Bohn SWN0075M2, R-507, R404A, R-22 Installation Manual

Refrigeration
Systems
H-IM-64L September 2007 Part No. 25001201
Replaces H-IM-64L (11/05)
Installation and
Operation Manual
H-IM-64L-0907 | Version 002
Table of Contents
General Safety Information...............................................................................2
Inspection ...............................................................................................................2
Warranty Statement ............................................................................................2
Unit Cooler Placement .......................................................................................3
Unit Cooler Mounting .........................................................................................4
Defrost Thermostat ..............................................................................................5
Condensate Drain Lines .....................................................................................9
Air Cooled Condensing Unit and Condenser Space and Location
Requirements ..........................................................................................10
Remote and Water Cooled Condensing Units Requirements ........... 11
Condensing Unit Rigging and Mounting ................................................. 12
Condensing Unit Accessories ................................................................13-17
Demand Cooling ...............................................................................................14
Head Pressure Control .....................................................................................15
Refrigerant Oils ...................................................................................................16
Phase Loss Monitor ...........................................................................................17
Recommended Refrigerant Piping Practices ..........................................17
Refrigeration Pipe Supports ......................................................................... 17
Suction Lines ....................................................................................................... 18
Suction Line Risers ............................................................................................ 18
Liquid Lines .........................................................................................................18
Hot Gas Defrost Systems ..........................................................................19-20
Line Sizing Charts ........................................................................................22-29
Weight of Refrigerants in Copper Lines During Operation ................30
City & Tower Water Connections ..................................................................31
Evacuation and Leak Detection ...................................................................31
Refrigerant Charging Instructions ...............................................................32
Field Wiring ..........................................................................................................32
Check Out and Start Up ..................................................................................32
Operational Check Out ....................................................................................33
System Balancing - Compressor Superheat .............................................33
Evaporator Superheat ......................................................................................34
General Sequence of Operation ..................................................................34
Electric Defrost Troubleshooting ................................................................. 35
Unit Cooler Troubleshooting Guide ...........................................................36
System Troubleshooting Guide .................................................................... 37
Preventive Maintenance Guidelines .....................................................38-39
InterLink Replacement Parts ......................................................................... 39
Typical Wiring Diagrams ...........................................................................40-45
Service Record .................................................................................................... 46
General Safety Information
1. Installation and maintenance to be performed only by qualied personnel who are familiar with this type of equipment.
2. Some units are pressurized with dry air or inert gas. All units must be evacuated before charging the system with refrigerant.
WARNING: Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
Inspection
Responsibility should be assigned to a dependable individual at the job site to receive material. Each shipment should be carefully checked against the bill of lading. The shipping receipt should not be signed until all items listed on the bill of lading have been accounted. Check carefully for concealed damage. Any shortage or damages should be reported to the delivering carrier. Damaged material becomes the delivering carrier’s responsibility, and should not be returned to the manufacturer unless prior approval is given to do so. When uncrating, care should be taken to prevent damage. Heavy equipment should be left on its shipping base until it has been moved to the nal location. Check the serial tag information with invoice. Report any discrepancies to your Heatcraft Refrigeration Products Sales Representative.
3. Make sure that all eld wiring conforms to the requirements of the equipment and all applicable national and local codes.
4. Avoid contact with sharp edges and coil surfaces. They are a potential injury hazard.
5. Make sure all power sources are disconnected before any service work is done on units.
area available through the distributor; the second through fth years, the purchaser must submit a proof-of-purchase of a compressor and supply it to Heatcraft Refrigeration Products Warranty Claims for reimbursement.
Seller makes no express warranties except as noted above. All implied warranties are limited to the duration of the Express Warranty. Liability for incidental and consequential damages is excluded.
The forgoing is in lieu of all other warranties, express or implied, notwithstanding the provisions of the uniform commercial code, the Magnuson-Moss Warranty - Federal Trade Commission Improvement Act, or any other statutory or common law, federal or state.
Warranty Statement
Seller warrants to its direct purchasers that products, including Service Parts, manufactured by SELLER shall be of a merchantable quality, free of defects in material or workmanship, under normal use and service for a period of one (1) year from date of original installation, or
eighteen (18) months from date of shipmen
first occurs. Any product covered by this order found to Seller’s satisfaction to be defective upon examination at Seller’s factory will at SELLER’s option, be repaired or replaced and returned to Buyer via lowest common carrier, or SELLER may at its option grant Buyer a credit for the purchase price of the defective article. Upon return of a defective product to SELLER’s plant, freight prepaid, by Buyer, correction of such defect by repair or replacement, and return freight via lowest common carrier, shall constitute full performance by SELLER of its obligations hereunder.
SELLER shall have no liability for expenses incurred for repairs made by Buyer except by prior, written authorization. Every claim on account of breach of warranty shall be made to SELLER in writing within the warranty period specied above – otherwise such claim shall be deemed waived. Seller shall have no warranty obligation whatsoever if its products have been subjected to alteration, misuse, negligence, free chemicals in system, corrosive atmosphere, accident, or if operation is contrary to SELLER’s or manufacturer’s recommendations, or if the serial number has been altered, defaced, or removed.
MOTOR COMPRESSORS:
Motor compressors furnished by SELLER are subject to the standard warranty terms set forth above, except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer (not at SELLER’s factory) and no freight shall be allowed for transportation of the motor compressor to and from the wholesaler. The replacement motor compressor shall be identical to the model of the motor compressor being replaced. Additional charges which may be incurred throughout the substitution of other than identical replacements are not covered by this warranty. An optional, non assignable, four (4) year extended compressor warranty may be purchased within the boundaries of the United Sates of America, its territories and possessions, and Canada. With this extended compressor warranty, replacements are administered by an authorized compressor distributor only. Replacements within the rst year of the warranty
2
t by SELLER, whichever
SELLER makes no warranty, express or implied, of fitness for any particular purpose, or of any nature whatsoever, with respect to products manufactures or sold by seller hereunder, except as specically set forth above and on the face hereof. It is expressly understood and agreed that SELLER shall not be liable to buyer, or any customer of buyer, for direct or indirect, special, incidental, consequential or penal damages, or for any expenses incurred by reason of the use or misuse by buyer or third parties of said products. To the extent said products may be considered "consumer products," As dened in Sec. 101 of the Magnuson-Moss Warranty - Federal Trade Commission Improvement Act, SELLER makes no warranty of any kind, express or implied, to "consumers," except as specically set forth above and on the face hereof.
The following conditions should be adhered to when installing this unit to maintain the manufacturers warranty:
(a) System piping must be in accordance with good refrigeration practices. (b) Inert gas must be charged into the piping during
brazing.
(c) The power supply to the unit must meet the
following conditions:
A. Three phase voltages must be +/­ 10% of nameplate ratings. Single phase must be within +10% or
-5% of nameplate ratings. B. Phase imbalance cannot exceed 2%. (d) All control and safety switch circuits must be
properly connected according to the wiring diagram.
(e) The factory installed wiring must not be changed
without written factory approval.
(f) All equipment is installed in accordance with Heatcraft Refrigeration Products specied minimum clearances.
© 2007, Heatcraft Refrigeration Products LLC
Unit Coolers
Recommended Unit Cooler Placement
Some general rules for evaporator placement which must be followed are:
1. The air pattern must cover the entire room.
2.
NEVER locate evaporators over doors.
3. Location of aisles, racks, etc. must be known.
4. Location relative to compressors for minimum
pipe runs.
5. Location of condensate drains for minimum run.
The size and shape of the storage will generally determine the type and number of evaporators to be used and their location. The following are some typical examples:
Minimum Unit Clearances
Figure 1. Medium Prole and Large Unit Coolers
NOTE:
W = Total width of evaporator coil surface.
One evaporator
Figure 2. Low Prole Unit Coolers
NOTE:
H = Total height evaporator coil surface.
NOTE: Leave space equal to unit height between bottom of unit and
product. Do not stack product in front of fans.
Two evaporators
One evaporator
Figure 3. Center Mount Unit Coolers
Recommended Maximum - Minimum Dimensions for
E S M T Max. Min. Max. Min. Max. Min. Max. Min. 25' 2' 20' 3' 40' 3' 40' 6'
Two evaporators
Center Mount Unit Cooler Installations.
3
Unit Cooler Mounting
Most evaporators can be mounted with rod hangers, lag screws, or bolts. Use 5/16" bolt and washers or rod for up to 250 pounds, 3/8" for up to 600 pounds and 5/8" for over 600 pounds. Care should be taken to mount the units level so that condensate drains properly. Note that some unit cooler designs achieve drain pan slope by using dierent height mounting brackets. In this situation, the top of the mounting brackets should be level. Adequate support must be provided to hold the weight of the unit.
When using rod hangers, allow adequate space between the top of
Figure 4. Large Coolers and Freezers Placement.
the unit and the ceiling for cleaning. To comply with NSF Standard 7, the area above the unit cooler must be sealed or exposed in such a way to facilitate hand cleaning without the use of tools. When lagging or bolting the unit ush to the ceiling, seal the joint between the top and the ceiling with an NSF listed sealant and ends of open hanger channels must be sealed to prevent accumulation of foreign matter.
When locating unit coolers in a cooler or freezer, refer to Figures 1 through 4 for guidelines.
NOTE: Always avoid placement of Unit Coolers directly above doors and door openings.
Baed Unit
Whe re o ne wa ll e vap orato r mounting is satisfactory.
Cooler or Freezer with Glass Display Doors
Cooler or Freezers where one wall will not accommodate all required evaporators or where air throw distance must be considered.
Bae
Glass Display Door
Allow sucient space between rear of Unit Cooler and wall to permit free return of air. Refer to Figures 1 through 3 for proper space.
Elevation view of glass display door cooler or freezer. Be sure air discharge blows above, not directly at doors. Provide bae if door extends above blower level.
Defrost
Many types of control arrangements can be used. In some applications, it may not be necessary to have scheduled defrost periods. The normal “o cycle” of the compressor may be adequate to keep the evaporator coil clear of frost. In other applications, a defrost timer may be necessary to help assure a clear coil. In a medium temperature environment, “air defrost” is initiated by the timer, but the evaporator fans continue to operate to facilitate the melting of frost on the n surface. Other types of defrost schemes require that the fans on the evaporator shut o
4
during the defrost period.
For most applications, two to four defrost cycles per day should be adequate. The defrost requirements will vary on each installation so the defrost settings should be determined by observing the system operation.
Defrost Thermostat
Adjustable (F25-209 Series)
The defrost duration is determined by the setting of the defrost termination thermostat. Initially, the thermostat should be set at mid­range. This will terminate the defrost at about a 60°F bulb temperature which will be satisfactory for most applications. A somewhat longer or shorter defrost can be obtained by adjusting the control clockwise for a shorter defrost and counterclockwise for a longer defrost. The fan delay temperature setting of the thermostat is factory set at 25°F. It can be adjusted upward by turning the adjusting screw next to the duration adjustment with a small screwdriver. Each complete clockwise rotation of this screw raises the setting approximately 3°F. This screw should not be adjusted more than four turns. Making this adjustment also raises the defrost termination temperature setting of the thermostat by a similar amount. For example, with the duration setting at mid-range, the termination temperature would be approximately 60°F. Turning the adjusting screw one turn would raise the fan delay temperature to about 28°F as well as changing the termination temperature from 60°F to 63°F. On medium temperature applications it may be necessary to raise the setting to assure that the thermostat will reset after a defrost.
Adjustable (060-100-00 Series)
This control has an adjustable defrost termination setpoint and an adjustable dierential for controlling the fan delay. A typical termination setting is 60°F with a 25°F dierential. Termination setting may be adjusted to increase/decrease the length of defrost. The dierential should be adjusted to turn on the fans at 30 to 35°F (Fan Temperature = Termination Temperature – Dierential). Actual coil temperature will be 5 to 10°F below this value. Some unit coolers are preset and labeled at the factory with special settings.
Note: Defrost controls are positioned as determined
by engineering test. Job conditions may require the sensing device to be relocated for optimal defrosting.
Bimetal Disc
A bimetal disc type thermostat is wired to the control circuit to terminate the defrost cycle when the coil temperature reaches approximately 55°F. The bimetal disc thermostat provides a fan delay to allow moisture on the coil to freeze after defrost termination.
Note: On systems where the suction temperature is
above approximately 25°F, the fans may not start for an extended period of time.
On freezer applications, it may be necessary to apply a jumper to the fan delay on a warm box. This can be corrected by jumping the fan switch contacts. This will allow the fans to start immediately after defrost termination. This will disable the fan delay.
If moisture blow-o is encountered without the fan delay, a higher temperature defrost thermostat can be ordered. This thermostat terminates defrost at 60°F and prevents the fans from running when the coil temperature is above 40°F. Refer to the replacement parts list for the correct number to order.
Table 1. Expansion Valve Selection For 100# Head Pressure Valve
BTUH R-507/R404A R-507/R404A R-22 R-22 at about -20 10° T.D. Sporlan ALCO Sporlan ALCO Sporlan ALCO Sporlan ALCO
3,000-5,000 EGSE 1/2 ZP HFESC-1/2-RZ EGSE 1/2 C HFESC-1/2-RC EGVE 1/2 Z HFESC-1-HZ EGVE 1/2 C HFESC-1/2-HC
5,500-7000 EGSE 1/2 ZP HFESC-1/2-RZ EGSE 1 C HFESC-1/2-RC EGVE 1 ZP HFESC-1-HZ EGVE 1 C HFESC-1-HC
7500-8000 EGSE 1 ZP HFESC-1/2-RZ EGSE 1 C HFESC-1-RC EGVE 1 ZP HFESC-1 1/2-HZ EGVE 1 C HFESC-1-HC
8500-10,000 EGSE 1 ZP HFESC-1-RZ EGSE 11/2 C HFESC-1 1/4-RC EGVE 11/2 ZP HFESC-1 1/2-HZ EGVE 1 C HFESC-1-HC
10,500-11,000 EGSE 1 ZP HFESC-1 1/4-RZ EGSE 11/2 C HFESC-1 1/4-RC EGVE 11/2 ZP HFESC-2-HZ EGVE 11/2 C HFESC-1-HC
11,500-13,000 EGSE 11/2 ZP HFESC-1 1/2-RZ EGSE 11/2 C HFESC-1 1/4-RC EGVE 11/2 ZP HFESC-2-HZ EGVE 11/2 C HFESC-1-HC
13,500-15,000 EGSE 11/2 ZP HFESC-2-RZ EGSE 2 C HFESC-1 1/2-RC EGVE 2 ZP HFESC-2 1/2-HZ EGVE 11/2 C HFESC-2-HC
15,500-17,000 EGSE 2 ZP HFESC-2-RZ EGSE 2 C HFESC-2-RC EGVE 2 ZP HFESC-2 1/2-HZ EGVE 2 C HFESC-2-HC
17,500-20,000 EGSE 2 ZP HFESC-3 1/2-RZ SSE 3 C HFESC-2-RC EGVE 3 ZP HFESC-3-HZ EGVE 2 C HFESC-2 1/2-HC
20,500-24,000 SSE 3 ZP HFESC-3 1/2-RZ SSE 3 C HFESC-3-RC SVE 3 ZP HFESC-3-HZ SVE 3 C HFESC-3-HC
24,500-28,000 SSE 3 ZP HFESC-3 1/2-RZ SSE 4 C HFESC-3-RC SVE 4 ZP HFESC-5 1/2-HZ SVE 3 C HFESC-3-HC
28,500-34,000 SSE 4 ZP HFESC-5-RZ SSE 4 C HFESC-3-RC SVE 5 ZP HFESC-5 1/2-HZ SVE 4 C HFESC-5 1/2-HC
34,500-40,000 OSE 6 ZP HFESC-5-RZ SSE 6 C HFESC-5-RC SVE 8 ZP HFESC-5 1/2-HZ SVE 4 C HFESC-5 1/2-HC
40,500-50,000 OSE 8 ZP HFESC-7-RZ OSE 8 C HFESC-5-RC SVE 10 ZP HFESC-8-HZ SVE 5 C HFESC-5 1/2-HC
50,500-60,000 OSE 9 ZP HFESC-10-RZ OSE 9 C HFESC-7-RC SVE 10 ZP HFESC-8-HZ SVE 8 C HFESC-8-HC
60,500-70,000 OSE 9 ZP HFESC-10-RZ OSE 9 C HFESC-10-RC OVE 15 ZP HFESC-10-HZ SVE 8 C HFESC-8-HC
70,500-80,000 OSE 12 ZP HFESC-10-RZ OSE 12 C HFESC-10-RC OVE 15 ZP HFESC-15-HZ SVE 10 C HFESC-10-HC
80,500-90,000 OSE 12 ZP HFESC-13-RZ OSE 12 C HFESC-10-RC OVE 15 ZP HFESC-15-HZ SVE 10 C HFESC-10-HC
90,500-100,000 OSE 12 ZP HFESC-13-RZ OSE 12 C HFESC-13-RC OVE 15 ZP HFESC-15-HZ OVE 15 C HFESC-15-HC
100,500-110,000 OSE 21 ZP TRAE-20-RZ OSE 21 C HFESC-13-RC OVE 20 ZP HFESC-20-HZ OVE 15 C HFESC-15-HC
110,500-120,000 OSE 21 ZP TRAE-20-RZ OSE 21 C HFESC-13-RC OVE 20 ZP HFESC-20-HZ OVE 15 C HFESC-15-HC
120,500-130,000 OSE 21 ZP TRAE-20-RZ OSE 21 C TRAE-20-RC OVE 20 ZP HFESC-20-HZ OVE 15 C HFESC-15-HC
NOTES:
1. Valve selections assume standard conditions and 100°F vapor-free liquid.
2. Equivalent valve may be used in place of selection.
3. For "Medium Temp R-507," valve designation will use “P” for refrigerant code.
˚F/-29˚C Evap. +25˚F/-4˚C Evap. -20˚F/-29˚C Evap. +25˚F/-4˚C Evap.
5
Table 2. Expansion Valve Selection 180# Head Pressure Valve
BTUH R-507/R404A R-507/R404A R-22 R-22 at about -20 10˚ T.D. Sporlan ALCO Sporlan ALCO Sporlan ALCO Sporlan ALCO
3,000-5,000 EGSE 1/2 ZP HFESC-1/2-RZ EGSE 1/2 C HFESC-1/2-RC EGVE 1/2 ZP HFESC-1/2-HZ EGVE 1/2 C HFESC-1/2-HC
5,500-7000 EGSE 1/2 ZP HFESC-1-RZ EGSE 1 C HFESC-1/2-RC EGVE 1 ZP HFESC-1-HZ EGVE 1/2 C HFESC-1-HC
7500-8000 EGSE 1 ZP HFESC-1-RZ EGSE 1 C HFESC-1/2-RC EGVE 1 ZP HFESC-1-HZ EGVE 1 C HFESC-1-HC
8500-10,000 EGSE 1 ZP HFESC-1-RZ EGSE 1 C HFESC-1-RC EGVE11/2 ZP HFESC-1 1/2-HZ EGVE 1 C HFESC-1-HC
10,500-11,000 EGSE 1 ZP HFESC-1 1/4-RZ EGSE 11/2 C HFESC-1-RC EGVE 11/2 ZP HFESC-1 1/2-HZ EGVE 1 C HFESC-1-HC
11,500-13,000 EGSE 1 1/2 ZP HFESC-1 1/4-RZ EGSE 11/2 C HFESC-1 1/4-RC EGVE 11/2 ZP HFESC-2-HZ EGVE 1 C HFESC-1 1/2-HC
13,500-15,000 EGSE 2 ZP HFESC-1 1/2-RZ EGSE 11/2 C HFESC-1 1/4-RC EGVE 2 ZP HFESC-2-HZ EGVE 11/2 C HFESC-1 1/2-HC
15,500-17,000 EGSE 2 ZP HFESC-2-RZ EGSE 2 C HFESC-1 1/2-RC EGVE 2 ZP HFESC-2 1/2-HZ EGVE 11/2 C HFESC-1 1/2-HC
17,500-20,000 EGSE 2 ZP HFESC-2-RZ EGSE 2 C HFESC-1 1/2-RC EGVE 3 ZP HFESC-2 1/2-HZ EGVE 11/2 C HFESC-2-HC
20,500-24,000 SSE 3 ZP HFESC-3-RZ SSE 3 C HFESC-2-RC SVE 3 ZP HFESC-3-HZ SVE 2 C HFESC-2-HC
24,500-28,000 SSE 4 ZP HFESC-3-RZ SSE 3 C HFESC-2-RC SVE 4 ZP HFESC-3-HZ SVE 3 C HFESC-2 1/2-HC
28,500-34,000 SSE 4 ZP HFESC-5-RZ SSE 4 C HFESC-3 1/2-RC SVE 4 ZP HFESC-5 1/2-HZ SVE 3 C HFESC-3-HC
34,500-40,000 SSE 6 ZP HFESC-5-RZ SSE 6 C HFESC-3 1/2-RC SVE 5 ZP HFESC-5 1/2-HZ SVE 3 C HFESC-3-HC
40,500-50,000 OSE 9 ZP HFESC-7-RZ SSE 6 C HFESC-3 1/2-RC SVE 8 ZP HFESC-5 1/2-HZ SVE 4 C HFESC-5 1/2-HC
50,500-60,000 OSE 9 ZP HFESC-7-RZ OSE 9 C HFESC-5-RC SVE 10 ZP HFESC-8-HZ SVE 5 C HFESC-5 1/2-HC
60,500-70,000 OSE 9 ZP HFESC-10-RZ OSE 9 C HFESC-7-RC OVE 15 ZP HFESC-8-HZ SVE 5 C HFESC-5 1/2-HC
70,500-80,000 OSE 12 ZP HFESC-10-RZ OSE 12 C HFESC-7-RC OVE 15 ZP HFESC-10-HZ SVE 8 C HFESC-8-HC
80,500-90,000 OSE 12 ZP HFESC-10-RZ OSE 12 C HFESC-10-RC OVE 15 ZP HFESC-10-HZ SVE 8 C HFESC-8-HC
90,500-100,000 OSE 12 ZP HFESC-13-RZ OSE 12 C HFESC-10-RC OVE 15 ZP HFESC-15-HZ SVE 10 C HFESC-8-HC
100,500-110,000 OSE 12 ZP HFESC-13-RZ OSE 12 C HFESC-10-RC OVE 20 ZP HFESC-15-HZ SVE 10 C HFESC-10-HC
110,500-120,000 OSE 12 ZP HFESC-13-RZ OSE 12 C HFESC-10-RC OVE 20 ZP HFESC-15-HZ SVE 10 C HFESC-10-HC
120,500-130,000 OSE 21 ZP HFESC-13-RZ OSE 12 C HFESC-13-RC OVE 20 ZP HFESC-15-HZ OVE 15 C HFESC-10-HC
˚F/-29˚C Evap. +25˚F/-4˚C Evap. -20˚F/-29˚C Evap. +25˚F/-4˚C Evap.
Figure 5. Bulb and Contact Location
Figure 6. Multiple Evaporators
6
Distributor Nozzles
Nozzles supplied with unit coolers are selected for numerous refrigerants at cataloged operating conditions and 95˚F liquid entering the expansion valve. If mechanical or another method of subcooling is used, the nozzle and expansion valve selection should be checked. For conditions outside those cataloged, use the charts to select a proper nozzle. Nozzle capacity should be within 135% to 180% of unit operating condition for optimum coil performance. Nozzles are available from Sporlan Wholesalers or from Heatcraft Refrigeration Products. A small nozzle can be drilled larger using the I.D. column in table 3, page 8. The hole must be accurately centered in the nozzle. A lathe is preferred for accurate drilling.
may occur and poor evaporator operation may be experienced. For peak performance, it is important to select an expansion valve with the correct capacity and selective charge. Thermostatic expansion valves may be mounted in any position, but they should be installed as close to the evaporator as possible. For best performance, the outlet of the expansion valve should be installed directly to the distributor body. If this is not possible, the distance between the valve outlet and distributor should not exceed 24 inches. Elbows located between the expansion valve and distributor will hinder proper distribution and therefore, are not recommended. Some accessories may, however, necessitate the use of elbows.
Expansion Valves and Distributor Nozzles
Before installing the expansion valve on the distributor of the evaporator, the proper distributor nozzle must be installed. Two nozzles are normally shipped with each evaporator for dierent refrigerants. Select the nozzle for the refrigerant that will be used. The size of the nozzles shipped with each evaporator is based on ordinary conditions, usually 95˚F liquid temperature and a maximum of 15˚F evaporator TD*. If a mechanical subcooler is to be used in your system, consult the factory or a representative for distributor nozzle sizing. This is very important as the nominal capacity of the nozzle increases as the liquid refrigerant temperature is lowered. If the correct size nozzle is not installed, poor refrigerant distribution
*Temperature Dierence (design room temperature minus saturated suction temperature)
Selecting Distributor Nozzle at the Job Site
You must know 4 things:
1. Refrigerant
2. Evaporating Temperature
3. Tons or BTUH
4. Highest Liquid Temperature
Locate the expansion valve bulb on a horizontal length of suction line as close to the suction header as possible. The bulb should be clamped tightly on the suction line and insulated with a waterproof type of insulation. The bulb should never be placed on a coupling or other obstruction so as to not make 100 % contact with the suction line. The bulb should never be placed in a trap or downstream of a trap in a suction line. Locating the bulb on the bottom of a suction line is not recommended. The bulb should be installed at the 3, 4 or 8, 9 o’clock position on the suction line. See Figure 5 on page 6.
EXAMPLE: Select a nozzle for R404A, -20˚F suction; 9,400 BTUH, 60˚F liquid entering TXV.
9,400
12,000
= .78 Tons
[1.83 Factor for 60˚F Liquid]
EXAMPLE: Select a nozzle for R22, 20˚F suction; 67,000 BTUH, 100˚F liquid entering TXV.
67,000
12,000
From Table 3 on page 8 select Size 4 rated at 3.84 tons. We prefer selecting at 135% - 180% of nominal rating. This is typically two sizes smaller than the closest tonnage in Table 3.
5.58
3.84
= 5.58 Tons
= 145% of Nominal Rating - okay.
0.78
1.83
From Table 3 on page 8 select Size 3/4 rated at 0.29 tons.
0.42
0.29
Typical selections would be between 135% and 180%.
= .42 Corrected Tons
= 145% of Nominal Rating - okay.
7
Worksheet:
Given Values
Refrigerant ____________________________
Suction Temperature ___________________˚F
BTUH _______________________________
Liquid Temperature _____________________˚F
Calculations: _____ BTUH ÷ 12,000 = _____ Tons
Liquid Correction Factor:
_____________˚F liquid = _____________ Factor
_____ Tons ÷ _____ Factor = ____Corrected Tons
Nozzle Selections (Table 3)
______ Tons ÷ _______ Nozzle Capacity = ______%
(if within 135% to 180%, it is acceptable)
Table 3. Distributor Nozzle Capacities in Tons of Refrigeration
Nozzle Evaporator (Saturated Suction) Temperature °F Orice R22
No. I.D. (in.) 40° 20° -20° -40° 40° 20° -20° -40° 40° 20°
1/4 0.052 0.34 0.26 0.21 0.18 0.15 0.23 0.17 0.13 0.11 0.09 0.20 0.15 0.12 1/3 0.060 0.44 0.34 0.28 0.23 0.20 0.30 0.23 0.18 0.14 0.11 0.26 0.20 0.15 1/2 0.070 0.61 0.48 0.38 0.32 0.27 0.41 0.31 0.24 0.19 0.16 0.36 0.27 0.21 3/4 0.086 0.92 0.72 0.58 0.48 0.41 0.62 0.47 0.37 0.29 0.24 0.54 0.41 0.32 1 0.100 1.23 0.96 0.78 0.64 0.55 0.83 0.63 0.49 0.39 0.32 0.72 0.54 0.43 1-1/2 0.120 1.79 1.40 1.13 0.94 0.80 1.20 0.92 0.71 0.57 0.46 1.05 0.79 0.63 2 0.141 2.46 1.92 1.55 1.29 1.10 1.65 1.26 0.98 0.78 0.64 1.44 1.09 0.86 2-1/2 0.157 3.07 2.39 1.93 1.60 1.37 2.06 1.57 1.22 0.97 0.79 1.79 1.35 1.07 3 0.172 3.68 2.87 2.32 1.93 1.65 2.47 1.88 1.47 1.17 0.95 2.15 1.63 1.28 4 0.199 4.92 3.84 3.10 2.58 2.20 3.31 2.52 1.96 1.56 1.27 2.88 2.18 1.72 5 0.221 6.07 4.74 3.83 3.18 2.72 4.08 3.11 2.42 1.93 1.57 3.55 2.68 2.12 6 0.242 7.28 5.68 4.59 3.81 3.26 4.89 3.72 2.91 2.31 1.88 4.26 3.22 2.54 8 0.266 8.77 6.84 5.52 4.59 3.93 5.89 4.49 3.50 2.79 2.27 5.13 3.88 3.06 10 0.281 9.83 7.67 6.19 5.15 4.40 6.60 5.03 3.92 3.12 2.54 5.75 4.35 3.43 12 0.313 12.10 9.47 7.65 6.36 5.43 8.16 6.21 4.84 3.86 3.14 7.10 5.37 4.24 15 0.348 15.10 11.70 9.48 7.88 6.74 10.10 7.70 6.01 4.78 3.89 8.81 6.65 5.25 17 0.368 16.80 13.10 10.60 8.81 7.54 11.30 8.61 6.72 5.35 4.35 9.85 7.44 5.87 20 0.404 20.30 15.80 12.80 10.60 9.08 13.60 10.40 8.10 6.45 5.24 11.90 8.97 7.08 25 0.453 25.50 19.90 16.10 13.40 11.40 17.10 13.10 10.20 8.11 6.60 14.90 11.30 8.91 30 0.484 29.20 22.80 18.40 15.30 13.10 19.60 14.90 11.60 9.27 7.54 17.10 12.90 10.20
R404A, R507, R402A R134a, R401A
Note: Based on 100°F liquid entering expansion valve. (1 ton = 12,000 BTU/H)
Table 4. Liquid Temperature Correction Factor
Liquid Temperature
Correction Factor 3.02 2.55 2.10 1.83 1.59 1.37 1.17
NOTE: Tons X Correction Factor = Nozzle Capacity Nozzle Capacity (Tons) X 12,000 = BTUH Rating
˚F 30˚ 40˚ 50˚ 60˚ 70˚ 80˚ 90˚ 95˚ 100˚ 110˚ 120˚
1.06 1.00 0.85 0.72
Table 5. Pressure Drop vs. Nozzle Loading
Actual Load at a Percent of Above Rating
Group 80% 90% 100% 110% 120% 130% 140% 150% 160% 170% Nozzle PSI *M 10 12 15 18 20 22 24 27 29 31
Drop
* M Group = R12, MP39, R134a.
H 16 20 25 30 35 38 40 43 46 49
H Group = R22, R404A, R502, R507, HP80.
8
Condensate Drain Lines
DRAIN LINE MIN. PITCH - 1/4”/ FT.
VAPOR SEAL
TRAP
OPEN
DRAIN
Either copper or steel drain lines should be used and properly protected from freezing. In running drain lines, provide a minimum 1/4 inch per foot pitch for proper drainage. Drain lines should be at least as large as the evaporator drain connection. All plumbing connections should be made in accordance with local plumbing codes. All condensate drain lines must be trapped, and run to an open drain. They must never be connected directly to the sewer system. Traps in the drain line must be located in a warm ambient. We recommend a trap on each evaporator drain line prior to any tee connections. Traps located outside, or extensive outside runs of drain line must be wrapped with a drain line heater. The heater should be connected so that it operates continuously. It is recommended that the drain line be insulated to prevent heat loss. A heat input of 20 watts per linear foot of drain line for 0˚F (-18˚C) room applications and 30 watts per linear foot for -20˚F (-29˚C) rooms is satisfactory. In freezers, the evaporator drain pan tting should be included when heating and insulating the drain line.
Inspect drain pan periodically to insure free drainage of condensate. If drain pan contains standing water, check for proper installation. The drain pan should be cleaned regularly with warm soapy water.
Figure 7. Condensate Drain Lines
WARNING: All power must be disconnected before clean-
Traps on low temperature units must be outside of refrigerated enclosures. Traps subject to freezing temperatures must be wrapped with heat tape and insulated.
NOTE: Always trap single evaporator system drain lines individually to prevent humidity migration.
ing. Drain pan also serves as cover of hazardous moving parts. Operation of unit without drain pan constitutes a hazard.
9
Space and Location Requirements for Air Cooled Condensing Units and Remote Condensers
The most important consideration which must be taken into account when deciding upon the location of air-cooled equipment is the provision for a supply of ambient air to the condenser, and removal of heated air from the condensing unit or remote condenser area. Where this essential requirement is not adhered to, it will result in higher head pressures, which cause poor operation and potential failure of equipment. Units must not be located in the vicinity of steam, hot air or fume exhausts. Corrosive atmospheres require custom designed condensers.
Figure 8. Space and Location Requirements for Condensing Units and Remote Condensers
Another consideration which must be taken is that the unit should be mounted away from noise sensitive spaces and must have adequate support to avoid vibration and noise transmission into the building. Units should be mounted over corridors, utility areas, rest rooms and other auxiliary areas where high levels of sound are not an important factor. Sound and structural consultants should be retained for recommendations.
Walls or Obstructions
The unit should be located so that air may circulate freely and not be recirculated. For proper air ow and access all sides of the unit should be a minimum of “W” away from any wall or obstruction. It is preferred that this distance be increased whenever possible. Care should be taken to see that ample room is left for maintenance work through access doors and panels. Overhead obstructions are not permitted. When the unit is in an area where it is enclosed by three walls the unit must be installed as indicated for units in a pit.
Units in Pits
The top of the unit should be level with the top of the pit, and side distance increased to “2W”.
If the top of the unit is not level with the top of pit, discharge cones or stacks must be used to raise discharge air to the top of the pit. This is a minimum requirement.
Multiple Units
For units placed side by side, the minimum distance between units is the width of the largest unit. If units are placed end to end, the minimum distance between units is 4 feet.
Decorative Fences
Fences must have 50% free area, with 1 foot undercut, a “W” minimum clearance, and must not exceed the top of unit. If these requirements are not met, unit must be installed as indicated for “Units in pits”.
10
Walls or Obstructions for Horizontal Air Flow
* “W” = Total width of the condensing unit or condenser.
Multiple Units with Horizontal Air Flow
Requirements for Remote and Water Cooled Condensing Units
General Installation
The indoor compressor units are designed to be used with a remote condenser. The water cooled units are similar, except that they have an integral water cooled condenser. Inlet and outlet water connections are to be made in the eld. On units having a compressor water jacket, incoming water shall be routed through the jacket prior to entering the condenser. For cleaning purposes, condenser end plates can be removed to give access to the water tubes. Cleaning is accomplished by a simple spiral tool powered by an ordinary electric drill. During installation, allow space for cleaning the condenser. Commercial equipment of this type is intended for installation by qualified refrigeration mechanics.
Typical Arrangements
Diagram 1 illustrates a typical piping arrangement involving a remote condenser located at a higher elevation, as commonly encountered when the condenser is on a roof and the compressor and receiver are on grade level or in a basement equipment room.
In this case, the design of the discharge line is very critical. If properly sized for full load condition, the gas velocity might be too low at reduced loads to carry oil up through the discharge line and condenser coil. Reducing the discharge line size would increase the gas velocity suciently at reduced load conditions; however, when operating at full load, the line would be greatly undersized, and thereby creating an excessive refrigerant pressure drop. This condition can be overcome in one of two of the following ways:
1. The discharge line may be properly sized for the desired pressure drop at full load conditions and an oil separator installed at the bottom of the trap in the discharge line from the compressor.
2. A double riser discharge line may be used as shown in Diagram 2. Line “A” should be sized to carry the oil at minimum load conditions and the line “B” should be sized so that at the full load conditions both lines would have sucient ow velocity to carry the oil to the condenser.
Water Regulating Valve
Using this control on the water cooled condensing units, the head pressure can be maintained by adjusting the ow of water through the condenser section. This type control is most often located on the water entering side of the condenser and is regulated by the refrigerant condensing pressure.
Subcooler
Diagrams 1 and 2 below show typical subcooler piping. Diagram 1 is the preferred connection with receiver as it provides maximum subcooling. Diagram 2 may be used if the receiver is located far from the condenser.
Notes:
1. All oil traps are to be as short in radius as possible. Common practice is to fabricate the trap using three 90 degree ells.
2. Pressure relief valves are recommended at the condenser for protection of the coil.
3. A pressure valve at the high point in the discharge line is recommended to aid in removing non-condensables.
4. The placement of a subcooler should be that it does not interfere with normal airow of the condenser. Increased static of the unit could cause a decrease in system capacity and fan motor damage.
GPM Requirements
The GPM Requirements table below can be used as a guide for determining water ow requirements of the condenser. Operation below the minimum ow rates may result in excessive fouling and poor heat transfer. Operation above the maximum ow rates risk premature impingement corrosion and tube failure.
Water Cooled Condenser GPM Requirements
Model Min GPM Max GPM Rated GPM*
SWN0075H2 0.7 5 1.25 SWN0075M2 0.7 5 1.5 SWN0090H2 0.7 5 2 SWN0090M6 0.7 5 2.25 SWN0100H2 0.7 5 2 SWN0150H2 0.7 5 2.5 SWN0150L6 0.7 5 1.5 SWN0199M6 0.7 5 4 SWN0200H2 2 18 4 SWN0200L6 2 18 2 SWN0200M2 2 18 5 SWN0200M6 2 18 7 SWN0210L6 2 18 3 SWN0310E6 4 18 5 SWN0300H2 4 18 6 SWN0310L6 4 18 4 SWN0310M6 4 18 9 SWN0311L6 4 18 6 SWN0400H2 4 18 11 SWN0400L6 4 18 7 SWN0499H2 7.5 23 10 SWN0500H2 7.5 23 12.5 SWN0500M6 7.5 23 15 SWN0599L6 7.5 23 7.5 SWN0600L6 7.5 23 10 SWN0601L6 7.5 23 10 SWN0750H2 10 25 12.5 SWN0750L6 10 25 10 SWN0760H2 10 25 15 SWN0761H2 10 25 20 SWN0900L6 20 67 20 SWN1000H2 20 67 30 SWN1000L6 20 67 20 SWN1500H2 20 80 35 SWN1500L6 20 80 20 SWN2000H2 20 80 40 SWN2200L6 20 80 25
* Low Temp. Rating Point: -20°F SST, 85°F EWT, 105°F CT, 5°F SC * Medium/High Temp. Rating Point: 25°F SST, 85°F EWT, 105°F CT, 5°F SC
Diagram 1
Diagram 2
11
Condensing Unit Rigging and Mounting
Rigging holes are provided on all units. Caution should be exercised when moving these units. To prevent damage to the unit housing during rigging, cables or chains used must be held apart by spacer bars. The mounting platform or base should be level and located so as to permit free access of supply air.
Ground Mounting
Concrete slab raised six inches above ground level provides a suitable base. Raising the base above ground level provides some protection from ground water and wind blown matter. Before tightening mounting bolts, recheck level of unit. The unit should in all cases be located with a clear space in all directions that is at a minimum, equal to the height of the unit above the mounting surface. A condensing unit mounted in a corner formed by two walls, may result in discharge air recirculation with resulting loss of capacity.
Roof Mounting
Due to the weight of the units, a structural analysis by a qualied engineer may be required before mounting. Roof mounted units should be installed level on steel channels or an I-beam frame capable of supporting the weight of the unit. Vibration absorbing pads or springs should be installed between the condensing unit legs or frame and the roof mounting assembly.
Access
Provide adequate space at the compressor end of the unit for servicing. Provide adequate space on the connection side to permit service of components.
Spring Mounted Compressor
Compressors are secured rigidly to make sure there is no transit damage. Before operating the unit, it is necessary to follow these steps:
a. Remove the upper nuts and washers.
b. Discard the shipping spacers.
c. Install the neoprene spacers. (Spacers located in the electrical panel or tied to compressor.)
d. Replace the upper mounting nuts and washers.
e. Allow 1/16 inch space between the mounting nut/ washer and the neoprene spacer. See Figures 9 and 11 below.
Rigid Mounted Compressor
Some products use rigid mounted compressors. Check the compressor mounting bolts to insure they have not vibrated loose during shipment. See Figure 10 below.
Figure 9. Spring Mount
Figure 10. Solid Mount for Mobile or Deep Sump Application.
Figure 11. Spring Mount
12
Condensing Unit Accessories
Suction Filters, Driers, Sight Glasses
There are two types of suction and liquid lter/driers used on Heatcraft Refrigeration Products units. Replaceable core and/or sealed units are used, dependent upon the option package ordered.
Suction lters, regardless of type, are always installed upstream of the compressor suction service valve, and any accumulators or other options that may be installed. Suction lters are equipped with “Schrader” type access valves to allow eld measurement of pressure drop across the device. This allows plugged lters and elements to be identied very quickly and easily so they can be replaced when the pressure drop is excessive. Refer to the specic manufacturers’ recommendation on servicing these units by make and model.
Liquid lter/driers, regardless of type, are always installed downstream of the receiver outlet service valve, and upstream of the liquid line solenoid valve (if supplied). Liquid line driers may or may not have an access valve, dependent on the size and application.
The basic servicing of these units is similar to suction lters. Liquid line driers should be replaced whenever there is evidence of excessive pressure drop across the lter, or the system becomes contaminated due to system leaks, compressor burnouts, acid formation, or moisture accumulation as indicated by the liquid line sight glass.
The sight glass is installed in the main liquid line assembly, downstream from the receiver outlet service valve, and immediately after the liquid line drier. The sight glass is designed to give a visual indication of system moisture content with refrigerant owing. Slight color indication on a new system is common and will be eliminated during system evacuation. Generally, it requires no eld service. However, in cases of extreme acid formation in a system after a compressor burnout, the acid may damage the sensing element or etch the glass. This would require that the sight glass be replaced, along with the liquid line drier after any compressor motor burnout.
Table 6. Recommended Low Pressure Control Settings for Outdoor Air Cooled Condensing Units
R-22 R-404A/R-507 R-134a *Minimum Cut-In Cut-Out Cut-In Cut-Out Cut-In Cut-Out Temp. ˚F PSI PSI PSI PSI PSI PSI
50 70 20 90 35 45 15 40 55 20 70 35 35 10 30 40 20 55 35 25 10 10 30 10 45 25 13 0 0 15 0 25 7 8 0
-10 15 0 20 1 --- ---
-20 10 0 12 1 --- ---
-30 6 0 8 1"Hg. --- ---
* Minimum ambient or box temperature anticipated, high pressure control setting: R-22, 360 PSI; R-404A, R-507, 400 PSI; R-134a, 225 PSI * The standard preset low pressure switch used for pumpdown is set for 15 PSI cut in / 4 PSI cut out and is a good setting for most pumpdown systems * ZB Scroll compressors should be set for 25 PSI cut in / 17 PSI cut out (R-404A / R-507)
CAUTION: Fans closest to the headers should not be cycled on standard temperature or pressure controls. Dramatic temperature and pressure changes at the headers as a result of fan action can result in possible tube failure. Fan motors are designed for continuous duty operation.
Fan cycling controls should be adjusted to maintain a mini mum of (5) minutes on and (5) minutes o. Short cycling of fans may result in a premature failure of motor and/or fan blade.
Compressors operating below +10°F SST must have air owing over the compressor at all times when the compres sor is running.
-
-
13
Evaporating Temperature (ºF)
Condensin
g
T
emper
atu
r
e (ºF)
Copeland Demand Cooling for Discus L2 Models
R-22, when used in a properly designed and controlled refrigeration system, is a realistic low temperature refrigerant alternative to R-502, which was phased out due to its high ozone depletion potential. However, experience has shown R-22 can present problems as a low temperature refrigerant because under some conditions the internal compressor discharge temperature exceeds the safe temperature limit for long term stability of refrigeration oil. For this reason suction to liquid heat exchangers are not recommended unless they are necessary to prevent another potential problem.
The Copeland Demand Cooling System
Copeland's demand cooling system uses modern electronics to provide a reliable, cost-eective solution to this problem. It is required for all single stage R-22 applications with saturated suction temperatures below -10˚F.
The Demand Cooling module uses the signal of a discharge head temperature sensor to monitor discharge gas temperature. If a critical temperature is reached, the module energizes a long life injection valve which meters a controlled amount of saturated refrigerant into the compressor suction cavity to cool the suction gas. Refer to Figure 13.
This process controls the discharge temperature to a safe level. If, for some reason, the discharge temperature rises above a preset maximum level, the Demand Cooling module will turn the compressor o (requiring a manual reset) and actuate its alarm contact. To minimize the amount of refrigerant which must be injected, the suction gas cooling process is performed after the gas has passed around and through the motor.
Operating Range
Demand Cooling is designed to protect the compressor from high discharge temperatures over the evaporating and condensing temperature ranges shown in Figure 12 at a maximum return gas temperature of 65˚F.
When Demand Cooling operates, it “diverts” refrigeration capacity in the form of injected saturated refrigerant from the evaporator to the compressor. The eect of this diversion on evaporator capacity is minimal because the diverted capacity is used to cool the gas entering the compressor. As the gas is cooled, it naturally becomes more dense, increasing the mass ow through the compressor, which partly compensates for the capacity diverted from the evaporator.
1. Compressor Return Gas Temperature: Suction lines should be well insulated to reduce suction line heat gain. Return gas superheat should be as low as possible consistent with safe compressor operation. Minimum 20˚F superheat at the compressor is required.
2. Condensing Temperatures: It is important when using R-22 as a low temperature refrigerant that condensing temperatures be minimized to reduce compression ratios and compressor discharge temperature.
3. Suction Pressure: Evaporator design and system control settings should provide the maximum suction pressure consistent with the application in order to have as low a compression ratio as possible.
In most cases, with floating head systems where condensing temperatures are low during most of the year, Demand Cooling will operate primarily as a compressor protection control much as the oil failure control protects the compressor during periods of low oil pressure. Demand Cooling will be allowed to operate only during those periods when condensing temperatures and return gas temperatures are high or in periods where a system failure (such as an iced evaporator, an expansion valve which does not control superheat, blocked condenser, or a failed condenser fan) raises condensing temperatures or return gas temperatures to abnormally high levels or lowers suction pressure to abnormally low levels.
Demand Cooling System Design
Figure 12. Demand Cooling Injection
Figure 13. Single Stage Internal Refrigerant Injection
14
Head Pressure Control
Several types of head pressure control systems are available on condensing units:
A. Dual Valve System. (See section on operation
and adjustment.)
B. Single Valve system. No adjustments are necessary.
(See section on operation.)
C. Ambient Fan Cycle Control. (See section on operation
and adjustment.)
D. No Control.
A. Dual Valve System
Operation and Adjustment
Condensing units with dual valves require sucient charge to partially ood the condenser during low ambient conditions.
Valve adjustment should be made with gauges connected to the discharge port of the compressor. Adjustments should be made during mild or low ambient conditions. Turning the valve stem “clockwise” on the ORI valve will increase the discharge pressure, while turning the valve stem “counterclockwise” will decrease the discharge pressure.
If adjustments are made during warm ambient conditions, it may not be possible to adjust the regulator valve as low as desired. Readjustment may be necessary once cooler conditions prevail.
The system employs an ORI (open on rise of inlet pressure) valve and an ORD ( open on rise of dierential pressure) valve. The high pressure discharge gas is introduced above the liquid in the receiver tank. The receiver discharge is regulated by the ORI valve.
The discharge pressure of the ORI valve must be adjusted to regulate the unit for proper operating conditions. Adjust the ORI valve shown on the following diagram to maintain a discharge pressure of 160 to 180 PSIG.
B. Single Valve System
The standard valve used on high pressure refrigerant systems controls the head pressure at approximately 180 PSIG. There is no adjustment for this valve. On low pressure refrigerant systems the valve controls pressure at approximately 100 PSIG. For energy eciency, the 100 PSIG valve is sometimes used on high pressure refrigerant systems. When this is done, refer to Table 1 on page 5 for expansion valve selections.
At condensing pressures above the valve setting, ow enters Port C and leaves Port R. When the condensing pressure falls below the valve setting, the valve modulates to permit discharge gas to enter Port D. Metering discharge gas into the refrigerant ow leaving the condenser produces a higher pressure at the condenser outlet, reduces the ow, and causes the level of liquid refrigerant to rise in the condenser. This “ooding” of the condenser with liquid refrigerant reduces the available condensing surface, holding the condensing pressure at the valve setting.
Figure 14. Dual Valve Piping Arrangement
Figure 15. Single Valve Flooding Valve Piping Arrangement
C. Ambient Fan Cycle Control
This is an automatic winter control method which will maintain a condensing pressure within reasonable limits by cycling fan motors in response to outside air temperature. The thermostat(s) should be eld adjusted to shut o the fan when the condensing temperature is reduced to approximately 90˚F. Table 7 lists approximate settings for several system T.D.’s. These settings are approximate as they do not take into account variations in load.
CAUTION: Under no circumstance should all condenser motors be allowed to cycle o on one control. At least one motor shall be wired to operate at all times. Under most circumstances, the condenser motor nearest the inlet header should remain on whenever the compressor is operating.
Table 7. Ambient Fan Cycle Thermostat Settings
Design Thermostat Settings Models T.D. T1 T2 T3
30 60 2-fan units: 25 65 20 70 4-fan units: 15 75 30 60 40 3-fan units: 25 65 55 20 70 60 6-fan units: 15 75 65 30 60 50 30 8-fan units: 25 65 55 40 20 70 65 50 15 75 70 60
NOTE: Cycle pairs of fans on double wide units.
15
Loading...
+ 33 hidden pages