating the equivalent flue length a flue bend is equivalent to 750mm of straight flue. After taking the measurement replace and tighten the sealing screw.
IMPORTANT
Disconnect the electrical supply at the mains and turn off the gas supply at the gas service cock on the appliance before servicing. After completing the service always test for gas soundness as indicated in BS 6891.
14. Inspection And Service13. Instructions To The User
18
Equivalent flue Carbon Carbon length (metres) Dioxide (%) Monoxide (%)
0.5 6.9 0.0008
1.0 7.0 0.0009
1.5 7.1 0.0010
2.0 7.3 0.0012
2.5 7.4 0.0013
Equivalent flue Carbon Carbon length (metres) Dioxide (%) Monoxide (%)
0.5 7.9 0.0017
1.0 8.0 0.0020
1.5 8.2 0.0024
2.0 8.5 0.0030
2.5 8.8 0.0035
Fig. 28. User controls.
Reset button
Mains indicator
C.H. temperature control and on/off knob
System pressure gauge
Page 19
14.3 DISMANTLE THE APPLIANCE
To carry out a full and comprehensive service of the appliance remove the following parts to gain access to the components which need to be checked or serviced.
(a) Cabinet Front Panel. Remove by lifting off the supports. (b) Inner Casing Cover. Check that the electricity supply to the
appliance is turned off. Remove the cabinet front panel. Unscrew the four screws securing the cover to the casing and lift off. See Fig. 29. (c) Facia Panel. Check that the electricity supply to the appliance is turned off. Remove the cabinet front panel. Unscrew the two upper screws as shown in Fig. 29. and hinge down the facia taking care not to damage the pressure gauge capillary tube or electrical connections.
(d) Bottom panel. Unclip and remove the appliance bottom panel. (e) Fan. Remove the inner casing cover. Carefully unplug the electrical connections and pull off the sensing tubes. Unscrew the four fixing screws and remove the fan assembly. See Fig. 30. (f) Combustion Chamber Front. Remove the inner casing cover. Undo the spring clips fixing the combustion chamber front. See Fig. 30. (g) Flue Hood Assembly. Remove the fan assembly. Remove the combustion chamber front. Lift and slide the flue hood assembly from the appliance. See Fig. 30. When refitting the hood ensure that the rear return edge passes under the lip at the rear of the combustion chamber. (h) Burner Assembly. Remove the combustion chamber front. Pull off the two spark electrode leads and disconnect the flame sense lead. Undo the burner fixing screws. Lift up and remove the burner assembly from the appliance. See Fig. 31.
14.4 SERVICE OF COMPONENTS Clean the Fan.
Any dust or fluff should be removed with a soft brush or by blowing. Take care not to distort the pressure sensing device. Clean the Main Burner. Brush the blade tops and mixing tube with a soft brush and check that all the flame ports are clear. Remove any blockages with a non-metallic brush. Inspect the injector and clean with a soft brush. Replace the injector if it appears damaged. Do not use a wire brush or anything likely to cause damage. Replace the spark and sense electrodes if they appear damaged. Clean the Gas to Water Heat Exchanger. Clean the heat exchanger using a soft brush. Remove the deposits from the bottom of the combustion chamber. Do not distort any of the blades. Combustion Chamber Insulation. Examine and replace any pads that are damaged. Remove any dust or deposits using a soft brush. Reassemble the appliance in the reverse order. Check that all components are in place and correctly fixed. Leave the cabinet front panel to be fitted after checking the operation of the appliance.
14.5 TEST THE APPLIANCE
On completion of the service and reassembly of the appliance, check for gas soundness and the correct operation of the appliance as described in Section 12 - Commissioning. Refit the cabinet front panel and reset the controls to the users requirements.
19
Fig. 31. Burner and electrode assembly.
Spark electrode
Injector
Fig. 30. Appliance components and fixings (upper assembly).
Flue hood
Overheat thermostat
Burner fixing screws (2)
Combustion chamber cover fixing clips (2)
Auto air vent
Fan assembly fixing screws (4)
Flue Gas Test Point
Fig. 29. Appliance casing and control equipment fixings.
Inner casing cover screws (4)
Side casing fixing screws (4)
Facia panel fixing screws (2)
Bottom facia panel fixing screws (3)
Page 20
15.1 IMPORTANT
Switch off the electricity and gas supplies before replacing any components. After the replacement of any components, check for gas soundness where relevant and carry out functional checks as described in Section 12 - Commissioning
15.2 COMPONENT ACCESS
To replace components it is necessary to remove one or more sections of the cabinet and cover plates within the appliance as described in Section 14.3. The facia panel may also need to be hinged down as described in Section 14.3 (c).
15.3 DRAINING THE APPLIANCE
Check that the electricity supply to the appliance is turned off. Before removing any component holding water it is important that as much water as possible is removed from the appliance. (a) Central Heating Circuit. Turn off the central heating flow and return valves at the appliance. Open the pressure relief valve, make sure that the dust cap on the auto air vent is removed. See Fig. 30. Close the pressure relief valve when the flow has stopped. Some water will remain in the expansion vessel, pump and Gas to Water heat exchangers and extra care must be taken when removing these components. (b) Domestic Hot Water Circuit. Turn off the mains cold supply valve at the appliance and open the lowest hot water tap. A quantity of water will remain in the Gas to Water heat exchanger, extra care must be taken when removing this component.
15.4 COMPONENT REPLACEMENT
1. Automatic Air Vent.
See Figs. 30. and 32. Remove the inner casing cover as described in Section 14.3 (b). Drain the central heating circuit as described in Section 15.3 (a). Unscrew air vent from the heat exchanger. Fit the replacement assembly ensuring thread sealant is applied and the dust cap is removed. Open the valves and fill and re-pressurise the system as described in Section 12.2.
2. Air Pressure Switch. See Fig. 34. Check that the electricity supply to the appliance is turned off. Remove the cabinet front panel as described in Section 14.3 (a) and lower the facia. Section 14.3(c). Carefully pull off the sensing tubes and the electrical connections from the switch. Remember to note their positions. Unscrew the two screws behind the Air Pressure Switch and remove the switch from the appliance. Fit the replacement switch in the reverse order ensuring that the electrical connections have been made to the correct terminals on the switch. Check that the sensing tubes are fitted correctly.
3. Fan. See Fig. 30. Check that the electricity supply to the appliance is turned off. Remove the fan assembly as described in Section 14.3(e). Fit the replacement fan in the reverse order.
4. Overheat Thermostat. See Fig. 30 and 32. Check that the electricity supply to the appliance is turned off. Remove the inner casing cover as described in Section 14.3 (b). Carefully pull off the two wires from the thermostat head. Undo the retaining nut on the top of the appliance and remove the retaining clip from the heat exchanger. Carefully withdraw the thermostat from the appliance. Fit the replacement thermostat in the reverse order ensuring that some heat sink compound is between the thermostat and the heat exchanger.
5. Gas to Water Heat Exchanger.See Fig. 32. Check that the electricity supply to the appliance is turned off. Drain the central heating circuit and domestic circuits as described in Section 15.3 (a) and (b). Remove the inner casing cover, fan, flue hood assembly, combustion chamber front, overheat thermostat, automatic air vent and combustion chamber side insulation as described in Sections 14.3 (b, e, f and g), 15.4 (1) and 15.4 (4). Fit the replacement heat exchanger in the reverse order ensuring that all the fibre washers are correctly fitted and a layer of heat sink compound is on the thermostat. Open the valves and fill and re-pressurise the system as described in Section 12.2.
15. Replacement Of Parts
20
Fig. 32. Combustion chamber.
Heat exchanger
Overheat Thermostat
Hot water heat exchanger connections
Cut-outs in combustion chamber sides
Pump bulk head connector
Central heating heat exchanger connections
Auto air vent
Page 21
6. Combustion Chamber Insulation.
Check that the electricity supply to the appliance is turned off. Drain the central heating circuit as described in Section 15.3(a). Remove the inner casing cover, fan, flue hood assembly, burner, and Gas to Water heat exchanger as described in Sections 14.3 (b, e and f), and 15.4 (5). Remove the fibre insulation pads from the combustion chamber side, rear, and front sections. Fit the replacement pads in the reverse order taking care not to damage them. Open the valves and fill and re-pressurise the system as described in Section 12.2.
7. Burner. See Fig. 31. Check that the electricity and gas supplies to the appliance are turned off. Remove the burner assembly as described in Section 14.3 (h). Fit the replacement burner in the reverse order taking care not to damage the electrode leads.
8. Burner Injector. See Fig. 31. Remove the burner as described in Section 14.3 (h). Unscrew the brass injector from the manifold. Fit the replacement injector in the reverse order.
9. Spark Electrode Assembly. See Fig. 31a. Remove the combustion chamber front as described in 14.3 (g) Carefully pull off the two electrode leads, Undo the M4 extended nut and remove the spark electrode assembly from the burner. Fit the replacement electrode in the reverse order, checking that the spark gap is 3.5 to 4.5mm.
10. Flame Sensor. See Fig. 31. Remove the burner as described in sections 14.3(h) and 15.4(8). Undo the M3 screw and remove the sense electrode from the burner. Fit the replacement electrode in the reverse order, checking that the sense gap is 5 to 6mm.
11. Gas Valve. See Figs. 33. and 34. Check that the electricity and gas supplies to the appliance are turned off. Hinge down the control box assembly in the servicing position as described in Section 14.3(d). Whilst supporting the valve unscrew the plug retaining screw and carefully pull off the electrical solenoid plug connection and the two modureg leads. Undo the 8 manifold screws and remove the gas valve. See Fig. 34. Fit the replacement gas valve in the reverse order ensuring the “O” rings are correctly fitted. Turn on the gas supply and check for soundness. To set the burner pressure. See Fig. 33. The minimum and maximum burner pressures must be set after a new gas control has been fitted. The maximum burner pressure must be set first, as any adjustment of the maximum pressure influences the minimum pressure setting. Start the appliance in the domestic hot water mode as described in section 12.4. - Appliance Operation. Adjust the maximum pressure adjustment screw on the gas valve to give a burner pressure of 13.6 mbar on natural gas, for propane the maximum pressure adjustment must be increased to maximum clockwise, this should give 33.0 - 35.0 mbar. End the demand and reset the appliance by interrupting the mains electricity supply. (Otherwise there is a four minute anti­cycle delay at the end of a demand).
Restart the appliance in central heating mode and adjust the minimum adjustment screw on the gas valve to give a pressure of 1.0 mbar on natural gas or 3.5 mbar on propane. See Fig. 33. After completing the adjustments, check the minimum and maximum pressures and re-adjust as necessary. Once this has been done the clear cap should be re-fitted to the adjuster and the retaining screw tightened. Coat the screw with paint or nail varnish to prevent user adjustment.
12. Central Heating Sensor. See Fig. 34. Check that the electricity supply to the appliance is turned off. Hinge the facia assembly in the servicing position as described in Section 14.3(c and d). Carefully pull off the two leads from the sensor. Pull off the sensor and spring retaining clip from the pipe. Fit the replacement sensor in reverse order with a layer of heat sink compound between the faces. Refit the leads.
21
Fig. 34. Gas valve pump and air pressure
switch.
Lower pump connection
Gas valve electrical connections
Pressure gauge connection
Central Heating Sensor
Air pressure switch
Air pressure switch
connecting tubes
PumpGas
valve
Top gas valve
connection (4 bolts)
Red pipe
Fig. 27. Gas valve.
Main gas valve connections (Black : blue : brown : green/yellow)
Burner pressure test point
Inlet pressure test point
Electrical connections Ð modulator (Blue : Blue)
Modulating solenoid
Minimum pressure adjuster
Maximum pressure adjuster Note: Clockwise to increase and anti­clockwise to decrease the pressure
Fig. 31a. Spark electrode assembly.
3.5-4.5mm
2.5-5mm
Page 22
13. Domestic Hot Water Sensor.
Check that the electricity supply to the appliance is turned off. Hinge the facia assembly in the servicing position as described in Section 14.3(c and d). Carefully pull off the two leads from the sensor. Undo and remove the clamping screw. Pull off the sensor and spring retaining clip from the pipe. Fit the replacement sensor in the reverse order ensuring a layer of heat sink compound is between the faces. Refit the leads.
14. Circulating Pump. See Figs. 32 and 34. Check that the electricity supply to the appliance is turned off. Drain the central heating circuit as described in Section 15.3(a). Hinge the facia assembly in the servicing position as described in Section 14.3(c). Undo the two union nuts and the pipe to the expansion vessel, remove the pump from the pipe-work. Support the pump and remove the electrical cover. Disconnect the electrical wires taking note of their positions. Fit the replacement pump in the reverse order using new sealing washers. (Alternatively replace the pump head only by removing the four Allen screws on the pump, remove the head and support whilst removing the electrical connections. Refit the new head). Open the valves and fill and re-pressurise the system as described in Section 12.2 Note: The direction of flow should be upwards. The speed should always be set to maximum.
15. Expansion Vessel.
Drain the central heating circuit as described in Section 15.3(a). Isolate the gas supply at the mains. Then either fit a separate expansion vessel on the central heating return to the appliance or replace the existing vessel as described below. Drain the domestic circuit as described in Section 15.3(b). Disconnect the flue system at the boiler. Disconnect the appliance pipework at the appliance entry points ensuring precautions are taken to cope with any water remaining in the appliance. Remove the appliance from the wall. Disconnect the expansion vessel from the appliance by undoing the fitting nut at it’s base. Fit the replacement vessel in the reverse order. Open the valves and fill and re-pressurise the system as described in Section 12.2
16. Pressure Relief Valve. See Fig. 35. Drain the central heating circuit as described in Section 15.3(a). Hinge down the facia assembly as described in Section 14.3(c) Remove the Bottom panel as described in Section 14.3(d) Undo the discharge pipe connection and remove the valve retaining clip. Remove the valve taking care not to distort the pipework. Fit the replacement valve in reverse order. Reconnect the discharge pipe. Open the valves and fill and re-pressurise the system as described in Section 12.2
17. Water Flow Switch. See Fig. 36. Check that the electricity supply to the appliance is turned off. Drain the domestic hot water circuit as described in Section
15.3(b). Remove the two upper screws and hinge down the facia panel as described in Section 14.3(c). Undo the two union nuts securing the “T” piece and remove the housing from the pipework. Disconnect the electrical connection. Fit the replacement water flow switch in the reverse order ensuring new fibre washers are fitted to the new switch body.
18. Domestic Hot Water Flow Restrictor. See Fig. 36. Remove the water flow switch as described in Section 15.4-17. Undo the two union nuts securing the “T” piece and remove the housing from the pipework. The plastic flow restrictor is located within the “T” piece on the water flow switch. Fit the replacement flow restrictor and reassemble in the reverse order ensuring the fibre washers are in place.
19. Pressure Gauge.
Check that the electricity supply to the appliance is turned off. Drain the central heating circuit as described in Section 15.3(a). Remove the two upper screws and hinge down the facia panel as described in Section 14.3(c). Prize back the retaining clips securing the gauge to the facia panel remove wire clip and unplug the gauge from the pump inlet pipe. Fit the replacement gauge in the reverse order ensuring the “O” ring is in place. Open the valves and fill and re-pressurise the system as described in Section 12.2
22
Fig. 35. Pressure relief valve.
Pressure relief valve. (Turn knob anti-clockwise to test).
Fig. 36. Water Flow Switch. (Side View)
Flow Restrictor
Water Flow Switch
ÒTÓ Piece
Page 23
20. Control Board.
Check that the electricity supply to the appliance is turned off. Undo the 3 screws and remove the facia bottom panel. Remove the two upper screws and hinge down the facia assembly. Carefully pull off all the connectors. Disconnect the mains supply lead at terminal
X1 and the earth connection at the back. Remove the four corner screws on the back of the facia and separate the metal back panel from the plastic facia. Remove and retain the brass nut and washer. Release the six pillars on the control board and pull the control board forward off the back panel. Fit the replacement board in the reverse order ensuring it is pushed firmly onto the six pillars and clicks into place. Special care should be taken with the brass post and nut to ensure a good earth contact. (Check earth continuity between the incoming earth and the appliance chassis). Refit the facia panel and hinge the control box assembly in the servicing position as described in Section 14.3 (c).
21. Gauze filter. See Fig. 37. Remove the water flow switch as described in section 15.4-17. Undo the lower union nut on flow switch housing. Undo the nut on the isolating valve and remove the mains water inlet pipe. Carefully extract the filter from the valve end of the pipe. Replace the filter and refit the pipe in reverse order.
22. Flue flow sensor. See Fig. 38. Check that the electricity supply to the appliance is turned off. Remove the fan assembly as described in Section 14.3(e). Unscrew the single central retaining screw and withdraw the sensor from the fan.
Fit the new sensor ensuring the correct orientation and carefully tighten the retaining screw. Refit the fan assembly in reverse order.
23
Fig. 37. Gauze Filter.
Gauze Filter
Positive
Isolating Valve
These instructions should be used when converting appli­ances from natural gas to LPG and vice versa. Only components supplied by Worcester Heat Systems should be used.
Only competent persons should attempt the conversion. Conversion from Natural Gas to LPG should not be carried out on appliances installed in a room or inter­nal space below ground level.
1.
Ensure the gas service cock is turned OFF and the elec-
trical supply is isolated.
2. Refer to section 14.3 Dismantle the Appliance to remove the boiler front panel and inner casing. Follow the dismantling instructions to remove the burner.
3. Remove the injector and replace with the injector from the kit.
4. Remove the nut, end cap and bracket from the end of the burner.
4.1 For conversion to Natural gas remove the internal
gauze.
4.2 For conversion to LPG fit the gauze into the burner
body.
5. Refit the end cap ensuring the bracket is in the correct orientation.
6. Refit the burner to the appliance and re-assemble the inner casing.
7. Follow the dismantling instructions to remove the gas valve and refit the new valve. See Installation Instructions: Section 15.4.11 Replacement of Parts, Component Replacement, Gas Valve.
8. Turn on the gas and electricity supplies and following the commissioning procedure confirm gas soundness and correct boiler operation.
9. Set the gas pressure to the required rate for the new gas type as specified on the data plate. When this is done refit the cap to the adjuster and seal its retaining screw with paint or nail varnish.
10. Turn off the boiler and when cool peel off the arrow from the data plate and re-stick it against the gas type for which the appliance is now converted.
11.Replace the boiler front panel.
The conversion is now complete.
16. Conversion Instructions
Item No. Description Natural Gas to LPG Kit LPG to Natural Gas Kit
7 716 192 131 7 716 192 132
1. Burner Injector 8 716 140 209 8 716 140 224 Stereomatic 2.78mm Stereomatic 4.3mm
2. Burner Gauze 8 716 142 601 Remove Gauze
3. Gas Valve 8 716 142 430 8 716 142 413
Parts List
Fig. 38. Flue flow sensor.
Page 24
24
End of a domestic
hot water overrun
Escape pause by
resetting the mains
electricity supply
OFF-ON
Anti-cycle delay
Main gas valve
OFF
6
EITHER
AUTOMATIC START-UP SEQUENCE
1. Central Heating Mode
NO
PASS
PRESENT
PRESENT
ABSENTABSENTFAIL
YES
Central heating
temperature 5°C
above set point
Operating Switch
(or programmer)
OFF
Fan overrun
4 minutes
Continue
pump overrun
for 6 secs pump
pulse after
2 miniutes.
Gas valve OFF
Room thermostat
OFF
Burner pressure
1.0 mbar for 60
seconds.
Burner pressure
automatically
adjusted for range
rating and then
modulated to
maintain set flow
temperature
AUTOMATIC
START-UP
SEQUENCE
CENTRAL
HEATING
DEMAND
SATISFIED
Water flow
temperature
monitored by central
heating sensor
Pump on
Operating Switch
(or programmer)
and room
thermostat on
CENTRAL HEATING
DEMAND
Internal
"Autofrostat"
demand
Is fan in
overrun mode?
Air pressure
switch test
Fan ON
Sense air
pressure
Main valve
opens
Sense
flame
Initiate
sparking
Stop
sparking
Wait
(fan or fan and
pump on)
Ignition Time -
out (after 9secs)
Ignition
Lock-out
Wait
(fan or fan and
pump on)
Wait (pump on
in central
heating mode)
17. Operational Flow Diagrams
Page 25
25
Signal from the
flow switch
HOT WATER
DEMAND
(Overrides all other
overrun modes
and functions)
No demand and
primary
temperature below
6°C monitored by
the central heating
sensor
Internal
"Autofrostat"
Demand
Run pump
Below 4°C
Above 8°C
4°C to 8°C
Monitor central
heating sensor
Burner pressure
at 1.0 mbar
6
Burner pressure adjusted
based on the temperature
rise over the previous
minute. Aiming at 4°C
rise/minute.
Burner never to be
extinguished
irrespective of the
rate of temperature
rise
At the set point
change to a wide
band proportional
control
Commence normal central
heating mode until heating
temperature reaches 20°C
Return to normal
OFF state
Pump on until
primary temperature
drops to 50°C
No demand and central
heating temperature above
50°C monitored by the
central heating sensor
End of hot water demand
with no central heating
demand. Hot water
thermistor above 40°C
6 second pump pulse with a
2nd 6 second pump pulse 2
minutes later.
End of demand or central
heating temperature above
70°C monitored by the
central heating sensor
Fan on for
4 minutes
Inhibit operations
for approximately
1 second. 6 second
delay before re-
ignition from any
other demand.
Is the central
heating mode
interrupted?
AUTOMATIC
START-UP
SEQUENCE
HOT WATER
DEMAND
SATISFIED
Pump OFF
Wait for hot water
temperature to
drop to factory
pre-set level
Gas valve OFF.
Fan remains ON
Hot water
temperature above
70°C
Modulate heat
input to maintain
hot water
temperature at the
factory pre-set
level
Gas valve OFF
Fan overrun
4 minutes
Operating
Switch (or
programmer
OFF)
Domestic hot water
temperature
monitored by hot
water sensor
3. "Autofrostat" Function
4. Pump Overrun Function
5. Fan Overrun Function
2. Domestic Hot Water Mode
6. Central Heating ramp control
Pump pulse 6
seconds then 2
minutes later
2nd pulse
Page 26
26
F1 2ATHRC
F2 1.25AT
Optional links
SparkFlame sense
Outputs Inputs
Mains indicator
Modulating
valve
Overheat stat
X6 Pins 8 & 9
X6 Pins 15 & 16
X6 Pins 5,6 & 7
X6 Pins 1 & 2
X6 Pins 19 & 20
X6 Pins 3 & 4
Flow signal
CH temp. sensor
DHW temp. sensor
CH control POT
Air pressure switch
MAINS PROGRAMMER/CLOCK
FULL SEQUENCE
CONTROLLER
GAS VALVE
LOW VOLTAGE ELECTRONICS
(Microcontroller)
ROOM STAT
X1
X2
321
1
2
3
4
6
5
RL1
X3
Pin 1 X3 Pin 2
X4 Pin 3
X5 Pin 3
X5 Pin 2X5 Pin 1
X4 Pin 1
FAN
PUMP
RL3
RL4
N
N
N
N
L
18. Fault Finding
Page 27
27
Fault in
Central Heating
Fault in
Domestic Hot Water
Is mains LED flashing?
Is mains LED
iluminated?
Turn control knob
fully clockwise
Set room stat to
call for heat
Ensure link is fitted at
X2 pins 2 & 3
Set clock to call for heat
Has overheat
thermostat tripped
Ensure link is fitted at
X2 pins 5 & 6
Is mains LED flashing?
GO TO
CHECK D
GO TO
CHECK K
GO TO
CHECK K
GO TO
CHECK E
GO TO
CHECK F
GO TO
CHECK O
GO TO
CHECK C
Is control knob
set for demand?
Is a room thermostat
fitted?
Is room thermostat
calling for heating?
Is programmer fitted?
Is programmer calling
for heat?
Is pump running?
Has overheat
thermostat tripped?
Is mains LED
illuminated?
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Page 28
28
No mains LED
Connect mains
supply
Replace fuseIs F1 (2ATHRC) OK?
Is F2 (1.25AT) OK?
Faulty PCB
Replace
Flashing mains LED
Remove
X6
Open circuit
Replace thermistor
Replace harness
Short circuit
Faulty PCB
Replace
Is resistance between
pins 3 & 4 between
690ohms & 33k
Is resistance between
pins 19 & 20 between
690ohms & 33k
Replace fuse
Is mains present at
X1 pins 1 & 3?
GO TO
CHECK H
GO TO
CHECK I
GO TO
CHECK H
GO TO
CHECK J
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO
NO
OK
OK
OK
OK
Faulty
Faulty
Faulty
Faulty
NO
Page 29
29
The overheat thermostat can be
reset by pressing the reset button,
but if it trips immediately or on a
regular basis a serious problem has
occurred therefore contact your
installer
Reset thermostat
Overheat Thermostat Check
Pump Check
Fan Check
Does button hold in?
Secure Connector
Secure Connector
Faulty pump
Is pump connector
secure on the PCB (X3)?
Is fan connector
secure on the
PCB (X4)?
Is mains present at the
pump connector
(X3 pins 1 & 2)?
Is mains present at the
fan connector
(X4 pins 1 & 2)?
ATTAC H to heat
exchanger
Is capillary broken?
Ensure appliance is
cool and retest
Replace overheat
thermostat
Is capillary firmly
ATTACHED
to exchanger?
GO TO
CHECK I
GO TO
CHECK O
GO TO
CHECK L
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
NO
NO
NO
Faulty Harness
Faulty fan
YES
Mains at fan
NO
Page 30
30
Thermistor Check
Harness Continuity Check
Harness Short Check
Remove connectors
from thermistor
Thermistor OK
Remove appropriate
connectors
Is continuity observed
between each end of
wire in question?
Faulty harness
or connector
Harness OK
Remove appropriate
connectors
Faulty harness
Harness OK
Is short circuit
observed between pair
of wires in question?
Is resistance between
terminals of thermistor
between 690ohms & 33k
Faulty thermistor
YES
YES
YES
YES
NO
NO
YES
YES
NO
Page 31
31
Ignition Check
Is fan running?
Is sparking present at
the electrodes?
Faulty PCB
Replace
Connect ignition leads
securely
Are leads breaking
down?
Ignition coil faulty
replace PCB
Replace leads
Does burner continue?
Does gas pressure
modulate?
Ignition OK
Faulty PCB
Replace
Is flame sense
electrode in flame?
Is lead secure
both ends?
Secure lead
Ensure flame sense
electrode in flame at
minimum burner
pressure
Are ignition leads
connected both
ends securely?
Does sparking occur?
Does ignition occur?
YES
YES
YES
YES
YES
HARNESS OK
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
GO TO
CHECK G
GO TO
CHECK E
GO TO
CHECK M
GO TO
CHECK I
GO TO
CHECK N
GO TO
CHECK L
Page 32
32
Remove BROWN and
WHITE terminals
from air pressure
switch
Air pressure switch
faulty
With no demand, is a
short-circuit observed
at exposed APS
terminals?
Reconnect the
WHITE & BROWN
wire and remove the
GREEN wire. Initiate
a demand.
Does the fan run?
PCB faulty
Air pressure switch
faulty
APS OK
Is gas pressure present
at input to gas valve?
Ensure gas supply
Faulty board
Replace
Faulty gas valve
Replace
Is live output present at
X5 pins 1 & 2 relative to
neutral at pin 3?
Is gas pressure present
at input to burner?
Gas valve OK
With fan running
disconnect BROWN
wire. (DO NOT touch
chassis with it). Is a
short circuit observed
across exposed APS
terminals?
Gas Valve Check
NO
NO
NO
YES
YES
YES
YES
YES
NO
NO
NO
Air Pressure Switch Check
Is there mains 230V at fan connector X4
pins 1 and 3?
YES
Fan or fan cable
faulty
NO
YES
L
Page 33
With pressure above
minimum, remove Modureg
Lead. Does pressure drop to
minimum?
33
Is minimum pressure
observed at burner at all
times?
Modulating Valve Check
Flow Switch Check
GO TO
CHECK I
YES
YES
GO TO
CHECK I
YES
YES
NO
NO
HARNESS OK
YES
YES
NO
NO
NO
NO
Is pressure at burner
always the same?
Is resistance
nominally 125ohms
Does voltage
go above 6.25V
Faulty PCB.
Replace
Reconnect X6 and measure
voltage across modulating
valve during operation
Gas valve OK
Remove
X6
Close all taps to set no
domestic flow
Faulty flow switch.
Replace
Faulty flow switch.
Replace
Is short circuit observed
at
X6 pins 1 & 2
Is open circuit observed
at X6 pins 1 & 2?
Open a tap fully to set
domestic flow
Flow Switch OK
Faulty modulating valve .
Replace gas valve
Remove X6, measure
resistance between
pins 15 & 16
N
YES
NO
Page 34
34
Key G.C. No. Part Manufacturer’s Reference Qty WHS No. Part No.
1 E01-579 Burner Assembly Natural Gas Aeromatic AC23/053586 1 8 716 142 604 0
E01-580 Burner Assembly LPG Aeromatic AC23/053587 1 8 716 142 611 0
2 E01-591 Injector Natural Gas Stereomatic O 4.3mm 1 8 716 140 224 0
E00-741 Injector LPG Stereomatic O 2.78mm 1 8 716 140 209 0
3 E01-892 Gas Valve Natural Gas SIT 1 8 716 142 413 0
E01-893 Gas Valve LPG SIT 1 8 716 142 430 0 4 E01-596 Air Pressure Switch Huba 605.99484 1 8 716 142 414 0 5 375 697 Spark Electrode Assembly Buccleuch 1 8 716 142 100 0 6 E01-612 Flame Sensor Buccleuch 1 8 716 120 345 0
E01-930 Flame Sensor Harness 1 8 716 120 126 0 7 E01-598 Ignition Harness Buccleuch 1 8 716 120 236 0 8 E01-599 Gas to Water Heat Exchanger Giannonni 1 8 716 142 905 0 9 E01-600 Insulation Pack WHS 1 7 716 192 216 0
10 E01-601 Auto Air Vent Intermes 1 8 716 140 504 0
11 299-506 Pressure Gauge Cewal 1 8 716 142 300 0 12 375 699 Pressure Relief Valve Caleffi 3141 3bar 1 8 716 142 404 0 13 E01-602 Pump with Harness Grundfos 15 60 special 1 8 716 143 107 0 14 E01-603 Expansion Vessel (8Ltr) 389mm Dia Winkelman Panhof 1 8 716 142 502 0 15 E01-604 PCB Boiler Control Pactrol 1 8 716 146 300 0 16 E04-582 Temperature Thermistors Elmwood 2 8 716 142 384 0
E01-900 CH Thermistor Clip 1 8 716 148 313 0
299-495 DHW Thermistor Clip 1 8 716 148 303 0 18 E01-605 DHW Flow Regulator 1 8 716 141 052 0 19 324-822 Gauze Filter WHS 1 8 716 148 401 0 20 299-363 Flow Sensor WHS 1 8 716 141 000 0
21 E01-606 Fan Assembly SIFAN 1 8 716 120 993 0 22 E01-607 Safety Temperature Limiter Ranco LM7 1 8 716 142 307 0 23 E01-886 Flow Switch Assembly SIKA 1 8 716 120 971 0 24 299-357 Fuse Pack WHS 1 7 716 192 206 0 25 E01-610 Gasket Pack WHS 1 7 716 192 218 0
ACCESSORIES
299-360 Mechanical Programmer Kit Deihl 7 716 192 002 0
E01-940 Gas Conversion Kit NG to LPG 7 716 192 131 0 E01-941 Gas Conversion Kit LPG to NG 7 716 192 132 0 E05-341 Mini Expansion Vessel Kit Including new pipe and Expansion Vessel 7 716 192 188 0
FLUE OPTIONS
E01-942 Telescopic Horizontal Flue Kit 127-350 mm 7 716 191 005 0 E01-943 Extension Flue Kit 750 mm 7 716 191 006 0 E01-944 Vertical Flue Kit 7 716 191 015 0 E01-945 Vertical Flue Adaptor 7 716 191 016 0 E01-946 Internal Fixing Kit Telescopic Flue 7 716 191 019 0 E01-058 Flue Elbow Kit 90 deg. 7 716 191 013 0 E01-059 Flue Elbow Kit 45 deg. 7 716 191 014 0
19. Component Parts List
Page 35
35
9
8
14
3
21
1
15
13
4
22
11
7
12
10
23
20
6
25 24
2
19
18
16
23
Page 36
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests
of continued improvement.
All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.
PUBLICATION 8 716 145 028C 11/98
Bosch Group
Worcester Heat Systems Limited, Cotswold Way, Warndon, Worcester WR4 9SW.
Telephone: (01905) 754624. Fax: (01905) 754619.
Technical Helpline (0990) 266241.
Loading...