Bohn MAC4X Installation Manual

MAC Series
Condensing Units
H-IM-67G December, 2003 Part #25006401
Replaces H-IM-67F (12/03)
Installation and Operation Manual
TABLE of CONTENTS
General safety and inspection
Condensing unit specifications................................ 2
Evaporator unit specifications ................................. 3
Evaporator placement ............................................. 4
Refrigerant piping and line sizes .......................... 6-8
Field wiring ............................................................ 10
Beacon II Controller
Installation ...........................................................11
Refrigerant line brazing
Power supply
Wiring ................................................................. 12
Box temp control settings Refrigerant charging
Start-up operation .............................................. 13
Initial power on
Operating mode display ..................................... 14
Program & review settings/changes .................. 15-19
Low ambient operation
Pumpdown .................................................... 19-20
Defrost................................................................ 20
Alarms and error indicator LED.......................... 21
Evaporator fans shut down by operators Power failure Service mode Space sensor terminal
Checking sensors............................................... 22
System defaults
Control sensor and piping .................................. 23
Checking operation of exp. valve
Exp. valve motor winding resistance.................. 24
Smart Controller ............................................ 25-36
Operational checkout ......................................... 37
Preventive maintenance................................ 38-40
Diagnostics....................................................... 41-44
Beacon II parts lists.......................................... 45-46
Startup Checklist ..............................................47-48
Wiring diagrams ............................................... 49-51
Warranty information............................................. 52
General Safety Information
General Safety Information
1. Installation and maintenance to be performed only by certified personnel who are familiar with this type of equipment.
2. Make sure that all field wiring conforms to the requirements of the equipment and all applicable national and local codes.
3. Avoid contact with sharp edges and coil surfaces. They are a potential injury hazard.
4. Make sure all power sources are disconnected before any service work is done on units.
WARNING: Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered
responsibly. Failure to follow this warning may result in personal injury or death.
Inspection
Responsibility should be assigned to a dependable individual at the job site to receive material. Each shipment should be carefully checked against the bill of lading. The shipping receipt should not be signed until all items listed on the bill of lading have been accounted for. Check carefully for concealed damage. Any shortage or damages should be reported to the delivering carrier. Damaged material becomes the delivering carrier’s responsibility and should not be returned to the manufacturer unless prior approval is given to do so. When uncrating, care should be taken to prevent damage. Heavy equipment should be left on its shipping base until it has been moved to the final location.
Condensing Unit Specifications
Figure 1.
Table 1. Condensing Unit Specifications
Model Location Compressor Voltage HP Unit Unit Unit 90% full
MCA MOP kW lbs.
MAC3X MAC4X MAC5X
MAC7X MAC8X
MCA = Minimum Circuit Ampacity MOP = Maximum Overcurrent Protection Note: Remote circuits internal volume = .10 cu. ft. Approximate unit weight = 825 lbs.
Freezer ZF09K4E 208-230/3/60 1 1/2 9.0
Cooler RS64C1E 208-230/1/60
Freezer ZF13K4E 208-230/3/60 3 9.0
Cooler RS43C1E 208-230/1/60
Freezer ZF15K4E 208-230/3/60 3 1/2 14.0
Cooler RS43C1E 208-230/1/60
Freezer ZF13K4E 208-230/3/60 3 9.0
Cooler CS10K6E 208-230/1/60 1 1/2 9.0
Freezer ZF15K4E 208-230/3/60 3 1/2 14.0
Cooler CS10K6E 208-230/1/60 1 1/2 9.0
3
/4 9.0
1
/2 9.0
1
/2 9.0
26.9 35.0 4.3
28.8 40.0 6.3
36.2 50.0 6.4
33.8 45.0 6.4
41.0 50.0 6.5
2
Receiver
Evaporator Unit Specifications
Table 2. Evaporator Unit Specifications
Evaporator Model Location Cap. No. of Dimensions (in.) Connections (In.) Amps Weight
BTUH Fans A B Suct. ID Liq. OD Mtrs. Htrs. (lbs.)
MAC3X
MAC7X
MAC8X
MAC4X
MAC5X
Figure 2.
ADT070BHB2N6MK Cooler 7,000 2 45.50 33.25
LET090BHB2N6MK Freezer 9,000 2 45.50 33.25
ADT104BHB2N6MK Cooler 10,400 2 45.50 33.25
LET120BHB2N6MK Freezer 12,000 3 61.50 49.25
ADT104BHB2N6MK Cooler 10,400 2 45.50 33.25
LET160BHB2N6MK Freezer 16,000 4 77.50 65.25
ADT052BHB2N6MK Cooler 5,200 1 45.50 17.25
LET120BHB2N6MK Freezer 12,000 3 61.50 49.25
ADT052BHB2N6MK Cooler 5,200 1 29.50 17.25
LET160BHB2N6MK Freezer 16,000 4 77.50 65.25
7 7 7 7 7
1 1
5
7
5
1 1
/8 /8 /8 /8 /8
/8
/8
/8
/8
/8
1
/2 1.0 45
1
/2 1.0 7.8 48
1
/2 1.0 49
1
/2 1.5 11.7 60
1
/2 1.0 49
1
/2 2.0 15.7 81
1
/2 0.5 31
1
/2 1.5 11.7 60
1
/2 0.5 31
1
/2 2.0 15.7 81
© 2002 Heatcraft Refrigeration Products LLC
3
Evaporator Placement
Figure 3. Evaporator Placement In Cooler/Freezer
Loading Door
1
Freezer
Note: Whenever possible always try to position the evaporator to blow towards the walk-in door.
Never position the evaporator over or adjacent to a door opening.
1
Cooler Freezer
Loading Door
or
Cooler
1
1
Evaporator Minimum Unit Clearance
1 1/2 H
Top View
1 1/2 H
1 1/2 H
Side View
H = Total Height of Unit’s Coil Surface
1 1/2 H
H
2 H
4
1/2 W 1/2 W
W
Condensing Unit Placement
Space and Location Requirements
The most important consideration which must be taken into account when deciding upon the location of air­cooled equipment is the provision for a supply of ambient air to the condenser, and removal of heated air from the condensing unit or remote condenser area. Where this essential requirement is not adhered to, it will result in higher head pressures, which cause poor operation and potential failure of equipment. Units must not be located in the vicinity of steam, hot air or fume exhausts. Corrosive atmospheres require custom designed condensers.
Another consideration which must be taken is that the unit should be mounted away from noise sensitive spaces and must have adequate support to avoid vibration and noise transmission into the building. Units should be mounted over corridors, utility areas, rest rooms and other auxiliary areas where high levels of sound are not an important factor. Sound and structural consultants should be retained for recommendations. (Refer to actual building plans for unit locations.)
Figure 4.
3 Feet
(minimum)
Clearance =
3 Feet from
Building
Wall
3 Feet
(minimum)
Clearance to
an Open Block
Wall or
Shrubs.
3 Feet
(minimum)
Clearance for
Contractor to Service Unit.
5
Refrigeration Piping And Line Sizing
Refrigeration Piping And Line Sizing
The system as supplied by Bohn/Heatcraft, was thoroughly cleaned and dehydrated at the factory . Foreign matter may enter the system by way of the evaporator to condensing unit piping. Therefore, care must be used during installation of the piping to prevent entrance of foreign matter. Install all refrigeration system components in accordance with applicable local and national codes and in conformance with good practice required for the proper operation of the system. The interconnecting pipe size is not necessarily the same size as the stub-out on the condensing unit or the evaporator.
The following procedures should be followed: (a) Do not leave dehydrated compressors or filter-driers on condensing units open to the atmosphere any longer
than is absolutely necessary .
(b) Use only refrigeration grade (ACR) copper tubing, properly sealed against contamination. (c) Suction lines should slope 1/4” per 10 feet towards the compressor (in direction of flow). (d) Suitable P-type oil traps should be located at the base of each suction riser to enhance oil return to the
compressor.
(e) For desired method of superheat measurement, a pressure tap should be installed in each evaporator
suction line in the proximity of the expansion valve bulb.
(f) When brazing refrigerant lines, an inert gas should be passed through the line at low pressure to prevent
scaling and oxidation inside the tubing. Dry nitrogen is preferred.
(g) Use only a suitable silver solder alloy on suction and liquid lines. (h) Limit the soldering paste of flux to the minimum required to prevent contamination of the solder joint internally .
Flux only the male portion of the connection, never the female. After brazing, remove excess flux.
(i) Remove temperature sensor attached to suction line on Beacon II systems before brazing of the
solder joint internally . Flux only the male portion of the connection – never the female. After brazing, remove excess flux.
(j) Wrap expansion valves with wet rags during brazing to the liquid line.
CAUTION: If the temperature gets too high, these components may be damaged. Heat absorbing compounds or wet rags must be used to protect the expansion valve when brazing to the refrigerant piping/line connections, and the suction line sensor must be removed per above instructions.
(k) Do not use “bull head” tees. This will cause oil return problems and can cause poor performance. (l) If isolation valves are installed at the evaporator, full port ball valves should be used.
Table 3. Recommended Line Size In Equivalent Lengths
Model Room Max. Max. Suction Line Liquid Line
Riser 25’ 50’ Plus 50’ 25’ 50’ Plus 50’
MAC3X
MAC4X MAC5X
MAC7X MAC8X
Freezer 7/8” 7/8” 7/8” Consult Factory 3/8” 3/8” Consult Factory
Cooler 5/8” 5/8” 5/8” Consult Factory 3/8” 3/8” Consult Factory
Freezer 7/8” 7/8” 7/8” Consult Factory 3/8” 3/8” Consult Factory
Cooler 5/8” 5/8” 5/8” Consult Factory 3/8” 3/8” Consult Factory
Freezer 1 1/8” 7/8” 1 1/8” Consult Factory 3/8” 3/8” Consult Factory
Cooler 5/8” 5/8” 5/8” Consult Factory 3/8” 3/8” Consult Factory
Freezer 7/8” 7/8” 7/8” Consult Factory 3/8” 3/8” Consult Factory
Cooler 7/8” 7/8” 7/8” Consult Factory 3/8” 3/8” Consult Factory
Freezer 1 1/8” 7/8” 1 1/8” Consult Factory 3/8” 3/8” Consult Factory
Cooler 7/8” 7/8” 7/8” Consult Factory 3/8” 3/8” Consult Factory
Remote Precharged Circuits
The remote precharged circuits are provided with a factory holding charge of R-404A. The system charge is located in the appropriate drink and ice machines. Schrader valve fittings are provided for liquid line charging at the condensing unit. Consult the appropriate drink and ice machine manufacturers for details on installation of precharged lines.
6
Refrigeration Piping
Suction Lines
NOTE: If the suction line must rise to the point higher than the suction connection on
the evaporator, a suction line trap at the outlet of the evaporator must be provided.
Horizontal suction lines should slope away from the evaporator toward the compressor at the rate of 1/4’ per 10 feet for good oil return.
Suction lines that are outside of refrigerated space must be insulated. See “Line Insulation” for more information.
Suction Line Risers
NOTE: To provide proper oil return, a suction trap must be provided at the base of
all suction risers.
Prefabricated wrought copper traps are available, or a trap can be made by using two street ells and one regular ell. The suction trap must be the same size as the suction line. For long vertical risers, additional traps may be necessary. Generally, one trap is recommended for each length of pipe (approximately 20 feet) to insure proper oil movement. See Figure 5 below for methods of constructing proper suction line P-traps.
Figure 5. Suction P-traps
Condensate Drain Lines
Copper drain lines should be used and properly protected from freezing. In running drain lines, provide a minimum of 4 inches per foot pitch for proper drainage. Drain lines should be at least as large as the evaporator drain connection. All plumbing connections should be made in accordance with local plumbing codes. All condensate drain lines must be trapped, and run to an open drain. They must never be connected directly to the sewer systems. Traps in the drain line must be located in a warm ambient. See Figure 6. We recommend a trap on all evaporators. Traps located outside, or extensive outside runs of drain line must be wrapped with a drain line heater. The heater should be connected so that it is continuously on. The drain line must be insulated to prevent heat loss. A heat input of 20 watts per lineal foot of drain line for 0ºF (-18°C) room applications and 30 watts per lineal foot for -20°F (-29°C) rooms is satisfactory.
Inspect the drain pan periodically to insure free drainage of condensate. If the drain pan contains standing water, check for proper installation. The drain pan should be cleaned regularly with warm soapy water.
WARNING: All power must be disconnected before cleaning. The drain pan also serves as cover for hazardous moving parts. Operation of unit without drain pan constitutes a hazard.
Figure 6. Drain Line
NOTE: Always trap drain lines individually
to prevent vapor migration.
7
Refrigeration Piping
Figure 7. Example of Pipe Support
1. Normally, any straight run of tubing must be supported in at least two locations near each end of the run. Long runs require additional supports. The refrigerant lines should be supported and fastened properly. As a guide, 3/8 to 7/8 should be supported every 5 feet, 1-1/8 and 1-3/8 every 7 feet; and 1-5/8 and 2-1/8 every 9 to 10 feet.
2. When changing directions in a run of tubing, no corner should be left unsupported. Supports should be placed a maximum of 2 feet in each direction from the corner.
3. Piping attached to a vibrating object (such as a compressor or compressor base) must be supported in such a manner that will not restrict the movement of the vibrating object. Rigid mounting will fatigue the copper tubing.
4. Do not use short radius ells. Short radius elbows have points of excessive stress concentration and are subject to breakage at these points.
5. Thoroughly inspect all piping after the equipment is in operation and add supports wherever line vibration is significantly greater than most of the other piping. Extra supports are relatively inexpensive as compared to refrigerant loss.
Figure 8.
Mac Unit
Line Insulation
After the final leak test, refrigerant lines exposed to high or low ambient conditions should be insulated to reduce heat loss or gain and prevent the formation of flash gas in the liquid lines. Suction lines must be insulated with 3/4’ wall Armstrong “Armaflex” or equivalent. Liquid lines must be insulated with 1/2-inch wall insulation or better. The insulation located in outdoor environments should be protected from UV exposure to prevent deterioration of insulating value.
8
Leak Detection And Evacuation
Leak Detection
After all lines are connected, the entire system must be leak tested. The complete system should be pressurized to not more than 150 psig with refrigerant and dry nitrogen. The use of an electronic type of leak detector is highly recommended because of its greater sensitivity to small leaks. As a further check, it is recommended that this pressure be held for a minimum of 12 hours and then rechecked. For a satisfactory installation, the system must be leak tight.
Within the last several years, manufacturers have developed fluorescent dye leak detection systems for use with refrigerants. These dyes mix with the lubricant and, when exposed to an ultraviolet light “fluoresce,” indicate the location of leaks. Copeland has tested and approved the Rigid “System Safe” dye and found it to be compatible with the compressor materials in systems.
Evacuation
CAUTION: Do not use the refrigeration compressor
It is of the utmost importance that proper system evacuation and leak detection procedures be employed. Copeland recommends a minimum evacuation to 500 microns. In addition, a vacuum decay test is strongly recommended to assure there is not a large pressure differential between the system and vacuum pump. Good evacuation processes include frequent vacuum pump oil changes and large diameter, short hose connections to both high and low sides of the system preferably using bronze braided hose.
to evacuate the system. Do not start the compressor while it is in a vacuum.
A good, deep vacuum pump should be connected to both the low and high side evacuation valves with copper tube or high vacuum hoses (1/4” ID minimum). If the compressor has service valves, they should remain closed. A deep vacuum gauge capable of registering pressure in microns should be attached to the system for pressure readings.
A shut-of f valve between the gauge connection and vacuum pump should be provided to allow the system pressure to be checked after evacuation. Do not turn off vacuum pump when connected to an evacuated system before closing shut-off valve.
The vacuum pump should be operated until a pressure of 1,500 microns absolute pressure is reached – at which time the vacuum should be broken with the refrigerant to be used in the system through a drier until the system pressure rises above “0” psig.
NOTE: Refrigerant used during evacuation can not be vented.
Reclaim all used refrigerant. EP A regulations are constantly
being updated. Ensure your procedures follow correct regulations. Repeat this operation a second time. Open the compressor’s service valves and evacuate the entire system to 500 microns absolute pressure. Raise the pressure to 2 psig with the refrigerant and remove the vacuum pump.
9
Field Wiring
WARNING: All wiring must be done in accordance with applicable codes and local ordinances.
The field wiring should enter the areas as provided on the unit. The wiring diagram for each unit is located on the inside of the electrical panel door. All field wiring should be done in a professional manner and in accordance with all governing codes. Before operating the unit, double check all wiring connections, including the factory terminals. Factory connections can vibrate loose during shipment.
1. The nameplate on the unit is marked with the electrical characteristic for wiring the unit.
2. Consult the wiring diagram in the unit cooler and in the condensing unit for proper connections.
3. Wire type should be of copper conductor only and of the proper size to handle the connected load.
4. The unit must be grounded.
Figure 9. Beacon II Board
Heater
Relay
Fan
Relay
LED
Display
Room
Sensor
Defrost
Sensor
Expansion
Valve
Connection
Selection
Buttons
24 V.
Terminal
Block
Suction
Sensor
Suction
Pressure
10
Beacon II Controller
Installation Tips
• Use a minimum 18 gauge wire for all low voltage connections.
• The Beacon II board get its 24 VAC power supply from a transformer mounted in the electrical end of each
evaporator. On 208-240 volt systems the multi-tap transformer is shipped from our factory wired for 240 volts. If your supply voltage is 208 volt you must change to the 208 volt tap on the transformer.
• Refer to wiring schematic shipped on units for wiring.
• Evaporators are shipped from our factory with a preset box setpoint temperature of 35°F for air defrost and
-10°F for electric defrost. If your box setpoint temperature requirements are different this must be set using directions outlined under “Room Temperature Control”.
• The suction line temperature sensor MUST be removed from the suction line before brazing the suction
tubing. The sensor MUST then be reinstalled on the suction line after brazing is completed and the tubing has cooled. Insulate when finished.
• The low pressure switch time delay relay, located in the condensing unit, must be set to one minute.
• Some systems may require the crankcase heater to be energized 24 hours prior to start-up. The Beacon II
should be de-energized for this period by placing it in the SERVICE MODE. This is done by pressing the “FORCE SERVICE” button twice. To start the system cooling, press the “CLEAR” button.
• Room sensors must be left connected on ALL evaporators.
• A pressure transducer is installed on the evaporator. Do not leak test system above 150 PSI or damage to
transducer could occur.
• Refer to the Beacon II Smart Controller Installation Manual, shipped with the Beacon II Smart Controller,
for installation, programming and monitoring information.
Condensing Unit
The condensing unit control panel contains the relays, contactors, and a terminal block which is appropriately marked to match the low voltage wiring connections. A sensor for outdoor air temperature measurement is installed on the condensing unit.
Condensing unit must be installed using proper refrigeration practices and codes. Make sure there is good airflow and good clearances around unit. See Figure 4, page 5.
Evaporator Unit
The evaporator contains the BEACON II controller(s), electric expansion valve(s), pressure transducer, distributor(s), orifice(s), transformer and three sensors. These components are all factory mounted and wired. The three sensors are factory mounted and provide input to the controller from the following: defrost temp., suction temp., room temp.
Each evaporator unit must be installed using proper refrigeration practices and codes. Make sure the piping is correctly sized and properly routed. Liquid and suction lines MUST be insulated. There must also be good clearance around the unit. See Figure 3, page 4.
11
Beacon II Controller
Refrigerant Line Brazing (
The electric expansion valve and the suction temperature sensor on the suction line are factory installed. Care must be taken when brazing these lines at the evaporator.
components. Heat absorbing compounds or wet rags must be used when brazing the refrigerant line connections. The suction line sensor should be removed before brazing.
CAUTION
)
Too high a temperature may destroy these
Power Supply
The Beacon II board gets its 24 VAC power supply from a transformer mounted in the electrical end of each evaporator. On 208-240 volt systems the multi-tap transformer is shipped from our factory wired for 240 volts. If your supply voltage is 208 volt you must change to the 208 volt tap on the transformer.
VERY IMPORTANT: If the supply voltage to the evaporator is 208 volts, the primary tap of the transformer must be moved to the 208 volt tap.
If the 24 VAC power supply falls below 18 VAC the system may power down and shut off. When the power supply is corrected to 24 VAC the system will restart after the four minute hold-off period and resume normal operation.
This must be done for all the evaporators on that system.
Wiring
Wiring between the condensing unit and the unit cooler(s) will be as follows (see attached wiring diagrams):
• High voltage – There may be high voltage on the defrost heater relay and the fan relay. See unit cooler spec. plate for ampacity.
• Low voltage – 24V Class II control circuit. A total of five low voltage leads are required to connect the condensing unit to the evaporator (see wiring diagram). Two of these leads are for connecting the outdoor temperature sensor. The other three leads are for connecting the compressor relay, service relay and 24V Common inputs.
• Number of wires in low voltage wiring bundles:
MAC to cooler evaporator - 5 MAC to freezer evaporator - 5 Cooler evaporator to Smart Controller - 6 Freezer evaporator to Smart Controller - 4
• Low voltage wiring must be 18 gauge minimum. For low voltage wiring, maximum distances are:
Condensing unit to evaporator 500 ft. Smart Controller to evaporator 1,000 ft.
• Alarm circuit – The onboard alarm is a dry set of NC contacts which closes to indicate an alarm. The type and wiring for the alarm is customer specified. Note that the alarm circuit does not distinguish or indicate what has caused the alarm.
• All wiring must comply with all applicable codes and ordinances.
All 24 volt wiring must be run separate from the line voltage wiring.
12
Beacon II Controller
Box Temperature Control Settings
There is an on board room thermostat on the Beacon II board which can be adjusted to the desired room temperature. The temperature differential is 2°F.
Temperature Differential When a system is in the cooling mode and the box setpoint is 35°F, the system will continue to cool until the box temperature gets to 34°F. At this point the compressor will pumpdown and shut off. The system will restart cooling when the box temperature has risen to 36°F.
It is important to note that Beacon II has a minimum 2-minute “ON” time and a minimum 4-minute “OFF” time. This means that the system will run in the cooling mode a minimum of 2 minutes even if the setpoint temperature is met. In applications where the system is grossly oversized, the box temperature could go below the differential temperature before the system cycles off.
In the “OFF” cycle, the system will be off for a minimum of 4 minutes even if the box temperature goes above the differential temperature before cooling will be restarted.
The on board room thermostat is factory set at 35°F for air defrost systems and -10°F for electric defrost systems.
Refrigerant Charging
The cooler and freezer systems utilize refrigerant side head pressure control. Charge each system by adding an initial charge of 5 lbs. of R-404a refrigerant to the liquid side of the receiver. This initial charge will allow the system to start. With the system running, continue to add refrigerant to the system until the sight glass is clear. Operate system until the cooler/freezer box achieves the desired temperature. The sight glass should be clear with no bubbles or flashing of refrigerant. Now the additional charge for the flooded condenser is to be weighed into each system in the amount as shown in Table 4.
Table 4.
MAC3X MAC4X MAC5X MAC7X MAC8X
Ambient Freezer Cooler Freezer Cooler Freezer Cooler Freezer Cooler Freezer Cooler
°F. ZF09 RS64 ZF13 RS43 ZF15 RS43 ZF13 CS10 ZF15 CS10
80 3.0 4.0 3.0 4.0 6.0 4.0 3.0 4.0 6.0 4.0 70 2.0 3.0 2.0 3.0 5.0 3.0 2.0 3.0 5.0 3.0 60 1.0 3.0 1.0 3.0 3.0 3.0 1.0 3.0 3.0 3.0 50 1.0 2.0 1.0 2.0 2.0 2.0 1.0 2.0 2.0 2.0
40 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 30 0.5 1.0 0.5 1.0 1.0 1.0 0.5 1.0 1.0 1.0 20 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 10 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
0 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Start-Up Operation
Check all wiring connections to be sure they are correct and tight.
On condensing unit:
- Check the setting of Time Delay relay. It should be set a one minute (the second marker).
- Check the Low Pressure switch setting on freezer units. It must be set to 0 PSIG cutout, 10 PSIG cut-in to allow positive start and operation, especially in cold ambients. This can be changed to a higher value in warmer climates. On cooler units, the Low Pressure switch has a fixed setting and cannot be adjusted.
13
Beacon II Controller
Initial Power On
At the initial application of power to the system, the compressor and the evaporator fans will be in a 4-minute hold-off cycle and will not start immediately. When there is a call for COOLING, the expansion valve (EEV) opens, then the compressor is started. The compressor will then run for a minimum of 2 minutes in the “hold­on” cycle. (This means that the compressor will run for a minimum of 2 minutes before shutting off even if the box temperature is met).
The LED alternately displays show while the expansion valve is opening. After the compressor starts, the LED will alternately display
TEMPERATURE
When the room thermostat setting is satisfied, and if the compressor ran for at least 2 minutes, the EEV will close and the compressor will pumpdown and shut off. The evaporator fans will continue to run. The LED will alternately display
When the room sensor detects a rise in temperature of approximately 2°F, and the compressor has been off for at least 4 minutes, the EEV will open to its last position then the compressor will start. The valve is then adjusted as necessary to obtain the setpoint superheat setting. During this time, the compressor will run for a minimum 2 minutes “hold-on” cycle.
The 4 minute “hold-off” can be bypassed and the system started immediately by pressing the “Reset” button on the Beacon II board.
and
oFF
Coo
BOX TEMPERATURE
.
and
BOX TEMPERATURE
and
.
MODE
of operation. On a call for cooling,
dLY
will
BOX
Figure 10. Operating Mode Display
oFF
–Off
Coo
– Cooling
Pdn
– Pumpdown
dEF
– Defrost
drn
Draining
dLY
– Delay
tSt
Test
SEr
Service
14
Beacon II Controller
Programming And Reviewing Settings/Changes
The Program Review button is used to program, review and change all program settings for the system. Press PROGRAM REVIEW button. The Setpoint item will appear on the LED. After a few seconds delay
the Setpoint value will display. Each time the button is pressed a different setpoint item is displayed.
PROGRAM
REVIEW
Next, use the “SELECT knob to change value of Setpoint Item.
SELECT
Next, when the desired value is selected, press the ENTER button to place it in program memory. If theENTER button is not pressed, the value will not be stored in the memory and thus will not be changed.
ENTER
PROGRAM REVIEW ITEMS
A-E rEF bot SUP SLA dFn dFF dFt dFS ALH ALL ALt F-C
Set Defrost Type ( – Set Refrigerant Type (R22, R404A or R507) – Set Box Temperature (-30°F to +70°F) Set Superheat (4°F to 20°F) Set Board as a Slave (Yes or No) – Set Number of Defrosts Per Day (1, 2, 3, 4, 5, 6, 8, 10 or 12 per day) – Set Defrost Fail-safe Time (10 to 200 minutes) – Set Defrost End Temperature (40°F to 100°F) Set Defrost Delay Start Time (0.5 Hours to 23.5 Hours) – Set Alarm High Temperature (-40°F to 90°F) Set Alarm Low Temperature (-40°F to 90°F) Set Alarm Time (2 to 120 minutes) – Set Fahrenheit/Celsius Temperature Units (°F / °C)
Air
or
ELE
)
15
Beacon II Controller
Programming And Reviewing Settings/Changes (continued)
Use the PROGRAM REVIEW button to select these items:
PROGRAM
Defrost Type – the system factory defaults for air defrost and electric defrost. (See default settings). Please note that the refrigerant type factory default settings.
Refrigerant Type –
A-E
– Selection is made for air defrost or electric defrost coil. This will automatically set
default
for air defrost is R22 and for electric defrost it is R404A. All units are shipped with
rEF
– Selection for type of refrigerant – R22, R404A or R507.
Default: Air defrost is R22 and for electric defrost is R404A.
Box Temperature –
bot
– Select box temperature setpoint. Selection range is -30°F to +70-°F.
Default: Electric defrost -10°F and air defrost +35°F.
Superheat – measures the evaporator saturation suction temperature and the suction pressure to determine the superheat. The superheat value at the evaporator can be changed to ensure a 20°F to 30°F superheat at the compressor.
SUP
– Evaporator superheat is controlled by the board on each evaporator. Each board
Default: 8°F.
Evaporator Board: SLAVE – programmed to be a MASTER or a SLAVE. Each board is shipped from our factory set as a MASTER. You must make this change to each SLAVE evaporator. A selection of “YES” is made for this setting.
SLA
– On multiple evaporator systems, each evaporator board has to be
Default: MASTER on each board. For a single evaporator system, no change is required.
Number of Defrosts Per Day – day – 1, 2, 3, 4, 5, 6, 8, 10 or 12 per day. If no selection is made:
dFn
– A selection must be made for the number of defrosts cycles per
Default: Electric defrost is 4 per day and air defrost is 2 per day.
Defrost fail-safe – terminated if the defrost end temperature is not attained when this time has expired.
dFF
– This is the maximum time allowed for a coil to remain in defrost. Defrost will be
Default: Electric defrost is 30 minutes and air defrost is 40 minutes.
Defrost End Temperature –
Default: Electric defrost is +60°F and air defrost is +45°F.
Defrost Delay Start Time –
Default: 0.5 hours to 23.5 hours.
dFt
– This is the temperature at which the defrost will be terminated.
dFS
– This allows the delay of the start of the defrost.
16
Beacon II Controller
Programming And Reviewing Settings/Changes (continued)
Alarm High Temperature – This does not apply during defrost.
ALH
– Temperature at which a high box temperature alarm will be triggered.
Default: Electric defrost is +5°F and air defrost is +50°F.
Alarm Low Temperature –
ALL
– Temperature at which a low box temperature alarm will be triggered.\
Default: Electric defrost is -15°F and air defrost is +30°F.
Alarm T ime – alarm is triggered.
ALt
– Time which high temperature or low temperature conditions must exceed before
Default: 60 minutes.
°F/°C –
F-C
– Select units to display temperature. Fahrenheit or Celsius.
Default: Fahrenheit.
Use the “MONITOR” button to review these items:
SUP ESP SCt SSt SCP Odt dFt dFS
dFE AC SPt
– Superheat (°F) – Expansion Valve Stems (0 to 255 steps) – Suction Temperature (°F) – Saturated Suction Temperature (°F) – Suction Pressure at Evaporator (PSIG / “HG) – Outdoor Temperature (°F) – Defrost Sensor Temperature (°F) – Time Left to New Defrost (hours) (on 1.8 versions)
– Last Defrost Elapsed Time (minutes) – Board Voltage – Spare Temperature Reading
MONITOR
FORCE
DEFROST
Use this button to RESET TIME Pressing this button will reset the time clock in the microprocessor to zero. At initial power up, pressing this button will bypass the “four minute” hold-off and the system will start immediately after the expansion valve opens. This display will show
Use this button to FORCE DEFROST To force a defrost, press the FORCE DEFROST button. The system will pumpdown and shut off the compressor. The heaters are then turned on. The display will show
dEF
.
dLy
.
FORCE
SERVICE
Use this button to FORCE SERVICE Pressing this button TWICE will cause the system to pumpdown and the compressor to shut off. The system will remain off until the “CLEAR” button is pressed. While in the “FORCE SERVICE”, the LED display will show
RESET
TIME
SEr
.
17
Beacon II Controller
Programming And Reviewing Settings/Changes (continued)
Use this button to CLEAR/TEST Pressing this button ONCE will return the LED display to the default display. With the system in the the
TEST
STATUS INDICATOR LED
A red, 3-digit, alphanumeric LED on the Beacon II board indicates status, alarms and error codes.
mode. In the
OFF
mode, pressing and holding this button will start
TEST
mode it will cycle through each output.
Status LED Display Description
CLEAR /
TEST
OFF Box Temp / All Evaporators
COOLING
Single Evaporator – Box Temp /
Pumpdown
All Evaporators
DEFROST
All Evaporators
TEST
All Evaporators
SERVICE
All Evaporators
ALARMS
Pdn
dEF
tSt
SEr A1
A2 A3
A4
oFF
Coo
Box Temperature / Mode is displayed
Box Temperature / Mode is displayed
High Box Temp Low Box Temp System Start-Up Failure Compressor pumps down and tries to restart after 4 minutes. Input Fault Box Temp., Suction Temp., Pressure Transducer open or not installed
18
Beacon II Controller
STATUS INDICATOR LED (continued)
Status LED Display Description
ERRORS
OTHERS
E1 E2 E3 E4 E5
E6 E7
E9 Coo
Loc UnL
Room temperature sensor shorted, open or not installed Defrost temperature sensor shorted, open or not installed Suction temperature sensor shorted, open or not installed Suction pressure transducer shorted, open or not installed Outdoor temperature sensor shorted Low superheat during cooling Compressor shutdown (high or low refrigerant pressure or low oil pressure) Multi-in/Multi-out wiring error
Room Temperature sensor open or not connected (Instead of displaying box temperature) Board is locked. Settings cannot be changed Unlock the board settings
Pumpdown
At the end of each cooling cycle, when the box temperature is met, the Beacon system will pumpdown and shut off the compressor.
To pumpdown, the EEV closes and the compressor runs until the low pressure switch opens or 2 minutes has elapsed. The compressor is then off and remains off until the start of the next cooling cycle.
While in the off cycle, the system will initiate a short pumpdown at 4-minute intervals, only if the Low Pressure Switch closes, to ensure that any refrigerant leakage will not cause a problem.
For Manual Pumpdown, a single pole, single throw switch can be used to connect SERVICE and Com. This can be done at the Beacon II board on the evaporator or at the terminal board in the condensing unit. This will cause the system to pump down and shut off.
NOTE: The system will not restart until the switch has been opened. The Beacon II board will display “SEr”.
or
The system can be pumped down by pressing the “SERVICE” button twice. To restart the system, press the “CLEAR” button.
or
The system can be pumped down for service by closing the liquid line service valve on the receivers in the condensing unit, then closing the suction line service valve when the system trips on the low pressure switch.
19
Beacon II Controller
Service Mode
A SPST switch (S1 & S2) is supplied, for each system, in the condensing unit for shutting off the system. Closing the “Service” switch in the condensing unit will cause the expansion valve to close and the compressor to pumpdown and shutoff. “SEr” will be the onboard LED display and “SERVIC” is displayed on the Smart Controller. The evaporator and heater relays on the Beacon II board will then be deactivated. The system will not restart until the switch is placed in the “NORMAL” or off position.
When the “Service” switch in the condensing unit is closed or ‘on’ (labeled SERVICE), the system is in the service mode. If the switch is ‘off’ (labeled NORMAL), the system is in normal operation.
Defrost
DEFROST TIMING
When power is first applied to the system, its timer starts counting time. If 4 defrosts are programmed, it will initiate a defrost every 6 hours from when power was first applied. Beacon II does not have a real time clock. Beacon II does provide the ability to delay the starting of the first defrost.
DEFROST DELAY START TIME
Example: The system is first powered up at 8:00 AM and is programmed for 4 defrosts per day. The user would like the first defrost at 10:00 AM. To accomplish this, use the PROGRAM REVIEW button to scroll to
dFS
. Use the SELECTOR switch to select 2 hours delay start, then press ENTER. The first defrost will
now occur at 10:00 AM and then a defrost will occur every 6 hours thereafter. TIME REMAINING UNTIL NEXT DEFROST (on version 1.8 boards)
To find out how much time is left until the next defrost is scheduled, use the MONITOR button to scroll to
dFS. The time displayed will be how much time until the next scheduled defrost.
DEFROST SCHEDULE IN MEMORY
Beacon II does not have a real time clock but it keeps track of the time that has elapsed in its memory. It also keeps in memory the number of defrosts scheduled and how much time has elapsed between defrosts. If a power failure occurs, when power is restored Beacon II will remember how many defrosts are scheduled and it will remember how much time was left until the next defrost. It will then defrost based on this timing. So, if the power failure lasted 15 minutes, the defrost schedule will be off by 15 minutes.
ELECTRIC DEFROST MODE
When a defrost is initiated, the EEV closes, the compressor is allowed to pumpdown and shut off. The evaporator fans are cycled off and the defrost heaters are energized.
There is a 2-minute condensate drain-down period after which the compressor is started for a refreeze period. The evaporator fan stays off (fan delay). The refreeze period will last until the evaporator suction temperature is at 28°F or 3 minutes has elapsed. After this sequence, the system is back in the refrigerating mode and the evaporators’ fans are not running.
AIR DEFROST MODE
The sequence is the same as for electric defrost except that there are no heaters and the evaporator fans run continuously.
20
Beacon II Controller
Alarms
Beacon II provides a set of dry contacts for use in signaling an alarm. These contacts can be connected to a light, a buzzer, a bell, etc., which will be activated when an alarm condition occurs. When the Beacon II is energized, the alarm contacts are OPENED. When an alarm condition is detected, the contacts are CLOSED.
Conditions under which the alarm contacts will close are:
A1
High Box Temperature – LED Display: for the Alarm time
ALt
, programmed.
– Room temperature has exceeded the Alarm High
ALH
value
Low Box Temperature – LED Display: A2 – Room temperature has dropped below the Alarm Low value for the Alarm time
System Start-Up Failure – LED Display: minutes.
Input Fault – LED Display: A4 – Box Temp., Suction Temp., or Pressure Transducer open or not installed.
Power Failure – Loss of power to the Evaporator.
ALARM CODES
A1
High Box Temp
A2
Low Box Temp
A3
System Start-Up Failure Compressor pumps down and tries to restart after four minutes.
A4
Input Fault Box Temp., Suction Temp., Pressure
ALt
, programmed.
A3
– Compressor pumps down and tries to restart after four
Transducer open or not installed
ALL
Error Indicator LED
At initial power up, each Beacon II board checks for system errors. The system error check involves checking the various temperature sensors to determine whether any of these sensors are shorted or open.
The system will pumpdown and cycle off and will not restart until the fault is cleared or the circuit breaker reset, for the following conditions:
– Suction sensor shorted, open or not installed – Room temperature sensor shorted or not installed – Pressure Transducer open or not installed
The system will pumpdown, cycle off and try to restart for these faults. Each try will be after the 4 minutes “Hold Off” period, for the following fault conditions:
– High pressure or low pressure cutout – Oil pressure
After the fourth try, the Alarm contacts will be closed and an alarm message displayed on the LED.
ERROR CODES
E1 E2 E3 E4 E5 E6 E7 E9
– Room temperature sensor shorted, open or not installed – Defrost temperature sensor shorted, open or not installed – Suction temperature sensor shorted, open or not installed – Suction pressure transducer shorted, open or not installed – Outdoor temperature sensor shorted – Low superheat – Compressor shut down (high or low pressure switch open or oil pressure switch open). – Multi-in / multi-out wiring error
21
Beacon II Controller
Evaporator Fans Shut Down By Operators
In some installations, it is desirable to shut off the evaporator fans for product loading. This is easily accomplished on Beacon II by wiring a single pole switch (SPST) between the terminals on the Beacon II board marked SERVICE and COM. Closing this switch will cause the system to pumpdown and shut off the compressor and the evaporator fans. The switch must be reopened before the system will restart.
SPST switch and wiring is field supplied and field installed.
Power Failures
In the event of a power failure, Beacon II will automatically close the expansion valve to prevent refrigerant from migrating throughout the system. After power returns, with 24 VAC at the board, the system will restart in the cooling mode after the 4-minute hold off period.
Spare Sensor Terminals
Beacon II provides a set of input terminals for customers who may want to monitor an additional temperature or items such as Product Temperature. This input terminal requires a signal from a thermistor which meets the temperature/resistance values in Table 5 below.
If a product temperature simulator is used, it must meet the resistance/temperature specification listed in Table 5. The temperature range for this input is -30°F to 140°F. Sensors on the Beacon II system, as supplied, will not simulate product temperature.
This
This input can be monitored on the LED display by using the “MONITOR” button and scrolling the values displayed will be the temperature of the spare sensor.
SPt
. The
Checking Sensors
DO NOT REMOVE SENSORS FROM COIL FOR CHECKING. Use the monitor button to display the value
the sensors are reading on the LED (suction temp. SCt, defrost temp. dFt or room temp.). Compare this value to the measured value with a thermometer at each of these points. If they do not match, change the sensor.
or
The sensors can be checked for their proper operation by placing it in a cup of ice water. Stir the ice water and measure the resistance of the sensor. At 32°F the resistance should be 32,650 ohms. If it is higher or lower by 5,000 ohms approximately, the sensor should be replaced.
Resistance of sensors at various temperatures.
Table 5. Resistance / Temperature Specification
Temperature °F Ohms Temperature °F Ohms
104 5,320 32 32,650 86 8,060 23 42,330 77 10,000 14 55,330 68 12,490 5 72,950 59 15,710 -4 97,070 50 19,900 -13 130,410 41 25,400 -22 176,960
22
Beacon II Controller
System Defaults
Table 6. System Defaults
Parameters Code Cooler Freezer
Refrigerant Box Temperature Superheat Slave Evaporator No. of Defrosts Per Day Defrost Fail-Safe Time Defrost End Temperature Defrost Delay Start Time Alarm High Temperature Alarm Low Temperature Alarm Time Temperature Units
Figure 11. Control Sensor And Piping
rEF
bot SUP SLA
dFn dFF
dFt
dFS ALH ALL
ALt
F-C
R404A R404A
35°F -10°F
8°F8°F
No No
24
40 min. 30 min.
45°F60°F
0 hrs. 0 hrs.
50°F5°F 30°F -15°F
60 min. 60 min.
°F °F
23
Beacon II Controller
Checking Operation Of Expansion Valve (EEV)
1. To check if the expansion valve is closing properly;
Install a pressure gauge-set to suction line at the condensing unit. With the system running, close the valve on the liquid receiver, at the condensing unit. The system should pumpdown and shut off on the Low Pressure switch (LPS). If the system does not pumpdown and trip on the LPS then the compressor valves are weak and needs to be changed.
After the system pumps-down and trip on the LPS, turn off the power to the Beacon II board, then turn the power back on. This will cause the Expansion valve to close.
Open the valve on the liquid receiver, at the condensing unit. The suction pressure reading on the gauge set should not increase. If the suction pressure increases then the expansion valve is leaking and should be changed.
2. The expansion valve position can be monitored from the LED display pressing the MONITOR button and scrolling to
This can also be checked by using the EXV test pins on the board. This is indicated by a 0 to 5 Volts DC signa. At 0 Volt the valve is closed and at 5 Volts the valve is fully open. At values between 0 and 5 Volt, the valve will be opened proportionately.
ESP
. This will indicate the number of steps the valve is open.
3. Use the “MONITOR” button to display displayed. Start the system and observe the pressure displayed. If the pressure does not increase, the expansion valve could be defective.
4. If the system is running, use the Record the pressure displayed. While the system is running, press the the pressure while the system is pumping down. The pressure should decrease. If it does not, this indicates a defective valve.
SCP
MONITOR
Evaporator Suction Pressure. Record the pressure
button to display
SCP
Evaporator Suction Pressure.
FORCE SERVICE
button. Observe
Expansion Valve Motor Winding Resistance
If the expansion valve is suspected of not functioning properly the motor windings resistance should be measured. This is a bipolar motor with two windings. Measure the resistance at the pins, on top of the valve, between locations A and B or C and D. (Note that the pins are not labeled A, B, C, D. This labeling is just for reference. Also, two of the pins, at location B and location D, have a wider spacing between them than between location A and C. See Figure 12.
Figure 12.
Expansion Valve
A
B
C
D
Motor Winding
Pins
For valve sizes 29320003 and 29320004, the resistance measured between pin locations A and B or C and D should be approximately 336 Ohms when the valve is at 75°F.
For valve sizes 29320007, 29320008, 29320013, and 29320014, the resistance measured between pin locations A and B or C and D should be approximately 116 Ohms when valve is at 75°F.
Measuring resistance between locations A and C or B and D will always show “Open” because these locations are between the motor windings.
When the valve is opening or closing, the voltage measured between A and B or C and D should be between 20 to 22 VAC.
Measuring the DC volt of the EXV TEST pins, on the board, will also indicate if the expansion valve is open or close. 0 volts DC indicates the valve us closed, 5 volts DC indicates the valve is fully open. A Values between 0 and 5 volts indicates how much the valve is open or close.
24
Beacon II Smart Controller
The Smart Controller performs all of the standard Beacon functions with the additional benefit of remote monitoring. The Smart Controller is mounted in the manager’s office and the refrigeration system can be monitored and changed without going to the cooler or freezer. The Smart Controller with LCD display will also alert you to any alarm conditions in your refrigeration system. The Smart Controller will display the problem in addition to letting you know when to call for service. See pages 49-51 for proper wiring instructions. Refer to the installation and operation manual that ships with each Smart Controller for complete instructions.
NOTE: One Smart Controller controls both the cooler and freezer.
25
Beacon II Smart Controller Features
The Beacon II Smart Controller performs all the standard Beacon functions with the additional benefit of:
a) Remote mounting for easy access b) Remote monitoring and programming c) Controlling four completely separate systems d) Logging data e) Smart Defrost f) Access via PC or modem g) Has buzzer to signal alarms h) Locking keypad
Beacon II Smart Controller allows complete programming and monitoring of the system. The Controller display has the following buttons: COOLING, DEFROST, PROG REVIEW, MONITOR, ENTER, CLEAR, SETPOINT AND TIME.
The normal LCD display will show the Programmed Box Set-point temperature. Actual Box Temperature, the Current Time of day and the Mode (i.e. COOL, DEFROST or OFF). When multiple systems are being controlled, the system number (i.e. SYS 1, SYS 2, SYS 3, SYS 4) will also be displayed on the LCD.
26
Beacon II Smart Controller Features
• Monitoring of the complete refrigeration system.
• Programming of a variety of parameters for the optimum control of the refrigeration system.
• The Beacon II Smart Controller has a Liquid Crystal Display (LCD) which shows: current time, actual box temperature, box temperature set-point and if there is an alarm or fault condition.
• Data Logging.
• Smart Defrost to save energy on defrost.
• Sounds a buzzer to indicate an Alarm condition.
• Can be mounted up to 1000 ft. away from the system being controlled.
• Each Beacon II Smart Controller can control four independent systems with up to 4 evaporators on each system.
• An RS232 port is provided which allows connection to system via PC or Modem.
• A Backup battery will maintain the clock settings for 10 years.
• Double E PROM Chip will maintain program settings indefinitely.
• Password protection system.
• Locking feature to prevent unauthorized access to program settings.
System
Number
Time of Day
Set-point Slide Bar
Box Set-point
Temperature
Operating
Mode
Box
Temperature
System
Selection Bar
27
Installation
INSTALLATION
The Smart Controller should be installed in a location where the large Liquid Crystal Display (LCD) can be viewed easily, yet is secure and vibration free. Because of the LCD screen, the Smart Controller II should not be mounted where it will experience temperatures below 40 ºF or above 100 ºF.
A terminal strip for wiring connections is located on the base of the Smart Controller. To access this terminal strip, pull both halves of the Smart Controller housing apart. Mounting holes are located in the plastic base.
Beacon II Smart Controller Base
24 V Terminal
Strip
RS-232
Connector
28
Wiring
WIRING All 24 volt wiring must be run separate from the line voltage wiring.
The terminal strip in the Smart Controller is labeled similarly to that of the Beacon II boards. Connect the corresponding terminals to those on the Beacon board.
For single Refrigeration system:
Connect MULTI OUT 1 from the Smart Controller to the MULTI IN on the Beacon board on the Evaporator. Then connect MULTI IN 1 from the Smart Controller to the MULTI OUT on the Beacon board on the Evaporator. See typical wiring diagram at the back of these instructions.
For MULTIPLE independent Refrigeration systems:
For the first system, connect MULTI OUT 1 from the Smart Controller to the MULTI IN on the Beacon board on the Evaporator in this first system. Then connect MULTI IN 1 from the Smart Controller to the MULTI OUT on the Beacon board on the
Evaporator on this first system. DO NOT disconnect the Room sensor from any of the Evaporators. See typical wiring diagram at the back of these instructions.
A minimum 18 gauge wire should be used. All low voltage wiring must be run separate from high voltage wiring.
POWER SUPPLY
The Beacon II Smart Controller gets it’s 24 VAC power supply from the evaporator. When controlling multiple systems, the Beacon II Smart Controller is powered from the evaporator of only one of the systems. If a power interruption occurs to the system supplying the Smart Controller II, the Smart Controller II LCD screen will go blank. The other systems will, however, continue to operate and maintain their box temperature.
If the Beacon II Smart Controller LCD displays all supply is below 18 VAC. When this occurs the system will power down and shut off. When the power supply is corrected to 24 VAC, the system will restart after the four-minute hold off period and resume normal operation. The Beacon II Smart Controller LCD display will then be normal.
88888
this indicates that the power
INITIALIZATION of Beacon II Smart Controller
When power is first applied to the Beacon II Smart Controller, it checks the configuration of the system to which it is connected and stores this in its memory. Beacon II Smart Controller checks how many condensing units there are and how many evaporators are connected to each condensing unit. This is called Initialization.
modified (changing the number of evaporators on a condensing unit), while connected to the Beacon II Smart Controller, the Beacon II Smart Controller must be re-initialized.
Whenever a system is added, removed or
29
Initialization of Beacon II Smart Controller
INITIALIZATION of BEACON II SMART CONTROLLER
When power is first applied to the Beacon II Smart Controller it checks the configuration of the system to which it is connected and stores this in its memory. Beacon II Smart Controller checks how many condensing units there are and how many evaporators are connected to each condensing unit. This is called Initialization.
added, removed or modified (changing the number of evaporators on a condensing unit), while connected to the Beacon II Smart Controller, Beacon II Smart Controller must be re-initialized.
Make sure all wiring changes to the system and Beacon II Smart Controller are complete before initializing the Beacon II Smart Controller.
INITIALIZATION STEPS (for version 1.2)
• Put all systems in “SERVICE” using the service switch, before turning on power.
• Turn power on and program any “SLAVE” evaporators as slave.
• Press and Hold both the “ENTER” and “CLEAR” buttons on Smart Controller.
• Hold both the “ENTER” and “CLEAR” buttons down until the LCD screen of the Smart Controller displays “EEROM?”
• When “EEROM?” is displayed, release both buttons and press the “ENTER” button.
• The Smart Controller LCD screen will display “WAIT.”
After “WAIT” is displayed it may take up to 2 minutes for the initialization to be completed
and the normal LCD screen is displayed.
Whenever a system is
CLOCK (+ -) This is used to set the time of day on the display.
• Depress the + button to move the clock forward
• Depress the - button to move the clock backward
• When in PROG Mode, these are used to step through values for setting superheat etc.
COOLING: Depressing this button will start the system in the cooling cycle immediately (The 4 minutes “Hold Off” is bypassed). This button will illuminate to indicate that the Cooling function is “ON”. System operation will be as described under REFRIGERATION MODE in the Beacon II installation manual.
Pressing the COOLING button while the system is cooling, and the button illuminated, will pumpdown the system and turn it off.
DEFROST: Depressing this button will force the system into defrost immediately (The “Hold Off/Hold On” times are bypassed). This button will illuminate to indicate that the Defrost function is “ON”. When in Defrost, pressing this button twice will end defrost.
30
Programming Beacon II Smart Controller
MONITOR: Depressing the MONITOR button will display the setpoints shown on page 10.
If one Beacon II Smart Controller is controlling two or more independent systems, you must press the monitor.
PROG REVIEW: This button allows stepping through each of the setpoints for initial
setup and to make changes.
If one Beacon II Smart Controller is controlling two or more independent systems, you must press the make program changes.
CLEAR: Used to clear incorrect entries while programming or to return to the System
display when monitoring.
TIME: Slide-bar is used to set the thermostat clock for Defrost times.
SETPOINT: Slide-bar is used to change settings while programming.
ENTER: To enter new settings into the program. NOTE: Settings are recorded in memory
even if power fails.
SELECTION BAR
SELECTION BAR
to display information on the system you want to
to display information on the system you want to
PROGRAMMING BEACON II SMART CONTROLLER
To make a change, press the PROG REVIEW3 button until the setpoint that needs changing is displayed. The SETPOINT Slide-bar is then used to change to the desired new setting. When the new desired setting is displayed, press the “ENTER” button. The new setting is now programmed into the Beacon II Smart Controller memory.
Press the PROG REVIEW button and follow the steps below:
DEFTYP
This selection will automatically set the defaults for Air and Electric Defrost. Important: This will set the refrigerant type to R22 for Air and R404A for Electric. You must change
to the refrigerant you are using in your application.
REFTYP
BOXTMP
then press “ENTER”)
SUPRHT
superheat temp., then press “ENTER”.
SMT DFT
then press “ENTER” (for version 1.2. When Smart Defrost is turned on, 8 defrost periods per day will automatically be programmed. These will be at 12:00 am, 3:00 am, 6:00 am, 9:00 am, 12:00 pm, 3:00 pm, 6:00 pm, and 9:00 pm. Also, the defrost fail safe time will be set to 60 minutes, and the defrost termination temperature will be set to 55°F. The user can change these as needed for the application).
DEF ST
bar to select first defrost time, then press “ENTER”. Use + button to scroll to next defrost period, dF 2, use “TIME” slide-bar to select second defrost time and press “ENTER”. Repeat steps for each required defrost period). If defrost times are not programmed the system will use the defaults: Electric Defrost - four per day at 4:00 AM, 10:00 PM, 4:00 PM, 10:00 AM. Air Defrost - two per day at 9:00 AM, 9:00 PM.
ELE or AIR: Select for Electric Defrost or Air Defrost then press “ENTER”.
22, 404, 507
– Box Temp: -30º F to 70º F. Use “SETPOINT” slide-bar to get desired temp.,
– Superheat: 4 to 20 º F. Use “SETPOINT” slide-bar to select desired
: Smart Defrost: On/Off. Use “SETPOINT” slide-bar to turn it ON or OFF,
- Defrost Start time: Up to 12 settings per day (For dF 1, use the “TIME” slide-
31
Monitoring with Beacon II Smart Controller
DEFSAF
elapsed, the defrost cycle will end, even if the programmed Defrost Termination temperature was not achieved. Use “SETPOINT” slide-bar to select desired time,
DEFTMP
ALR HI
select desired temp., then press “ENTER”.
ALR LO
select desired temp., then press “ENTER”.
ALRMIN
indicated: 2 to 120 min. Use “SETPOINT” slide-bar to select desired time, then press “ENTER”.
º F / º C
12/24H
“SETPOINT” slide-bar to select, then press “ENTER”.
TEST
cycle each output at 10 second intervals. Use “SETPOINT” slide-bar to select, then press “ENTER”. Return to “OFF” and then press “ENTER” to end the test.
SERVIC
down and shut it off. The system will not restart until OFF mode.
Defrost Fail Safe Time: 10 to 200 minutes. When this time has
then press “ENTER”.
Defrost Termination Temperature: 40 to 100º F. Use “SETPOINT”
slide-bar to select desired temp., then press “ENTER”.
– Alarm High Temperature. -40 to 90º F. Use “SETPOINT” slide-bar to
– Alarm Low Temperature -40 to 90º F. Use “SETPOINT” slide-bar to
– Alarm Time, in minutes. Condition must exceed before alarm is
º F or º C. Use “SETPOINT” slide-bar to select then press “ENTER”.
– Clock: 12H is for standard time. 24H is for international time. Use
: OFF or ON: Puts all evaporators in TEST mode. Use with Caution. This will
ON or OFF: When placed in the ON mode this will pump the system
SERVIC
is placed back in the
MONITORING with BEACON II SMART CONTROLLER
The Monitoring function can be used to monitor live system data. The information displayed, such as superheat, is the actual superheat of the system as it is changing.
Press the MONITOR button and follow the steps below:
SUPRHT
EXVSET
+ button to check other evaporators if Master/slave)
SUCTMP
SSVTMP
SUCPRE
OD TMP
DEFTMP
DEFTIM
CMPCYC
CMPRUN
SPRTMP
– Superheat (use + button to check superheat of other evaporators, if
Master/slave)
- Expansion valve step setting (Stepper motor setting 0 to 255 steps: useEvaporator Suction temperature (Measured by the Suction sensor)
Saturated Suction temperature at the Evaporator
Evaporator Suction Pressure
Actual outdoor ambient temperature (Measured at the condensing
unit)
Evaporator coil temperature (Used to terminate defrost)
- Defrost Time: Length of last defrost
- Comp Cycles: No of Compressor Cycles since 12:00 midnight
- Comp run time (Measured since 12:00 midnight)
Spare sensor temperature input
32
Locking Beacon II Smart Controller
VERSON
evaporators, if Master/slave)
VERSON
When multiple evaporators are connected as master/slave depressing the + or - button will display information specific to each evaporator. Units in a master/slave connection are numbered 1 through 4.
The first evaporator connected to the SMART CONTROLLER Terminals is Evaporator # 1.
LOCKING BEACON II SMART CONTROLLER
BEACON II SMART CONTROLLER is lockable to prevent programmed settings to be changed by unauthorized personnel. When the Controller is Locked, all the Buttons, except for the Monitor and Prog Review Buttons, are disabled.
To LOCK the settings, do the following:
Software Version: For each controller (use + button to check other
- Software Version: for Beacon II Smart Controller
MULTI-OUT
• Press “PROG REVIEW” button.
• Press and hold “MONITOR” button
While holding “MONITOR” button, Press “ENTER” button.
• The LCD will display LOCK
This will prevent unauthorized persons from changing any settings.
To UNLOCK the Controller, repeat these steps.
ERROR CODES
BXSEN -
DFSEN -
STSEN -
SPSEN -
ODSEN -
SUPLO -
SHTDN -
The error code will flash alternately with the normal display information. When the error condition is corrected, the error code will no longer be displayed and only the normal information will be displayed.
Room temperature sensor shorted, open or not installed
Defrost temperature sensor shorted, open or not installed
Suction Temperature sensor shorted, open or not installed
Suction pressure transducer shorted, open or not installed
Outdoor temperature sensor shorted Superheat too low Compressor shutdown (High or low refrigerant pressure or low oil pressure)
WIRING ERROR
If the Beacon II Smart Controller LCD displays error in the communication wiring or that the wiring is broken or disconnected.
+COMM+
, this indicates that there is an
The communication wiring is the MULTI IN and MULTI OUT connections. Check to make sure the OUT is connected to IN. Never connect OUT to OUT or IN to IN.
33
Alarm Codes
ALARM CODES
*BOXHI
*BOXLO
*STRUP
*INFLT Power failure
• When an ALARM condition occurs, the BEACON II SMART CONTROLLER will display
“CALL FOR SERVICE”, the ALARM code, the SYSTEM Number and will sound an internal buzzer.
The alarm code will flash alternately with the normal display information. When the alarm condition is corrected, the alarm code will no longer be displayed and only the normal information will be displayed.
The system will pumpdown and cycle off and will not restart until the fault is cleared for the following conditions:
: Box temperature too high
: Box temperature too low
:System Start-up failure Compressor pumps down and tries to restart
after 4 minutes.
: Input fault (Box Temp., Suction Temp., Pressure
Transducer open or not installed)
Suction sensor shorted, open or not installed Room temperature sensor shorted, open or not installed Pressure Transducer open or not installed
The system will pumpdown, cycle off and try to restart for three consecutive times. Each try will be after the 4 minutes “Hold Off” period, for the following fault conditions.
Oil pressure High pressure or low pressure cutout
After the fourth try, the Alarm contacts will be closed and an alarm message displayed on the LCD screen. To clear this condition, the system should be cycled through the “Service” mode after correction is complete.
On Multiple systems the Alarm contacts on each of the Master Evaporator will announce Alarms for that system.
ALARM BUZZER
The ALARM buzzer will sound when an Alarm condition occurs. This buzzer will turn off when the Alarm condition is cleared. The buzzer can also be silenced at any time by pressing the “CLEAR” button.
34
Smart Defrost
DATA LOGGING
Beacon II Smart Controller logs system data in its memory every 15 minutes. The length of time it records data is dependent on how many systems are being controlled by the Beacon II Smart Controller. It keeps writing data to its memory until the memory is full. When the memory is full it will overwrite its oldest stored data in memory with newly recorded data.
Data recorded: System Mode, Box Temperature, AUX Temperature, Superheat,
Suction Pressure and the Number of Compressor cycles since midnight.
Errors and Alarms recorded: Date, Time, System #, Unit #, Error type, Alarm type, Error
duration and Alarm duration
Length of data recorded: One System = 30 days
Two Independent Systems = 15 days Three Independent Systems = 10 days Four Independent Systems =7 days
Recording intervals:Every 15 minutes All recorded data will have a date/time stamp.
On multiple evaporator systems, the data recorded is from the master evaporator only. This data is available via connection to a PC through the Smart Controller’s RS232 serial port. The data can be viewed on a PC using our Windows based SMART II software and can be imported into an Excel spreadsheet.
Real-time data can also be recorded and stored on a Desktop PC while the PC is connected to the Smart Controller. The PC will continuously request information from the Smart Controller regarding system operation and setup and record this data every minute, in an Excel Spreadsheet. This information is stored to the PC hard drive, which depending on the size of the hard drive, would allows for many days of recording. This data may also be periodically saved on a disk by the user.
The SMART II software is sold separately from the Beacon II Smart Controller.
SMART DEFROST
The Beacon II Smart Controller continuously monitors the system performance to determine the need for defrost. It uses a variety of data such as the outdoor ambient and box temperature in it’s decision making process.
Activating Smart Defrost:
You must program multiple defrost times into the Smart Controller to provide flexibility for the system to defrost the coil properly. Smart Defrost will only allow the system to defrost at a programmed defrost time. The system will not defrost in between programmed defrost times. Hence, we recommend that a minimum of
35
PC and Modem Access
8 defrost periods be programmed when Smart Defrost is turned on. The system
will not defrost eight times per day but with this many defrost periods it will have better options to keep the coil clear.
After programming the minimum 8 defrost periods, all that’s needed to activate Smart Defrost is to press the button until “
SMT DFT
” is displayed.
“PROG REVIEW”
Move the “ return to the main screen.
For version 1.2., when Smart Defrost is turned on, 8 defrost periods per day will automatically be programmed. These will be at 12:00 am, 3:00 am, 6:00 am, 9:00 am, 12:00 pm, 3:00 pm, 6:00 pm, and 9:00 pm. Also, the defrost fail safe time will be set to 60 minutes, and the defrost termination temperature will be set to 55°F. The user can change these as needed for the application.
Deactivating Smart Defrost:
To turn Smart Defrost off move the “ “
ENTER
SETPOINT
”. Press “
” slide-bar to “ON” then press “
SETPOINT
CLEAR
” to return to the main screen.
ENTER
” slid-bar to “
”. Press “
OFF
” then press
CLEAR
” to
PC & MODEM ACCESS
For access to the system from a PC directly or via a modem, the SMART II Software must be purchased and installed on your PC. With PC access, ALL system settings can be monitored, changed or logged from a remote location. The stored data can be viewed in an Excel spreadsheet.
36
Operational Checkout
After the system has been charged and has operated for at least 2 hours at normal operating conditions without any indication of malfunction, it should be allowed to operate overnight on automatic controls. Then a thorough recheck of the entire system operation should be made as follows:
(a) Check compressor discharge and suction pressures. If not within system design limits, determine why
and take corrective action.
(b) Check liquid line sight glass and expansion valve operation. If there are indications that more
refrigerant is required, leak test all connections and system components and repair any leaks before adding refrigerant.
(c) Using suitable instruments, carefully check line voltage and amperage at the compressor terminals.
Voltage must be within 10% of that indicated on the condensing unit nameplate. If high or low voltage is indicated, notify the power company. If amperage draw is excessive, immediately determine the cause and take corrective action. On 3 phase motor compressors, check to see that a balanced load is drawn by each phase.
(d) The maximum approved settings for high pressure controls on Bohn/Heatcraft air cooled condensing
equipment is 400 psig. On air cooled systems, check as follows:
• Disconnect the fan motors or block the condenser inlet air.
• Watch high pressure gauge for cutout point.
• Recheck all safety & operating controls for proper operation and adjust if necessary. (e) Check head pressure controls for pressure setting. (f) Check crankcase heater operation if used. (g) Install instruction card and control system diagram for use of building manager or owner.
Check-Out & Start-Up
After the installation has been completed, the following points should be covered before the system is placed in operation: (a) Check all electrical and refrigerant connections. Be sure they are all correct and tight. (b) Check voltage taps on transformer. The transformer is shipped wired to 240 voltage tap/connection. If your supply voltage is 208 volt systems, change to 208 voltage tap. (b) Check setting of time delay relay for low pressure switch in condensing unit. It should be set at one minute (the second marker). (c) Check high and low pressure controls, pressure regulating valves, oil pressure safety controls, and all other safety controls and adjust them, if necessary. (d) On freezers only, check the low pressure switch setting. It must be set to 0 PSIG cut out, 10 PSIG cut in, to allow start and operation, especially in cold ambients. (e) Liquid line should always be insulated. (f) Wiring diagrams, instruction bulletins, etc. attached to the condensing units should be read and filed for future reference. (g) All fan motors on air cooled condensers, evaporators, etc. should be checked for proper rotation. Fan motor mounts should be carefully checked for tightness and proper alignment. (h) Observe system pressures during charging and initial operation. Do not add oil while the system is short of refrigerant unless oil level is dangerously low. (i) Continue charging until system has sufficient refrigerant for proper operation. Do not overcharge. Remember that bubbles in a sight glass may be caused by a restriction as well as a shortage of refrigerant. (j) Do not leave unit unattended until the system has reached normal operating conditions and the oil charge has been properly adjusted to maintain the oil level at the center of the sight glass. (k) At initial start-up, the system may cycle off at 2 minutes and display a low superheat error, then restart itself. This cycle may be repeated a few times. Do not shut the system off. Let the system run, as it may take a few cycles for the electric expansion valve to attain the correct setting for the desired superheat.
CAUTION: Extreme care must be taken in starting compressors for the first time after system charging. At this time, all of the oil and most of the refrigerant might be in the compressor creating a condition which could cause compressor damage due to slugging. Activating the crankcase heater for 24 hours prior to start-up is recommended. If no crankcase heater is present, then directing a 500 watt heat lamp or other safe heat source on the lower shell of the compressor for approximately thirty minutes will be beneficial in eliminating this condition which might never reoccur.
37
Preventive Maintenance
Routine preventive maintenance of any mechanical equipment is critical to its long term reliability. During even normal operation all equipment will experience some deterioration during its lifetime caused by wear and environmental influences. For that reason, regularly scheduled maintenance of your refrigeration equipment is required in order to keep it operating to its maximum efficiency while avoiding potentially costly repairs of a premature failure due to equipment neglect. The following is Bohn/Heatcraft’s minimum recommendations for regularly scheduled preventive maintenance of your McDonald’s refrigeration system. Qualified and licensed refrigeration companies only should perform all preventive and corrective maintenance on refrigeration equipment. While we cannot guarantee that close adherence to these recommendations will eliminate all equipment problems, it will greatly reduce the potential for mechanical and electrical failures thus providing increased reliability.
38
Preventive Maintenance
CONDENSING UNIT
QUARTERLY SEMI-ANNUALLY DATE DATE DATE DATE
Visually inspect unit ✔✔
1
Look for signs of oil stains on interconnection piping and condenser coil. Pay close attention to
areas around solder joints, building penetrations and pipe clamps. Check any suspect areas with an
electronic leak detector
✔✔
2
Check condition of moisture indicator in the sight glass of all systems. Look for indication of moisture
or flash gas.
✔✔
3 Check condition of condenser. Look for accumulation of dirt and debris. Clean as required. ✔✔
4 Check for unusual noise or vibration. Take corrective action as required. ✔✔
5
Inspect wiring for signs of wear or discoloration
✔✔
Clean condenser coil and blades
1
Periodic cleaning can be accomplished by using a brush, pressurized water and a commercially
available foam coil cleaner. If foam cleaner is used, it should not be an acid based cleaner. Follow
label directions for appropriate use
2 Rinse until no residue remains
Check operation of condenser fans
1
Check that each fan rotates freely and quietly. Replace any fan motor that does not rotate smoothly
or makes excessive noise.
2 Check all fan blade set screws and tighten as required
3
Check all fan blades for signs of cracks, wear or stress. Pay close attention to the hub and spider.
Replace blades as required.
4 Verify that all motors are mounted securely
Inspect electrical wiring and components
1 Verify that all electrical and ground connections are secure, tighten as required.
2
Check condition of compressor, defrost heater and condenser fan contactors. Look for
discoloration and pitting. Replace as required
3 Check operation and calibration of all timers, relays pressure controls and safety controls
4
Clean electrical cabinet. Look for signs of moisture, dirt, debris, insects and wildlife. Take corrective
action as required
5
Verify operation of crankcase heaters by measuring amp draw
Check refrigeration cycle for all systems
1 Check suction and discharge temperatures & pressures. If abnormal take appropriate action
2 Check operation of liquid injection on freezer system
3 Check pressure drop across all filters and driers. Replace as required.
4 Verify that superheat at the compressor conforms to specification. (30F to 45F)
Inspect suction accumulators
1 Inspect all accumulators for signs of leaks and corrosion.
2 Pay close attention to all copper to steel brazed connections
3 Wire brush all corroded areas and peeling paint.
4 Apply an anticorrosion primer and paint as required.
5 Re-attach insulation and replace any damaged sections
39
Preventive Maintenance
UNIT COOLERS
QUARTERLY SEMI-ANNUALLY DATE DATE DATE DATE
Visually inspect unit ✔✔
1 Look for signs of corrosion on fins, cabinet, copper tubing and solder joints ✔✔
2
Look for excessive or unusual vibration for fan blades or sheet metal panels when in operation.
Identify fan cell(s) causing vibration and check motor and blade carefully.
✔✔
3
Look for oil stains on headers, return bends, and coil fins. Check any suspect areas with an
electronic leak detector.
✔✔
4
Check drain pan to insure that drain is clear of debris, obstructions or ice build-up and is free
draining.
✔✔
5
Insure that there is sufficient clearance free of obstructions around unit coolers to allow proper
airflow through coils
✔✔
6 Verify Box setpoint temperature is being met ✔✔
Clean Evaporator coil and blades
1
Periodic cleaning can be accomplished by using a brush, pressurized water or a commercially
available Evaporator Coil Cleaner or mild detergent.
Never
use an acid based cleaner. Always
follow label directions for appropriate use. Be sure the product you use is approved for use in food
service applications.
2 Flush and rinse coil until no residue remains.
3 Pay close attention to drain pan, drain line and trap.
Check the operation of all fans and ensure airflow is unobstructed
1
Check that each fan rotates freely and quietly. Replace any fan motor that does not rotate
smoothly or makes an unusual noise.
2 Check all fan set screws and tighten if needed.
3
Check all fan blades for signs of stress or wear. Replace any blades that are worn, cracked or bent.
4
Verify that all fan motors are securely fastened.
Inspect electrical wiring and components
1
Visually inspect all wiring for wear, kinks, bare areas and discoloration. Replace any wiring found to
be damaged
2 Verify that all electrical and ground connections are secure, tighten if necessary.
3 Check operation/calibration of all fan cycle and defrost controls when used.
4 Look for abnormal accumulation of ice patterns and adjust defrost cycles accordingly
5 Compare actual defrost heater amp draw against unit data plate. (freezer only)
6
Visually inspect heaters to ensure even surface contact with the coil. If heaters have creeped
decrease defrost termination temperature and be sure you have even coil frost patterns. (freezer
only)
7 Check low voltage wiring at Beacon board for broken wires
8 Check voltage at Beacon board. Should be between 18 to 30 Volts
Check Beacon sensors
1 Press MONITOR button to display sensor reading for Box Temp., Suction Temp. and Defrost Temp.
2 Use an accurate Thermometer to measure temperatures at the same locations as the sensors.
3 LED readings should match measured values, within 3 °F at same locations as sensors.
Check Beacon Pressure Transducer
1 Press MONITOR button to display Suction Pressure reading at the Evaporator
2 Use an accurate Gauge Set to measure Evaporator Pressure.
3 Measured suction pressure should match LED displayed value within 2 Psig.
Check Drain Line Heater
1 Check heater amps
2
Check that heater is wrapped around entire length of drain line inside the walk-in freezer
Refrigeration Cycle
1 Check unit cooler superheat and compare reading for your specific application
2 Visually inspect coil for even refrigerant distribution
40
Diagnostics
Beacon II Troubleshooting Guide
PROBLEM Step ACTION ITEM IF OK IF NOT OK
1. Check Primary Power Supply Disconnect 1. Check fuses and circuit breakers
LED is not lit. 3. Check Transformer Secondary Output Volts next step 3. Replace if necessary
LED shows compressor will not run. 3. Check Compressor Contactor Coil Voltage next step 3. Check internal condensing unit wiring
ERROR CODES:
E1
E2 E3 E4
E5 Outdoor Sensor Check Sensor, wiring and Board Connection Replace or remove
E6
During Cooling 4. Check Electric Expansion Valve Closure Go to 4. Pumpdown system see if LPS opens or if it
(0°F for 2 minutes) next step times out (EEV is bad or LPS is set
Coo
, but (24 Volts across “COMP” and “C” at board) Go to primary) and wiring of 208V power taps.
Room Sensor Check Sensor and Board Connection Replace as needed Defrost Sensor Check Sensor and Board Connection Replace as needed Suction Sensor Check Sensor and Board Connection Replace as needed Suction Transducer Check Transducer and Board Connection Replace as needed
Low Superheat 3. Check Control Board step position from board LED 3. Replace board if EEV steps not at 2.
2. Check Voltage to Evaporator Transformer Go to 2. Check field wiring for breaks
4. Check Voltage at Control Board (24V and C) 4. Check factory wiring and connections
5. Replace Control Board
1. Check Compressor internal overloads 1. Wait for reset
2. Check Control Power to Condensing Unit 2. Check transformer voltage (secondary and
4. Check Compressor Contactor “pulled in” 4. Replace as needed
1. Check Refrigerant Type 1. Compare board setpoint and refrigerant
2. Check coil for ice 2. Defrost coil and check defrost cycle settings/setpoints, defrost sensor and heater amps.
incorrectly, if times out) – See Pumpdown.
5. Compressor Not Operating 5. Check overloads and contactor.
6. Check Suction Temperature Sensor 6. Compare board sensor reading against actual suction line temperature.
7. Check Suction Pressure Transducer 7. Compare pressure reading against gauges.
41
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEM Step ACTION ITEM IF OK IF NOT OK
1. Check wiring connection to the board • Correct field wiring to the board
2. Low Pressure Safety (LPS) Tripped:
• Check for correct refrigerant type • Change setpoint to match refrigerant
• Check refrigerant charge • Add more refrigerant to proper charge
• Check LPS setting • Correct LPS setting
• Check LPS wiring • Correct LSP wiring
• Check EEV operation (stuck?) • Clean or replace EEV
• Check coil for icing • Defrost coil (see
• Check for correct superheat reading • Check/replace sensor or transducer
• Check for correct nozzle selection • Replace distributor nozzle
• Check for clogged EEV inlet screen • Replace EEV
• Check line sizing • Correct line sizing
• Check LPS time delay relay setting • Reset to 1 minute
• Check operation of LPS • Replace Low Pressure Safety Switch
3. High Pressure Safety (HPS) Tripped:
• Check for system overcharge • Reclaim/recover excess charge
• Check for non-condensables • Remove all non-condensables
• Check condenser fan motor and blade • Repair or replace motor and/or blade
• Check for dirty condenser coil • Clean condenser coil
• Check head pressure controls • Adjust or replace faulty controls
• Check fan cycling controls • Adjust or replace faulty controls
• Check liquid line sizing • Correct line sizing
• Check for liquid line restrictions • Repair line or remove restrictions
• Check operation of HPS • Replace HPS if necessary
E6
, step 2)
E7
Compressor 4. Oil Pressure Safety (OPS) Tripped:
Shutdown • Check oil level in compressor • Add oil to crankcase to minimum level
• Check oil sump screen pickup • Clean or replace pickup screen
• Check oil pump pressure • Replace compressor oil pump
• Check for proper piping practices Go to • Correct piping to minimize oil logging
• Check for low superheat (see E6) next step • Correct per steps in
• Check operation of auxiliary relay (R6) • Replace auxiliary relay
• Check OPS sensor • Replace faulty OPS sensor
• Check operation of OPS • Replace faulty OPS
5. Compressor Module Tripped (when supplied):
• Check module • Replace faulty module
• Check superheat at compressor inlet • Reduce superheat (TXV adjust, etc.)
• Check compressor for overheating • Correct overheating problem
• Check suction pressure (too low?) • Consider crankcase pressure regulator or other measures
6. Phase Loss Monitor (PLM) Tripped:
• Check presence of all phase legs • Correct power phase problem
• Check power supply • Correct power supply problems
• Check operation of PLM • Replace faulty PLM
7. Demand Cooling (when supplied):
• Check auxiliary relay • Replace auxiliary relay
• Check demand cooling device • Replace faulty demand cooling device
8. Check compressor relay on board • Replace board if relay is faulty
E6
42
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEM Step ACTION ITEM IF OK IF NOT OK
E9
Multi-out to Multi-in 1. Check for 24 volts power to the board 1. If no voltage, see “LED is not lit” above
Communication Wiring for low voltage, see “88888 LED display” (only shows after initial 2. Check for crossed communication wiring Go to successful connection) (multi-out not wired to multi-in terminals) next step
3. Check for broken communication wiring
Break in the designated lines will cause errors as follows:
[With SMART Controller II]
Line # SMART Cooler or Freezer
1 +COMM+ E9 2 +COMM+ no error
SMART II
in out
Cooler or Freezer
in out
1
2
PROBLEM Step ACTION ITEM IF OK IF NOT OK
88888 LED display 1. Check Voltage to Evaporator Transformer 1. Check field wiring for breaks or shorts (power is below 18V and 2. Check Transformer Secondary Output Volts Go to 2. Replace if necessary appears at initial power) 3. Check Voltage at Control Board (24 and C) next step 3. Check factory wiring and connections
LED displays then displayed errors board to condensing unit terminal connection compressor contactor.
dLy
oFF
with no 2. Check for short in field wiring from “comp” on next step. 2. Check internal factory wiring to
4. Check Voltage at SMART Controller II 4. Check field wiring from board
1. Check for low voltage 1. Check all steps for “88888 LED display” Go to Voltage could drop off too fast to show.
3. Replace defective contactor (holding coil)
43
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEM Step ACTION ITEM IF OK IF NOT OK
1. Check system operation: Is it running? 1. Check power to condensing unit
2. Check system charge 2. Add or remove refrigerant to proper charge
3. Check for proper operating superheat 3. Check EEV operation
4. Check for high superheat and EEV wide open 4. Check EEV inlet screen and restrictions
Cannot get to box 6. Compare equipment capacity with requirements Go to 6. Add or replace with more/larger equipment temperature 7. Check box temperature setpoint next step 7. Correct setpoint to proper value
Service Mode *ONLY Master board on multiple evaporator systems Mode, all must be “open” to terminate the mode.)
(
SEr
is displayed)
Controller,
5. Check Low Pressure Safety Switch 5. Check everything for E7 LPS above
8. Check compressor performance 8. Check compressor application limitations
9. Check condenser coil for dirt/debris 9. Clean condenser coil
10. Check condenser for non-condensables 10. Remove all non-condensables
11. Check condenser fan operation 11. Replace/repair fan blade, motor, cycling
12. Check for correct refrigerant type 12. Compare board setpoint and refrigerant
13. Check for iced evaporator coil 13. Defrost coil and check defrost cycle (see E2)
14. Check defrost parameters 14. Correct defrost setpoints in program
15. Check superheat setpoint (too high?) 15. Correct setpoint for more cooling surface
16. Check display values (°F or °C) 16. Correct setpoint for proper display values
Placing system into SERVICE MODE Terminating SERVICE MODE
(BOARDS ONL Y) (BOARDS ONLY)
1. Use Remote Service Switch in condensing unit 1. Must terminate using same switch
2. Pressing “Force Service” button board* twice 2. Press “Clear” button on board
3. Connection between “Ser” and “C” on board* 3. Open connection between “Ser” and “C” (all are wired in parallel; all will activate mode) (Note: If multiple switches were placed in Service
(with Beacon II Smart Controller) (with Beacon II Smart Controller)
1. Use Remote Service Switch in condensing unit 1. Must terminate using same switch
2. Connection between “Ser” and “C” on board* 2. Open connection between “Ser” and “C”
3. From program menu of Beacon II Smart Controller, 3. From program menu of Beacon II Smart Change SERVICE setpoint to “On”. Change SERVICE setpoint to “Off”
[all are wired in parallel; any/all will activate mode.] [Note: If multiple switches were placed in Service *ONLY Master board on multiple evaporator systems Mode, all must be “open” to terminate the mode.)
Check position of Service Mode switches Check compressor overloads and contactor
Check control board EEV signal Check suction sensor and transducer
Check liquid line sizing Check head pressure controls
Check integrity of compressor operation (impaired, worn or damaged components)
switch or make corrective adjustments.
settings/setpoints and defrost sensor (frequency and termination of defrosts)
44
Parts
Table 7. Condensing Unit Parts List
CONDENSING UNITS
PART DESCRIPTION
Compressor - Freezer ZF09K4E ZF13K4E ZF15K4E ZF13K4E ZF15K4E Compressor - Cooler RS64C1E CS10K6E CS10K6E RS43C1E RS43C1E Disconnect Fuses 22510110 22510112 22510113 22510111 22510113 Start Relay - Cooler 1007647 1007660 1007647 Start Capacitor - Cooler 7076956 7076957 7076959 Run Capacitor - Cooler 7076951 7075858 7076950 Compr Contactor - Cooler 2254304 Compr Contactor - Freezer 2255845 Condenser Fan Motor 25399101 Condenser Fan Blade 22999901 Fan Guard 23104401 Head Pressure Valve:
Cooler 29317401
Freezer 29317303 29317304 29317304 29317304 29317303 High Pressure Control 28903201 Lo Pressure Control - Freezer 2891402 Lo Pressure Control - Cooler 2890099 Lo Pressure Time Delay 22536801 Crankcase Htr - Freezer 24701301 Fan Cycling Thermostat 2890019 Ambient Temperature Sensor* 88904902 Evaporator Fuses - Freezer 22510002 Evaporator Fuses - Cooler 22510001 Fan Relay (R3, R4 - 240v) 22505201 Fan Relay (R1, R2 - 24v) 22521901 Terminal Block 2251423
MAC3X
MAC7X MAC8X
MAC4X MAC5X
Table 8. Evaporator Parts List
PART DESCRIPTION PART NUMBER EVAPORATORS
Fan Motor 25308601 ALL Fan Blade 5140C ALL Fan Guard 37000701 ALL
24752002 LET090BHB2N6MK
Defrost Heater 24752003 LET120BHB2N6MK
24752004 LET160BHB2N6MK 24752202 LET090BHB2N6MK
Defrost Pan Heater 24752203 LET120BHB2N6MK
24752204 LET160BHB2N6MK 29320004 ADT070BHB2N6MK 29320004 LET090BHB2N6MK 29320004 ADT052BHB2N6MK 29320004 LET120BHB2N6MK
Electric Expansion Valve 29320004 ADT052BHB2N6MK
29320004 LET160BHB2N6MK 29320004 ADT104BHB2N6MK 29320004 LET120BHB2N6MK 29320004 ADT104BHB2N6MK
29320007 LET160BHB2N6MK Expansion Valve Controller 22515201 ALL Beacon II Control Board 28910101 ALL Temperature Sensor Kit* 89904902 ALL Transformer (240/24 - 40 VA) 22529602 ALL Pressure Transducer 28911201 ALL Pressure Transducer Harness 22515101 ALL
*Only the sensor with white leads is shipped as a Service Replacement Part.
45
Beacon II Smart Controller
Table 9. Beacon II Smart Controller Parts List
PART DESCRIPTION NUMBER
Beacon II Smart Controller 89704301 *Smart Controller Software Package 89704101
*Smart Controller Software Package is sold separately.
Table 10. Beacon II Operational Limits
OPERATIONAL LIMITS
Voltage 18 VAC to 30 VAC Controlling Box Temp. Range -30°F to 70°F Box Temp. Dead-Band +/-1°F Cold Ambient Limits Start and operate to -20°F
PART
46
Startup Checklist
Date of Start-up Store Address
CONDENSING UNIT MODEL # SERIAL # COOLER UNIT MODEL # SERIAL # FREEZER UNIT MODEL # SERIAL #
ELECTRICAL
Check Primary Supply voltage.
If 208 V, change transformer wiring in the Cooler and Freezer to the 208 V tap
YES
• Check Compressor Amps for COOLER and FREEZER compressors. Should match nameplate.
YES NO
PIPING
• Is suction line trapped at the Cooler?
YES NO
• Is suction line trapped at the Freezer?
YES NO
DRAIN LINES
• Are drain lines sloped properly?
YES NO
• Is drain line trapped outside the Cooler?
YES NO
• Is drain line trapped outside the Freezer?
YES NO
• Is heat tape wrapped along entire length of the drain line in the Freezer?
YES NO
• Is heat tape plugged in and heating the drain line?
YES NO
INSULATION
• Are Liquid lines fully insulated?
YES NO
• Are Suction lines fully insulated?
YES NO
SETTINGS
• Check Beacon II board settings for the following: FREEZER Refrigerant Type R404A Box Setpoint Temp. -10°F. Superheat 8°F. No. of Defrost/Day 4 Defrost End Temp. 65°F.
COOLER Refrigerant Type R404A Box Setpoint Temp. 35°F. Superheat 8°F. No. of Defrost/Day 2 Defrost End Temp. 50°F.
SYSTEM CHECKS
• Check Compressor Superheat for the COOLER (Should be between 20°F. & 30°F.)
YES NO
• Check Compressor Superheat for the FREEZER (Should be between 20°F. & 30°F.)
YES NO
• Force unit into a Defrost Check heater amps. Should match nameplate amps.
YES NO
• Check LPS Time Delay Relays. Should be set at 1 minute for both the COOLER and FREEZER.
YES NO
• Check Low Pressure Switch on FREEZER. Should be set at 0 psig Cut-out/10 psig Cut-in.
YES NO
• Did FREEZER and COOLER cycle off on LPS at Set-point Temperature?
YES NO
• Is the sight glass free of bubbles?
YES NO
• Are the COOLER and FREEZER fans at proper speeds?
YES NO
• Check system for refrigerant leaks. Are there any leaks on the COOLER, FREEZER, CONDENSING UNIT or INTERCONNECTING PIPING?
YES NO
• Check system piping for unusual vibration or noise. Is there any unusual vibration or noise on the COOLER, FREEZER, CONDENSING UNIT or INTERCONNECTING PIPING?
YES NO
• Start the FREEZER only. Does the compressor start and evaporator fans run for this FREEZER?
YES NO
47
Startup Checklist
RECORD
OUTDOOR TEMPERA TURE ______°F. SYSTEM VOLTAGE ______Volts ______PH ______Hz Cooler Compressor Amps ______L1 ______L2 ______L3 Freezer Compressor Amps ______L1 ______L2 ______L3 Cooler Discharge Pressure ______PSIG Freezer Discharge Pressure ______PSIG Cooler Suction Pressure ______PSIG Freezer Suction Pressure ______PSIG Cooler Suction Temp. ______°F. Freezer Suction Temp. ______°F. Cooler Refrigerant Charge ______lbs. Freezer Refrigerant Charge ______lbs. Cooler Compressor Superheat ______°F. Freezer Compressor Superheat ______°F. Cooler Evaporator Superheat ______°F. Freezer Evaporator Superheat ______°F. Cooler Discharge Temp. ______°F. Freezer Discharge Temp. ______°F.
48
Wiring Diagrams
Diagram 1. Low Profile Evaporator Wiring
49
Wiring Diagrams
Diagram 2. MAC Unit Wiring
50
Wiring Diagrams
Diagram 3. 24 Volt Connection Wiring with Smart Controller
51
For Warranty Service 24 Hours a Day, 7 Days a Week
Call Toll Free (877) HTCRAFT (877-482-7238)
Warranty Coverage
Standard Parts & Labor - 1 Year
Beacon Parts (TXV, Sensors, Board, Smart Controller) - 3 Years
Compressor Part - 5 Years
Due to ongoing efforts in product improvement, specifications are subject to change without notice.
A Brand of Heatcraft Refrigeration Products LLC
2175 West Park Place Blvd. Stone Mountain, GA 30087
770.465.5600 Fax: 770.465.5990 www.heatcraftrpd.com
© 2003, Heatcraft Refrigeration Products LLC
52
Loading...