BNRCUTB
June 2009
(Replaces BN-RCUTB, 04/07)
REMOTE INDOOR COMPRESSOR UNITS
Model SRN - Semi-Hermetic Reciprocating Compressor
Technical Guide
www.thecoldstandard.com
TABLE OF CONTENTS
Nomenclature..................................................................................................................................................................................2
Features & Benets.........................................................................................................................................................................3
Options...............................................................................................................................................................................................4
Performance Data, High & Medium Temperature (R-22/R-404A/R-507).....................................................................5
Performance Data, Low Temperature (R-404A/R-507) ......................................................................................................6
Electrical Data...............................................................................................................................................................................7-9
Dimensional Data ........................................................................................................................................................................10
Physical Data .................................................................................................................................................................................11
NOMENCLATURE
S R N 0500 H 2 C
Compressor Model Application Model Size Temp. Refrigerant Voltage
S = SemiHermetic
Reciprocating
2
R = Remote N = Indoor 0075 - 2200 H = High
L = Low
M = Medium
E = Extra Low
2 = R–22
6 = R–404A/507
© 2009 Heatcraft Refrigeration Products, LLC
B = 208/230/1/60
G = 230/1/60
C = 208/230/3/60
D = 460/3/60
E = 575/3/60
FEATURES & BENEFITS
The indoor SRN remote compressor unit is specically designed for use in supermarket, restaurant, warehouse and
other commercial and industrial applications. The design focuses on ease of installation and maintenance along with
the exibility to t most application requirements.
Construction
• Spacious, pre-painted electrical box
• Fixed low pressure switch (adjustable on low temp models)
• Fixed high pressure switch
• Pump down switch
• 230V control circuit transformer on 460V units
• Standard 16-3/4” tall box - (large 29 - 1/4” tall box is standard when defrost
components are selected)
• Sealed liquid line lter drier and sight glass
Serviceability
• Easy access refrigerant piping
• Captive door fasteners
• Single electrical connection location
• Removable electrical box provides convenient front access to the oil pump
and compressor
Quality
• Pre-bent tubing reduces the possibility of leaks
• Shipped with dry nitrogen charge
• Heavy duty base plate
• Non-metallic conduit on all wiring runs
Components
• Semi-hermetic reciprocating compressors
• Compressor contractor and control circuit fusing
• Oil pressure switch (when required)
• Rigid mounted compressors (models 0075-0400)
• Spring mounted compressors with suction and discharge vibration
eliminators (models 0499 and above)
• Compressor head cooling fan (when required)
• Compressor solid state protection model (on units with 4D compressors)
NOTES: SRN pictured with optional suction accumulator,
liquid solenoid valve, sealed suction lter and
head pressure valve
N.Y. MEA
3
OPTIONS
Factory-Installed Options
• Dual pressure switch
• Oil separator with discharge check valve and oil return hand valve
• Compressor and control circuit breaker
• Two tier rack
• Suction accumulator
• Sealed suction lter
• Replaceable core suction lter (0300-2200)
• Replaceable core liquid lter (0300-2200)
• Liquid line solenoid valve
• Spring mounted compressors with suction and discharge vibration eliminators (models 0075 to 0400)
• Crankcase heater
• Air defrost timer
• Electric defrost kit. Kit includes timer, evaporator fan contactor, defrost heater contactor(s), lockout relay
and terminal block
• Remote load fusing for electric defrost kit. Includes evaporator fan motor and defrost heater fuses
• Fixed head pressure control valve
• Beacon II™ compatible (contact factory)
• Demand cooling for low temperature R-22 (contact factory)
4