Bohn DTSX-IM-120 Installation Manual

5 (2)

DT S X T im e I nitia te d, T e m pe ra ture , P re s s ure or T im e Te rm ina te d 4 0 A De fr os t T im e rs

DTSX-IM-120

Defrost Timer Synchronous}Drive: 40A

Blank: Plastic NEMA 3R

IM: Indoor Metal NEMA 1

M: Mechanism Only P: Panel Mount w/standoff

B: Bracket Mount

120 VAC }

240 VAC

S P E C I F I C A T I O N S

 

 

E lectrical R atings :

 

 

[2] & [4] Contacts

[1] & [3] Contacts

[1] & [F] Contacts

30A Resistive

40A Resistive

30A Resistive

@120~240VAC

@120~240VAC

@120~240VAC

1HP @ 120VAC

1HP @ 120VAC

1HP @ 120VAC

2HP @ 240VAC

2HP @ 240VAC

2HP @ 240VAC

E nvironmental R atings : Ambient Temperature: -40F to 130F Humidity: 0-95% non-condensing

Wiring C onnections :

S crew clamp terminals for #22AWG up to #8AWG wire.

Use #8 AWG wire with 90C rating for 40A loads. Use #10 AWG wire with 90C rating for 30A loads.

E nclos ures :

Plastic NE MA 3R R aintight Indoor/Outdoor Metal NE MA 1 Indoor

L E D Indication: G reen LE D when in refrigeration mode R ed LE D when in defrost mode

A P P L I C A T I O N

The DTS X Defrost Timer is identical in function, terminal identifi- c ation, and wiring to the Paragon 8140 and Prec is ion 6140 series Defrost Timers . The DTS X may also be used to replace Paragon 8040 and Precision 6040 series time terminated defrost timers . With the addition of a remote pressure switch, the DTS X can replace the Paragon 8240 series and Precision 6240 series pressure terminated defrost timers .

Defrosts will be initiated at the times set on the timer, which will accept from 1 to over 24 defrost initiation settings per day at 15 minute intervals (8:00AM, 8:15AM, 8:30AM, etc .) Defrost duration is settable in 15 minute intervals from a minimum of 15 minutes up to several hours (15 minutes, 30 minutes, 45 minutes, 1 hour, 1 hour-15 minutes, etc .) The defrost duration determines the termination time.

In standard configuration, the contacts between terminals 1 and 3 are normally open and c los e during a defros t to energize defrost heaters; the contacts between terminals 2 and 4 are normally c los ed (when timer is energized) and open during a defrost to de-energize refrigeration and fans .

DT S X T ime Initiated, R emote T emperature, P res s ure or T ime T erminated: Is used in electric or hot gas defrost applications where the defrost is terminated when the coil is frost free, as sensed by a temperature or pressure switc h, even though the defrost programmed termination time has not been reached. The time termination functions as a fail-safe and will terminate the defrost if the temperature or pressure switch fails to do so. The temperature or pres s ure s witc h on the refrigeration c oil have contacts which close on a temperature or pressure rise to above the freezing level, indicating that frost and ice have melted from the coil. Typically a wide differential S PDT temperature switc h is used, with it's normally c losed c ontac ts wired to the fans, so that the fans are delayed from turning on after defrost termination, until the c oil temperature has dropped bac k to below freezing. In most applications, the contacts at terminals 2-4 are normally closed (when timer is energized) and control the fans and refrigeration equipment or compressor. For hot gas defrost, or for double pole switching, the 2-4 contacts may be c onfigured as normally open by moving jumper S 1 to the "B " position. R efer to wiring diagrams 1 thru 12.

ÒF Ó T erminal: The DTS X c ontains a normally c los ed c ontac t between terminals 1-F. This terminal may be used for switching the fans off during a defrost rather than the 2-4 terminals . For hot gas defrost applications, with S 1 in the "B " position, the fans may be connected to the "F" terminal.

I N S T A L L A T I O N

Note: For outdoor loc ations, R aintight, or wet loc ation c onduit hubs that comply with requirements of UL 514B (standard for fittings for conduit and outlet boxes) are to be used.

1.R emove 2 screws retaining the interior cover panel and remove panel by prying out with a thin blade (NE MA3R ).

2.S elect knockouts to be used. R emove the inner (1/2") knockout by inserting a screwdriver in the slot and carefully punch knockout loose. R emove slug. If the 3/4" knockout is required, remove the outer ring with pliers after removing the 1/2" knockout. S mooth edges with knife if necessary.

3.Place enclosure in desired mounting location and mark the three mounting holes .

4.Drill holes for #10 screws, start screws in holes .

5.Place enclosure over screws and tighten screws .

6.C onnect conduit hubs to conduit before connecting the hubs to the enclosure. After inserting hubs into enclosure, carefully tighten hub lock nut. Do not over-torque.

7.If us ing NE MA1 Metal E nclos ure connect ground wires

to ground lug on bottom of enclos ure.

(Not applicable for NE MA3R plas tic enclos ure). 8. Wire in accordance with National and Local C odes .

9. R eplace interior cover panel and 2 screws (NE MA3R ).

G rounding: NE MA 3R enclosure is of plastic construction and does not require a ground connection or bonding.

N E M A 3 R e nc lo s u r e do e s no t pr o v ide gr o u nding be t w e e n c o ndu it s . W he n u s ing no n -m e t a llic c o ndu it o r c a ble ,

c o nne c t t he gr o u nd w ir e s o f a ll c a ble s t o ge t he r w it h a w i r e n u t . W h e n m e t a l l i c c o n d u i t i s u s e d , u s e gr o u nding t y pe bu s hings a nd a ju m pe r w ir e be t w e e n e a c h c o ndu it .

C A U T I O N : Do not c he c k c irc uits by Òs pa rk ingÓ w ire s to te rm ina ls . Da m a ge to the de fros t tim e r m a y r e s u lt .

Bohn DTSX-IM-120 Installation  Manual

P R O G R A M M I N G (S ynchronous and Quartz E lectromechanical Models )

S etting the T ime:

Turn the minute hand clockwise until the time of day (and AM or PM) on the outer dial is aligned with the triangle marker on the inner dial.

DO N O T R O T A T E M I N U T E H A N D C O U N T E R -C L O C K W I S E S etting Defros t Initiation T ime:

Move a white tab (tripper) on the outer dial outward at each des ired initiation time. For example, to s et defros t initiation times at 6:00AM, 11:30AM, 4:30PM and 11:00PM, move the tab adjacent to the "M" in AM on the dial (6:00AM), the tab that lies between 11:30AM and 11:45 AM, the tab between 4 : 3 0 P M a nd 4 : 4 5 P M, a nd the ta b a d ja c e nt to the 11:00-11:15PM marks . (S ee note for 8243/6243 replacement.)

S etting Maximum Defros t Duration:

Different defrost durations may be set for each defrost initiation setting. Each white tab (tripper) provides a 15 minute interval. The tabs that set the initiation time provide a minimum of 15 minutes of defrost. For longer defrost duration, move additional tabs (following in time) from the initiation tab. For example, if a

45 minute defros t is to s tart at 7:00AM,

 

 

 

 

 

 

move the tab outward that lies between

 

 

 

7:00 and 7:15 on the AM side of the dial,

 

 

 

and the tabs adjac ent to 7:15-7:30 and

 

 

 

7:30-7:45. (3 tabs moved outward). The

 

 

 

defrost will initiate at 7:00AM and time ter-

8

7

 

minate at 7:45AM (if temperature termina-

A

 

 

 

 

 

 

tion does not occur first.)

 

 

M

 

 

 

F or elec tronic models , refer to s eparate programming ins tructions .

IMP OR T ANT

INF OR MAT ION: T he

Normally C los ed

contacts

between terminals 2

and

4 are only clos ed

when the defros t

 

 

 

 

 

 

 

 

timer is energized . T he 2-4 contacts

are the Normally Open contacts

of

relay

K 2.

(Normal Open relay contacts are more

reliable than

Normally C los ed).

When

checking

continuity

of the

control

with no

voltage applied,

the 2-4 contacts will

appear as open ; this is normal. T he

1-3 contacts will

appear

as

open and

the

1-F contacts will

appears as clos ed. We

recommend that the control be

tes ted

by us ing a

voltmeter,

with

rated

voltage

applied.

 

 

Note: A definite purpose contactor must be used to switch loads greater than the following maximum loads:

Max. Defrost Heater Load:

120V: 4800Watts

Max. Fan & C ompressor Load:

120V: 1HP

 

208/240V: 2HP

 

208V: 8320Watts

 

 

Max. Fan Load on Terminal "F"

120V: 1HP

 

240V: 9600Watts

 

 

 

208/240V: 2HP

T Y P I C A L W I R I N G DI A G R A M S

All switch positions are shown in refrigeration cycle operation, and change position upon initiation of a defrost.

DT S X T ime/T ime - E lectric Defrost Wiring Diagram

DT S X T ime/T ime - E lectric Defrost Wiring Diagram

8045 R eplacement

 

8041 R eplacement

1 S 1 P osition A with 8045 Label Applied

2

S 1 P osition A with 8041 Label Applied

 

 

 

 

 

 

T IME R

 

 

 

 

 

 

 

T IME R

 

 

 

 

 

 

R E LE AS E

 

 

 

 

 

 

 

 

 

 

 

 

T IME R

 

 

 

 

 

 

 

R E LE AS E

 

 

 

 

 

R E LAY

 

 

 

 

 

T IME R

 

 

 

 

 

 

 

 

 

 

 

 

R E LAY

F

3

1-N

2

4

X

LABE L

N

 

1

3

2

4

X

LABE L

 

 

 

 

 

 

8045

 

 

 

 

 

 

 

8041

L1

 

 

T HE R MOS TAT

 

 

 

L1

 

 

 

 

T HE R MOS TAT

 

 

 

 

 

C OMP R E S S OR

 

FAN

 

 

 

 

 

 

C OMP R E S S OR

 

 

 

 

 

 

MOT OR

 

 

LINE

 

 

 

OR

 

 

LINE

 

DE F R OS T

OR

 

 

FAN

 

DE F R OS T

 

S OLE NOID VALV E

 

 

 

S OLE NOID VALV E

 

 

 

 

 

OR

 

 

 

 

HE AT E R

OR

 

 

 

 

 

 

HE AT E R

 

C ONTAC TOR C OIL

 

 

 

 

C ONTAC T OR C OIL

 

 

 

 

 

 

 

 

 

 

L2

 

 

 

 

 

 

L2

 

 

 

 

 

 

 

DT S X T ime/T ime - E lectric Defrost Wiring Diagram 4 8047 R eplacement - Double P ole S witching

S 1 P osition B with 8047 Label Applied

 

 

 

 

 

 

 

T IME R

 

 

 

 

 

 

 

R E LE AS E

 

 

 

 

 

 

 

R E LAY

 

 

 

 

 

 

T IME R

 

 

N

1

3

4

2

2

8047

 

LABE L

L1

 

 

 

 

 

 

 

LINE

S OLE NOID

 

 

 

 

 

 

VALVE

 

DE F R OS T

 

 

 

 

 

OR

 

 

 

 

 

 

C ONTAC T OR

 

HE AT E R

 

 

 

 

L2

NOT E : Move B ridge to 2-2

 

 

 

 

 

 

 

 

NOT E :

 

 

 

 

 

DT S X Time/Temp. - E lectric Defrost Wiring Diagram 7 8141 R eplacement

S 1 P osition A with 8141 Label Applied

 

 

 

 

 

 

T IME R

 

 

 

 

 

T IME R

R E LE AS E

 

 

 

 

 

R E LAY

N

 

1

3

2

4

X

L1

 

 

 

 

T HE R MOS TAT

 

 

 

 

 

 

 

 

 

 

 

 

C OMP R E S S OR

 

FAN

LINE

 

 

 

OR

 

 

 

 

S OLE NOID VALV E

 

 

 

DE F R OS T

 

OR

 

 

 

 

C ONTAC TOR C OIL

 

 

 

 

HE AT E R

 

 

 

 

 

 

 

 

L2

 

 

 

 

 

 

8141 LABE L

TE R MINATION THE R MOS TAT W/FAN DE LAY

DT S X Time/Temp. - E lectric Defrost Wiring Diagram 5 8145 R eplacement

S 1 P osition A - No Label R equired

 

 

 

 

 

 

T IME R

 

 

 

 

 

T IME R

R E LE AS E

 

 

 

 

 

R E LAY

F

3

1

2

4

N

X

L1

 

 

T HE R MOS TAT

 

 

 

 

 

 

 

 

FAN

TE R MINATION

 

 

 

C OMP R E S S OR

 

THE R MOS TAT

LINE

 

DE F R OS T

OR

 

MOT OR

W/FAN DE LAY

 

S OLE NOID VALV E

 

 

 

 

 

HE AT E R

OR

 

 

 

 

 

C ONTAC T OR C OIL

 

 

 

L2

 

 

 

 

 

 

DT S X T ime/Temp. - Hot G as Defrost Wiring Diagram 8 8143 R eplacement

S 1 P osition B with 8143 Label Applied

 

1

N

3

4

2

L1

 

 

 

 

 

LINE

 

HOT

 

C ONNE C T AC R OS S

FAN

G AS

 

 

 

VALVE

 

C OMP R E S S OR

 

 

 

 

T HE R MOS TAT

L2

 

 

 

 

 

T IME R

R E LE AS E

R E LAY

T IME R

X

8143

LABE L

TE R MINATION

THE R MOS TAT

W/FAN DE LAY

NOT E : R emove B ridge B etween 3-4 *S ee Note 1

DT S X T ime/T ime - Hot G as Defrost Wiring Diagram

8043 R eplacement

 

 

 

 

3 S 1 P osition B with 8043 Label Applied

 

 

 

 

 

 

 

T IME R

 

 

 

 

 

 

R E LE AS E

 

 

 

 

 

 

R E LAY

 

 

 

 

 

T IME R

 

F

3

1

4

2

N

8043

LABE L

L1

 

 

 

 

 

 

LINE

HOT

 

C ONNE C T AC R OS S

 

 

G AS

 

 

 

 

VALVE

 

C OMP R E S S OR

 

 

 

 

 

T HE R MOS TAT

 

 

L2

 

 

 

 

 

 

 

NOT E : R emove B ridge B etween 1-4

 

DT S X Time/Temp. - E lectric Defrost Wiring Diagram 6 120V F an & Defrost Heater; 240V C ompressor

S 1 P osition A - No Label R equired

 

 

 

 

 

 

 

T IME R

 

 

 

 

 

120V

 

R E LE AS E

 

 

 

 

 

T IME R

 

R E LAY

 

 

 

 

 

 

 

 

F

3

1

2

4

N

X

L1

 

 

 

 

T HE R MOS TAT

 

 

 

 

 

 

 

 

 

 

120V

 

DE F R OS T

 

 

TE R MINATION

 

FAN

 

 

THE R MOS TAT

240V

HE AT E R

 

 

 

 

 

 

 

 

 

W/FAN DE LAY

 

 

 

 

 

 

 

L2

N

 

 

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

C OMP R E S S OR

 

 

 

 

 

 

 

S OLE NOID VALV E

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

C ONTAC TOR C OIL

 

 

DT S X T ime/Temp. - E lectric Defrost Wiring Diagram 9 8143 R eplacement - Double P ole S witching

S 1 P osition B with 8143 Label Applied

T IME R

R E LE AS E

R E LAY

 

 

 

 

 

 

T IME R

 

1

N

3

4

2

X

L1

 

 

 

 

 

 

LINE

S OLE NOID

 

 

 

 

 

VALVE

 

DE F R OS T

 

 

 

OR

 

 

 

 

C ONTAC T OR

 

HE AT E R

 

 

 

 

 

 

 

 

L2

NOT E : R emove B ridge B etween 3-4

 

 

NOT E : C onnect B ridge B etween 2-X

8143 LABE L

TE R MINATION THE R MOS TAT

Loading...
+ 2 hidden pages