Lightning Detection Systems
ERL-10-SS-09202012 page 1/2
©2012 Boltek Corp. All rights reserved
Short Range System
ERL-10 Lightning Relay Module
☑ Con gurable for 1, 2 or 3 alarms levels (Red,
Red/Yellow, Red/Orange/Yellow)
☑ All Clear output (Green)
☑ Con gurable alarm distances and durations
☑ 20 miles / 37 km range, optionally extendable to
50+ miles/80km
☑ Coincidence Mode virtually eliminates false
alarms
Operation
e ERL-10 receives data from the EFM-100 Electric Field
Mill short-range sensor (<20 miles/32 km) and optionally
also an LD-250 long range lightning detector. It constantly
monitors for lightning and activates its timed relay outputs
when lightning is detected. Up to three alarms can be con gured, referred to as Red, Orange and Yellow Alert levels.
e green All Clear state is entered when no lightning has
been detected within the con gured time period.
When the ERL-10 is rst turned on it enters Survey Mode
where it looks for lightning. A er several minutes without
lightning (con gurable but typically 10-20 minutes) the
system enters the All Clear state. e green All Clear light
on the ERL-10 illuminates and the All Clear relay output
activates.
Coincidence Mode
With Coincidence Mode enabled a lightning strike must be
detected by both the EFM-100 and LD-250 for an alarm to
activate. is virtually eliminates false alarms that could be
caused by persons, animals, insects, etc. near the EFM-100
sensor. Coincidence Mode is only applicable within the
range of the EFM-100 (0-20 miles/0-32 km)
☑ Fault output indicates status of the system
☑ Status Monitor so ware shows current alarm
state and minutes : seconds until All Clear
☑ USB port for con guration and/or Status Moni-
tor so ware
☑ RS-485 output for transmitting status messages
to other equipment and/or to a distant Status
Monitor computer
All Clear
status
Status Monitor
e ERL-10 Status Monitor so ware (included) allows
the system status and countdown timers to be displayed.
Countdown timers clearly indicate the number of minutes
until All Clear. Alarm activations are timestamped and
logged to disk. Graphical log le viewing so ware is also
included.
info@boltek.com www.boltek.com Tel. +1 (905) 734-8045
Stacklight connected
to an ERL-10
(stacklight not
included)
ERL-10 Status
Monitor So ware
(included)
ERL-10 Lightning Relay Module
LD-250
USB
Fiber
Optic
EFM
ERL-10 EFM Relay Output Module
+
-
12V
Reset
Reflash
NC C NO 2 1 0V 0V
- +
+12
VDC
POWER
EFM
DATA
GREEN
ORANGE
FAULT
FAULT
CODE
RS-485
GREEN
FAULT
RED
POWER
ADVISORY USE ONLY
DOES NOT INCLUDE SELF-TEST
CIRCUITRY
ADDITIONAL MEASURES SHOULD BE
LD-250
DATA
YELLOW
2 1 2 1 2 1
ORANGEYELLOW
LIGHTNINGALERT LEVELS
RED
12VDC
Power
Supply
RS232
Optional
Computer
(Not Provided)
EFM-100
Short-Range
Lightning Sensor
Fiber Optic
Optional Long-Range
Lightning Detector
USB
Optional
Customer
Hardware
OUTDOOR MOUNTED SENSORS
Lightning
Status
Display
Computer Monitor
(Not Provided)
Long-Range
Lightning Sensor
LD-250
ERL-10-SS-09202012 page 2/2
©2012 Boltek Corp. All rights reserved
Alarms
SPECIFICATIONS
Number of alert levels 1, 2 or 3 confi gurable
Red Alert Confi gurable range
0 - 50+ miles / 0 - 80+ km
Orange Alert Confi gurable range
0 - 50+ miles / 0 - 80+ km
Yellow Alert Confi gurable range
0 - 50+ miles / 0 - 80+ km
LED Indicators
Power (GREEN) On when power applied
EFM Data (GREEN) Flashes as EFM data is received
LD-250 Data (GREEN) Flashes as LD-250 data is
received
Fault (RED) On when a sensor or module fault
is detected
Fault Code (RED) Blinks active fault codes
All Clear (GREEN) On when no lightning is detected
Yellow Alert (YELLOW) On when lightning is detected
within the confi gured Yellow Alert
range
Orange Alert (ORANGE) On when lightning is detected
within the confi gured Orange Alert
range
Red Alert (RED) On when lightning is detected
within the confi gured Red Alert
range
Fault Codes
0 ERL-10 Processor Fault
1 No EFM Data
2 No LD-250 Data
3 EFM Rotor Fault
4 EFM Selftest Fault
(EFM-200 only)
5 EFM Syntax Fault
6 EFM Checksum Fault
7 EFM Unknown Fault
8 Watchdog Timer Reset
9 Confi guration Fault
10 LD-250 Syntax Fault
11 LD-250 Checksum Fault
12 LD-250 Unknown Fault
Software
ERL-10 Confi guration Software Included
ERL-10 Status Display Software Included
Operating System Microsoft Windows 7,
Vista, XP, 2000, NT
Communications
Confi guration Port USB
Status Data Port USB, RS-485
RS-485 Format Delimited ASCII Sentences
115,200 bps, 8N1
EFM Data Multimode ST fi ber optic
LD-250 Data RS-232, 9600 bps 8N1
Relay Outputs
Red Alert Solid-state relay 80VDC/57VAC/2A
confi gurable NO/NC
Orange Alert Solid-state relay 80VDC/57VAC/2A
confi gurable NO/NC
Yellow Alert Solid-state relay 80VDC/57VAC/2A
confi gurable NO/NC
All Clear Solid-state relay 80VDC/57VAC/2A
confi gurable NO/NC
Fault SPDT relay 250VAC/8A, 30VDC/5A
with both NO/NC connections
Power
Connector 2.1mm/5.5mm coaxial, screw terminals
Voltage 11.5VDC - 14VDC
Power Consumption 4 W
Source 120VAC US plug or 120-240VAC
international multi-plug wall adapter
Enclosure
Material Aluminum
IP Rating 20
Dimensions 3.9” x 4.5” x 1.1” /
100 mm x 114mm x 28mm
Environmental
Operating Temperature -40 to 60 C / -40 to 140 F
Operating Humidity 0 to 99% non-condensing
Agency Approvals CE, FCC, cULus, C-tick
Warranty 1 Year
Ordering Information
ERL10-KIT1-120V-100FT ERL-10/EFM-100 for 120VAC
ERL10-KIT2-120V-100FT ERL-10/EFM-100/LD-250 for 120VAC
ERL10-KIT1-220V-100FT ERL-10/EFM-100 for 220VAC
ERL10-KIT2-220V-100FT ERL-10/EFM-100/LD-250 for 220VAC
Standard kit includes 100’/30m sensor cables. Additional cable lengths
available on request.
CONNECTION DIAGRAM
ADVISORY USE ONLY
is equipment does not include self-test circuitry to
warn of loss of functionality. Additional measures
should be in place to safeguard personnel or equipment.
info@boltek.com www.boltek.com Tel. +1 (905) 734-8045