Bosch 12-18, 25-32kW, 18-25 User Manual

GREENSTAR HEATSLAVE EXTERNAL
THE APPLIANCE IS FOR USE WITH KEROSENE ( 28 SECOND
OIL) ONLY
INSTRUCTION MANUAL
GB
12/18, 18/25, 25/32kW
FLOOR STANDING EXTERNAL OIL FIRED CONDENSING COMBINATION BOILER USING BALANCED FLUE SYSTEM
FOR OPEN VENT AND SEALED CENTRAL HEATING SYSTEMS WITH DOMESTIC MAINS FED HOT WATER
THE APPLIANCE IS FOR USE WITH KEROSENE ( 28 SECOND
OIL) ONLY
GB
INSTRUCTION MANUAL
INSTALLATION & SERVICING INSTRUCTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
1
Check List Hardware/Literature pack
Item Qty
Greenstar Heatslave External Installation/Servicing Instructions.........1
Users Instructions............................................................................................1
Hardware Pack.................................................................................................1
100mm Ø Services Duct................................................................................1
Condensate Trap Kit........................................................................................1
Warranty Return Envelope.............................................................................1
Cabinet Key.......................................................................................................1
SYMBOLS USED IN THIS MANUAL:
Domestic hot water
Central heating
Room thermostat
Frost thermostat
Wait time period
Programmer/timer OFF
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION.
THESE INSTRUCTIONS ARE APPLICABLE TO THE WORCESTER APPLIANCE MODEL(S) STATED ON THE FRONT COVER OF THIS MANUAL ONLY AND MUST NOT BE USED WITH ANY OTHER MAKE OR MODEL OF APPLIANCE.
THE INSTRUCTIONS APPLY IN THE UK ONLY AND MUST BE FOLLOWED EXCEPT FOR ANY STATUTORY OBLIGATION.
THIS APPLIANCE MUST BE INSTALLED BY A COMPETENT PERSON. FAILURE TO INSTALL CORRECTLY COULD LEAD TO PROSECUTION.
COMPLYING WITH THE BUILDING R EGULATIONS:
This heating appliance forms part of the controlled services for the building. It is law that all controlled services for buildings must comply with building regulations. You must be able to satisfy your Local Authority Building Control Body (LABC) that the work carried out concerning the installation and commissioning of this heating appliance has been carried out to a satisfactory standard.
OFTEC operate a competent persons scheme and registered installers are able to certify that their work complies with building regulations. Under the scheme;
OFTEC must be informed about every installation.OFTEC will issue a building regulations compliance certificate to the householder and will
notify the LABC.
OFTEC provide controlled document forms CD10 and CD11 for use during installation and commissioning respectively.
Other organisations operate self-certification schemes e.g. NAPIT and BESCA Ltd. and it may be possible for installers who are members of these organisations to self certify their work.
Alternatively you must submit a building control notice to the LABC before installing any boiler. The LABC will then arrange regular inspection visits during the work to ensure that the installation complies with the regulations.
IF YOU ARE IN ANY DOUBT CONTACT THE WORCESTER TECHNICAL HELPLIN E.
DISTANCE LEARNING AND TRAI NING COURSES ARE AVAILABLE FROM WORCESTER.
PLEASE LEAVE THESE INSTRUCTIONS WITH THE COMPLETED COMMISSIONING FORM AND THE USER MANUAL WITH THE OWNER OR WITH THE APPLIANCE AFTER INSTALLATION OR SERVICING. THE SERVICE INTERVAL RECORD CAN BE FOUND ON THE BACK PAGE OF THIS MANUAL.
ABBREVIATIONS USED IN THIS MANUAL: Ø Diameter CH Central Heating DHW Domestic Hot Water TRV Thermostatic Radiator Valve IP Ingress Protection CF Conventional flue BF Balanced flue N/A Not allowed SEDBUK Seasonal Efficiency of Domestic Boilers in the United Kingdom OFTEC Oil Firing Technical Association for the Petrolium Industry IEE Institute of Electrical Engineers LABC Local Authority Building Control Body
STORE THE APPLIANCE IN A DRY AREA PRIOR TO INSTALLATION.
INSTALLATION & SERVICING INSTRUCTIONS
IMPORTANT HANDLING INSTRUCTIONS: It is advised that more than one person is involved in the transfer of the packaged appliance from the van to the point of installation. It is advised that no attempt should be made to move the packaged appliance without the use of a suitable truck. At all times the correct method for handling heavy objects should be strictly observed.
GENERAL HANDLING GUIDELINES:
• Lift only a manageable weight, or ask for help.
• When lifting, bend the knees, and keep the back straight and feet apart.
• Do not lift and twist at the same time.
• Lift and carry items close to the body.
• Wear protective clothing and gloves to protect from any sharp edges.
Programmer ON CH only
Programmer ON DHW only
Programmer ON CH and DHW
Cold water main supply
Electricity supply
SAFETY & REGULATIONS
IMPORTANT INFORMATION AND SYMBOLS 1
SAFETY PRECAUTIONS AND I NSTALLATION REGULATIONS 3
APPLIANCE INFORMATION
GENERAL INFORMATION 4
TECHNICAL DATA 5
LAYOUT & COMPONENTS 6
PRE-INSTALLATION
CLEANING PRIMARY SYSTEMS 7
MAINS SUPPLIES 8
OIL SUPPLY 9
WATER SYSTEMS & PIPEWORK 10-11
CONDENSATE & PRESSURE RELIEF PIPEWORK 12
BOILER LOCATION & CLEARANCES 13
CABINET MOUNTED LOW LEVEL FLUE TERMINAL POSITIONS 14
HIGH LEVEL FLUE TERMINAL POSITIONS 15
EXTERNAL OILFIT BALANCED FLUE OPTIONS 16
CABINET MOUNTED HORIZONTAL BALANCED FLUE OPTIONS 17
INSTALLATION
UNPACKING THE BOILER 18
PIPEWORK & FLUE POSITIONS 19
BOILER INSTALLATION 20
FLUE INSTALLATION 21
COMBUSTION CHAMBER 22
PIPEWORK CONNECTIONS 23-24
OIL BURNER AND PUMP 25
REFITTING COMPONENTS 26
ELECTRICS 27-28
COMMISSIONING
PRE-COMMISSIONING CHECKS - APPLIANCE 29
FILLING THE SYSTEM 30
STARTING THE APPLIANCE 31-34
WATER TREATMENT 35
FINISHING COMMISSIONING - APPLIANCE 36
SERVICING & SPARES
INSPECTION AND SERVICE 37-40
SHORT PARTS LIST 12/18 41
SHORT PARTS LIST 18/25 42
SHORT PARTS LIST 25/32 43
FAULT FINDING & DIAGNOSIS
FAULT FINDING 44-45
FAULT FINDING LOGIC FOR SATRONIC CONTROL BOX 46
FAULT FINDING LOGIC FOR 535 SE/LD RDB CONTROL BOX 47
ELECTRICAL SCH EMATIC 48
COMMISSIONING & SERVICE RECORDS
COMBUSTION RECORD 49
SERVICE INTERVAL RECORD 50
CONTENTS
CONTENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
2
SAFETY &
REGULATIONS
APPLIANCE
INFORMATION
PRE -
INSTALLATION
INSTALLATIONCOMMISSIONING
SERVICING
& SPARES
FAU LT FIND ING
& DIAGRAMS
SAFETY PRECAUTIONS & INSTALLATION REGULATIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
3
SAFETY &
REGULATIONS
SAFETY PRECAUTIONS INSTALLATION REGULATIONS
OIL SMELLS, LEAKS OR FUMES FROM THE APPLIANCE:
Extinguish any naked flames.
Isolate the electrical supply.
Isolate the fuel supply to the boiler.
Rectify fault.
HEALTH & SAFETY:
The appliance contains no asbestos and no substances have been used in the construction process that contravene the COSHH Regulations (Control of Substances Hazardous to Health Regulations 1988). Where applicable, the CE mark indicates compliance with relative EU Directives.
COMBUSTIBLE AND CORROSIVE MATERIALS: Do not store or use any combustible materials (paper, thinners, paints etc.) inside or within the
vicinity of the appliance. The combustion air must be kept clear of chemically aggressive substances which can corrode the appliance and invalidate any warranty.
FITTING & MODIFICATIONS:
Fitting the appliance and any controls to the appliance may only be carried out by a competent engineer in accordance with these instructions and the relevant Installation Regulations. Flue systems must not be modified in any way other than as described in the fitting instructions. Any misuse or unauthorised modifications to the appliance, flue or associated components and systems could invalidate the warranty. The manufacturer accepts no liability arising from any such actions, excluding statutory rights.
SERVICING:
Advise the user to have the system regularly serviced by a competent, qualified engineer (such as OFTEC registered personnel) using approved spares, to help maintain the economy, safety and reliability of the appliance.
Failure to install appliances correctly could lead to prosecution.
The appliance should be installed by a competent person. The person installing the appliance should be aware of the Health and Safety at Work Act and take appropriate action to ensure that the regulations are adhered to. In order to give optimum efficiency and trouble free operation the appliance must be commissioned by a qualified OFTEC engineer.
The compliance with a British Standard does not, in itself, confer immunity from legal obligations. In particular the installation of this appliance must be in accordance with the relevant requirements of the following British Standards and regulations in respect of the safe installation of equipment: BS 5410: part 1: Code of practice for Oil Fired Boilers. BS 799: part 5: Specification for Oil Storage Tanks. BS 7593: Code of Practice for treatment of water in domestic hot water central heating systems. BS 5449: part 1: Specification for forced circulation hot water central heating for domestic premises. BS 5955: part 8: Specification for the installation of thermoplastic pipes and associated fittings for use in domestic hot and cold water services and heating systems. BS 7291: Thermoplastic pipes and associated fittings for hot and cold water for domestic purposes and heating installations in buildings. BS 7074: part 1: Application, selection and installation of expansion vessels and ancillary equipment for sealed water systems. BS 7671: IEE Wiring Regulations, current edition. BS 1362: Specification for general purpose fuse links for domestic and similar purposes. The Building Regulations Part J and L1 England and Wales; Part F and Part J Section III Scotland; Part L and Part F Northern Ireland. Local water company bye-laws. The Control of Pollution (Oil) Regulations. OFTEC Standards. Where no specific instruction is given, reference should be made to the relevant codes of practice.
GENERAL INFORMATION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
4
APPLIANCE
INFORMATION
GENERAL INFORMATION
STANDARD PACKAGE:
A - Floor standing oil fired condensing boiler for
open vent and sealed domestic central heating and mains fed hot water.
B - Literature pack.
C -Condensate trap kit.
D - 100mmØ services duct.
E - Cabinet key
Check List
Item Qty
Greenstar Heatslave External Installation/Servicing Instructions........1
Users Instructions ..........................................................................................1
100mm Ø Services Duct...............................................................................1
Condensate Trap Kit.......................................................................................1
Warranty Return Envelope ............................................................................1
Cabinet Key.......................................................................................................1
770mm
640mm
950mm
A
B
C
D
E
TECHNICAL DATA
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
5
TECHNICAL DATA
Central Heating
Primary water capacity (total) litres
Maximum static head metres
Minimum static head metres
Available pump head (20°C difference) at max. output metres water
Max. permissible sealed system operating pressure bar
in accordance with WRAS guidelines
Flow restrictor colour
Domestic Hot Water
Optimum flow rate (±15%) litres/min
Minimum inlet pressure (dynamic) for optimum flow rate bar
Maximum hot water rise for 90 litres draw off (@optimum flow rate) °C
Flue
Exit flue gas mass flow kg/hr
Pipework connections
Fuel line (compression) mm
CH flow mm
CH return mm
Water main inlet mm
DHW outlet mm
Open vent (optional) BSP
CH drain/optional feed and expansion BSP
Condensate (polypropylene) mm
Electrical
Electrical power supply voltage AC...V
Frequency Hz
Max. power consumption W
Thermostats
CH control thermostat range (cut in/cut out) °C
DHW control thermostat range (cut in/cut out) °C
CH & DHW control thermostat differential °C
Boiler high limit thermostat set point °C
Boiler manual reset overheat thermostat set point °C
Flue reset overheat thermostat set point °C
General Data
Maximum hearth temperature °C
SEDBUK (Band A) %
Appliance protection rating IP
Weight (excluding packaging) kg
Emissions class for NOx and CO class
Typical NOx emissions figure mg/kW hr
DESCRIPTION UNITS 12/18 18/25 25/32
APPLIANCE
INFORMATION
69
30
1
4.7
2.5
Lime
15
1. 5
40
29
10
22
22
15
22
1
3
/
4
21. 5
230
50
240
55/81
55/72
5
92
105
110
<100
90.2
45
19 5
3
75
69
30
1
4.0
2.5
18
1. 2
40
40
10
22
22
15
22
1
3
/
4
21. 5
230
50
240
55/81
55/72
5
92
105
110
<100
90.1
45
19 5
3
70
72
30
1
4.2
2.5
22
0.9
40
51
10
28
28
15
22
1
3
/
4
21. 5
230
50
263
55/81
55/72
5
92
105
110
<100
90.3
45
206
3
75
LAYOUT & COMPONENTS
The diagram opposite excludes the top, front and RH side casing panels.
1. CONTROL BOX ASSEMBLY
2. DIVERTER VALVE
3. PRESSURE GAUGE
4. AUTO AIR VENT
5. CH CONTROL AND MANUAL RESET OVERHEAT THERMOSTAT PHIAL
6. CASING SIDE PANEL
7. CIRCULATING PUMP
8. AUTO-RESET HIGH LIMIT THERMOSTAT PHIAL
9. DHW FLOW SWITCH
10. PRESSURE RELIEF VALVE
11. DHW HEAT EXCHANGER
12. FLUE GAS SAMPLING POINT
13. FLUE OVERHEAT THERMOSTAT PHIAL
14. CASING SUPPORT PANEL
15. FLUE MANIFOLD ACCESS COVER
16. AIR INLET PIPE AND CASING
17. SECONDARY HEAT EXCHANGER BLEED POINT (ONE ON EITHER SIDE)
18. SECONDARY HEAT EXCHANGER
19. SECONDARY HEAT EXCHANGER DRAIN
20. EXPANSION VESSEL
21. OPTIONAL OPEN VENT/AIR VENT
22. DRAIN AND OPTIONAL FEED AND EXPANSION
23. CONDENSATE OUTLET
24. PRIMARY HEAT EXCHANGER
25. TRAY
26. OIL ISOLATION VALVE
27. CONDENSATE TRAP
28. CONDENSATE TRAP BRACKET
29. COMBUSTION CHAMBER ACCESS DOOR
30. HEATSLAVE TANK DRAIN
31. HEATSLAVE TANK
32. MODE SWITCH
33. BOILER MODE INDICATOR
34. LOCKOUT INDICATOR
35. OVERHEAT RESET BUTTONS (boiler & flue temperature)
36. LOCKOUT RESET BUTTON
37. SERVICE CONNECTION
38. CH TEMPERATURE CONTROL
39. DHW TEMPERATURE CONTROL
40. DATA LABEL
41. FROST THERMOSTAT SENSORS
42a. BENTONE STERLING BURNER (12/18 & 18/25) i) CONTROL BOX ii) MOTOR iii) AIR INTAKE CASING iv) OIL PUMP v) COMBUSTION HEAD
42b. RIELLO RDB 2.2 BURNER (25/32) i) CONTROL BOX ii) MOTOR iii) AIR INTAKE CASING iv) OIL PUMP v) COMBUSTION HEAD
43. CLIP - AIR INTAKE HOSE
44. AIR INTAKE HOSE
LAYOUT & COMPONENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
6
APPLIANCE
INFORMATION
1
6
2
4
8
7
5
10
20
11
14
3
13
15
12
16
17
19
21
22
23
18
24
25
29
40
30
31
32
33
9
35/36
39
38
42a
42b
43
44
43
44
v)
iv)
iii)
ii)
i)
v)
iii)
i)
ii)
iv)
41
26
27
28
37
34
CLEANING PRIMARY SYSTEMS
BEFORE CLEANING THE SYSTEM:
ENSURE THE SYSTEM AND PIPEWORK IS IN GOOD WORKING ORDER.
FLUSH THE EXISTING SYSTEM WITH A POWER FLUSHING MACHINE OR WITH A CHEMICAL CLEANER BEFORE INSTALLING NEW COM PONENTS.
CLEANING THE PRIMARY SYSTEM: Cleanse the system in accodance with
BS 7593.
Fill the system with cold mains water to the
recommended pressure and check for leaks.
Open all drain cocks and drain the system.
Close drain cocks and add a suitable flushing
agent at the correct strength for the system condition in accordance with the manufacturer's instructions.
Circulate the flushing agent before the boiler
is fired up.
Run the boiler and system at normal operating
temperature in accordance with the manufacturer's instructions.
Drain and thoroughly flush the system to
remove the flushing agent and any debris.
IMPORTANT: All the following Pre-Installation sections must be read and requirements met before starting boiler or flue installation.
CAUTION: ISOLATE THE MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
IMPORTANT: Debris from the system can damage the boiler and reduce efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance warranty.
CLEANING PRIMARY SYSTEMS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
7
PRE -
INSTALLATION
MAINS SUPPLIES
ELECTRIC SUPPLY:
• Supply: 230V - 50Hz.
• Cable: PVC insulated 0.75mm2(24 x
0.2mm) temperature rated to 90°C.
• Protection IP45.
• External 5A fuse to BS 1362.
• The appliance must be earthed.
• Please refer to IEE regulations for cross bonding requirements.
• It must be possible to isolate the appliance from the electric supply with at least a 3mm contact separation in both poles supplying the appliance.
• Wiring between the appliance and the
electrical supply must comply with IEE wiring regulations and any local regulations which may apply for fixed wiring to a stationary appliance.
• Any system connected to the boiler must not
have a separate electrical supply.
WATER SUPPLY:
The following are general requirements and if necessary the advice of the local water company should be sought before fitting the appliance.
• The appliance cold water supply should be the first connection off the water main where possible.
• Maximum mains fed water pressure 10 bar. If necessary, fit a pressure reducing valve.
IMPORTANT: Non-return, back flow prevention devices (including those associated with water meters) fitted to the mains water supply can cause a pressure build up which could damage the boiler and other household appliances.
• Where the water main supply has a non­return, back flow prevention valve fitted, a mini expansion vessel (A) must be connected to the mains water inlet pipe (B) between the non-return valve (C) and the boiler (D) as shown opposite.
Use in hard water areas:
Normally there is no need for water treatment to prevent scale formation as the maximum temperature of the heat exchanger is limited by the control circuit. In areas where the temporary water hardness exceeds 200ppm, consideration may need to be given to the fitting of a scale prevention device. In such circumstances, the advice of the local water authority should be sought.
MAINS WATER EXPANSION VESSEL:
A - Mini expansion vessel, part No. 7 716 102 105 B - Mains water inlet C - Non-return valve D - Boiler
A
B
C
D
MAINS SUPPLIES
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
8
PRE -
INSTALLATION
12/18kW
Water Mains Pressure:
Minimum dynamic mains water pressure for
optimum performance.
1.5 bar 1.2 bar
0.9 bar
18/25kW 25/32kW
IMPORTANT: The appliance provides a permanent external electrical supply for servicing and must therefore be fed via a circuit breaker incorporating earth leakage protection.
OIL SUPPLY
This appliance is suitable for kerosene (28 second oil) only, no other fuel must be used.
OIL SUPPLY:
• Plastic or steel tanks should be installed to BS 5410. A steel tank should conform to BS 799: part 5 and have a slope of 1 in 24 away from the outlet valve with a sludge cock at its lower end.
• Do not use galvanised steel tanks or pipework for the oil supply system.
• Do not use soldered joints on the oil supply pipework.
a) Single pipe gravity feed system:
The oil storage tank (A) must be positioned so that the oil level does not exceed 4 metres above the level of the burner oil pump (J) and in addi­tion the oil level must be at least 300mm above the oil pump (J). Where the maximum oil level in the oil storage tank exceeds 4 metres, a head breaking device must be installed between the tank (A) and the burner oil pump (J).
b) Double pipe sub-gravity feed system:
Maximum suction height 3.5 metres. Non-return valves must be fitted to the inlet and return oil line between the oil pump (J) and oil storage tank (A).
c) Single pipe suction lift with de-aerator
Maximum suction height 3.5 metres. The oil tank (A) must be positioned below the oil pump (J). Create an inlet and return loop between the de-aerator (M) and oil pump (J).
A non-return valve must be incorporated within the de-aerator or fitted to the oil line between the oil storage tank (A) and the de-aerator (M).
A top feed oil tank fitted with a de-aerator using an internal non-return valve should have any non-return valves fitted in the base of the tank to the suction line removed to assist purging air from the oil line.
Pipework
Use copper pipe of the correct diameter
according to the information shown opposite. Use flexible hoses to connect to the oil pump (J).
Lay the oil supply pipe (H) as straight and
level as possible to avoid air pockets and unnecessary friction losses. Route away from the boiler access door or other hot surfaces.
Install a manual isolating valve (B) to the oil
supply pipe (H), as close to the oil storage tank (A) as possible.
Fit an oil strainer and water seperator (C) to
the oil supply pipe, near the oil storage tank. Fit an additional oil filter (N, 16µm max filtration size) close to the boiler, but not inside the boiler casing.
Fit a fire valve in accordance with BS 5410.
The fire valve (D) must be fitted externally at least 1 metre from the appliance with the fire valve sensor (F) located within the appliance case.
A capillary type valve provides a neat and simple installation. Alternatively, a fusible link or electrical system may be used.
Under no circumstances should a combination isolating/fire valve be used as the sole fire protection device.
A
F
BN
GJ
4m (13ft) max.
K
a)
H
300mm
min.
B DB C
MAXIMUM PIPE RUN FOR SINGLE PIPE GRAVITY FEED SYSTEM
B
A
DB
C
E
K
3.5m (11.5ft) max.
L
L
b)
H
F
G
B
MAXIMUM PIPE RUN FOR DOUBLE PIPE SUB-GRAVITY FEED SYSTEM
N
J
B
A
M
B
F
C
G
J
3.5m (11.5ft) max.
E
D
c)
MAXIMUM PIPE RUN FOR SINGLE PIPE SUCTION LIFT WITH DE-AERATOR
H
FUEL FLOW RATE
FUEL FLOW RATE
K
1m
min
.
1m
min
.
1m
min
.
E
OIL SUPPLY
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
9
PRE -
INSTALLATION
A - Oil storage tank B - Isolating valve C - Oil strainer & water seperator D - Fire valve to BS5410 E - External casing F - Fire valve sensor G - Oil burner
H - Oil supply pipe J - Oil pump K - Full base (plastic tanks) L - Non-return valve M - De-aerator N - Oil filter (16µm max filtration size)
NOTE: All dimensions are in metres unless stated otherwise. The maximum pipe run figures are based on using copper pipe with an inside diameter of 2mm less than the Ø.
HEAD 10mmØ 12mmØ
0.5 12 30
1. 0 25 69
1. 5 37 91
2.0 49 100
HEAD 10mmØ 12mmØ
2.5 62 100
3.0 74 100
3.5 87 100
4.0 99 100
HEAD 10mmØ 12mmØ
050 100
0.5 44 100
1. 0 3 8 9 5
1. 5 3 2 80
HEAD 10mmØ 12mmØ
2.0 26 66
2.5 20 50
3.0 14 37
3.5 8 22
HEAD 2.5kg/h 5kg/h 10kg/h 10kg/h
8mmØ 8mmØ 8mmØ 10mmØ
0 100 55 26 100
0.5 95 45 23 100
1.0 80 40 20 90
1. 5 70 3 5 17 75
HEAD 2.5kg/h 5kg/h 10kg/h 10kg/h
8mmØ 8mmØ 8mmØ 10mmØ
2.0 60 30 14 65
2.5 45 25 11 50
3.0 35 15 8 35
3.5 25 10 5 20
The table and illustration above is a guide only and does not in any way override the de­aerator manufacturers instructions.
TYPICAL OPEN VENT SYSTEM
INSTALLATIONCOMMISSIONING
A - Appliance expansion vessel B - Extra expansion vessel C - Automatic bypass valve D - Drain cock E - Feed & expansion cistern
WATER SYSTEMS & PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
10
PRE -
INSTALLATION
F - Feed & expansion 15mmØ min G - Appliance H - Open vent 22mmØ min L - Lockshield valve P - Pressure relief discharge
R - Radiators S - Static head T - TRV U - To filling system
WATER SYSTEMS & PIPEWORK
PRIMARY SYSTEM PLASTIC PIPEWORK:
Plastic pipework must not
be used for
the DHW system.
• Any plastic pipework used for the CH system must have a polymeric barrier, comply with BS 7921 and installed to BS 5955 with 1000mm (minimum) length of copper or steel pipe connected to the boiler.
• Plastic pipework used for underfloor heating must be correctly controlled with a thermostatic blending valve limiting the temperature of the circuits to approx. 50°C with 1000mm (minimum) length of copper or steel pipe connected to the boiler.
PRIMARY SYSTEM/CONNECTIONS/VALVES:
• Do not use galvanised pipes or radiators.
• All system connections, taps and mixing valves must be capable of sustaining a pressure of 3 bar.
• Radiator valves should conform to BS 2767:10.
• All other valves should conform to BS 1010.
• On new installations TRVs must be used on all radiators except the radiator where the room thermostat is sited, this must be fitted with lockshield valves and left open. All installations should have TRVs fitted to radiators within the sleeping accommodation.
• An automatic bypass valve must be connected between the heating flow and return where TRVs are used on all radiators, fitted to give at least a 3m circuit when activated.
• Drain cocks are required at all the lowest points on the system.
• Air vents are required at all high points on the system.
OPEN VENT PRIMARY SYSTEM:
• In order to comply with BS 5449 the feed and expansion pipe and the open vent pipe, (or the combined feed and vent pipe), must be connected to the BSP outlet/s on the right hand side of the primary heat exchanger.
• The feed and expansion cistern (E) must be positioned to provide a static head (S) of at least 1 metre above the highest point in the heating system to the water level in the feed and expansion cistern (E).
• Ensure adequate space is left in the expansion cistern for expansion of the system water.
• No valve shall be fitted in the open vent pipe (H) or the feed and expansion pipe (F).
• The open vent pipe (H) must be at least 22mmØ.
SEALED PRIMARY SYSTEM:
• Where the system volume is more than 180 litres at 0.5 bar or exceeds 2.65bar at maximum heating temperature an extra expansion vessel (B) must be fitted as close as possible to the appliance in the central heating return.
• Pressurise the extra expansion vessel (B) to the same figure as the expansion vessel built into the appliance.
IMPORTANT: The boiler should not be allowed to operate with a return temperature of less than 40°C when the system is up to operating temperature.
E
F
G
TYPICAL SEALED SYSTEM
A
G
B
U
P
S
1000mm min.
H
C
D
C
D
R R
T
R R
L
R R
T
R R
L
T
L
T
L
T
L
T
L
L
L
L
L
D
D
WATER SYSTEMS & PIPEWORK
FILLING PRIMARY SEALED SYSTEMS:
• Filling the system must comply with one of the methods shown opposite.
• The filling point must be at low level and must never be a permanent direct fixing to the mains water supply.
• Filling loops must be WRAS approved.
SHOWERS/BIDETS:
• If a shower head can be immersed in water or comes closer than 25mm from the top edge of a bath or shower tray spill over level then an anti-siphon device must be fitted to the shower hose.
• Only thermostatically controlled showers are suitable for use with this appliance.
• Bidets with direct hot & cold mains water can be used (with the approval of the local water authority) and must be the over rim flushing type with shrouded outlets to prevent the fitting of hand held sprays.
DOMESTIC HOT WATER:
Plastic pipework must not
be used for
the DHW system.
• Taps and mixing valves must be capable of sustaining a pressure up to 10 bar in accordance with the Water Regulations as they will be operating at mains water pressure.
• Hot water temperature and flow rate are affected by the size and insulation of pipework making up the distribution system and are controlled by the hot water tap and the water main inlet pressure. A mixing valve can be fitted if a more permanent setting is required.
• If using more than one outlet at once causes water flow starvation, fit flow balancing valves or Ball-O-Fix valves to the appropriate outlets.
Heating return
Hose
return
Non return
valve
Non return
valve
Test cock
Stop cock
Water main
supply
Stop cock
Temporary hose
Heating return
Auto air
vent
Non return
valve
Stop cock
Make up
vessel
1000mm above the highest point of the system
Fill Point
INSTALLATIONCOMMISSIONING
WATER SYSTEMS & PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
11
PRE -
INSTALLATION
CONDENSATE &
PRESSURE RELIEF PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
12
PRE -
INSTALLATION
CONDENSATE &
PRESSURE RELIEF PIPEWORK
CONDENSATE PIPEWORK:
• All national and, where appropriate, local
regulations for the discharge and neutralisation of condensate should be followed.
• The condensate pipe must be a minimum of
21.5mmØ polypropylene pipe.
• The condensate pipework must fall at least
50mm per metre towards the outlet and should take the shortest practicable route and not exceed 3 metres outside the building. If a run greater than 3m is required, 32mmØ polypropylene pipe must be used.
• The pipework must follow one of the options
shown opposite:
a - Internal waste drainage system
b - Soil/vent stack
c - External drainage system
d - External condensate absorption point
• Condensate pipework must not be connected
to rainwater downpipes.
• Use waterproof pipe insulation in exposed
positions and for external pipework
IMPORTANT: Condensate pipework must not leak and the condensate trap must be filled with water before the boiler is started to prevent the possibility of potentially harmful flue products escaping via the condensate route.
A - Condensate from the boiler condensate
trap (supplied) which has a 75mm minimum water seal.
B - Sink.
C - 21.5mm Ø polypropylene condensate pipe.
D - Gully.
E - Internal soil and vent stack. F - 300mm x 100mm Ø sealed plastic tube.
G - Ground level.
H - Drainage holes 50mm from base of tube
(12mm Ø at 25mm centres) facing away from building.
I - Limestone chippings.
PRESSURE RELIEF PIPEWORK:
IMPORTANT: The pressure relief valve is a safety device for the boiler and if activated may discharge boiling water or steam through the relief valve drain pipe. Care should be taken when siting the outlet pipe so that it does not cause an obstruction or discharge above a window, entrance or other public access where it could cause a hazard.
• The pressure relief drain pipe (K) should be
at least 15mm diameter copper pipe and run downwards away from the boiler and discharge away from any electrics or other hazard, preferably to an external drain or soakaway.
• Pipe (K) should be finished with a partial
bend, near the outlet to face the external boiler casing (as shown) to help prevent freezing.
J - External boiler casing.
K - Pressure relief pipe.
a
B
75mm
min.
b
C
E
c
A
A
450 min.
Invert
d
C
(Unsuitable for clay soil types)
500mm min.
A
200mm min.
J
K
C
A
D
C
D
F
25mm
min.
G
400mm
I
min.
H
BOILER LOCATION & CLEARANCES
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
13
PRE -
INSTALLATION
BOILER LOCATION &
CLEARANCES
WARN ING:
This appliance should not be installed where there is a potential for excessive ground water coverage.
This boiler is only suitable for installing externally at a suitable location onto a fixed permanent rigid surface capable of supporting the boiler weight.
There must be a sufficient hard standing around the appliance to allow for servicing.
The boiler must be installed on a flat level surface to ensure that condensate does not enter the primary heat exchanger.
Tarmac and wood hardstandings are not recommended.
CLEARANCES: Min service & flue clearances
Above 600mm Front 600mm
RH/LH flue outlet on opposite side 10mm RH flue outlet on rear 85mm LH flue outlet on rear 10mm
Rear = flue outlet on side 150mm** Rear = rear flue outlet 2500mm*
It is strongly recommended that the flue terminal faces away from walls to reduce the possibility of wetting occuring.
*This can be reduced to 1200mm if there is at least 2500mm clearance on both sides of the
flue.
** 200mm if a high level terminal is used exiting
through the rear panel.
600mm
2500mm*
600mm
BASE
FRONT
FRONT
2500mm*
150mm**
85mm10mm
600mm
10mm
600mm
2500mm*
FRONT
FRONT
2500mm*
10mm
600mm
150mm**
Plan view
Plan view
Plan view
600mm
(min)
CABINET MOUNTED LOW LEVEL
FLUE TERMINAL POSITIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
14
PRE -
INSTALLATION
Minimum dimensions of flue terminal positions for oil fired appliances:
TERMINAL POSITION B(H)
A
1
Directly below an opening, air brick, opening windows, etc 600mm
B
1
Horizontally to an opening, air brick, opening window, etc 600mm
C Below a plastic/painted gutter, drainage pipe or eaves if 75mm
combustible material protected
D
2
Below a plastic/painted gutter, drainage pipe or eaves without 600mm protection to combustible material
E From vertical sanitary pipework 300mm
F From an external or internal corner or from a surface or boundry 300mm
alongside the terminal
G Above ground or balcony level 300mm*
H 1From a surface or boundary facing the terminal with 2500mm 1200mm
clearance to both sides of the terminal
H 2From a surface or boundary facing the terminal with less than 2500mm
2500mm clearance to either side of the terminal
I 1From a terminal facing the terminal with 2500mm clearance to 1200mm
clearance to both sides of the terminal
I 2From a terminal facing the terminal with less than 2500mm 2500mm
clearance to either side of the terminal
K Horizontally from a terminal 750mm
B(H) Balanced Horizontal flue
1 An opening means an openable
element, such as an openable window, or a permanent opening such as a permanently open air vent.
Notwithstanding the dimensions above, a terminal should be at least 300mm from combustible material, e.g. a window frame.
2 A way of providing protection of
combustible material would be to fit a heat shield at least 750mm wide.
• Flue terminals must be positioned to avoid combustion products entering into buildings.
• The flue must be fitted and terminated in accordance with the recommendations of BS5410.
• The flue must not cause an obstruction.
• Discharge from the flue outlet must not be a nuisance.
• Flue gases have a tendency to plume and in certain weather conditions a white plume of condensation will be discharged from the flue outlet which could be regarded as a nuisance, for example, near security lighting.
• There should be no restriction preventing the clearance of combustion products from the terminal.
• The air inlet/outlet duct and the terminal of the boiler must not be closer than 25mm to any combustible material. Detailed recommendations on protection of combustible materials are given in BS 5410:1
• A protective terminal guard must be fitted if the terminal is 2m or less above a surface where people have access.
Stainless steel terminal guard. Part No: 7 716 190 050
• The following additional guidelines (from part L Exceptions Guidance Document) are recommended when determining the flue outlet position:
• Avoid discharging flue gases into car ports or narrow passageways.
• *Minimum distance of the flue terminal from above ground is 2100mm where directed to a public footpath, private access route or a frequently used area and 2500mm from a car parking area.
boundary
F
I
H
B
A
G
E
C, D
F
F
J
K
boundary
CABINET MOUNTED LOW LEVEL
FLUE TERMINAL POSITIONS
HIGH LEVEL FLUE TERMINAL POSITIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
8 716 106 252d (08/07)
15
PRE -
INSTALLATION
Minimum dimensions of flue terminal positions for oil fired appliances:
TERMINAL POSITION B(H) B(V)
A
1 2
Directly below an opening, air brick, opening window, etc 600mm N/A
B
1 2
Horizontally to an opening, air brick, opening window, etc 600mm N/A
C Below a plastic/painted gutter, drainage pipe or eaves if 75mm N/A
combustible material protected
D3Below a plastic/painted gutter, drainage pipe or eaves without 600mm N/A
protection to combustible material
E From vertical sanitary pipework 300mm N/A
F From an external or internal corner or from a surface or boundry 300mm N/A
alongside the terminal
G Above ground or balcony level 300mm* N/A
H From a surface or boundary facing the terminal 600mm** N /A
J From a terminal facing the terminal 1200**mm
K Vertically from a terminal on the same wall 1500mm N/A
L Horizontally from a terminal on the same wall 750mm —
M Above the point of highest intersection with the roof — 600mm
N From a vertical structure on the side of the terminal — 750mm
O Above a vertical structure less than 750mm from the side of the terminal — 600mm
P From a ridge terminal to a vertical structure on the roof — —
Q Above or to the side of any opening on a flat or sloping roof — 300mm
R Below any opening on a sloping roof — 1000mm
Key: — Not applicable, N/A Not allowed, B(H) Balanced Horizontal flue, B(V) B alanced Vertical flue.
Notes:
1. Terminals should be positioned so as to avoid products of combustion accumulating in stagnant pockets around the building or entering into buildings.
2. Vertical structure in N, O and P includes tank or lift rooms, parapets, dormers etc.
3. Terminating positions should be at least 1.8m from an oil storage tank unless a wall with at least 30 min fire resistance and
extending 300mm higher and wider than the tank is provided between the tank and the terminating position.
4. Where a flue is terminated less than 600mm away from a projection above it and the projection consists of plastics or has a combustible or painted surface, then a heat shield of at least 750mm wide should be fitted.
5. If the lowest part of the terminal is less than 2m above the ground, balcony, flat roof or other place to which any person has access, the terminal should be protected by a guard.
6. Notwithstanding the dimensions given above, a terminal should not be sited closer than 300mm to combustible material. In the case of a thatched roof, double this separation distance should be provided. It is also advisable to treat the thatch with a fire retardant material and close wire in the vicinity of the flue.
7. It is essential that a flue or chimney does not pass through the roof within the shaded area delineated by dimensions Q and R.
8. Where protection is provided for plastic components, such as guttering, it is essential that this is to the standard specified by the
manufacturer of the plastic components.
• Flue terminals must be positioned to avoid combustion products entering into buildings.
• The flue must be fitted and terminated in accordance with the recommendations of BS 5410.
• The flue must not cause an obstruction.
• Discharge from the flue outlet must not be a nuisance.
• Flue gases have a tendency to plume and in certain weather conditions a white plume of condensation will be discharged from the flue outlet which could be regarded as a nuisance, for example, near security lighting.
• There should be no restriction preventing the clearance of combustion products from the terminal.
• The air inlet/outlet duct and the terminal of the boiler must not be closer than 25mm to any combustible material. Detailed recommendations on protection of combustible materials are given in BS 5410:1
• A protective terminal guard must be fitted if the terminal is 2m or less above a surface where people have access. The guard must be spaced equally (minimum 50mm) around the flue and fixed to the wall with plated screws.
Stainless steel terminal guard. Part No: 7 716 190 050
The following additional guidelines (from part L Exceptions Guidance Document) are recommended when determining the flue outlet position:
• Avoid discharging flue gases into car ports or narrow passageways.
• *Minimum distance of the flue terminal from above ground is 2100mm where directed to a public footpath, private access route or a frequently used area and 2500mm from a car parking area.
• **Minimum distance of the flue terminal to a facing wall, fence, building or property boundary is 2500mm.
HIGH LEVEL FLUE TERMINAL
POSITIONS
P
boundary
F
M
Pitched roof
Q
Q
Q
Q
Q
Q
O
N
R
Q
Flat roof
C, D
boundary
J
A
B
H
E
G
K
F
F
L
Loading...
+ 36 hidden pages