Bosch 12-18, 25-32kW, 18-25 User Manual

Page 1
GREENSTAR HEATSLAVE EXTERNAL
THE APPLIANCE IS FOR USE WITH KEROSENE ( 28 SECOND
OIL) ONLY
INSTRUCTION MANUAL
GB
12/18, 18/25, 25/32kW
FLOOR STANDING EXTERNAL OIL FIRED CONDENSING COMBINATION BOILER USING BALANCED FLUE SYSTEM
FOR OPEN VENT AND SEALED CENTRAL HEATING SYSTEMS WITH DOMESTIC MAINS FED HOT WATER
THE APPLIANCE IS FOR USE WITH KEROSENE ( 28 SECOND
OIL) ONLY
GB
INSTRUCTION MANUAL
Page 2
INSTALLATION & SERVICING INSTRUCTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
1
Check List Hardware/Literature pack
Item Qty
Greenstar Heatslave External Installation/Servicing Instructions.........1
Users Instructions............................................................................................1
Hardware Pack.................................................................................................1
100mm Ø Services Duct................................................................................1
Condensate Trap Kit........................................................................................1
Warranty Return Envelope.............................................................................1
Cabinet Key.......................................................................................................1
SYMBOLS USED IN THIS MANUAL:
Domestic hot water
Central heating
Room thermostat
Frost thermostat
Wait time period
Programmer/timer OFF
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION.
THESE INSTRUCTIONS ARE APPLICABLE TO THE WORCESTER APPLIANCE MODEL(S) STATED ON THE FRONT COVER OF THIS MANUAL ONLY AND MUST NOT BE USED WITH ANY OTHER MAKE OR MODEL OF APPLIANCE.
THE INSTRUCTIONS APPLY IN THE UK ONLY AND MUST BE FOLLOWED EXCEPT FOR ANY STATUTORY OBLIGATION.
THIS APPLIANCE MUST BE INSTALLED BY A COMPETENT PERSON. FAILURE TO INSTALL CORRECTLY COULD LEAD TO PROSECUTION.
COMPLYING WITH THE BUILDING R EGULATIONS:
This heating appliance forms part of the controlled services for the building. It is law that all controlled services for buildings must comply with building regulations. You must be able to satisfy your Local Authority Building Control Body (LABC) that the work carried out concerning the installation and commissioning of this heating appliance has been carried out to a satisfactory standard.
OFTEC operate a competent persons scheme and registered installers are able to certify that their work complies with building regulations. Under the scheme;
OFTEC must be informed about every installation.OFTEC will issue a building regulations compliance certificate to the householder and will
notify the LABC.
OFTEC provide controlled document forms CD10 and CD11 for use during installation and commissioning respectively.
Other organisations operate self-certification schemes e.g. NAPIT and BESCA Ltd. and it may be possible for installers who are members of these organisations to self certify their work.
Alternatively you must submit a building control notice to the LABC before installing any boiler. The LABC will then arrange regular inspection visits during the work to ensure that the installation complies with the regulations.
IF YOU ARE IN ANY DOUBT CONTACT THE WORCESTER TECHNICAL HELPLIN E.
DISTANCE LEARNING AND TRAI NING COURSES ARE AVAILABLE FROM WORCESTER.
PLEASE LEAVE THESE INSTRUCTIONS WITH THE COMPLETED COMMISSIONING FORM AND THE USER MANUAL WITH THE OWNER OR WITH THE APPLIANCE AFTER INSTALLATION OR SERVICING. THE SERVICE INTERVAL RECORD CAN BE FOUND ON THE BACK PAGE OF THIS MANUAL.
ABBREVIATIONS USED IN THIS MANUAL: Ø Diameter CH Central Heating DHW Domestic Hot Water TRV Thermostatic Radiator Valve IP Ingress Protection CF Conventional flue BF Balanced flue N/A Not allowed SEDBUK Seasonal Efficiency of Domestic Boilers in the United Kingdom OFTEC Oil Firing Technical Association for the Petrolium Industry IEE Institute of Electrical Engineers LABC Local Authority Building Control Body
STORE THE APPLIANCE IN A DRY AREA PRIOR TO INSTALLATION.
INSTALLATION & SERVICING INSTRUCTIONS
IMPORTANT HANDLING INSTRUCTIONS: It is advised that more than one person is involved in the transfer of the packaged appliance from the van to the point of installation. It is advised that no attempt should be made to move the packaged appliance without the use of a suitable truck. At all times the correct method for handling heavy objects should be strictly observed.
GENERAL HANDLING GUIDELINES:
• Lift only a manageable weight, or ask for help.
• When lifting, bend the knees, and keep the back straight and feet apart.
• Do not lift and twist at the same time.
• Lift and carry items close to the body.
• Wear protective clothing and gloves to protect from any sharp edges.
Programmer ON CH only
Programmer ON DHW only
Programmer ON CH and DHW
Cold water main supply
Electricity supply
Page 3
SAFETY & REGULATIONS
IMPORTANT INFORMATION AND SYMBOLS 1
SAFETY PRECAUTIONS AND I NSTALLATION REGULATIONS 3
APPLIANCE INFORMATION
GENERAL INFORMATION 4
TECHNICAL DATA 5
LAYOUT & COMPONENTS 6
PRE-INSTALLATION
CLEANING PRIMARY SYSTEMS 7
MAINS SUPPLIES 8
OIL SUPPLY 9
WATER SYSTEMS & PIPEWORK 10-11
CONDENSATE & PRESSURE RELIEF PIPEWORK 12
BOILER LOCATION & CLEARANCES 13
CABINET MOUNTED LOW LEVEL FLUE TERMINAL POSITIONS 14
HIGH LEVEL FLUE TERMINAL POSITIONS 15
EXTERNAL OILFIT BALANCED FLUE OPTIONS 16
CABINET MOUNTED HORIZONTAL BALANCED FLUE OPTIONS 17
INSTALLATION
UNPACKING THE BOILER 18
PIPEWORK & FLUE POSITIONS 19
BOILER INSTALLATION 20
FLUE INSTALLATION 21
COMBUSTION CHAMBER 22
PIPEWORK CONNECTIONS 23-24
OIL BURNER AND PUMP 25
REFITTING COMPONENTS 26
ELECTRICS 27-28
COMMISSIONING
PRE-COMMISSIONING CHECKS - APPLIANCE 29
FILLING THE SYSTEM 30
STARTING THE APPLIANCE 31-34
WATER TREATMENT 35
FINISHING COMMISSIONING - APPLIANCE 36
SERVICING & SPARES
INSPECTION AND SERVICE 37-40
SHORT PARTS LIST 12/18 41
SHORT PARTS LIST 18/25 42
SHORT PARTS LIST 25/32 43
FAULT FINDING & DIAGNOSIS
FAULT FINDING 44-45
FAULT FINDING LOGIC FOR SATRONIC CONTROL BOX 46
FAULT FINDING LOGIC FOR 535 SE/LD RDB CONTROL BOX 47
ELECTRICAL SCH EMATIC 48
COMMISSIONING & SERVICE RECORDS
COMBUSTION RECORD 49
SERVICE INTERVAL RECORD 50
CONTENTS
CONTENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
2
SAFETY &
REGULATIONS
APPLIANCE
INFORMATION
PRE -
INSTALLATION
INSTALLATIONCOMMISSIONING
SERVICING
& SPARES
FAU LT FIND ING
& DIAGRAMS
Page 4
SAFETY PRECAUTIONS & INSTALLATION REGULATIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
3
SAFETY &
REGULATIONS
SAFETY PRECAUTIONS INSTALLATION REGULATIONS
OIL SMELLS, LEAKS OR FUMES FROM THE APPLIANCE:
Extinguish any naked flames.
Isolate the electrical supply.
Isolate the fuel supply to the boiler.
Rectify fault.
HEALTH & SAFETY:
The appliance contains no asbestos and no substances have been used in the construction process that contravene the COSHH Regulations (Control of Substances Hazardous to Health Regulations 1988). Where applicable, the CE mark indicates compliance with relative EU Directives.
COMBUSTIBLE AND CORROSIVE MATERIALS: Do not store or use any combustible materials (paper, thinners, paints etc.) inside or within the
vicinity of the appliance. The combustion air must be kept clear of chemically aggressive substances which can corrode the appliance and invalidate any warranty.
FITTING & MODIFICATIONS:
Fitting the appliance and any controls to the appliance may only be carried out by a competent engineer in accordance with these instructions and the relevant Installation Regulations. Flue systems must not be modified in any way other than as described in the fitting instructions. Any misuse or unauthorised modifications to the appliance, flue or associated components and systems could invalidate the warranty. The manufacturer accepts no liability arising from any such actions, excluding statutory rights.
SERVICING:
Advise the user to have the system regularly serviced by a competent, qualified engineer (such as OFTEC registered personnel) using approved spares, to help maintain the economy, safety and reliability of the appliance.
Failure to install appliances correctly could lead to prosecution.
The appliance should be installed by a competent person. The person installing the appliance should be aware of the Health and Safety at Work Act and take appropriate action to ensure that the regulations are adhered to. In order to give optimum efficiency and trouble free operation the appliance must be commissioned by a qualified OFTEC engineer.
The compliance with a British Standard does not, in itself, confer immunity from legal obligations. In particular the installation of this appliance must be in accordance with the relevant requirements of the following British Standards and regulations in respect of the safe installation of equipment: BS 5410: part 1: Code of practice for Oil Fired Boilers. BS 799: part 5: Specification for Oil Storage Tanks. BS 7593: Code of Practice for treatment of water in domestic hot water central heating systems. BS 5449: part 1: Specification for forced circulation hot water central heating for domestic premises. BS 5955: part 8: Specification for the installation of thermoplastic pipes and associated fittings for use in domestic hot and cold water services and heating systems. BS 7291: Thermoplastic pipes and associated fittings for hot and cold water for domestic purposes and heating installations in buildings. BS 7074: part 1: Application, selection and installation of expansion vessels and ancillary equipment for sealed water systems. BS 7671: IEE Wiring Regulations, current edition. BS 1362: Specification for general purpose fuse links for domestic and similar purposes. The Building Regulations Part J and L1 England and Wales; Part F and Part J Section III Scotland; Part L and Part F Northern Ireland. Local water company bye-laws. The Control of Pollution (Oil) Regulations. OFTEC Standards. Where no specific instruction is given, reference should be made to the relevant codes of practice.
Page 5
GENERAL INFORMATION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
4
APPLIANCE
INFORMATION
GENERAL INFORMATION
STANDARD PACKAGE:
A - Floor standing oil fired condensing boiler for
open vent and sealed domestic central heating and mains fed hot water.
B - Literature pack.
C -Condensate trap kit.
D - 100mmØ services duct.
E - Cabinet key
Check List
Item Qty
Greenstar Heatslave External Installation/Servicing Instructions........1
Users Instructions ..........................................................................................1
100mm Ø Services Duct...............................................................................1
Condensate Trap Kit.......................................................................................1
Warranty Return Envelope ............................................................................1
Cabinet Key.......................................................................................................1
770mm
640mm
950mm
A
B
C
D
E
Page 6
TECHNICAL DATA
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
5
TECHNICAL DATA
Central Heating
Primary water capacity (total) litres
Maximum static head metres
Minimum static head metres
Available pump head (20°C difference) at max. output metres water
Max. permissible sealed system operating pressure bar
in accordance with WRAS guidelines
Flow restrictor colour
Domestic Hot Water
Optimum flow rate (±15%) litres/min
Minimum inlet pressure (dynamic) for optimum flow rate bar
Maximum hot water rise for 90 litres draw off (@optimum flow rate) °C
Flue
Exit flue gas mass flow kg/hr
Pipework connections
Fuel line (compression) mm
CH flow mm
CH return mm
Water main inlet mm
DHW outlet mm
Open vent (optional) BSP
CH drain/optional feed and expansion BSP
Condensate (polypropylene) mm
Electrical
Electrical power supply voltage AC...V
Frequency Hz
Max. power consumption W
Thermostats
CH control thermostat range (cut in/cut out) °C
DHW control thermostat range (cut in/cut out) °C
CH & DHW control thermostat differential °C
Boiler high limit thermostat set point °C
Boiler manual reset overheat thermostat set point °C
Flue reset overheat thermostat set point °C
General Data
Maximum hearth temperature °C
SEDBUK (Band A) %
Appliance protection rating IP
Weight (excluding packaging) kg
Emissions class for NOx and CO class
Typical NOx emissions figure mg/kW hr
DESCRIPTION UNITS 12/18 18/25 25/32
APPLIANCE
INFORMATION
69
30
1
4.7
2.5
Lime
15
1. 5
40
29
10
22
22
15
22
1
3
/
4
21. 5
230
50
240
55/81
55/72
5
92
105
110
<100
90.2
45
19 5
3
75
69
30
1
4.0
2.5
18
1. 2
40
40
10
22
22
15
22
1
3
/
4
21. 5
230
50
240
55/81
55/72
5
92
105
110
<100
90.1
45
19 5
3
70
72
30
1
4.2
2.5
22
0.9
40
51
10
28
28
15
22
1
3
/
4
21. 5
230
50
263
55/81
55/72
5
92
105
110
<100
90.3
45
206
3
75
Page 7
LAYOUT & COMPONENTS
The diagram opposite excludes the top, front and RH side casing panels.
1. CONTROL BOX ASSEMBLY
2. DIVERTER VALVE
3. PRESSURE GAUGE
4. AUTO AIR VENT
5. CH CONTROL AND MANUAL RESET OVERHEAT THERMOSTAT PHIAL
6. CASING SIDE PANEL
7. CIRCULATING PUMP
8. AUTO-RESET HIGH LIMIT THERMOSTAT PHIAL
9. DHW FLOW SWITCH
10. PRESSURE RELIEF VALVE
11. DHW HEAT EXCHANGER
12. FLUE GAS SAMPLING POINT
13. FLUE OVERHEAT THERMOSTAT PHIAL
14. CASING SUPPORT PANEL
15. FLUE MANIFOLD ACCESS COVER
16. AIR INLET PIPE AND CASING
17. SECONDARY HEAT EXCHANGER BLEED POINT (ONE ON EITHER SIDE)
18. SECONDARY HEAT EXCHANGER
19. SECONDARY HEAT EXCHANGER DRAIN
20. EXPANSION VESSEL
21. OPTIONAL OPEN VENT/AIR VENT
22. DRAIN AND OPTIONAL FEED AND EXPANSION
23. CONDENSATE OUTLET
24. PRIMARY HEAT EXCHANGER
25. TRAY
26. OIL ISOLATION VALVE
27. CONDENSATE TRAP
28. CONDENSATE TRAP BRACKET
29. COMBUSTION CHAMBER ACCESS DOOR
30. HEATSLAVE TANK DRAIN
31. HEATSLAVE TANK
32. MODE SWITCH
33. BOILER MODE INDICATOR
34. LOCKOUT INDICATOR
35. OVERHEAT RESET BUTTONS (boiler & flue temperature)
36. LOCKOUT RESET BUTTON
37. SERVICE CONNECTION
38. CH TEMPERATURE CONTROL
39. DHW TEMPERATURE CONTROL
40. DATA LABEL
41. FROST THERMOSTAT SENSORS
42a. BENTONE STERLING BURNER (12/18 & 18/25) i) CONTROL BOX ii) MOTOR iii) AIR INTAKE CASING iv) OIL PUMP v) COMBUSTION HEAD
42b. RIELLO RDB 2.2 BURNER (25/32) i) CONTROL BOX ii) MOTOR iii) AIR INTAKE CASING iv) OIL PUMP v) COMBUSTION HEAD
43. CLIP - AIR INTAKE HOSE
44. AIR INTAKE HOSE
LAYOUT & COMPONENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
6
APPLIANCE
INFORMATION
1
6
2
4
8
7
5
10
20
11
14
3
13
15
12
16
17
19
21
22
23
18
24
25
29
40
30
31
32
33
9
35/36
39
38
42a
42b
43
44
43
44
v)
iv)
iii)
ii)
i)
v)
iii)
i)
ii)
iv)
41
26
27
28
37
34
Page 8
CLEANING PRIMARY SYSTEMS
BEFORE CLEANING THE SYSTEM:
ENSURE THE SYSTEM AND PIPEWORK IS IN GOOD WORKING ORDER.
FLUSH THE EXISTING SYSTEM WITH A POWER FLUSHING MACHINE OR WITH A CHEMICAL CLEANER BEFORE INSTALLING NEW COM PONENTS.
CLEANING THE PRIMARY SYSTEM: Cleanse the system in accodance with
BS 7593.
Fill the system with cold mains water to the
recommended pressure and check for leaks.
Open all drain cocks and drain the system.
Close drain cocks and add a suitable flushing
agent at the correct strength for the system condition in accordance with the manufacturer's instructions.
Circulate the flushing agent before the boiler
is fired up.
Run the boiler and system at normal operating
temperature in accordance with the manufacturer's instructions.
Drain and thoroughly flush the system to
remove the flushing agent and any debris.
IMPORTANT: All the following Pre-Installation sections must be read and requirements met before starting boiler or flue installation.
CAUTION: ISOLATE THE MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
IMPORTANT: Debris from the system can damage the boiler and reduce efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance warranty.
CLEANING PRIMARY SYSTEMS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
7
PRE -
INSTALLATION
Page 9
MAINS SUPPLIES
ELECTRIC SUPPLY:
• Supply: 230V - 50Hz.
• Cable: PVC insulated 0.75mm2(24 x
0.2mm) temperature rated to 90°C.
• Protection IP45.
• External 5A fuse to BS 1362.
• The appliance must be earthed.
• Please refer to IEE regulations for cross bonding requirements.
• It must be possible to isolate the appliance from the electric supply with at least a 3mm contact separation in both poles supplying the appliance.
• Wiring between the appliance and the
electrical supply must comply with IEE wiring regulations and any local regulations which may apply for fixed wiring to a stationary appliance.
• Any system connected to the boiler must not
have a separate electrical supply.
WATER SUPPLY:
The following are general requirements and if necessary the advice of the local water company should be sought before fitting the appliance.
• The appliance cold water supply should be the first connection off the water main where possible.
• Maximum mains fed water pressure 10 bar. If necessary, fit a pressure reducing valve.
IMPORTANT: Non-return, back flow prevention devices (including those associated with water meters) fitted to the mains water supply can cause a pressure build up which could damage the boiler and other household appliances.
• Where the water main supply has a non­return, back flow prevention valve fitted, a mini expansion vessel (A) must be connected to the mains water inlet pipe (B) between the non-return valve (C) and the boiler (D) as shown opposite.
Use in hard water areas:
Normally there is no need for water treatment to prevent scale formation as the maximum temperature of the heat exchanger is limited by the control circuit. In areas where the temporary water hardness exceeds 200ppm, consideration may need to be given to the fitting of a scale prevention device. In such circumstances, the advice of the local water authority should be sought.
MAINS WATER EXPANSION VESSEL:
A - Mini expansion vessel, part No. 7 716 102 105 B - Mains water inlet C - Non-return valve D - Boiler
A
B
C
D
MAINS SUPPLIES
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
8
PRE -
INSTALLATION
12/18kW
Water Mains Pressure:
Minimum dynamic mains water pressure for
optimum performance.
1.5 bar 1.2 bar
0.9 bar
18/25kW 25/32kW
IMPORTANT: The appliance provides a permanent external electrical supply for servicing and must therefore be fed via a circuit breaker incorporating earth leakage protection.
Page 10
OIL SUPPLY
This appliance is suitable for kerosene (28 second oil) only, no other fuel must be used.
OIL SUPPLY:
• Plastic or steel tanks should be installed to BS 5410. A steel tank should conform to BS 799: part 5 and have a slope of 1 in 24 away from the outlet valve with a sludge cock at its lower end.
• Do not use galvanised steel tanks or pipework for the oil supply system.
• Do not use soldered joints on the oil supply pipework.
a) Single pipe gravity feed system:
The oil storage tank (A) must be positioned so that the oil level does not exceed 4 metres above the level of the burner oil pump (J) and in addi­tion the oil level must be at least 300mm above the oil pump (J). Where the maximum oil level in the oil storage tank exceeds 4 metres, a head breaking device must be installed between the tank (A) and the burner oil pump (J).
b) Double pipe sub-gravity feed system:
Maximum suction height 3.5 metres. Non-return valves must be fitted to the inlet and return oil line between the oil pump (J) and oil storage tank (A).
c) Single pipe suction lift with de-aerator
Maximum suction height 3.5 metres. The oil tank (A) must be positioned below the oil pump (J). Create an inlet and return loop between the de-aerator (M) and oil pump (J).
A non-return valve must be incorporated within the de-aerator or fitted to the oil line between the oil storage tank (A) and the de-aerator (M).
A top feed oil tank fitted with a de-aerator using an internal non-return valve should have any non-return valves fitted in the base of the tank to the suction line removed to assist purging air from the oil line.
Pipework
Use copper pipe of the correct diameter
according to the information shown opposite. Use flexible hoses to connect to the oil pump (J).
Lay the oil supply pipe (H) as straight and
level as possible to avoid air pockets and unnecessary friction losses. Route away from the boiler access door or other hot surfaces.
Install a manual isolating valve (B) to the oil
supply pipe (H), as close to the oil storage tank (A) as possible.
Fit an oil strainer and water seperator (C) to
the oil supply pipe, near the oil storage tank. Fit an additional oil filter (N, 16µm max filtration size) close to the boiler, but not inside the boiler casing.
Fit a fire valve in accordance with BS 5410.
The fire valve (D) must be fitted externally at least 1 metre from the appliance with the fire valve sensor (F) located within the appliance case.
A capillary type valve provides a neat and simple installation. Alternatively, a fusible link or electrical system may be used.
Under no circumstances should a combination isolating/fire valve be used as the sole fire protection device.
A
F
BN
GJ
4m (13ft) max.
K
a)
H
300mm
min.
B DB C
MAXIMUM PIPE RUN FOR SINGLE PIPE GRAVITY FEED SYSTEM
B
A
DB
C
E
K
3.5m (11.5ft) max.
L
L
b)
H
F
G
B
MAXIMUM PIPE RUN FOR DOUBLE PIPE SUB-GRAVITY FEED SYSTEM
N
J
B
A
M
B
F
C
G
J
3.5m (11.5ft) max.
E
D
c)
MAXIMUM PIPE RUN FOR SINGLE PIPE SUCTION LIFT WITH DE-AERATOR
H
FUEL FLOW RATE
FUEL FLOW RATE
K
1m
min
.
1m
min
.
1m
min
.
E
OIL SUPPLY
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
9
PRE -
INSTALLATION
A - Oil storage tank B - Isolating valve C - Oil strainer & water seperator D - Fire valve to BS5410 E - External casing F - Fire valve sensor G - Oil burner
H - Oil supply pipe J - Oil pump K - Full base (plastic tanks) L - Non-return valve M - De-aerator N - Oil filter (16µm max filtration size)
NOTE: All dimensions are in metres unless stated otherwise. The maximum pipe run figures are based on using copper pipe with an inside diameter of 2mm less than the Ø.
HEAD 10mmØ 12mmØ
0.5 12 30
1. 0 25 69
1. 5 37 91
2.0 49 100
HEAD 10mmØ 12mmØ
2.5 62 100
3.0 74 100
3.5 87 100
4.0 99 100
HEAD 10mmØ 12mmØ
050 100
0.5 44 100
1. 0 3 8 9 5
1. 5 3 2 80
HEAD 10mmØ 12mmØ
2.0 26 66
2.5 20 50
3.0 14 37
3.5 8 22
HEAD 2.5kg/h 5kg/h 10kg/h 10kg/h
8mmØ 8mmØ 8mmØ 10mmØ
0 100 55 26 100
0.5 95 45 23 100
1.0 80 40 20 90
1. 5 70 3 5 17 75
HEAD 2.5kg/h 5kg/h 10kg/h 10kg/h
8mmØ 8mmØ 8mmØ 10mmØ
2.0 60 30 14 65
2.5 45 25 11 50
3.0 35 15 8 35
3.5 25 10 5 20
The table and illustration above is a guide only and does not in any way override the de­aerator manufacturers instructions.
Page 11
TYPICAL OPEN VENT SYSTEM
INSTALLATIONCOMMISSIONING
A - Appliance expansion vessel B - Extra expansion vessel C - Automatic bypass valve D - Drain cock E - Feed & expansion cistern
WATER SYSTEMS & PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
10
PRE -
INSTALLATION
F - Feed & expansion 15mmØ min G - Appliance H - Open vent 22mmØ min L - Lockshield valve P - Pressure relief discharge
R - Radiators S - Static head T - TRV U - To filling system
WATER SYSTEMS & PIPEWORK
PRIMARY SYSTEM PLASTIC PIPEWORK:
Plastic pipework must not
be used for
the DHW system.
• Any plastic pipework used for the CH system must have a polymeric barrier, comply with BS 7921 and installed to BS 5955 with 1000mm (minimum) length of copper or steel pipe connected to the boiler.
• Plastic pipework used for underfloor heating must be correctly controlled with a thermostatic blending valve limiting the temperature of the circuits to approx. 50°C with 1000mm (minimum) length of copper or steel pipe connected to the boiler.
PRIMARY SYSTEM/CONNECTIONS/VALVES:
• Do not use galvanised pipes or radiators.
• All system connections, taps and mixing valves must be capable of sustaining a pressure of 3 bar.
• Radiator valves should conform to BS 2767:10.
• All other valves should conform to BS 1010.
• On new installations TRVs must be used on all radiators except the radiator where the room thermostat is sited, this must be fitted with lockshield valves and left open. All installations should have TRVs fitted to radiators within the sleeping accommodation.
• An automatic bypass valve must be connected between the heating flow and return where TRVs are used on all radiators, fitted to give at least a 3m circuit when activated.
• Drain cocks are required at all the lowest points on the system.
• Air vents are required at all high points on the system.
OPEN VENT PRIMARY SYSTEM:
• In order to comply with BS 5449 the feed and expansion pipe and the open vent pipe, (or the combined feed and vent pipe), must be connected to the BSP outlet/s on the right hand side of the primary heat exchanger.
• The feed and expansion cistern (E) must be positioned to provide a static head (S) of at least 1 metre above the highest point in the heating system to the water level in the feed and expansion cistern (E).
• Ensure adequate space is left in the expansion cistern for expansion of the system water.
• No valve shall be fitted in the open vent pipe (H) or the feed and expansion pipe (F).
• The open vent pipe (H) must be at least 22mmØ.
SEALED PRIMARY SYSTEM:
• Where the system volume is more than 180 litres at 0.5 bar or exceeds 2.65bar at maximum heating temperature an extra expansion vessel (B) must be fitted as close as possible to the appliance in the central heating return.
• Pressurise the extra expansion vessel (B) to the same figure as the expansion vessel built into the appliance.
IMPORTANT: The boiler should not be allowed to operate with a return temperature of less than 40°C when the system is up to operating temperature.
E
F
G
TYPICAL SEALED SYSTEM
A
G
B
U
P
S
1000mm min.
H
C
D
C
D
R R
T
R R
L
R R
T
R R
L
T
L
T
L
T
L
T
L
L
L
L
L
D
D
Page 12
WATER SYSTEMS & PIPEWORK
FILLING PRIMARY SEALED SYSTEMS:
• Filling the system must comply with one of the methods shown opposite.
• The filling point must be at low level and must never be a permanent direct fixing to the mains water supply.
• Filling loops must be WRAS approved.
SHOWERS/BIDETS:
• If a shower head can be immersed in water or comes closer than 25mm from the top edge of a bath or shower tray spill over level then an anti-siphon device must be fitted to the shower hose.
• Only thermostatically controlled showers are suitable for use with this appliance.
• Bidets with direct hot & cold mains water can be used (with the approval of the local water authority) and must be the over rim flushing type with shrouded outlets to prevent the fitting of hand held sprays.
DOMESTIC HOT WATER:
Plastic pipework must not
be used for
the DHW system.
• Taps and mixing valves must be capable of sustaining a pressure up to 10 bar in accordance with the Water Regulations as they will be operating at mains water pressure.
• Hot water temperature and flow rate are affected by the size and insulation of pipework making up the distribution system and are controlled by the hot water tap and the water main inlet pressure. A mixing valve can be fitted if a more permanent setting is required.
• If using more than one outlet at once causes water flow starvation, fit flow balancing valves or Ball-O-Fix valves to the appropriate outlets.
Heating return
Hose
return
Non return
valve
Non return
valve
Test cock
Stop cock
Water main
supply
Stop cock
Temporary hose
Heating return
Auto air
vent
Non return
valve
Stop cock
Make up
vessel
1000mm above the highest point of the system
Fill Point
INSTALLATIONCOMMISSIONING
WATER SYSTEMS & PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
11
PRE -
INSTALLATION
Page 13
CONDENSATE &
PRESSURE RELIEF PIPEWORK
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
12
PRE -
INSTALLATION
CONDENSATE &
PRESSURE RELIEF PIPEWORK
CONDENSATE PIPEWORK:
• All national and, where appropriate, local
regulations for the discharge and neutralisation of condensate should be followed.
• The condensate pipe must be a minimum of
21.5mmØ polypropylene pipe.
• The condensate pipework must fall at least
50mm per metre towards the outlet and should take the shortest practicable route and not exceed 3 metres outside the building. If a run greater than 3m is required, 32mmØ polypropylene pipe must be used.
• The pipework must follow one of the options
shown opposite:
a - Internal waste drainage system
b - Soil/vent stack
c - External drainage system
d - External condensate absorption point
• Condensate pipework must not be connected
to rainwater downpipes.
• Use waterproof pipe insulation in exposed
positions and for external pipework
IMPORTANT: Condensate pipework must not leak and the condensate trap must be filled with water before the boiler is started to prevent the possibility of potentially harmful flue products escaping via the condensate route.
A - Condensate from the boiler condensate
trap (supplied) which has a 75mm minimum water seal.
B - Sink.
C - 21.5mm Ø polypropylene condensate pipe.
D - Gully.
E - Internal soil and vent stack. F - 300mm x 100mm Ø sealed plastic tube.
G - Ground level.
H - Drainage holes 50mm from base of tube
(12mm Ø at 25mm centres) facing away from building.
I - Limestone chippings.
PRESSURE RELIEF PIPEWORK:
IMPORTANT: The pressure relief valve is a safety device for the boiler and if activated may discharge boiling water or steam through the relief valve drain pipe. Care should be taken when siting the outlet pipe so that it does not cause an obstruction or discharge above a window, entrance or other public access where it could cause a hazard.
• The pressure relief drain pipe (K) should be
at least 15mm diameter copper pipe and run downwards away from the boiler and discharge away from any electrics or other hazard, preferably to an external drain or soakaway.
• Pipe (K) should be finished with a partial
bend, near the outlet to face the external boiler casing (as shown) to help prevent freezing.
J - External boiler casing.
K - Pressure relief pipe.
a
B
75mm
min.
b
C
E
c
A
A
450 min.
Invert
d
C
(Unsuitable for clay soil types)
500mm min.
A
200mm min.
J
K
C
A
D
C
D
F
25mm
min.
G
400mm
I
min.
H
Page 14
BOILER LOCATION & CLEARANCES
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
13
PRE -
INSTALLATION
BOILER LOCATION &
CLEARANCES
WARN ING:
This appliance should not be installed where there is a potential for excessive ground water coverage.
This boiler is only suitable for installing externally at a suitable location onto a fixed permanent rigid surface capable of supporting the boiler weight.
There must be a sufficient hard standing around the appliance to allow for servicing.
The boiler must be installed on a flat level surface to ensure that condensate does not enter the primary heat exchanger.
Tarmac and wood hardstandings are not recommended.
CLEARANCES: Min service & flue clearances
Above 600mm Front 600mm
RH/LH flue outlet on opposite side 10mm RH flue outlet on rear 85mm LH flue outlet on rear 10mm
Rear = flue outlet on side 150mm** Rear = rear flue outlet 2500mm*
It is strongly recommended that the flue terminal faces away from walls to reduce the possibility of wetting occuring.
*This can be reduced to 1200mm if there is at least 2500mm clearance on both sides of the
flue.
** 200mm if a high level terminal is used exiting
through the rear panel.
600mm
2500mm*
600mm
BASE
FRONT
FRONT
2500mm*
150mm**
85mm10mm
600mm
10mm
600mm
2500mm*
FRONT
FRONT
2500mm*
10mm
600mm
150mm**
Plan view
Plan view
Plan view
600mm
(min)
Page 15
CABINET MOUNTED LOW LEVEL
FLUE TERMINAL POSITIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
14
PRE -
INSTALLATION
Minimum dimensions of flue terminal positions for oil fired appliances:
TERMINAL POSITION B(H)
A
1
Directly below an opening, air brick, opening windows, etc 600mm
B
1
Horizontally to an opening, air brick, opening window, etc 600mm
C Below a plastic/painted gutter, drainage pipe or eaves if 75mm
combustible material protected
D
2
Below a plastic/painted gutter, drainage pipe or eaves without 600mm protection to combustible material
E From vertical sanitary pipework 300mm
F From an external or internal corner or from a surface or boundry 300mm
alongside the terminal
G Above ground or balcony level 300mm*
H 1From a surface or boundary facing the terminal with 2500mm 1200mm
clearance to both sides of the terminal
H 2From a surface or boundary facing the terminal with less than 2500mm
2500mm clearance to either side of the terminal
I 1From a terminal facing the terminal with 2500mm clearance to 1200mm
clearance to both sides of the terminal
I 2From a terminal facing the terminal with less than 2500mm 2500mm
clearance to either side of the terminal
K Horizontally from a terminal 750mm
B(H) Balanced Horizontal flue
1 An opening means an openable
element, such as an openable window, or a permanent opening such as a permanently open air vent.
Notwithstanding the dimensions above, a terminal should be at least 300mm from combustible material, e.g. a window frame.
2 A way of providing protection of
combustible material would be to fit a heat shield at least 750mm wide.
• Flue terminals must be positioned to avoid combustion products entering into buildings.
• The flue must be fitted and terminated in accordance with the recommendations of BS5410.
• The flue must not cause an obstruction.
• Discharge from the flue outlet must not be a nuisance.
• Flue gases have a tendency to plume and in certain weather conditions a white plume of condensation will be discharged from the flue outlet which could be regarded as a nuisance, for example, near security lighting.
• There should be no restriction preventing the clearance of combustion products from the terminal.
• The air inlet/outlet duct and the terminal of the boiler must not be closer than 25mm to any combustible material. Detailed recommendations on protection of combustible materials are given in BS 5410:1
• A protective terminal guard must be fitted if the terminal is 2m or less above a surface where people have access.
Stainless steel terminal guard. Part No: 7 716 190 050
• The following additional guidelines (from part L Exceptions Guidance Document) are recommended when determining the flue outlet position:
• Avoid discharging flue gases into car ports or narrow passageways.
• *Minimum distance of the flue terminal from above ground is 2100mm where directed to a public footpath, private access route or a frequently used area and 2500mm from a car parking area.
boundary
F
I
H
B
A
G
E
C, D
F
F
J
K
boundary
CABINET MOUNTED LOW LEVEL
FLUE TERMINAL POSITIONS
Page 16
HIGH LEVEL FLUE TERMINAL POSITIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
8 716 106 252d (08/07)
15
PRE -
INSTALLATION
Minimum dimensions of flue terminal positions for oil fired appliances:
TERMINAL POSITION B(H) B(V)
A
1 2
Directly below an opening, air brick, opening window, etc 600mm N/A
B
1 2
Horizontally to an opening, air brick, opening window, etc 600mm N/A
C Below a plastic/painted gutter, drainage pipe or eaves if 75mm N/A
combustible material protected
D3Below a plastic/painted gutter, drainage pipe or eaves without 600mm N/A
protection to combustible material
E From vertical sanitary pipework 300mm N/A
F From an external or internal corner or from a surface or boundry 300mm N/A
alongside the terminal
G Above ground or balcony level 300mm* N/A
H From a surface or boundary facing the terminal 600mm** N /A
J From a terminal facing the terminal 1200**mm
K Vertically from a terminal on the same wall 1500mm N/A
L Horizontally from a terminal on the same wall 750mm —
M Above the point of highest intersection with the roof — 600mm
N From a vertical structure on the side of the terminal — 750mm
O Above a vertical structure less than 750mm from the side of the terminal — 600mm
P From a ridge terminal to a vertical structure on the roof — —
Q Above or to the side of any opening on a flat or sloping roof — 300mm
R Below any opening on a sloping roof — 1000mm
Key: — Not applicable, N/A Not allowed, B(H) Balanced Horizontal flue, B(V) B alanced Vertical flue.
Notes:
1. Terminals should be positioned so as to avoid products of combustion accumulating in stagnant pockets around the building or entering into buildings.
2. Vertical structure in N, O and P includes tank or lift rooms, parapets, dormers etc.
3. Terminating positions should be at least 1.8m from an oil storage tank unless a wall with at least 30 min fire resistance and
extending 300mm higher and wider than the tank is provided between the tank and the terminating position.
4. Where a flue is terminated less than 600mm away from a projection above it and the projection consists of plastics or has a combustible or painted surface, then a heat shield of at least 750mm wide should be fitted.
5. If the lowest part of the terminal is less than 2m above the ground, balcony, flat roof or other place to which any person has access, the terminal should be protected by a guard.
6. Notwithstanding the dimensions given above, a terminal should not be sited closer than 300mm to combustible material. In the case of a thatched roof, double this separation distance should be provided. It is also advisable to treat the thatch with a fire retardant material and close wire in the vicinity of the flue.
7. It is essential that a flue or chimney does not pass through the roof within the shaded area delineated by dimensions Q and R.
8. Where protection is provided for plastic components, such as guttering, it is essential that this is to the standard specified by the
manufacturer of the plastic components.
• Flue terminals must be positioned to avoid combustion products entering into buildings.
• The flue must be fitted and terminated in accordance with the recommendations of BS 5410.
• The flue must not cause an obstruction.
• Discharge from the flue outlet must not be a nuisance.
• Flue gases have a tendency to plume and in certain weather conditions a white plume of condensation will be discharged from the flue outlet which could be regarded as a nuisance, for example, near security lighting.
• There should be no restriction preventing the clearance of combustion products from the terminal.
• The air inlet/outlet duct and the terminal of the boiler must not be closer than 25mm to any combustible material. Detailed recommendations on protection of combustible materials are given in BS 5410:1
• A protective terminal guard must be fitted if the terminal is 2m or less above a surface where people have access. The guard must be spaced equally (minimum 50mm) around the flue and fixed to the wall with plated screws.
Stainless steel terminal guard. Part No: 7 716 190 050
The following additional guidelines (from part L Exceptions Guidance Document) are recommended when determining the flue outlet position:
• Avoid discharging flue gases into car ports or narrow passageways.
• *Minimum distance of the flue terminal from above ground is 2100mm where directed to a public footpath, private access route or a frequently used area and 2500mm from a car parking area.
• **Minimum distance of the flue terminal to a facing wall, fence, building or property boundary is 2500mm.
HIGH LEVEL FLUE TERMINAL
POSITIONS
P
boundary
F
M
Pitched roof
Q
Q
Q
Q
Q
Q
O
N
R
Q
Flat roof
C, D
boundary
J
A
B
H
E
G
K
F
F
L
Page 17
BALANCED EXTERNAL OILFIT
FLUE OPTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
16
PRE -
INSTALLATION
IMPORTANT: The weather seal (supplied)
must be fitted to every flue joint to give the required level of weather protection.
The diagrams (opposite) show the components used and the maximum flue length (L) for each flue configuration.
In all cases L is measured from the outside of the boiler casing.
• To achieve the maximum flue length (L), a flue section will have to be reduced in length.
• Only the straight flue extensions can be
reduced in length by cutting.
IMPORTANT: All horizontal sections must rise away from the boiler by 52mm per metre (3°) to allow the condensate to drain back to the boiler.
A - Horizontal terminal B - Straight flue extension C - Flue bend 90° D - Flue bend 45° E - Vertical Terminal Kit (incl. 90° elbow) F - Horizontal terminal kit (incl. 90° elbow)
Calculating the flue length:
Measure the total flue length required, noting that the maximum straight flue length including the terminal is: Horizontal 80/125mmØ: 4000mm. Vertical 80/125mmØ / 100/150mmØ (25/32 only): 7000mm.
Then reduce the total straight flue length for each extra flue bend (excluding the vertical flue kit 90° elbow) by:
1000mm for 90°
500mm for 45°
Flue Extension lengths:
Horizontal & Vertical: 1000mm overall length.
Effective length when engaged into sockets within the flue run is 950mm.
Flue Terminal lengths:
Horizontal 80/125mmØ: 720mm
Vertical 80/125mmØ: 1080mm + cage
* Rear exit only. ** Horizontal flue runs should be kept as
short as possible.
L = 2000mm
BALANCED EXTERNAL OILFIT
FLUE OPTIONS
High level horizontal terminal (rear outlet)
*
**
Vertical terminal (rear outlet)
Vertical terminal (rear outlet)
Vertical terminal (side outlet)
**
**
**
F
B
125mmØ x2
L
L = 7000mm
E
B
125mmØ x5
L
A
B
C
D
F
E
L = 6000mm
D
E
D
B
125mmØ x4
L = 6000mm
E
C
B
125mmØ x4
L
L
Page 18
BALANCED FLUE OPTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
17
PRE -
INSTALLATION
CABINET MOUNTED BALANCED
HORIZONTAL FLUE OPTIONS
• The horizontal flue is fitted to the rear or either side of the cabinet.
IMPORTANT:
It is strongly recommended that the flue terminal faces away from walls to minimise the occurance of wetting.
A - External horizontal flue kit
Part No. 7 716 190 052
B - 90° inline elbow 80/125mm
Part No. 7 716 190 034
C - Terminal guard
Part No. 7 716 190 050
FRONT
FRONT
FRONT
Plan view
Plan view
Plan view
REAR FLUE OUTLET
A + C
LEFT HAND FLUE OUTLET
A + B + C
RIGHT HAND FLUE OUTLET
A + B + C
Page 19
Unpacking:
It is advised that two or more persons are involved in the transfer of the packaged boiler from the van to the point of delivery.
1 Once the packaged boiler has been
delivered, the outer carton is removed first. Care should be taken when releasing the straps. If a sharp implement is used make sure the outer carton is not pierced and that the implement is used in such a way so that it may not cause personal injury. All sharp objects must be covered or the blade retracted after use and put away in a safe place.
2 Lift carton up and away from the boiler.
Remove the plastic bag from the boiler and
place safely aside.
UNPACKING THE BOILER
LIFTING AND CARRYING PRECAUTIONS:
• Lift only a manageable weight, or ask for help.
• When lifting or putting things down, bend the knees, and keep the back straight and feet apart.
• Do not lift and twist at the same time.
• Lift and carry objects close to the body.
• Wear protective clothing and gloves to protect from any sharp edges.
IIMPORTANT: All the previous Pre-Installation sections must be read
and requirements met before starting boiler or flue installation.
1
2
UNPACKING THE BOILER
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
18
INSTALLATION
Page 20
All dimensions in mm
256
650
58
802
258
81
10 5
171
374
161
650
787
670
518
10 5
94
55
269
658 669 705 715
650
794
670
518
15 8
12 4
89.5 55
658 679 698 718
528
230
INSTALLATIONCOMMISSIONING
SAFETY:
All relevant safety precautions must be undertaken. Protective clothing, footwear, gloves and safety goggles must be worn as appropriate.
PIPEWORK CONNECTIONS:
CH flow 22mmØ copper (28mmØ on 25/32kW model)
DHW flow 22mmØ copper Mains water inlet 15mmØ CH return 22mmØ copper (28mmØ on
25/32kW model) Optional open vent 1'' BSP Services duct 100mmØ Drain/optional fill/feed & expansion
3
/
4
'' BSP Pressure relief pipe 15mmØ Condensate outlet 21.5mmØ
NOTE: For servicing purposes, keep the condensate and pressure relief discharge pipes away from components and pipework connections.
CAUTION: Ensure there are no pipes, electric cables, damp proof courses or other hazards before drilling.
PIPEWORK & FLUE POSITIONS
PIPEWORK & FLUE POSITIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
19
Condensate
Flue
Services
PRV
Fire valve capillary & drain access
Flue
Services
Condensate
PRV Oil
Flue
Services
Condensate
Oil
PRV
LEFT HAND SIDE
RIGHT HAND SIDE
REAR
Fire valve capillary & drain access
Page 21
BOILER INSTALLATION
Note: The cabinet is not load bearing it only provides weather protection for the boiler inside.
1Mark position of the 100mm services
duct on the exterior wall and make a hole through.
2Remove the key for the door fastners
from its transport position in the left hand side panel flue outlet aperture. Undo the screws at the bottom of the front panel (using the key provided) and remove the screws from the rear panel pulling both panels out and down to remove. Store safely away from the installation point.
3Remove the screws from the top panel
and lift up to remove, store safely away from the installation point.
4Slide the pressure gauge up out of its
bracket and carefully rest on top of the heat exchanger taking care not to snag or kink the capillary.
5Remove the screws securing the control
box to the side panels and carefully rest the control box on top of the heat exchanger taking care not to snag or kink the capillaries.
6Remove the screws securing the side
panels to the base panel and lift the side panels off complete with the rear support bar (shaded grey) and carefully stand the panels away from the installation point.
7Loosen the flexable air duct clamp (A)
and remove the air duct from the burner.
Depress the locking ears to unplug the
burner lead (B) from the control box (C).
Unscrew the burner retainers (D), then
withdraw the burner (E) from the boiler and store safely away from the installation point.
8Remove the screws securing the base
panel to the transit pallet and lift the boiler off the pallet and into its installation position taking care not to scrape the base panel across the hard standing. Do
not attempt to lift and position the boiler on your own. Do not use the copper pipes to move the boiler.
Fasten the base to the hard standing
using the holes provided. Care should be taken to ensure that the base is level.
9Refit the side panels and rear support
bar and screw the side panels to the baseplate and boiler.
Refit the control box and pressure
gauge taking care not to kink the capillary tubes.
Measure the 100mmØ services duct to
give at least 10mm inside the casing and to finish flush with the interior wall surface, cut to size and fit the duct. Fit the 100mm sealing ring where the duct enters the casing and seal the joint to the exterior wall and inside the cabinet with a suitable sealant.
BOILER INSTALLATION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
20
INSTALLATION
WARNING: THIS APPLIANCE IS SERVICED AND REPAIRED EXTERNALLY.
EXTERNAL EQUIPMENT OPERATED AT 230V SHOULD NOT BE INSTALLED, SERVICED OR REPAIRED UNDER ADVERSE WEATHER CONDITIONS.
THIS APPLIANCE IS INSTALLED AND SERVICED EXTERNALLY TO THE PROPERTY, BUT THE ENGINEER MUST HAVE ACCESS TO THE INSIDE OF THE PROPERTY WHEN INSTALLING OR SERVICING THE APPLIANCE.
7
C
B
3
45
2
6
8
2
E
D
7
A
Page 22
INSTALLATION NOTES:
Ensure all the seals are in good condition
and seated properly.
To ease assembly of flue components,
grease seals lightly with the solvent free grease supplied.
A terminal guard must be fitted if the
terminal is 2m or less above a surface where people have access.
All flue options:
1 Lightly grease the flue cowl seal with the
solvent free grease supplied.
2 Carefully remove the blanking plate from
the appropriate flue aperture (if necessary) and refit the blanking plate in the unused aperture.
3 Carefully remove the insulation from the
flue aperture in the cabinet that the flue is to pass through, and fit to the unused aperture (if necessary).
4 Refer to the flue manual supplied with the
flue kit for flue installation.
FLUE INSTALLATION
FLUE INSTALLATION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
21
INSTALLATION
Page 23
COMBUSTION CHAMBER
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
22
INSTALLATION
Combustion chamber:
1Release retaining nuts and washers (B).
Remove combustion chamber access
door (A).
2Ensure the baffles (C) and baffle retainer
(D) are correctly fitted for the boiler output
as shown in the plan views opposite.
3Refit combustion chamber door (A).
Secure with nuts and washers (B) and
tighten until the door is firmly secured, do not over tighten the nuts.
4Unscrew screws (E) and remove flue
manifold access cover (F).
5Check that all the baffles (G) and baffle
retainer (H) or ( J ) are correctly fitted to the secondary heat exchanger.
COMBUSTION CHAMBER
H
F
2
E
4
G
5
A
B
1
3
D
C
12/18 & 18/25kW
Plan sectional view
D
C
25/32kW
Plan sectional view
J
Hook the retainer ( J ) over the end two baffles
or
FRONT FRONT
Page 24
PIPEWORK CONNECTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
23
INSTALLATION
PIPEWORK CONNECTIONS
A - CH flow 22mmØ copper (28mmØ on
25/32 models) B - DHW flow 22mmØ C - Water main inlet 15mmØ D - CH return 22mmØ copper (28mmØ on
25/32 models) E - 10mmØ oil supply pipe connection F - Oil isolating valve (10mmØ) G - Flexible oil hose N - Optional open vent/air vent O - Drain/optional feed and expansion P - Fixing point for optional return oil pipe
WATER CONNECTIONS:
All service pipes into the property must pass
through the services duct.
Insulate all the system/supply pipes where
the pipes pass through the duct with at least 22mm insulation around the pipes.
Remove the transit bungs from the pipework
connections on the boiler.
NOTE: that surplus water may be present due to factory testing.
Ensure all pipework is clean.Align water pipework through the 100mm Ø
duct and connect, ensuring that the expansion tank and control box fit correctly before permanently connecting the pipework.
Check that all unused sockets have been
capped.
OIL SUPPLY CONNECTIONS:
NOTE: Oil filters and de-aeration devices are not to be fitted within the casing and the fire valve body must be at least 1 metre from the external casing.
Route the oil supply pipe through the
appropriate casing hole as required and connect to the isolating valve (F) and ensure the valve is closed.
Connect the flexible oil hose (G) to the
isolating valve (F).
Pass the fire valve sensor through the most
appropriate casing hole and locate the capillary in the cut out at the bottom of the hole.
Clip the sensor into the clip provided at the
rear of the control box.
Rotate the cover plate and seal so it does not
cover the capillary, then secure with the screws provided.
CAUTION: ISOLATE THE OIL & WATER MAINS SUPPLY BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
Page 25
PIPEWORK CONNECTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
24
INSTALLATION
PIPEWORK CONNECTIONS
H - Flue manifold condensate outlet J - Condensate outlet (21.5mmØ) - supplied K - Condensate pipe - not supplied L - Condensate trap with clamp - supplied M - Pressure relief (15mmØ)
CONDENSATE CONNECTION:
The condensate trap (L) must be installed
onto the bracket supplied.
Measure condensate pipe (J) mark and cut
square to length required.
Fit sealing washer inside condensate pipe
nut and connect to the flue manifold outlet (H).
Connect 21.5mm polypropylene pipe (K) (not
supplied) to the condensate pipe (J) and condensate trap (L) before terminating to waste.
Secure the condensate trap (L) with clamp
supplied.
Ensure that the condensate pipe runs away
from the boiler at a constant fall of 50mm
(min.) for every metre.
Carefully pour 500ml of water into the
condensate collection (R) to fill condensate trap.
Check the water is running away and the
condensate pipework joints are water tight.
Check the flue manifold seal is undamaged
and seated correctly.
Refit flue manifold access cover (Q) and
secure with screws (P).
IMPORTANT: The condensate trap must be correctly filled to prevent the possibility of potentially harmful flue products escaping via the condensate pipework.
PRESSURE RELIEF CONNECTION:
Connect the pressure relief pipe (M) to a
copper discharge pipe (15mmØ min.) and terminate externally to the appliance casing.
Blank all unused casing holes with the bungs
or cover plates and seals supplied. The drain/fire valve capillary hole covers should be rotated so that the unused capillary slot is covered by the cover plate and seal.
Refit rear panel.Seal all joints where pipes pass through the
casing, with suitable waterproof sealant.
IMPORTANT: Insulate all external condensate pipe work or run in 32mm pipe work to prevent freezing.
Page 26
OIL BURNER & PUMP
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
25
INSTALLATION
CAUTION: ISOLATE THE OIL & WATER MAINS SUPPLY BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
OIL BURNER:
1Check the nozzle (A) and electrode (B)
settings are correct for the relevant burner as shown opposite.
Ensure nozzle (A) is aligned centrally within
the combustion head (C).
Inspect for any visible defects.
IMPORTANT: Whenever replacing the combustion head, ensure that the photocell is lined up with the sight hole.
OIL PUMP:
Connecting the oil pump for a single pipe system:
The pump is factory set for single pipe operation with the flexible oil hose fitted. Check connections before use.
Converting the oil pump for a double pipe system:
1Check the inlet hose connection.
a) DANFOSS BFP 11 L3:
Remove pump front cover (A) ensuring a
suitable receptacle is used to catch any oil residue.
Remove changeover screw (B).
Remove horseshoe washer (C).
Refit changeover screw (B).
Refit front cover (A).
Remove oil pump return plug (2).
b) SUNTEC AS47C:
Remove return port plug (2) and insert
grub screw (B).
c) RIELLO RDB:
Unscrew return plug (2).
Screw in by-pass screw (3).
2Connect the flexible oil return hose
(not supplied) between the oil pump and
the return line connection, and tighten to secure.
5mm
Electrode gap
2.5 - 3.0mm
7.5mm
B
A
1
C
1
2
B
1
2
B
C
A
5mm
a) DANFOSS BFP 11 L3 OIL PUMP
b) SUNTEC AS47C OIL PUMP
5mm
Electrode gap 4mm
B
A
1
C
5mm
c) RIELLO RDB OIL PUMP
1
2
3
25/32 kW
12/18 & 18/25 kW
OIL BURNER & PUMP
Page 27
REFITTING COMPONENTS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
26
INSTALLATION
REFITTING COMPONENTS
1Align burner combustion head (A) into boiler
housing tube with gasket (B) correctly fitted.
Push firmly down to compress the gasket (B).
Tighten burner retainers (C) sufficiently to
ensure a good seal.
IMPORTANT: Ensure the gasket is a good seal between the burner combustion head and the boiler housing to prevent flue gases escaping from the combustion chamber into the cabinet.
Attach the flexible air duct and tighten
clamp(D) to secure to the burner air intake.
2Plug burner lead (E) into control box (F).
F
A
B
C
D
E
Page 28
ELECTRICS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
27
INSTALLATION
ELECTRICS
1
DANGER - 230V:
ISOLATE THE MAINS ELECTRICITY SUPPLY BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
IMPORTANT: THIS APPLIANCE PROVIDES A PERMENANT EXTERNAL ELECTRICAL SUPPLY FOR SERVICING AND MUST THEREFORE BE FED VIA A CIRCUIT BREAKER INCORPORATING EARTH LEAKAGE PROTECTION.
IMPORTANT: OBSERVE ELECTRONIC
STATIC DISCHARGE PRECAUTIONS. DO NOT TOUCH THE PCB CIRCUITS.
WARNING: EXTERNAL EQUIPMENT OPERATED AT 230 VOLTS SHOULD NOT BE SERVICED OR REPAIRED UNDER ADVERSE WEATHER CONDITIONS.
Access to 230V connections:
1Release screws (B) and remove cover
panel (C) from control box (A).
2Release screws (D) from cable clamp (E).
Pull inner clamp part (F) outwards.Feed sufficient power cable (G) through the
cable clamp (E) and secure grip with screw (D).
Separate wires from cable end and strip to 6mm.
230V connections (terminal block X1):
3Connect LIVE wire (Brown) to terminal L.
Connect NEUTRAL wire (Blue) to
terminal N.
Connect EARTH wire (Green/Yellow) to
the connector . Route the power cable down the side panel and through the service duct to the internal property connection point avoiding any potentially hot surfaces.
Any external device connected to the boiler must take its power supply from the boiler supply only and must NOT have a separate supply.
External 230V programmer (terminal block X4):
4 Remove 4 pin plug (M) from X4.
Remove test links (P) from plug block (M).Connect wires to plug block (M) as shown.Fit plug into terminal block X4.Connect earth to terminal block X1connector
230V room thermostat (terminal block X2):
6 Remove link (K).
Connect LIVE supply to terminal L
S.
Connect SWITCHED LIVE supply to
terminal LR.
NOTE: This is sometimes refered to as ‘call for heat’ or ‘heating load’.
Connect NEUTRAL to terminal Ns.
NOTE: Some devices do not require this.
Refit electric control panel cover:
Refit panel (C) and secure with screws (B).
NOTE: Both frost thermostats are fitted as standard to the external appliance to provide frost protection.
C
B
A
4
P
M
G
D
E
2/3
230V
MAINS
SUPPLY
X2
6
Neutral (if required)
Switched Live
Live
FROST STAT(1)
FROST
STAT(2)
7 k 7
ROOMSTAT
Accelerator resistor (if fitted)
PROG RAMMER (EXTERNAL)
5
clock
CH channel
HW channel
N Supply
L Supply
HW Demand
CH Demand
X4
Fuse
CONTROL BOARD
.
M
B
G
F
Fs
Ns
L
R
F
R
F
R
Ls
N
L
DHW
CH
Page 29
ELECTRICS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
28
INSTALLATION
X4
X3
X12
X11
X2
X13
X9
X1
X10
X8
X7
X6
gygy bl br
gy or bl br g
gy bl
br
gy
bl
br
g
pk or
y
pk pk
pk pk
y y
y y
bk r g gy w
123456
r r
r r
r
gor
43
2
3
2
w
2
3
4
or pk y
w w
w
w
987654321
bk r g gy w
g
bk
123456
A
g bk r gy w
bl
br
gy bl
br
gy or bl br
g
230V
w
1
2
3
4
5
6
7
8
9
11
15
16
17
13
14
12
18
bl
br
w g
10
1
N
L
Mains connection
Service connection
Mode switch
ELECTRICS
Electrical components:
1 Printed circuit board 2 Thermostat - boiler high limit 3 Thermostat - DHW control 4 Thermostat - CH control 5 Indicator lamp - boiler mode 6 Indicator lamp - lock-out 7 Manual reset - overheat thermostat 8 Manual reset - flue overheat thermostat 9 Manual reset - burner lock-out 10 External programmer (not supplied) 11 Burner socket 12 Burner plug 13 Burner control box (12/18 & 18/25 shown) 14 Flow switch 15 Circulating pump 16 Diverter valve 17 Frost stat 18 Frost stat
Wire colour code:
br - Brown bl - Blue gy - Green/Yellow r - Red w - White y - Yellow g - Grey bk - Black or - Orange pk - Pink
Page 30
PRE-COMMISSIONING CHECKS - APPLIANCE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
29
PRE-COMMISSIONING CHECKS -
APPLIANCE
CAUTION: ISOLATE THE MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
1Check that the service and water pipes are
connected correctly.
Check that all unused sockets are capped.
2Check that the oil supply is kerosene and
that the pipework is connected correctly to the oil pump via the supplied flexible oil hose.
Turn on the main oil supply valve at the
tank, check the oil supply pipework and connections. Rectify any leaks.
3Check the flue is correctly fitted and the
connections are secure.
4Check the condensate pipework is
correctly fitted and connected.
Check the condensate trap is filled with
water.
5Check the CH circulating pump is set to 3.
NOTE: The CH circulating pump is preset to number 3 and should not be altered. The diagrams opposite show the pump outputs.
NOTE: The cabinet is not load bearing, it only provides weather protection for the boiler inside.
IMPORTANT: If the boiler is not to be commissioned immediately then:
After successfully completing all of the checks and any rectification work, close the water valves, shut off the oil supply and electrically isolate the boiler.
Complete the installation part of the Guarantee Registration Card, and complete a CD10 or its equivalent, to inform the LABC of the installation.
COMMISSIONING
1
3
2
5
4
12/18 & 18/25
0.6
Bar
Bar
0.5
0.4
0.3
0.2
0.1
0
200
400 600 800 1000 1200 1400 1600
0
Litres per hour
25/32
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
200
400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
0
Litres per hour
Page 31
FILLING THE SYSTEM
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
30
COMMISSIONING
1Pull lever (C) up and push to the left to
move the diverter valve to the mid-position between ports A and B.
Push and hold lever (C) down to lock.
2Loosen the automatic air vent cover. 4Sealed systems only; check and if required,
adjust the expansion vessel pressure using the Schraeder type valve (D).
The charge pressure of the built-in 12 Litre expansion vessel is 0.5 bar as dispatched, which is equivalent to a static head of 5 metres (16.7 ft).
If an extra expansion vessel is fitted to the central heating return, adjust this to the same pressure as the appliance internal expansion vessel, refer to separate instructions supplied with the extra expansion vessel.
4Open all system and radiator valves (E).
Turn on the water main stop cock.
Open vented systems only; turn on the
water to the system feed and expansion cistern and allow the system to fill.
Sealed systems only; fill the system to
between 1 and 2 bar pressure via a WRAS approved filling link. Monitor the pressure gauge during venting and repressurise if required.
Check air is being discharged from the
automatic air vent.
Vent all radiators, retighten when completed,
check the system and correct any leaks.
Bleed air from both of the secondary heat
exchanger air vents (F).
Bleed air from the pipework using the
pump bleed screw.
5Sealed systems only; connect a suitable
hose to the Heatslave tank drain. Open the drain valve to reduce the system to the correct pressure, then close the drain valve.
Ensure safe disposal of the discharge. Rotate the adjustable pointer on the pressure gauge to record the set system
pressure.
6 Check system and rectify any leaks.
Push lever (C) to the left and pull
upwards to allow the lever to return to position A.
Leave the lever (C) unlocked at
position A.
FILLING THE SYSTEM
2
1
4
3
6
5
B
A
C
B
A
C
1 - 2 bar
F
D
EE
Total system
volume (litres)
18 0 107 13 8
Initial system
pressure (bar)
0.5
1. 0
1. 0
Initial charge
pressure (bar)
0.5
0.5
1. 0
Page 32
STARTING THE APPLIANCE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
31
COMMISSIONING
F
H
G
Return
Flow
TANK
A
B
C
A
B
C
A - Bleed & pressure gauge port
B - Pressure adjustment
C - Vacuum gauge port
D - Retaining screws - cover
D
D
DANFOSS
BFP 11 L3 OIL PUMP
SUNTEC
AS47C OIL PUMP
BURNER LOCKOUT
C
B
A
D
RIELLO
RDB OIL PUMP
BURNER LOCKOUT RESET BUTTON (D) FOR
25/32 MODEL
GREENSTAR HEATSLAVE EXTERNAL
max
flue
reset
boiler reset
max
lockout
on
service
1
BURNER LOCKOUT RESET
BUTTON (D) FOR 12/18
& 18/25 MODELS
(Under control box)
(On top of burner control box)
E - Lockout indicator
STARTING THE APPLIANCE
IMPORTANT: Never run the appliance when the appliance/system is unpressurised (sealed systems) or empty.
1Check the oil supply is correctly fitted and
in good working order before turning on the oil supply valves to the boiler.
Turn on the main oil supply valve at the tank
and draw off at least 21/2litres of oil until a steady flow of clear uncontaminated oil can be seen as follows:
The oil supply to the boiler should be
primed before the burner is operated to avoid unnecessary pump wear.
The use of an oil suction pump will prime and flush through any oil supply set up simply and easily, alternatively the following procedures can be used.
Single pipe gravity feed systems:
Disconnect the flexible oil hose and open
the isolating valve to discharge the oil into a suitable container.
If a top entry tank has been used the
pipework will need to be primed before the oil will discharge under gravity.
When completed, close the isolating valve,
reconnect the flexible oil hose.
Double pipe sub-gravity feed systems
and single pipe suction lift with de-aerator:
To prime a de-aerator, disconnect the
flexible oil inlet hose (F) from the isolation valve and place in a container of kerosene (G). Connect a spare flexible oil hose (H), to discharge into container (G). Open the isolating valve, turn on the power to the boiler and set the programmer to ON. Prime the de-aerator until there is a steady flow of oil into container (G). Turn off the boiler then
reconnect the flexible oil inlet hose (F).
Turn on the boiler, the oil level in the
de-aerator will drop as the oil is used until the oil is drawn from the tank. If the de-aerator empties and the burner locks out before the oil is drawn from the tank, prime the de-aerator again.
Open the isolating valve and the oil pump
bleed valve (A) to discharge into a suitable container once the boiler is started up.
Switch on the electricity supply to the boiler.
Set the programmer to ON for CH and DHW.
Turn on the boiler CH control thermostat.
Allow the burner to run through to lockout
indicated by the illumination of the lockout
indicator (E).
Wait 2 minutes then press the lockout reset
button (D).
Repeat the procedure at least 3 times or until a
steady stream of oil, without air, runs from the bleed port, then relock the bleed port (A).
Switch off the boiler.
Remove the oil pump filter, clean with
kerosene and refit.
The internal filter is accessed by removing the oil pump cover on the Danfoss BFP 11
L3, Suntec AS47C and Riello RDB.
Safely dispose of the container/discharge.
Page 33
STARTING THE APPLIANCE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
32
COMMISSIONING
STARTING THE APPLIANCE
2Remove plastic cover from the burner casing
(there is no plastic cover on the Riello burner).
Fit a suitable pressure gauge to port (A) on
the oil pump.
Adjust the air shutter (L) and pump pressure
(B) as shown in the table opposite. The burner should ignite following a pre-ignition period of approx. 15 seconds.
Boiler lockout indicator on:
If the burner fails to establish a normal firing pattern or flame failure occurs the flame monitoring photocell mounted in the burner body will alert the burner control box to shut the burner down and provide a safe lockout state indicated by the illumination of the lockout indicator (E).
Wait 2 minutes then press the lockout
reset button (D) to initiate another start sequence.
Repeat procedure until a flame is established.
3Start and run for 3 minutes then switch off.
Check for after-spurting from the nozzle,
indicated by oil saturation on the combustion
head (F).
If after-spurting occurs:
Release the burner retainers.Remove the burner, combustion head (F).
and electrodes, hold the burner vertical to unscrew the nozzle and fill the nozzle holder with oil.
Refit nozzle, electrodes, combustion
head (F) and the burner.
Restart and run for 3 minute intervals until
after-spurting stops.
4Start and run for 20 minutes.
Remove sampling point plug (K) to check
the smoke reading is between 0-1. If the smoke level is above 1, check the combustion settings are correct and the oil nozzle is in good condition.
Note; smoke readings may be inaccurate until the smoke from burning organic binder in the access door insulation has ceased.
Check the CO2levels and adjust the air
shutter (L) setting according to the table opposite.
Check the flue gas temperature is close to
the values shown in the table.
If the flue gas temperature is too high and the baffles are correctly fitted, then reduce the oil pump pressure (B) 5-10p.s.i. to compensate for nozzle variations.
Turn off the electrical supply. Isolate the oil supply to the burner.Remove the oil pressure gauge.Refit the blanking plug (A).Check and rectify any oil leaks.
5Switch on the oil supply.
Switch on the electrical supply.Restart the boiler and run for 5 minutes.Recheck the CO2levels and if required,
adjust the air shutter setting (L) to obtain the correct CO2level.
2
E
D 12/18 & 18/25
(under control box)
3
F
G
DANFOSS
BFP 11 L3 OIL PUMP
A
B
C
SUNTEC
AS47C OIL PUMP
A
C
B
A - Bleed & pressure gauge port
B - Pressure adjustment
C - Vacuum gauge port
5
L
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE USING 28sec KEROSENE:
NOZZLE
OIL PUMP
PRESSURE
(p.s.i.)
12/18 - Bentone Sterling 40 Burner:
0.35 80°SR
0.45 80°S
0.50 80°ES
115
115
140
18/25 - Bentone Sterling 50 Burner:
0.50 80°EH
0.55 80°EH
0.65 80°EH
130
145
150
25/32 - Riello RDB Burner:
0.75 60°ES
0.75 60°ES
0.85 60°ES
105
140
150
FUEL
FLOW RATE
Kg/h l/h
1.04
1.32
1.29
1.63
1.55
1.96
1.56
1.98
1.86
2.36
2.17
2.75
2.15
2.72
2.45
3.1
2.75
3.48
APPROX.
FLUE GAS
TEMP °C
66
70
73
72
79
82
78
80
83
%CO
11.5
12.0
12.5
11.5
12.0
12.5
11.5
12.0
12.5
2
APPROX.
AIR
SETTING
2.5
4.5
5.25
4.25
6.0
8.0
3.0
4.0
5.0
D 25/32
(on top of burner control box)
K
RIELLO
RDB OIL PUMP
L
APPLIANCE
INPUT OUTPUT
kW Btu/hr kW Btu/hr
42300
52900
63500
63500
75750
88000
87000
99300
12
15
18
18
21.5
25
25
28.5
32
12.4
15.5
18.6
18.6
22.2
25.8
25.5
29.1
111600
32.7
4
C
B
A
40900
51200
61400
61400
73400
85300
85300
97200
109200
Page 34
STARTING THE APPLIANCE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
33
COMMISSIONING
STARTING THE APPLIANCE
Domestic hot water:
1Set the CH/DHW programmer to OFF.
Fully open a hot water tap.
The burner should be OFF and the circulating pump ON.
2Close the hot water tap.
Set the DHW thermostat control (C) to
minimum as shown.
Set the programmer to DHW ON.
The burner should be ON with the circulating
pump to heat the water in the Heatslave
external tank.
When minimum set temperature is reached the burner and circulating pump will switch off.
3Fully open a hot water tap.
The burner should be ON with the circulating
pump.
Check the water flow rate using a suitable
measuring container; 12/18KW 15 litres/min 18/25kW 18 litres/min* 25/32kW 22 litres/min*
* Manually regulate using the water main
inlet isolating valve on the boiler.
4Fully close the hot water tap.
Check the burner and circulating pump**
switch off.
**The high limit thermostat may activate
pump overrun until the correct
temperature is restored.
1
2
on
max
max
flue
boiler
reset
reset
lockout
GREENSTAR HEATSLAVE EXTERNAL
service
C
3
on
max
max
flue
boiler
reset
reset
lockout
GREENSTAR HEATSLAVE EXTERNAL
service
4
on
max
max
flue
boiler
reset
reset
lockout
GREENSTAR HEATSLAVE EXTERNAL
service
Page 35
STARTING THE APPLIANCE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
34
COMMISSIONING
STARTING THE APPLIANCE
Central heating:
1Open all radiator valves.
Set room thermostat to maximum.Set programmer to ON for CH.Turn the DHW thermostat control (C) fully
anti-clockwise.
Turn the CH thermostat control (D) to max.
The burner should be ON with the circulating pump. The diverter valve (E) should open to port B for CH.
Ensure all radiators are heating up evenly
and balance the system to the temperature difference required across the heating flow and return relevant to the heating load.
2Set the room thermostat to minimum.
The burner and circulating pump should be off. The diverter valve (E) should return to port A for DHW (default).
Domestic hot water & central heating:
3Set the room thermostat to maximum.
Set the programmer to ON for DHW & CH.Turn the DHW thermostat control (C) fully
anti-clockwise.
Set the CH thermostat control (D) to max.
The burner should be ON with the circulating pump. The diverter valve (E) should open to port B for CH.
4Set the DHW thermostat control (C) to max.
The diverter valve (E) should move to port A and divert the flow to the Heatslave tank.
1
on
max
C
D
max
flue
boiler
reset
reset
lockout
GREENSTAR HEATSLAVE EXTERNAL
service
E
2
on
max
max
flue
boiler
reset
reset
lockout
GREENSTAR HEATSLAVE EXTERNAL
service
E
3
on
max
C
D
max
flue
boiler
reset
reset
lockout
GREENSTAR HEATSLAVE EXTERNAL
service
E
4
on
max
max
flue
boiler
reset
reset
lockout
GREENSTAR HEATSLAVE EXTERNAL
service
C
D
E
Page 36
WATER TREATMENT
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
35
COMMISSIONING
WATER TREATMENT
IMPORTANT: Debris from the system can damage the boiler and reduce efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance warranty.
FLUSHING (Central Heating):
1Switch off the boiler.
Open vented systems only: turn off the
water to the system header tank.
Open all radiator valves/drain cocks (C) and
drain the system while the appliance is hot.
Close drain cocks (C).
2Add a suitable flushing agent (F) and refill
the system at the correct strength for the system condition in accordance with the manufacturer's instructions.
Vent the boiler (there are two vent points
(A) at the top of the secondary heat exchanger. Only one may be in use, the other may be obscured by side fluing. Always vent (A) and the vent screw (B) on the pump and all radiators.
Run the boiler/system at normal operating
temperature for the time stated by the flushing agent manufacturer.
3Drain and thoroughly flush the system and
boiler to remove the flushing agent and debris (C).
INHIBITOR (Central Heating):
4Check drain cocks (C) and manual air vents
are closed and all radiator valves are open.
5Add a suitable inhibitor (I), (or combined
inhibitor/anti-freeze if the system is exposed to freezing conditions) to the heating system in accordance with the manufacturers instructions.
The inhibitor or combined inhibitor/anti-freeze must not cause damage to the materials within the boiler (mild steel, stainless steel, copper and brass) and any other materials/components within the system.
Open vented systems only: turn on the
water to the system header tank and allow the system to fill.
Sealed systems only: fill the system to
between 1 and 2 bar via a WRAS approved filling loop. Check the system pressure during venting and repressurise if necessary.
6Vent the boiler (there are two vent points
(A) at the top of the secondary heat
exchanger. Only one may be in use, the other maybe obscured by side fluing. Always vent (A) and the vent screw (B) on the pump and all radiators; retighten vents when complete.
7Record the date when the inhibitor was
added to the system on the guarantee card.
NOTE: The concentration level of inhibitor
in the system should be checked every 12 months or sooner if system content is lost.
The addition of sealing agents to the system water is not advised as this can cause problems with deposits left in the heat exchanger and invalidate the appliance and heat exchanger warranty .
2
1
3
4
5
6
1 - 2 bar
A
A
B
B
C
C
C
C
C
Page 37
31
FINISHING COMMISSIONING -
APPLIANCE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
36
COMMISSIONING
FINISHING COMMISSIONING -
APPLIANCE
1Refit the top panel and press down to
compress the seal when fitting the securing screws (A).
2Push the front panel up behind the top
panel and push in at the base to secure the screws (B) with the tool provided.
Always apply pressure at the edges of the panels when securing to avoid accidental damage.
Handover:
Complete the guarantee registration card,
combustion record (page 49) and a CD11 or an equivalent commissioning form.
Set up the controls and show the user how
to operate all the controls shown in the User Guide, and all system controls.
Where applicable, instruct the customer how
to repressurise the system.
If the appliance is unused and exposed to
freezing conditions, shut off all the mains supplies and drain the system and boiler to prevent damage to the system and boiler.
NOTE: Release drain point (K) to drain the secondary heat exchanger.
A
A
1
2
C
B
B
K
Page 38
INSPECTION AND SERVICE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
37
INSPECTION AND SERVICE
CAUTION: ISOLATE THE WATER, ELECTRICITY AND OIL MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS.
DO NOT USE PRESSURE WASHERS OR STEAM CLEANERS ON THIS APPLIANCE OR ITS CABINET.
WARNING: EXTERNAL EQUIPMENT OPERATED AT 230 VOLTS SHOULD NOT BE SERVICED OR REPAIRED UNDER ADVERSE WEATHER CONDITIONS
Routine servicing:
To maintain efficient boiler operation, the following should be carried out at least once a year:
Carry out a pre-service check and note any
operational faults:
Pre-Service Check:
1Unndo the screws at the base of the
front panel using the tool provided and pull the panel down and out to remove. Store safely away from the working area.
Operate the appliance and system and note any faults which may need to be corrected during the service.
Switch into service mode at switch (A).
2Depress locking ears and unplug burner
lead (B) from control box (C).
• An adapter lead is available to allow mains voltage service aids to be operated from the service connection (G). (Service lead Part No. 8 716 113 483 0).
3Loosen clip (D) to detach air duct.
4Unscrew burner retainers (E) to release
the burner combustion head (F).
Lift burner away, taking care not to over
strain the flexible oil hose/s or connections.
See the following instructions for detail of some of the service requirements listed below:
Check and clean the burner.Replace burner nozzle and flexible oil
hose/s.
Check and clean the baffle retainers.Check and clean the baffles.Check and clean the heat exchangers
surfaces.
Check the combustion chamber access
door insulation board.
Check that the flue system is unobstructed
and clean as necessary.
Clean or replace all oil filters.Check that the condensate system is not
obstructed, clean and refill the condensate trap as necessary.
Sealed systems only: The PRV is a safety
device and must be checked for correct operation. The expansion vessel pressure must be checked and adjusted as required.
SERVICING
& SPARES
on
A
service
1
C
2
B
G
3
D
4
F
E
Page 39
INSPECTION AND SERVICE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
38
SERVICING
& SPARES
1 Clean the Burner:
Remove the air intake cover (H) and clear
any debris from the air intake and air damper.
Disassemble the burner to allow access to
the fan impeller.
Check the condition of the gaskets between
these parts and replace if necessary.
Note the position of the air damper
adjustment and check the air damper moves freely.
Clean both sides of the fan impeller and
remove any debris from the burner housing.
Check that the impeller rotates freely.Reassemble the components.Remove the combustion head (K) and
thoroughly clean any deposits.
Remove the nozzle (E).
2 12/18 & 18/25 Inspection of Mechanical
Shut-off Valve:
Fasten an M5 screw, with a minimum length
of 30mm, into the threaded hole (L) and pull the screw to withdraw the check valve (M).
Check that the nozzle holder (N) is clear of
any debris and clean if necessary.
Check that the three holes in the check valve
(M) are clear of any debris. Check the
condition of the 'O' ring (O). Discard the check valve if the holes cannot be cleared, if the unit is defective or if the 'O' ring is damaged and replace with a new one.
Refit the check valve.
25/32
Check the nozzle holder is clear of any debris
and clean if neccessary.
12/18, 18/25 & 25/32
Fit a new oil atomising nozzle (E).
DO NOT dismantle the nozzle and DO NOT clean the nozzle tip.
Check the electrodes (F) and reset if
necessary as shown opposite.
Refit the combustion head. Check that the
nozzle (E) lies centrally in the combustion head and the head settings are as shown. Ensure that the photocell is lined up with the sight hole.
Withdraw the photocell (P) from its housing
and wipe clean.
Remove the oil pump internal filter, clean in
kerosene and reassemble.
The internal filter is accessed by removing screws (A) and the oil pump cover (B) on the Danfoss BFP 11 L3, Suntec AS47C and Riello RDB.
Replace the standard flexible oil hose/s at
every annual service to prevent the possibility of leakage due to ageing.
Reassemble the burner components.Check the sponge O-ring seal located
around the combustion head and replace if necessary.
This seal must be in good condition since failure will cause flue gases to escape into the cabinet.
INSPECTION AND SERVICE
A
B
A - Retaining screws - cover
B - Cover - oil pump
HPD
5mm
Electrode gap
2.5 - 3.0mm
7.5mm
F
E
5mm
K
L
N
M
O
DANFOSS
BFP 11 L3 OIL PUMP
SUNTEC
AS47C OIL PUMP
A
RIELLO
RDB OIL PUMP
B
5mm
Electrode gap 4mm
F
E
K
5mm
HPD
A
B
25/32
12/18 & 18/25
Page 40
INSPECTION AND SERVICE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
39
SERVICING
& SPARES
INSPECTION AND SERVICE
External oil filter:
Remove the paper element from the external
oil filter and replace it. If the filter contains a washable element, thoroughly clean in kerosene and reassemble into the filter.
Clean the boiler:
Manifold access:
Remove top cover by releasing the
screws at each corner and lift free.
Release screws (E) to remove the flue
manifold access cover (F) and clear any debris.
Check the condensate route (G) is clear and
clean the condensate trap and pipework.
Check the flue system and clean if necessary.Remove the baffle retainer (J) and baffles (H)
from the secondary heat exchanger.
Check and clean the secondary heat
exchanger surfaces.
NOTE: Do not use wire brushes and cleaning agents to clean the stainless steel secondary heat exchanger components.
Pour 500ml of water into drain (G) to refill the
condensate trap.
Clean the secondary heat exchanger baffles
(H) if necessary and refit correctly.
Refit the baffle retainer (J).Check the seal on the manifold access cover
(F) and replace if necessary.
Refit the flue manifold access cover (F)
and secure with screws (E).
Combustion chamber:
Release the M10 retaining nuts and washers
(B) and remove combustion chamber access door (A).
Check the fibreglass rope seal on the
combustion chamber access door (A) and replace if necessary.
Remove and check the baffle retainer (D).Remove the baffles (C), clean and check the
condition of the baffles and the acoustic insulation. Replace any baffles or insulation pads considered to be badly corroded/degraded.
Thoroughly clean all of the heat exchanger
surfaces using a suitable brush and clear all loose debris from the combustion chamber.
Check the condition of the combustion
chamber access door insulation. If the insulation is damaged the door assembly must be replaced.
Refit the items in reverse order ensure the
baffles (C) and baffle retainers (D) are correctly fitted for the boiler output as shown in the plan view opposite.
Refit combustion access door (A).Secure with nuts and washers (B) and
tighten until the door is firmly secured, do not over tighten the nuts.
Fire valve:
Check that the oil supply pipe has a fire valve
fitted at least 1m away from the appliance with the fire valve sensor located within the appliance case. A fire valve sensor clip (K) is provided for this purpose.
FRONT FRONT
E
F
J
H
G
or
J
H
G
A
B
K
Plan sectional view
12/18kW & 18/25kW
Plan sectional view
25/32kW
C
C
D
D
Page 41
INSPECTION AND SERVICE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
40
SERVICING
& SPARES
INSPECTION AND SERVICE
Re-commission the burner:
1Align burner combustion head (A) into the
boiler housing tube with gasket (B) correctly fitted.
Push firmly down to compress the gasket (B).Tighten burner retainers (C) sufficiently to
ensure a good seal.
IMPORTANT: Ensure the gasket is a good seal between the burner combustion head and the boiler housing to prevent flue gases escaping.
Refit flexible air duct and secure with clip (D).
2Plug burner lead (E) into control box (F).
Connect an oil pressure gauge to the oil
pump, run the burner and check the oil pressure is correct for the required boiler output. Check that the smoke reading is between 0 and 1, if the smoke reading is above 1 check the air setting. If the air setting is correct check that the burner has been reassembled correctly.
Allow the boiler to warm up then check the combustion settings are correct as indicated in the table below, adjust the CO
2
if necessary using the air shutter. When the combustion is correct turn off the boiler, remove the pressure gauge and refit the blanking plug and plastic cover.
Refit panels:
3Refit the top panel and press down to
compress the seal when fitting the securing screws.
Push the front panel up behind the top
panel and push in at the base to secure the screws with the tool provided.
After service handover:
Make a note of the date of any water treatment.Set the controls back to the users
requirements.
Complete the service interval record at the
back of this manual and a CD11 or an equivalent form.
If the appliance is unused and exposed to
freezing conditions; shut off all the mains supplies, isolate the boiler and drain the system and boiler, including the secondary heat exchanger.
%CO
2
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE USING 28sec KEROSENE:
NOZZLE
12/18 - Bentone Sterling 40 Burner:
OIL PUMP
PRESSURE
(p.s.i.)
FUEL
FLOW RATE
Kg/h l/h
APPROX.
FLUE GAS
TEMP °C
APPROX.
AIR
SETTING
APPLIANCE
INPUT OUTPUT
kW Btu/hr kW Btu/hr
0.35 80°SR
0.45 80°S
0.50 80°ES
115
115
140
1.04
1.29
1.55
1.32
1.63
1.96
66
70
73
11.5
12.0
12.5
2.5
4.5
5.25
42300
52900
63500
12
15
18
40900
51200
61400
12.4
15.5
18.6
25/32 - Riello RDB Burner:
0.75 60°ES
0.75 60°ES
0.85 60°ES
105
140
150
2.15
2.45
2.75
2.72
3.1
3.48
78
80
83
11.5
12.0
12.5
3.0
4.0
5.0
87000
99300
111600
25
28.5
32
85300
97200
109200
25.5
29.1
32.7
18/25 - Bentone Sterling 50 Burner:
0.50 80°EH
0.55 80°EH
0.65 80°EH
130
145
150
1.56
1.86
2.17
1.98
2.36
2.75
72
79
82
11.5
12.0
12.5
4.25
6.0
8.0
63500
75750
88000
18
21.5
25
61400
73400
85300
18.6
22.2
25.8
E
A
B
C
D
F
Page 42
SHORT PARTS LIST 12/18
1 Burner - Sterling 40
Part Number: 8 716 112 507 0
2 Combustion head - burner
Part Number: 8 716 112 604 0
3 Control box Satronic DKO 970
Part Number: 8 716 142 396 0
4 Photocell Satronic MZ770s
Part Number: 8 716 156 692 0
5 Control box base Satronic S98 12 pole
Part Number: 8 716 142 782 0
6 Ignition electrode
Part Number: 8 716 156 683 0
7 Motor
Part Number: 8 716 156 645 0
8 Oil pump - Danfoss BFP 11 L3
Part Number: 8 716 142 736 0
8a Oil pump - Suntec AS47C
Part Number: 8 716 157 014 0
9 Transformer (Excludes cable)
Part Number: 8 716 156 696 0
10 Mechanical shut-off valve
Part Number: 8 716 156 658 0
11 Flexible oil line kit
Part Number: 8 716 106 346 0
12 Burner 'O' ring gasket
Part Number: 8 716 109 158 0
13 Heating control thermostat
Part Number: 8 716 107 621 0
14 Auto reset High Limit thermostat
Part Number: 8 716 107 640 0
15 Manual reset High Limit thermostat
Part Number: 8 716 107 625 0
16 Manual reset flue thermostat
Part Number: 8 716 107 624 0
17 DHW control thermostat
Part Number: 8 716 107 637 0
18 Cleaning brush
Part Number: 8 716 109 428 0
19 Manifold access cover seal
Part Number: 8 716 107 536 0
20 Secondary Heat Exchanger gasket
Part Number: 8 716 112 954 0
21 Frost thermostat
Part Number: 8 716 105 965 0
22 Service lead
Part Number: 8 716 113 483 0
23 Oil nozzle
0.35 80° SR (12kW output) Part Number: 8 716 112 628 0
0.45 80° S (15kW output) Part Number: 8 716 106 197 0
0.50 80° ES (18kW output) Part Number: 8 716 156 669 0
1
SHORT PARTS LIST 12/18
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
41
SERVICING
& SPARES
2
3456
78
10
14
18
22
11
15 16
19 20
23
8a
12
9
13
17
21
Page 43
SHORT PARTS LIST 18/25
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 113 389b (09/07)
42
SERVICING
& SPARES
SHORT PARTS LIST 18/25
1 Burner - Sterling 50
Part Number: 8 716 112 570 0
2 Combustion head - burner
Part Number: 8 716 108 573 0
3 Control box Satronic DKO 970
Part Number: 8 716 142 396 0
4 Photocell Satronic MZ770s
Part Number: 8 716 156 692 0
5 Control box base Satronic S98 12 pole
Part Number: 8 716 142 782 0
6 Ignition electrode
Part Number: 8 716 156 683 0
7 Motor
Part Number: 8 716 156 645 0
8 Oil pump - Danfoss BFP 11 L3
Part Number: 8 716 142 736 0
8a Oil pump - Suntec AS47C
Part Number: 8 716 157 014 0
9 Transformer (Excludes cable)
Part Number: 8 716 156 696 0
10 Mechanical shut-off valve
Part Number: 8 716 156 658 0
11 Flexible oil line kit
Part Number: 8 716 106 346 0
12 Burner 'O' ring gasket
Part Number: 8 716 109 158 0
13 Heating control thermostat
Part Number: 8 716 107 621 0
14 Auto reset High Limit thermostat
Part Number: 8 716 107 640 0
15 Manual reset High Limit thermostat
Part Number: 8 716 107 625 0
16 Manual reset flue thermostat
Part Number: 8 716 107 624 0
17 DHW control thermostat
Part Number: 8 716 107 637 0
18 Cleaning brush
Part Number: 8 716 109 428 0
19 Manifold access cover seal
Part Number: 8 716 107 536 0
20 Secondary Heat Exchanger gasket
Part Number: 8 716 112 954 0
21 Frost thermostat
Part Number: 8 716 105 965 0
22 Service lead
Part Number: 8 716 113 483 0
21 Oil nozzle
0.50 80° EH (18kW output) Part Number: 8 716 156 672 0
0.55 80° EH (21.5kW output) Part Number: 8 716 156 671 0
0.65 80° EH (25kW output) Part Number: 8 716 110 362 0
1
2
3456
78
10
14
18
22
11
15 16
19 20
23
8a
12
9
13
17
21
Page 44
SHORT PARTS LIST 25/32
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
43
SERVICING
& SPARES
SHORT PARTS LIST 25/32
1 Burner - Riello RDB 2.2 25/32 HE
Part Number: 8 716 112 512 0
2 Combustion head - burner
Part Number: 8 716 112 521 0
3 Control box 535 SE/LD
Part Number: 8 716 109 203 0
4 Photocell
Part Number: 8 716 109 193 0
5 Ignition electrode
Part Number: 8 716 109 183 0
6 Motor
Part Number: 8 716 109 186 0
7 Oil pump - Riello RDB
Part Number: 8 716 109 182 0
8 Flexible oil line kit
Part Number: 8 716 106 346 0
9 Burner 'O' ring gasket
Part Number: 8 716 109 158 0
10 Heating control thermostat
Part Number: 8 716 107 621 0
11 Auto reset High Limit thermostat
Part Number: 8 716 107 640 0
12 Manual reset High Limit thermostat
Part Number: 8 716 107 625 0
13 Manual reset flue thermostat
Part Number: 8 716 107 624 0
14 DHW control thermostat
Part Number: 8 716 107 637 0
15 Cleaning brush
Part Number: 8 716 109 428 0
16 Manifold access cover seal
Part Number: 8 716 107 536 0
17 Secondary Heat Exchanger gasket
Part Number: 8 716 112 954 0
18 Frost thermostat
Part Number: 8 716 105 965 0
19 Service lead
Part Number: 8 716 113 483 0
20 Oil nozzle
0.75 60° ES (25 & 28.5kW output) Part Number: 8 716 106 156 0
0.85 60° ES (32kW output) Part Number: 8 716 110 083 0
1
2
56
8
12
16
910
13
17
34
7
7a
11
14
18
15
19
20
Page 45
PROBLEM CAUSE REMEDY
LOCKOUT:
Pulsation on start Combustion settings incorrect Set up as in installation instructions
Faulty nozzle Replace nozzle
Intermittent lockout Bad electrical connection Check control box/electrical connections
Intermittent flame detection fault See flame detection fault
Burner motor fails to operate
Faulty motor or electrical supply to motor
Check for 230v at motor plug during startup period
Control box fault Replace control box
Flame detection Photocell filmed over (dirty) Wipe clean
fault Photocell faulty Replace
Control box faulty Replace
Incorrect CO
2
Air adjustment fault Set up as in installation instructions
Oil pressure incorrect Set up as in installation instructions
No oil from nozzle No oil at pump Check and refill oil tank/bleed oil line
Check and clean filters & valves from oil tank to boiler
Air in pump Bleed pump
Nozzle blocked Replace nozzle
Faulty pump or drive Replace
Faulty mechanical shut off valve Clean or replace
(12/18 & 18/25 only)
Ignition failure Electrode settings incorrect Set up as in installation instructions
Faulty ignition transformer Replace
Open circuit ignition Check and replace electrodes or high
tension leads if necessary
Faulty control box or electrical connections not properly made
Correct control box electrical connections or replace control box
BURNER FAILS No power to boiler Check electrical / control circuit
TO START Faulty boiler thermostat Check by temporarily linking out high
limit and control thermostats
Programmer open circuit Check by temporarily linking 8 & 9 on
the connector
Faulty control box Replace
HIGH SMOKE Air intake/flue blocked Check & clear air intake/flue
NUMBER Incorrect combustion settings Set up as in installation instructions
Oil pressure incorrect Adjust to correct pressure
Incorrect components used on combustion head
Check with installation instructions
Faulty nozzle Replace nozzle
FAULT FINDING
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 106 252b (07/06
44
FAU LT FIND ING
& DIAGRAMS
FAULT FINDING
BOILER LOCKOUT :
Indicated by the illumination of the 'Lockout' indicator on the fascia. To reset, wait 2 minutes then press the lockout reset button.
Also refer to fault finding logic on pages 46 and 47.
UNDER NO CIRCUMSTANCES MUST AN APPLIANCE BE LEFT TO OPERATE WITH ANY CONTOL LINKED OUT OR OVERRIDDEN.
Page 46
FAULT FINDING
PROBLEM CAUSE REMEDY
FAULTY BOILER OPERATION:
Noisy operation Pump noise from air in pump or
worn pump
Bleed air from pump or replace pump
Worn motor bearings Replace motor
Fan out of balance Replace fan
Boiling Faulty boiler thermostat Replace if necessary
Short circuit boiler thermostat Take out of circuit to check
Thermostat bulb not fully home in pocket
Ensure bulb is pushed fully home
No primary water circulation Check system / circulating pump
Short Cycling Burner rating incorrect Correct burner rating
Boiler thermostat differential incorrect
Replace boiler thermostat
External controls not operating correctly
Check and correct external controls
OIL SMELLS: Blocked flue, fumes on startup Check seals/gaskets
Oil soaked boiler, faulty burner operation, numerous lockouts
Rectify burner operation and lockouts
Odour in cabinet, oil leaks from pipework, flexible hoses connections
Rectify oil leaks, replace components if necessary
FAULT FINDING
& DIAGRAMS
FAULT FINDING
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
45
Page 47
Boiler not
operating
with a
heating /
hot water
demand
Burner
motor runs?
Burner
lights
immediately
motor runs?
230V at
solenoid coil
in purge?
Replace
control box
Replace
pump
230V at
motor?
Motor or
pump
seized?
Replace
motor
capacitor
Motor 40
across
L& N?
L & N to
control box?
Control box
locks out?
Check boiler
controls &
supply
Check
connections/
replace leads
Replace
motor/
pump
Replace
motor
Replace
control box
Lockout
within 1
second?
Replace oil
pump
Oil to
pump?
Drive
coupling
broken?
Pump
produces
pressure?
Replace
transformer
Electrodes
& leads
OK?
230V at
transformer?
Spark
produced?
Lockout
after purge
before oil
solenoid
opens?
Replace
control box
Transformer
lead OK?
Photo cell
lead OK?
Disconnect photo cell,
reset lockout, burner
lights then locks out?
Stray light
on photo
cell?
Combustion
head set
correctly?
Combustion
air setting
correct?
Flame off
and
re-lights?
Nozzle
atomising
fuel?
Replace
photo cell
Photo cell
functional?
If BF
remove
burner
snorkle tube
& retest.
Lights OK?
Replace
photo cell
Replace coil
lead
230V at
solenoid
coil?
Coil lead
OK?
Boiler or
flue blocked
Reseal BF
on
reposition
Replace
control box
Replace
control box
Solenoid
operating?
2.2k
across
solenoid
coil?
Pipe to
nozzle
holder OK?
Oil check
valve OK?
(if fitted)
Replace
nozzle
Replace
solenoid coil
Replace
pump
Replace oil
check valve
(if fitted)
Yes
Yes
Yes
No
No
Yes
Yes
No
No
No
No
No
Yes
Yes
No
No
Yes
No
No
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
Yes
Replace
lead
No
Reset air
setting
No
Reset
combustion
head
No
FAULT FINDING LOGIC FOR
SATRONIC CONTROL BOX
Note: This chart assumes all wiring within the control box base is correct, if in doubt check the wiring against the diagram on
the base of the control box before replacing any components.
All resistance measurements are actual measured values and some variation is to be expected, therefore measured values
should be similar to but not necessarily identical to the given values.
The operation of the photo cell can be tested by measuring the resistance across the photo cell, it should be a high resistance
(greater than 10Mor open circuit) in the dark and low resistance (15kor less) in light.
Burners on balanced flue systems can recirculate flue products resulting in the burner cycling, if this happens check the flue
system integrity and the terminal position.
These fault finding charts are provided to assist competent and suitably qualified engineers to locate and rectify faults. Whilst every effort has been taken to ensure the information given is correct and complete we cannot guarantee that every eventuality has been covered. Worcester, Bosch Group cannot be held responsible for costs incurred by persons not deemed to be competent.
Measure all 230V tests between
Neutral (N) and the pin, wire or
terminal specified.
FAULT FINDING
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 106 252b (07/06
46
FAU LT FIND ING
& DIAGRAMS
Page 48
Boiler not
operating
with a
heating /
hot water
demand
Burner
motor runs?
Lockout
within 1
second?
Replace
control box
Replace
motor/pump
Check boiler
controls &
supply
Replace
motor
L & N to
control box?
Motor or
pump
seized?
Photo cell
functional?
Solenoid coil
functional
(100)?
Replace
photo cell
Motor gives
50 Volts on
white wire?
Lockout
after 12 sec
purge?
Replace
control box
Replace
solenoid coil
Replace
motor
Ignition
spark
proved?
Oil to pump?
Drive
coupling
broken?
Purge
pressure
1-2 bar?
Pump
produces
pressure?
Replace
pump stem
valve,
pressure
OK?
Replace
solenoid coil
Pipe to
nozzle
holder OK?
Replace
nozzle
Replace oil
pump
Replace
control box
Eectrodes &
leads OK?
Yes
No
NO
Yes
No
Yes
No
Yes
Yes
No
No
Yes
Yes
No
No
Yes
Yes
No
Yes
Motor 40
between blue &
black wires ?
Replace
control box
Yes
Yes
No
Yes
No
Yes
No
No
No
Yes
No
Nozzle
atomising
fuel?
Combustion
air setting
correct?
Yes
Yes
Combustion
head set
correctly?
Solenoid operating?
Increase the pump
pressure, pressure OK?
Solenoid coil
functional
(100)?
No
Coil lead
OK?
Yes
Yes
Replace
control box
No
Remove
burner
snorkle tube
& retest.
Lights OK?
Flame off &
re-lights?
Yes
Photo cell
functional?
No
Yes
Replace
photo cell
No
Boiler or flue
blocked
No
Reseal BF
Yes
Replace
control box
Yes
Replace
electrodes/
leads
No
Unblock or
replace pipe
No
Reset air
setting
No
Reset
combustion
head
No
FAULT FINDING LOGIC FOR
535 SE/LD RDB CONTROL BOX
All resistance measurements are actual measured values and some variation is to be expected, therefore measured
values should be similar to but not necessarily identical to the given values.
The operation of the photo cell can be tested by measuring the resistance across the photo cell, it should be a high
resistance (greater than 10Mor open circuit) in the dark and low resistance (3kor less) in light.
Burners on balanced flue systems can recirculate flue products resulting in the burner cycling, if this happens check the
flue system integrity and the terminal position.
These fault finding charts are provided to assist competent and suitably qualified engineers to locate and rectify faults. Whilst every effort has been taken to ensure the information given is correct and complete we cannot guarantee that every eventuality has been covered. Worcester, Bosch Group cannot be held responsible for costs incurred by persons not deemed to be competent.
FAULT FINDING
& DIAGRAMS
FAULT FINDING
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
47
Page 49
ELECTRICAL SCHEMATIC
ELECTRICAL SCHEMATIC
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32 8 716 106 252b (07/06
48
FAU LT FIND ING
& DIAGRAMS
N
MOTORISE D
X8 (PIN 3)
DIVERTER
brown
X8 (PIN 4)
VALVE
LOC KOUT
BURNER
4
2
6
RESET SWITCH
grey
white
grey
X12 (PIN 4)
PLUG IN
CONNECTOR
CENTRAL HEATING
CONTROL THERMOSTAT
AUTO RESET HIGH LIMIT
orange
orange
THERMOSTAT
NCNO
red
2
3
(C)
4
red
NO
4
(C)
yellow
X13 (PIN 1)
3
2
NC
pink
X13 (PIN 3)
MANUAL RESET BOILER
MANUAL RESET FLUE
OVERHEAT THERMOSTAT
OVERHEAT THERMOSTAT
red
red
grey
X7 (PIN 4)
X8 (PIN 6)
PUMP
N
brown
brown
X7 (PIN 3)
X7 (PIN 1)
white
N
X11 (PIN 3)
X12 (PIN 3)
LOC KOUT
INDICATOR
R1
X11 (PIN 2)
X3 (PIN 3 (L))
X13 (PIN 2)
4
X13 (PIN 5)
RELAY
N
1
4
3
RELAY 2
431
N
grey
X8 (PIN 2)
32
DIVERTER
END SWITCH
orange
X8 (PIN 5)
X10 (PIN 3) X10 (PIN 1)
124
3
RELAY
whitewhite
THERMOSTAT
DHW CONTROL
N
C1
R1
bluebrown
SWITCH
WATER FLOW
X6 (PIN 2) X6 (PI N 4)
N
4
1
2
3
RELAY 1
X2
(LR)
N
X2
(NS)
LINK
(REMOVE)
X2
(LS)
ROOM
THERMOSTAT
LIVE SUPPLY FOR ALTERNATIVE DIVERTER VALVE
X3 (PIN 3)
X8 (PIN 1)
grey
X2 (FR)
X2 (FR)
white
X4 (PIN 1)
X4 (PIN 2)
CH
brown
X4 (PIN 3)
DHW
FUSE F1
3.15A
FAST
CERAMIC
SERVICE
CONNECTION
FROST THERMOSTATS
BOILER MODE
INDICATOR
X9 (PIN 2)
N
X1 (PIN 5)
X9 (PIN 1)
X1 (PIN 6)
MAINS
CONNECTION
LN
X2
(FS)
MODE
PROGRAMMER
X1 (PIN 1)
SWITCH
N
C1
X1 (PIN 3)
Page 50
SERVICE INTERVAL RECORD It is recommended that the heating system is serviced regularly and
that you complete the appropriate Service Interval Record Overleaf.
Service Provider. Before completing the appropriate Service Interval Record overleaf, please ensure you have carried out the service as described in this manual. Always use Worcester, Bosch Group specified spare parts when replacing all controls.
COMMISSIONING ENGINEER COMBUSTION CHECKS
COMPANY NAME
:
PUMP PRESSURE
(PSI):
ADDRESS: CO2%:
SMOKE READING:
ENGINEERS NAME: F.G.T°C:
SIGNATURE: FLUE PRESSURE:
DATE: BURNER MODEL:
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS YES
OIL TYPE USED IS KEROSENE YES
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE INSTRUCTIONS? YES
THE SYSTEM CLEANER USED:
THE INHIBITOR USED:
BOILER MODEL SERIAL No.
OIL BOILER COMBUSTION RECORD
49
Page 51
SERVICE 1
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 3
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 5
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 7
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 9
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 2
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 4
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 6
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 8
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
SERVICE 10
DATE ENGINEER NAME COMPANY NAME TEL No. OFTEC REG No. PUMP PRESSURE: psi CO2%: NOZZLE CHANGED? YES NO F.G.T. °C FLUE PRESSURE: COMMENTS
SIGNATURE
50
Page 52
CONTACT INFORMATION
WORCESTER, BOSCH GROUP:
TECHNICAL: 08705 266241 SERVICE: 08457 256206 SPARES: 01905 752571 LITERATURE: 01905 752556 TRAINING: 01905 752526 SALES: 01905 752640 WEBSITE: www.worcester-bosch.co.uk
WATER TREATMENT:
FERNOX 01799 550811 www.fernox.com
SENTINEL 0151 420 9595 www.betzdearborn.com/sentinel
FLUE TERMINAL GUARD:
PART No. 7 716 190 050
In the unlikely event the boiler does not give complete satisfaction, before calling for a service engineer, the installer should check the following:-
General checks
1. Is the mode switch in boiler mode (indicator on)?
2. Is there 230V across the boiler live and neutral terminals?
3. Is the polarity correct? (230V across live and earth, 0V across neutral and earth)
4. Is the air bled from the primary system?
5. Is the air bled from the oil supply?
6. Is the flue sized and routed correctly?
Boiler runs straight to lockout
1. Has the oil line been purged of air?
2. Where an air eliminator is used in conjunction with a top feed oil tank the non-return valve, (if fitted), should be removed from the oil dip pipe.
Boiler locks out at the start of a demand (Heating off overnight for example)
1. If an air eliminator is being used, check that there are no leaks that allow air to be pulled into the oil supply.
2. If a two pipe oil supply is a being used, has a non-return valve been fitted to the inlet pipe? Refer to the instructions for guidelines.
No domestic hot water (external programmer)
1. Is the mains water in connected to the 15mm isolation valve?
2. Is there a domestic hot water demand from the programmer and has the tank reached temperature?
3. Is there 230V on pin 2 of terminal block X4?
4. Remove the external wiring from terminal block X4 and fit a link across 1 and 2, if the domestic hot water now operates there is a problem with the external programmer and/or its wiring.
No central heating (external programmer)
1. Are both programmer and room thermostat on demand for central heating?
2. Is the room thermostat wired correctly?
3. Refit the link across pins L
S and LR on terminal X2, if the central heating
now operates correctly the room thermostat and/or its wiring are faulty.
4. Is there 230V on pin 1 of terminal block X4?
5. Remove the external wiring to terminal block X4 and fit a link across pins 1 and 3 on terminal X4, if the central heating now operates correctly the room programmer and/or its wiring are faulty.
EXCELLENCE COMES AS STANDARD
Worcester, Bosch Group
Cotswold Way, Warndon, Worcester WR4 9SW.
Tel. 01905 754624 Fax. 01905 754619
Worcester, Bosch Group is a trading name of BBT
Thermotechnology UK Ltd.
www.worcester-bosch.co.uk
8 716 113 389b (09/07)
UNDER NO CIRCUMSTANCES MUST AN APPLIANCE BE LEFT
TO OPERATE WITH ANY CONTROL LINKED OUT OR OVER RIDDEN.
Loading...