1. Installation and maintenance to be performed only by certified personnel who are familiar with this type of
equipment.
2. Make sure that all field wiring conforms to the requirements of the equipment and all applicable national
and local codes.
3. Avoid contact with sharp edges and coil surfaces. They are a potential injury hazard.
4. Make sure all power sources are disconnected before any service work is done on units.
WARNING:Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered
responsibly. Failure to follow this warning may result in personal injury or death.
Inspection
Responsibility should be assigned to a dependable individual at the job site to receive material. Each
shipment should be carefully checked against the bill of lading. The shipping receipt should not be signed
until all items listed on the bill of lading have been accounted for. Check carefully for concealed damage. Any
shortage or damages should be reported to the delivering carrier. Damaged material becomes the delivering
carrier’s responsibility and should not be returned to the manufacturer unless prior approval is given to do so.
When uncrating, care should be taken to prevent damage. Heavy equipment should be left on its shipping
base until it has been moved to the final location.
Condensing Unit Specifications
Figure 1.
Table 1. Condensing Unit Specifications
ModelLocationCompressorVoltageHPUnitUnitUnit90% full
Note:Whenever possible always try to position the evaporator to blow towards the walk-in door.
Never position the evaporator over or adjacent to a door opening.
1
CoolerFreezer
Loading Door
or
Cooler
1
1
Evaporator Minimum Unit Clearance
1 1/2 H
Top View
1 1/2 H
1 1/2 H
Side View
H = Total Height of Unit’s Coil Surface
1 1/2 H
H
2 H
4
1/2 W1/2 W
W
Condensing Unit Placement
Space and Location Requirements
The most important consideration which must be taken into account when deciding upon the location of aircooled equipment is the provision for a supply of ambient air to the condenser, and removal of heated air from
the condensing unit or remote condenser area. Where this essential requirement is not adhered to, it will
result in higher head pressures, which cause poor operation and potential failure of equipment. Units must
not be located in the vicinity of steam, hot air or fume exhausts. Corrosive atmospheres require custom
designed condensers.
Another consideration which must be taken is that the unit should be mounted away from noise sensitive
spaces and must have adequate support to avoid vibration and noise transmission into the building. Units
should be mounted over corridors, utility areas, rest rooms and other auxiliary areas where high levels of
sound are not an important factor. Sound and structural consultants should be retained for recommendations.
(Refer to actual building plans for unit locations.)
Figure 4.
3 Feet
(minimum)
Clearance =
3 Feet from
Building
Wall
3 Feet
(minimum)
Clearance to
an Open Block
Wall or
Shrubs.
3 Feet
(minimum)
Clearance for
Contractor to
Service Unit.
5
Refrigeration Piping And Line Sizing
Refrigeration Piping And Line Sizing
The system as supplied by Bohn/Heatcraft, was thoroughly cleaned and dehydrated at the factory . Foreign
matter may enter the system by way of the evaporator to condensing unit piping. Therefore, care must be used
during installation of the piping to prevent entrance of foreign matter. Install all refrigeration system components
in accordance with applicable local and national codes and in conformance with good practice required for the
proper operation of the system. The interconnecting pipe size is not necessarily the same size as the stub-out on
the condensing unit or the evaporator.
The following procedures should be followed:
(a) Do not leave dehydrated compressors or filter-driers on condensing units open to the atmosphere any longer
than is absolutely necessary .
(b) Use only refrigeration grade (ACR) copper tubing, properly sealed against contamination.
(c) Suction lines should slope 1/4” per 10 feet towards the compressor (in direction of flow).
(d) Suitable P-type oil traps should be located at the base of each suction riser to enhance oil return to the
compressor.
(e) For desired method of superheat measurement, a pressure tap should be installed in each evaporator
suction line in the proximity of the expansion valve bulb.
(f) When brazing refrigerant lines, an inert gas should be passed through the line at low pressure to prevent
scaling and oxidation inside the tubing. Dry nitrogen is preferred.
(g) Use only a suitable silver solder alloy on suction and liquid lines.
(h) Limit the soldering paste of flux to the minimum required to prevent contamination of the solder joint internally .
Flux only the male portion of the connection, never the female. After brazing, remove excess flux.
(i) Remove temperature sensor attached to suction line on Beacon II systems before brazing of the
solder joint internally . Flux only the male portion of the connection – never the female. After brazing,
remove excess flux.
(j) Wrap expansion valves with wet rags during brazing to the liquid line.
CAUTION: If the temperature gets too high, these components may be damaged. Heat absorbing
compounds or wet rags must be used to protect the expansion valve when brazing to the refrigerant
piping/line connections, and the suction line sensor must be removed per above instructions.
(k) Do not use “bull head” tees. This will cause oil return problems and can cause poor performance.
(l) If isolation valves are installed at the evaporator, full port ball valves should be used.
Table 3. Recommended Line Size In Equivalent Lengths
The remote precharged circuits are provided with a factory holding charge of R-404A. The system charge is
located in the appropriate drink and ice machines. Schrader valve fittings are provided for liquid line charging
at the condensing unit. Consult the appropriate drink and ice machine manufacturers for details on
installation of precharged lines.
6
Refrigeration Piping
Suction Lines
NOTE: If the suction line must rise to the point higher than the suction connection on
the evaporator, a suction line trap at the outlet of the evaporator must be provided.
Horizontal suction lines should slope away from the evaporator toward the compressor at the rate of 1/4’ per
10 feet for good oil return.
Suction lines that are outside of refrigerated space must be insulated. See “Line Insulation” for more
information.
Suction Line Risers
NOTE: To provide proper oil return, a suction trap must be provided at the base of
all suction risers.
Prefabricated wrought copper traps are available, or a trap can be made by using two street ells and one
regular ell. The suction trap must be the same size as the suction line. For long vertical risers, additional
traps may be necessary. Generally, one trap is recommended for each length of pipe (approximately 20 feet)
to insure proper oil movement. See Figure 5 below for methods of constructing proper suction line P-traps.
Figure 5. Suction P-traps
Condensate Drain Lines
Copper drain lines should be used and properly protected from freezing. In running drain lines, provide a
minimum of 4 inches per foot pitch for proper drainage. Drain lines should be at least as large as the
evaporator drain connection. All plumbing connections should be made in accordance with local plumbing
codes. All condensate drain lines must be trapped, and run to an open drain. They must never be connected
directly to the sewer systems. Traps in the drain line must
be located in a warm ambient. See Figure 6. We
recommend a trap on all evaporators. Traps located
outside, or extensive outside runs of drain line must be
wrapped with a drain line heater. The heater should be
connected so that it is continuously on. The drain line must
be insulated to prevent heat loss. A heat input of 20 watts
per lineal foot of drain line for 0ºF (-18°C) room applications
and 30 watts per lineal foot for -20°F (-29°C) rooms is
satisfactory.
Inspect the drain pan periodically to insure free drainage of
condensate. If the drain pan contains standing water, check
for proper installation. The drain pan should be cleaned
regularly with warm soapy water.
WARNING: All power must be disconnected
before cleaning. The drain pan also serves as
cover for hazardous moving parts. Operation
of unit without drain pan constitutes a hazard.
Figure 6. Drain Line
NOTE: Always trap drain lines individually
to prevent vapor migration.
7
Refrigeration Piping
Figure 7. Example of Pipe Support
1. Normally, any straight run of tubing must be supported in at least two locations near each end of the run.
Long runs require additional supports. The refrigerant lines should be supported and fastened properly.
As a guide, 3/8 to 7/8 should be supported every 5 feet, 1-1/8 and 1-3/8 every 7 feet; and 1-5/8 and 2-1/8
every 9 to 10 feet.
2. When changing directions in a run of tubing, no corner should be left unsupported. Supports should be
placed a maximum of 2 feet in each direction from the corner.
3. Piping attached to a vibrating object (such as a compressor or compressor base) must be supported in
such a manner that will not restrict the movement of the vibrating object. Rigid mounting will fatigue the
copper tubing.
4. Do not use short radius ells. Short radius elbows have points of excessive stress concentration and are
subject to breakage at these points.
5. Thoroughly inspect all piping after the equipment is in operation and add supports wherever line vibration
is significantly greater than most of the other piping. Extra supports are relatively inexpensive as
compared to refrigerant loss.
Figure 8.
Mac
Unit
Line Insulation
After the final leak test, refrigerant lines exposed to high or low ambient conditions should be insulated to
reduce heat loss or gain and prevent the formation of flash gas in the liquid lines. Suction lines must be
insulated with 3/4’ wall Armstrong “Armaflex” or equivalent. Liquid lines must be insulated with 1/2-inch wall
insulation or better. The insulation located in outdoor environments should be protected from UV exposure to
prevent deterioration of insulating value.
8
Leak Detection And Evacuation
Leak Detection
After all lines are connected, the entire system must be leak tested. The complete system should be pressurized
to not more than 150 psig with refrigerant and dry nitrogen. The use of an electronic type of leak detector is highly
recommended because of its greater sensitivity to small leaks. As a further check, it is recommended that this
pressure be held for a minimum of 12 hours and then rechecked. For a satisfactory installation, the system must
be leak tight.
Within the last several years, manufacturers have developed fluorescent dye leak detection systems for use with
refrigerants. These dyes mix with the lubricant and, when exposed to an ultraviolet light “fluoresce,” indicate the
location of leaks. Copeland has tested and approved the Rigid “System Safe” dye and found it to be compatible
with the compressor materials in systems.
Evacuation
CAUTION: Do not use the refrigeration compressor
It is of the utmost importance that proper system evacuation and leak detection procedures be employed.
Copeland recommends a minimum evacuation to 500 microns. In addition, a vacuum decay test is strongly
recommended to assure there is not a large pressure differential between the system and vacuum pump. Good
evacuation processes include frequent vacuum pump oil changes and large diameter, short hose connections to
both high and low sides of the system preferably using bronze braided hose.
to evacuate the system. Do not start the
compressor while it is in a vacuum.
A good, deep vacuum pump should be connected to both the low and high side evacuation valves with copper
tube or high vacuum hoses (1/4” ID minimum). If the compressor has service valves, they should remain closed.
A deep vacuum gauge capable of registering pressure in microns should be attached to the system for pressure
readings.
A shut-of f valve between the gauge connection and vacuum pump should be provided to allow the system
pressure to be checked after evacuation. Do not turn off vacuum pump when connected to an evacuated system
before closing shut-off valve.
The vacuum pump should be operated until a pressure of 1,500 microns absolute pressure is reached – at which
time the vacuum should be broken with the refrigerant to be used in the system through a drier until the system
pressure rises above “0” psig.
NOTE: Refrigerant used during evacuation can not be vented.
Reclaim all used refrigerant. EP A regulations are constantly
being updated. Ensure your procedures follow correct regulations.
Repeat this operation a second time.
Open the compressor’s service valves and evacuate the entire system to 500 microns absolute pressure.
Raise the pressure to 2 psig with the refrigerant and remove the vacuum pump.
9
Field Wiring
WARNING:All wiring must be done in accordance with applicable codes and local ordinances.
The field wiring should enter the areas as provided on the unit. The wiring diagram for each unit is located on the
inside of the electrical panel door. All field wiring should be done in a professional manner and in accordance with
all governing codes. Before operating the unit, double check all wiring connections, including the factory
terminals. Factory connections can vibrate loose during shipment.
1.The nameplate on the unit is marked with the electrical characteristic for wiring the unit.
2.Consult the wiring diagram in the unit cooler and in the condensing unit for proper connections.
3.Wire type should be of copper conductor only and of the proper size to handle the connected load.
4.The unit must be grounded.
Figure 9. Beacon II Board
Heater
Relay
Fan
Relay
LED
Display
Room
Sensor
Defrost
Sensor
Expansion
Valve
Connection
Selection
Buttons
24 V.
Terminal
Block
Suction
Sensor
Suction
Pressure
10
Beacon II Controller
Installation Tips
• Use a minimum 18 gauge wire for all low voltage connections.
• The Beacon II board get its 24 VAC power supply from a transformer mounted in the electrical end of each
evaporator. On 208-240 volt systems the multi-tap transformer is shipped from our factory wired for 240
volts. If your supply voltage is 208 volt you must change to the 208 volt tap on the transformer.
• Refer to wiring schematic shipped on units for wiring.
• Evaporators are shipped from our factory with a preset box setpoint temperature of 35°F for air defrost and
-10°F for electric defrost. If your box setpoint temperature requirements are different this must be set using
directions outlined under “Room Temperature Control”.
• The suction line temperature sensor MUST be removed from the suction line before brazing the suction
tubing. The sensor MUST then be reinstalled on the suction line after brazing is completed and the tubing
has cooled. Insulate when finished.
• The low pressure switch time delay relay, located in the condensing unit, must be set to one minute.
• Some systems may require the crankcase heater to be energized 24 hours prior to start-up. The Beacon II
should be de-energized for this period by placing it in the SERVICE MODE. This is done by pressing the
“FORCE SERVICE” button twice. To start the system cooling, press the “CLEAR” button.
• Room sensors must be left connected on ALL evaporators.
• A pressure transducer is installed on the evaporator. Do not leak test system above 150 PSI or damage to
transducer could occur.
• Refer to the Beacon II Smart Controller Installation Manual, shipped with the Beacon II Smart Controller,
for installation, programming and monitoring information.
Condensing Unit
The condensing unit control panel contains the relays, contactors, and a terminal block which is appropriately
marked to match the low voltage wiring connections. A sensor for outdoor air temperature measurement is
installed on the condensing unit.
Condensing unit must be installed using proper refrigeration practices and codes. Make sure there is good
airflow and good clearances around unit. See Figure 4, page 5.
Evaporator Unit
The evaporator contains the BEACON II controller(s), electric expansion valve(s), pressure transducer,
distributor(s), orifice(s), transformer and three sensors. These components are all factory mounted and wired.
The three sensors are factory mounted and provide input to the controller from the following: defrost temp.,
suction temp., room temp.
Each evaporator unit must be installed using proper refrigeration practices and codes. Make sure the piping is
correctly sized and properly routed. Liquid and suction lines MUST be insulated. There must also be good
clearance around the unit. See Figure 3, page 4.
11
Beacon II Controller
Refrigerant Line Brazing (
The electric expansion valve and the suction temperature sensor on the suction line are factory installed.
Care must be taken when brazing these lines at the evaporator.
components. Heat absorbing compounds or “wet rags” must be used when brazing the refrigerant
line connections. The suction line sensor should be removed before brazing.
CAUTION
)
Too high a temperature may destroy these
Power Supply
The Beacon II board gets its 24 VAC power supply from a transformer mounted in the electrical end of each
evaporator. On 208-240 volt systems the multi-tap transformer is shipped from our factory wired for 240 volts.
If your supply voltage is 208 volt you must change to the 208 volt tap on the transformer.
VERY IMPORTANT: If the supply voltage to the evaporator is 208 volts, the primary tap of the transformer
must be moved to the 208 volt tap.
If the 24 VAC power supply falls below 18 VAC the system may power down and shut off. When the power
supply is corrected to 24 VAC the system will restart after the four minute hold-off period and resume normal
operation.
This must be done for all the evaporators on that system.
Wiring
Wiring between the condensing unit and the unit cooler(s) will be as follows (see attached wiring diagrams):
• High voltage – There may be high voltage on the defrost heater relay and the fan relay. See unit cooler
spec. plate for ampacity.
• Low voltage – 24V Class II control circuit. A total of five low voltage leads are required to connect the
condensing unit to the evaporator (see wiring diagram). Two of these leads are for connecting the outdoor
temperature sensor. The other three leads are for connecting the compressor relay, service relay and 24V
Common inputs.
• Number of wires in low voltage wiring bundles:
MAC to cooler evaporator - 5
MAC to freezer evaporator - 5
Cooler evaporator to Smart Controller - 6
Freezer evaporator to Smart Controller - 4
• Low voltage wiring must be 18 gauge minimum. For low voltage wiring, maximum distances are:
Condensing unit to evaporator500 ft.
Smart Controller to evaporator1,000 ft.
• Alarm circuit – The onboard alarm is a dry set of NC contacts which closes to indicate an alarm. The type
and wiring for the alarm is customer specified. Note that the alarm circuit does not distinguish or indicate
what has caused the alarm.
• All wiring must comply with all applicable codes and ordinances.
All 24 volt wiring must be run separate from the line voltage wiring.
12
Beacon II Controller
Box Temperature Control Settings
•There is an on board room thermostat on the Beacon II board which can be adjusted to the desired
room temperature. The temperature differential is 2°F.
Temperature Differential
When a system is in the cooling mode and the box setpoint is 35°F, the system will continue to cool until
the box temperature gets to 34°F. At this point the compressor will pumpdown and shut off. The system
will restart cooling when the box temperature has risen to 36°F.
It is important to note that Beacon II has a minimum 2-minute “ON” time and a minimum 4-minute “OFF”
time. This means that the system will run in the cooling mode a minimum of 2 minutes even if the setpoint
temperature is met. In applications where the system is grossly oversized, the box temperature could go
below the differential temperature before the system cycles off.
In the “OFF” cycle, the system will be off for a minimum of 4 minutes even if the box temperature goes
above the differential temperature before cooling will be restarted.
•The on board room thermostat is factory set at 35°F for air defrost systems and -10°F for electric defrost
systems.
Refrigerant Charging
The cooler and freezer systems utilize refrigerant side head pressure control. Charge each system by adding
an initial charge of 5 lbs. of R-404a refrigerant to the liquid side of the receiver. This initial charge will allow the
system to start. With the system running, continue to add refrigerant to the system until the sight glass is
clear. Operate system until the cooler/freezer box achieves the desired temperature. The sight glass should
be clear with no bubbles or flashing of refrigerant. Now the additional charge for the flooded condenser is to
be weighed into each system in the amount as shown in Table 4.
•Check all wiring connections to be sure they are correct and tight.
•On condensing unit:
-Check the setting of Time Delay relay. It should be set a one minute (the second marker).
-Check the Low Pressure switch setting on freezer units. It must be set to 0 PSIG cutout, 10 PSIG
cut-in to allow positive start and operation, especially in cold ambients. This can be changed to a
higher value in warmer climates. On cooler units, the Low Pressure switch has a fixed setting and
cannot be adjusted.
13
Beacon II Controller
Initial Power On
At the initial application of power to the system, the compressor and the evaporator fans will be in a 4-minute
hold-off cycle and will not start immediately. When there is a call for COOLING, the expansion valve (EEV)
opens, then the compressor is started. The compressor will then run for a minimum of 2 minutes in the “holdon” cycle. (This means that the compressor will run for a minimum of 2 minutes before shutting off even if the
box temperature is met).
The LED alternately displays
show while the expansion valve is opening. After the compressor starts, the LED will alternately display
TEMPERATURE
When the room thermostat setting is satisfied, and if the compressor ran for at least 2 minutes, the EEV will
close and the compressor will pumpdown and shut off. The evaporator fans will continue to run. The LED will
alternately display
When the room sensor detects a rise in temperature of approximately 2°F, and the compressor has been off
for at least 4 minutes, the EEV will open to its last position then the compressor will start. The valve is then
adjusted as necessary to obtain the setpoint superheat setting. During this time, the compressor will run for a
minimum 2 minutes “hold-on” cycle.
The 4 minute “hold-off” can be bypassed and the system started immediately by pressing the “Reset” button
on the Beacon II board.
and
oFF
Coo
BOX TEMPERATURE
.
and
BOX TEMPERATURE
and
.
MODE
of operation. On a call for cooling,
dLY
will
BOX
Figure 10. Operating Mode Display
oFF
–Off
Coo
– Cooling
Pdn
– Pumpdown
dEF
– Defrost
drn
–Draining
dLY
– Delay
tSt
–Test
SEr
–Service
14
Beacon II Controller
Programming And Reviewing Settings/Changes
The Program Review button is used to program, review and change all program settings for the system.
Press “PROGRAM REVIEW” button. The Setpoint item will appear on the LED. After a few seconds delay
the Setpoint value will display. Each time the button is pressed a different setpoint item is displayed.
PROGRAM
REVIEW
Next, use the “SELECT” knob to change value of Setpoint Item.
SELECT
Next, when the desired value is selected, press the “ENTER” button to place it in program memory. If the
“ENTER” button is not pressed, the value will not be stored in the memory and thus will not be changed.
ENTER
“PROGRAM REVIEW” ITEMS
A-E
rEF
bot
SUP
SLA
dFn
dFF
dFt
dFS
ALH
ALL
ALt
F-C
–Set Defrost Type (
–Set Refrigerant Type (R22, R404A or R507)
–Set Box Temperature (-30°F to +70°F)
–Set Superheat (4°F to 20°F)
–Set Board as a Slave (Yes or No)
–Set Number of Defrosts Per Day (1, 2, 3, 4, 5, 6, 8, 10 or 12 per day)
–Set Defrost Fail-safe Time (10 to 200 minutes)
–Set Defrost End Temperature (40°F to 100°F)
–Set Defrost Delay Start Time (0.5 Hours to 23.5 Hours)
–Set Alarm High Temperature (-40°F to 90°F)
–Set Alarm Low Temperature (-40°F to 90°F)
–Set Alarm Time (2 to 120 minutes)
–Set Fahrenheit/Celsius Temperature Units (°F / °C)
Air
or
ELE
)
15
Beacon II Controller
Programming And Reviewing Settings/Changes (continued)
Use the “PROGRAM REVIEW” button to select these items:
PROGRAM
•Defrost Type –
the system factory defaults for air defrost and electric defrost. (See default settings). Please note that the
refrigerant type
factory default settings.
•Refrigerant Type –
“A-E”
– Selection is made for air defrost or electric defrost coil. This will automatically set
default
for air defrost is R22 and for electric defrost it is R404A. All units are shipped with
“rEF”
– Selection for type of refrigerant – R22, R404A or R507.
Default: Air defrost is R22 and for electric defrost is R404A.
•Box Temperature –
“bot”
– Select box temperature setpoint. Selection range is -30°F to +70-°F.
Default: Electric defrost -10°F and air defrost +35°F.
•Superheat –
measures the evaporator saturation suction temperature and the suction pressure to determine the
superheat. The superheat value at the evaporator can be changed to ensure a 20°F to 30°F superheat at
the compressor.
“SUP”
– Evaporator superheat is controlled by the board on each evaporator. Each board
Default: 8°F.
•Evaporator Board: SLAVE –
programmed to be a MASTER or a SLAVE. Each board is shipped from our factory set as a MASTER.
You must make this change to each SLAVE evaporator. A selection of “YES” is made for this setting.
“SLA”
– On multiple evaporator systems, each evaporator board has to be
Default: MASTER on each board. For a single evaporator system, no change is required.
•Number of Defrosts Per Day –
day – 1, 2, 3, 4, 5, 6, 8, 10 or 12 per day. If no selection is made:
“dFn”
– A selection must be made for the number of defrosts cycles per
Default: Electric defrost is 4 per day and air defrost is 2 per day.
•Defrost fail-safe –
terminated if the defrost end temperature is not attained when this time has expired.
“dFF”
– This is the maximum time allowed for a coil to remain in defrost. Defrost will be
Default: Electric defrost is 30 minutes and air defrost is 40 minutes.
•Defrost End Temperature –
Default: Electric defrost is +60°F and air defrost is +45°F.
•Defrost Delay Start Time –
Default: 0.5 hours to 23.5 hours.
“dFt”
– This is the temperature at which the defrost will be terminated.
“dFS”
– This allows the delay of the start of the defrost.
16
Beacon II Controller
Programming And Reviewing Settings/Changes (continued)
•Alarm High Temperature –
This does not apply during defrost.
“ALH”
– Temperature at which a high box temperature alarm will be triggered.
Default: Electric defrost is +5°F and air defrost is +50°F.
•Alarm Low Temperature –
“ALL”
– Temperature at which a low box temperature alarm will be triggered.\
Default: Electric defrost is -15°F and air defrost is +30°F.
•Alarm T ime –
alarm is triggered.
“ALt”
– Time which high temperature or low temperature conditions must exceed before
Default: 60 minutes.
•°F/°C –
“F-C”
– Select units to display temperature. Fahrenheit or Celsius.
Default: Fahrenheit.
Use the “MONITOR” button to review these items:
SUP
ESP
SCt
SSt
SCP
Odt
dFt
dFS
dFE
AC
SPt
– Superheat (°F)
– Expansion Valve Stems (0 to 255 steps)
– Suction Temperature (°F)
– Saturated Suction Temperature (°F)
– Suction Pressure at Evaporator (PSIG / “HG)
– Outdoor Temperature (°F)
– Defrost Sensor Temperature (°F)
– Time Left to New Defrost (hours) (on 1.8 versions)
– Last Defrost Elapsed Time (minutes)
– Board Voltage
– Spare Temperature Reading
MONITOR
FORCE
DEFROST
Use this button to “RESET TIME”
Pressing this button will reset the time clock in the microprocessor to zero. At initial
power up, pressing this button will bypass the “four minute” hold-off and the system will
start immediately after the expansion valve opens. This display will show
Use this button to “FORCE DEFROST”
To force a defrost, press the “FORCE DEFROST” button. The system will
pumpdown and shut off the compressor. The heaters are then turned on.
The display will show
“dEF”
.
“dLy”
.
FORCE
SERVICE
Use this button to “FORCE SERVICE”
Pressing this button TWICE will cause the system to pumpdown and the
compressor to shut off. The system will remain off until the “CLEAR” button is
pressed. While in the “FORCE SERVICE”, the LED display will show
RESET
TIME
“SEr”
.
17
Beacon II Controller
Programming And Reviewing Settings/Changes (continued)
Use this button to “CLEAR/TEST”
Pressing this button ONCE will return the LED display to the default display.
With the system in the
the
“TEST”
STATUS INDICATOR LED
A red, 3-digit, alphanumeric LED on the Beacon II board indicates status,
alarms and error codes.
mode. In the
OFF
mode, pressing and holding this button will start
“TEST”
mode it will cycle through each output.
StatusLED DisplayDescription
CLEAR /
TEST
• OFFBox Temp /
All Evaporators
•COOLING
Single Evaporator –Box Temp /
• Pumpdown
All Evaporators
• DEFROST
All Evaporators
• TEST
All Evaporators
•SERVICE
All Evaporators
• ALARMS
Pdn
dEF
tSt
SEr
A1
A2
A3
A4
oFF
Coo
Box Temperature / Mode is displayed
Box Temperature / Mode is displayed
High Box Temp
Low Box Temp
System Start-Up Failure
Compressor pumps down and tries
to restart after 4 minutes.
Input Fault
Box Temp., Suction Temp., Pressure
Transducer open or not installed
18
Beacon II Controller
STATUS INDICATOR LED (continued)
StatusLED DisplayDescription
• ERRORS
• OTHERS
E1
E2
E3
E4
E5
E6
E7
E9
Coo
Loc
UnL
Room temperature sensor shorted, open
or not installed
Defrost temperature sensor shorted, open
or not installed
Suction temperature sensor shorted, open
or not installed
Suction pressure transducer shorted, open
or not installed
Outdoor temperature sensor shorted
Low superheat during cooling
Compressor shutdown (high or low
refrigerant pressure or low oil pressure)
Multi-in/Multi-out wiring error
Room Temperature sensor open or not
connected (Instead of displaying box
temperature)
Board is locked. Settings cannot be changed
Unlock the board settings
Pumpdown
At the end of each cooling cycle, when the box temperature is met, the Beacon system will pumpdown and
shut off the compressor.
To pumpdown, the EEV closes and the compressor runs until the low pressure switch opens or 2 minutes has
elapsed. The compressor is then off and remains off until the start of the next cooling cycle.
While in the off cycle, the system will initiate a short pumpdown at 4-minute intervals, only if the LowPressure Switch closes, to ensure that any refrigerant leakage will not cause a problem.
For Manual Pumpdown, a single pole, single throw switch can be used to connect “SERVICE” and “Com”.
This can be done at the Beacon II board on the evaporator or at the terminal board in the condensing unit.
This will cause the system to pump down and shut off.
NOTE: The system will not restart until the switch has been opened. The Beacon II board will display “SEr”.
or
The system can be pumped down by pressing the “SERVICE” button twice. To restart the system, press the
“CLEAR” button.
or
The system can be pumped down for service by closing the liquid line service valve on the receivers in the
condensing unit, then closing the suction line service valve when the system trips on the low pressure switch.
19
Beacon II Controller
Service Mode
A SPST switch (S1 & S2) is supplied, for each system, in the condensing unit for shutting off the system.
Closing the “Service” switch in the condensing unit will cause the expansion valve to close and the
compressor to pumpdown and shutoff. “SEr” will be the onboard LED display and “SERVIC” is displayed on
the Smart Controller. The evaporator and heater relays on the Beacon II board will then be deactivated. The
system will not restart until the switch is placed in the “NORMAL” or off position.
When the “Service” switch in the condensing unit is closed or ‘on’ (labeled SERVICE), the system is in the
service mode. If the switch is ‘off’ (labeled NORMAL), the system is in normal operation.
Defrost
DEFROST TIMING
When power is first applied to the system, its timer starts counting time. If 4 defrosts are programmed, it will
initiate a defrost every 6 hours from when power was first applied. Beacon II does not have a real time clock.
Beacon II does provide the ability to delay the starting of the first defrost.
DEFROST DELAY START TIME
Example: The system is first powered up at 8:00 AM and is programmed for 4 defrosts per day. The user
would like the first defrost at 10:00 AM. To accomplish this, use the “PROGRAM REVIEW” button to scroll to
dFS
. Use the “SELECTOR” switch to select 2 hours delay start, then press “ENTER”. The first defrost will
now occur at 10:00 AM and then a defrost will occur every 6 hours thereafter.
TIME REMAINING UNTIL NEXT DEFROST (on version 1.8 boards)
To find out how much time is left until the next defrost is scheduled, use the “MONITOR” button to scroll to
dFS. The time displayed will be how much time until the next scheduled defrost.
DEFROST SCHEDULE IN MEMORY
Beacon II does not have a real time clock but it keeps track of the time that has elapsed in its memory. It also
keeps in memory the number of defrosts scheduled and how much time has elapsed between defrosts. If a
power failure occurs, when power is restored Beacon II will remember how many defrosts are scheduled and
it will remember how much time was left until the next defrost. It will then defrost based on this timing. So, if
the power failure lasted 15 minutes, the defrost schedule will be off by 15 minutes.
ELECTRIC DEFROST MODE
When a defrost is initiated, the EEV closes, the compressor is allowed to pumpdown and shut off. The
evaporator fans are cycled off and the defrost heaters are energized.
There is a 2-minute condensate drain-down period after which the compressor is started for a refreeze period.
The evaporator fan stays off (fan delay). The refreeze period will last until the evaporator suction temperature
is at 28°F or 3 minutes has elapsed. After this sequence, the system is back in the refrigerating mode and the
evaporators’ fans are not running.
AIR DEFROST MODE
The sequence is the same as for electric defrost except that there are no heaters and the evaporator fans run
continuously.
20
Beacon II Controller
Alarms
Beacon II provides a set of dry contacts for use in signaling an alarm. These contacts can be connected to a
light, a buzzer, a bell, etc., which will be activated when an alarm condition occurs. When the Beacon II is
energized, the alarm contacts are OPENED. When an alarm condition is detected, the contacts are CLOSED.
Conditions under which the alarm contacts will close are:
A1
•High Box Temperature – LED Display:
for the Alarm time
ALt
, programmed.
– Room temperature has exceeded the Alarm High
ALH
value
•Low Box Temperature – LED Display: A2 – Room temperature has dropped below the Alarm Low
value for the Alarm time
•System Start-Up Failure – LED Display:
minutes.
•Input Fault – LED Display: A4 – Box Temp., Suction Temp., or Pressure Transducer open or not installed.
•Power Failure – Loss of power to the Evaporator.
ALARM CODES
A1
High Box Temp
A2
Low Box Temp
A3
System Start-Up FailureCompressor pumps down and tries to restart after four minutes.
A4
Input FaultBox Temp., Suction Temp., Pressure
ALt
, programmed.
A3
– Compressor pumps down and tries to restart after four
Transducer open or not installed
ALL
Error Indicator LED
At initial power up, each Beacon II board checks for system errors. The system error check involves checking
the various temperature sensors to determine whether any of these sensors are shorted or open.
The system will pumpdown and cycle off and will not restart until the fault is cleared or the circuit breaker
reset, for the following conditions:
– Suction sensor shorted, open or not installed
– Room temperature sensor shorted or not installed
– Pressure Transducer open or not installed
The system will pumpdown, cycle off and try to restart for these faults. Each try will be after the 4 minutes
“Hold Off” period, for the following fault conditions:
– High pressure or low pressure cutout
– Oil pressure
After the fourth try, the Alarm contacts will be closed and an alarm message displayed on the LED.
ERROR CODES
E1
E2
E3
E4
E5
E6
E7
E9
– Room temperature sensor shorted, open or not installed
– Defrost temperature sensor shorted, open or not installed
– Suction temperature sensor shorted, open or not installed
– Suction pressure transducer shorted, open or not installed
– Outdoor temperature sensor shorted
– Low superheat
– Compressor shut down (high or low pressure switch open or oil pressure switch open).
– Multi-in / multi-out wiring error
21
Beacon II Controller
Evaporator Fans Shut Down By Operators
In some installations, it is desirable to shut off the evaporator fans for product loading. This is easily
accomplished on Beacon II by wiring a single pole switch (SPST) between the terminals on the Beacon II
board marked “SERVICE” and “COM”. Closing this switch will cause the system to pumpdown and shut off
the compressor and the evaporator fans. The switch must be reopened before the system will restart.
SPST switch and wiring is field supplied and field installed.
Power Failures
In the event of a power failure, Beacon II will automatically close the expansion valve to prevent refrigerant
from migrating throughout the system. After power returns, with 24 VAC at the board, the system will restart in
the cooling mode after the 4-minute hold off period.
Spare Sensor Terminals
Beacon II provides a set of input terminals for customers who may want to monitor an additional temperature
or items such as Product Temperature. This input terminal requires a signal from a thermistor which meets the
temperature/resistance values in Table 5 below.
If a product temperature simulator is used, it must meet the resistance/temperature specification listed in
Table 5. The temperature range for this input is -30°F to 140°F. Sensors on the Beacon II system, as supplied,
will not simulate product temperature.
This
This input can be monitored on the LED display by using the “MONITOR” button and scrolling the
values displayed will be the temperature of the spare sensor.
SPt
. The
Checking Sensors
DO NOT REMOVE SENSORS FROM COIL FOR CHECKING. Use the monitor button to display the value
the sensors are reading on the LED (suction temp. SCt, defrost temp. dFt or room temp.). Compare this value
to the measured value with a thermometer at each of these points. If they do not match, change the sensor.
or
The sensors can be checked for their proper operation by placing it in a cup of ice water. Stir the ice water
and measure the resistance of the sensor. At 32°F the resistance should be 32,650 ohms. If it is higher or
lower by 5,000 ohms approximately, the sensor should be replaced.
Refrigerant
Box Temperature
Superheat
Slave Evaporator
No. of Defrosts Per Day
Defrost Fail-Safe Time
Defrost End Temperature
Defrost Delay Start Time
Alarm High Temperature
Alarm Low Temperature
Alarm Time
Temperature Units
Figure 11. Control Sensor And Piping
rEF
bot
SUP
SLA
dFn
dFF
dFt
dFS
ALH
ALL
ALt
F-C
R404AR404A
35°F-10°F
8°F8°F
NoNo
24
40 min.30 min.
45°F60°F
0 hrs.0 hrs.
50°F5°F
30°F-15°F
60 min.60 min.
°F°F
23
Beacon II Controller
Checking Operation Of Expansion Valve (EEV)
1. To check if the expansion valve is closing properly;
Install a pressure gauge-set to suction line at the condensing unit. With the system running, close
the valve on the liquid receiver, at the condensing unit. The system should pumpdown and shut off
on the Low Pressure switch (LPS). If the system does not pumpdown and trip on the LPS then the
compressor valves are weak and needs to be changed.
After the system pumps-down and trip on the LPS, turn off the power to the Beacon II board, then
turn the power back on. This will cause the Expansion valve to close.
Open the valve on the liquid receiver, at the condensing unit. The suction pressure reading on the
gauge set should not increase. If the suction pressure increases then the expansion valve is leaking
and should be changed.
2. The expansion valve position can be monitored from the LED display pressing the “MONITOR” button and
scrolling to
This can also be checked by using the EXV test pins on the board. This is indicated by a 0 to 5 Volts DC
signa. At 0 Volt the valve is closed and at 5 Volts the valve is fully open. At values between 0 and 5 Volt, the
valve will be opened proportionately.
ESP
. This will indicate the number of steps the valve is open.
3. Use the “MONITOR” button to display
displayed. Start the system and observe the pressure displayed. If the pressure does not increase, the
expansion valve could be defective.
4. If the system is running, use the
Record the pressure displayed. While the system is running, press the
the pressure while the system is pumping down. The pressure should decrease. If it does not, this indicates a
defective valve.
“SCP”
“MONITOR”
Evaporator Suction Pressure. Record the pressure
button to display
“SCP”
Evaporator Suction Pressure.
“FORCE SERVICE”
button. Observe
Expansion Valve Motor Winding Resistance
If the expansion valve is suspected of not functioning properly the motor windings resistance should be
measured. This is a bipolar motor with two windings. Measure the resistance at the pins, on top of the valve,
between locations A and B or C and D. (Note that the pins are not labeled A, B, C, D. This labeling is just for
reference. Also, two of the pins, at location B and location D, have a wider spacing between them than
between location A and C. See Figure 12.
Figure 12.
Expansion Valve
A
B
C
D
Motor Winding
Pins
For valve sizes 29320003 and 29320004, the resistance measured between pin locations A and B or C and D
should be approximately 336 Ohms when the valve is at 75°F.
For valve sizes 29320007, 29320008, 29320013, and 29320014, the resistance measured between pin
locations A and B or C and D should be approximately 116 Ohms when valve is at 75°F.
Measuring resistance between locations A and C or B and D will always show “Open” because these
locations are between the motor windings.
When the valve is opening or closing, the voltage measured between A and B or C and D should be between
20 to 22 VAC.
Measuring the DC volt of the EXV TEST pins, on the board, will also indicate if the expansion valve is open or
close. 0 volts DC indicates the valve us closed, 5 volts DC indicates the valve is fully open. A Values between
0 and 5 volts indicates how much the valve is open or close.
24
Beacon II Smart Controller
The Smart Controller performs all of the standard Beacon functions with the additional
benefit of remote monitoring. The Smart Controller is mounted in the manager’s office and
the refrigeration system can be monitored and changed without going to the cooler or
freezer. The Smart Controller with LCD display will also alert you to any alarm conditions in
your refrigeration system. The Smart Controller will display the problem in addition to letting
you know when to call for service. See pages 49-51 for proper wiring instructions. Refer to
the installation and operation manual that ships with each Smart Controller for complete
instructions.
NOTE: One Smart Controller controls both the cooler and freezer.
25
Beacon II Smart Controller Features
The Beacon II Smart Controller performs all the standard Beacon functions with the
additional benefit of:
a) Remote mounting for easy access
b) Remote monitoring and programming
c) Controlling four completely separate systems
d) Logging data
e) Smart Defrost
f)Access via PC or modem
g) Has buzzer to signal alarms
h) Locking keypad
Beacon II Smart Controller allows complete programming and monitoring of the system.
The Controller display has the following buttons: COOLING, DEFROST, PROG REVIEW,
MONITOR, ENTER, CLEAR, SETPOINT AND TIME.
The normal LCD display will show the Programmed Box Set-point temperature. Actual Box
Temperature, the Current Time of day and the Mode (i.e. COOL, DEFROST or OFF).
When multiple systems are being controlled, the system number (i.e. SYS 1, SYS 2, SYS
3, SYS 4) will also be displayed on the LCD.
26
Beacon II Smart Controller Features
• Monitoring of the complete refrigeration system.
• Programming of a variety of parameters for the optimum control of the refrigeration
system.
• The Beacon II Smart Controller has a Liquid Crystal Display (LCD) which shows: current
time, actual box temperature, box temperature set-point and if there is an alarm or fault
condition.
• Data Logging.
• Smart Defrost to save energy on defrost.
• Sounds a buzzer to indicate an Alarm condition.
• Can be mounted up to 1000 ft. away from the system being controlled.
• Each Beacon II Smart Controller can control four independent systems with up to 4
evaporators on each system.
• An RS232 port is provided which allows connection to system via PC or Modem.
• A Backup battery will maintain the clock settings for 10 years.
• Double E PROM Chip will maintain program settings indefinitely.
• Password protection system.
• Locking feature to prevent unauthorized access to program settings.
System
Number
Time of Day
Set-point
Slide Bar
Box Set-point
Temperature
Operating
Mode
Box
Temperature
System
Selection Bar
27
Installation
INSTALLATION
The Smart Controller should be installed in a location where the large Liquid Crystal
Display (LCD) can be viewed easily, yet is secure and vibration free. Because of the LCD
screen, the Smart Controller II should not be mounted where it will experience
temperatures below 40 ºF or above 100 ºF.
A terminal strip for wiring connections is located on the base of the Smart Controller. To
access this terminal strip, pull both halves of the Smart Controller housing apart. Mounting
holes are located in the plastic base.
Beacon II Smart Controller Base
24 V Terminal
Strip
RS-232
Connector
28
Wiring
WIRING
All 24 volt wiring must be run separate from the line voltage wiring.
The terminal strip in the Smart Controller is labeled similarly to that of the Beacon II boards.
Connect the corresponding terminals to those on the Beacon board.
For single Refrigeration system:
Connect MULTI OUT 1 from the Smart Controller to the MULTI IN on the Beacon
board on the Evaporator. Then connect MULTI IN 1 from the Smart Controller to the
MULTI OUT on the Beacon board on the Evaporator. See typical wiring diagram at
the back of these instructions.
For MULTIPLE independent Refrigeration systems:
For the first system, connect MULTI OUT 1 from the Smart Controller to the MULTI
IN on the Beacon board on the Evaporator in this first system. Then connect MULTI
IN 1 from the Smart Controller to the MULTI OUT on the Beacon board on the
Evaporator on this first system. DO NOT disconnect the Room sensor from any of
the Evaporators. See typical wiring diagram at the back of these instructions.
A minimum 18 gauge wire should be used. All low voltage wiring must be run separate
from high voltage wiring.
POWER SUPPLY
The Beacon II Smart Controller gets it’s 24 VAC power supply from the evaporator. When
controlling multiple systems, the Beacon II Smart Controller is powered from the evaporator
of only one of the systems. If a power interruption occurs to the system supplying the Smart
Controller II, the Smart Controller II LCD screen will go blank. The other systems will,
however, continue to operate and maintain their box temperature.
If the Beacon II Smart Controller LCD displays all
supply is below 18 VAC. When this occurs the system will power down and shut off. When
the power supply is corrected to 24 VAC, the system will restart after the four-minute hold
off period and resume normal operation. The Beacon II Smart Controller LCD display will
then be normal.
88888
this indicates that the power
INITIALIZATION of Beacon II Smart Controller
When power is first applied to the Beacon II Smart Controller, it checks the configuration of the
system to which it is connected and stores this in its memory. Beacon II Smart Controller
checks how many condensing units there are and how many evaporators are connected to
each condensing unit. This is called Initialization.
modified (changing the number of evaporators on a condensing unit), while connected
to the Beacon II Smart Controller, the Beacon II Smart Controller must be re-initialized.
Whenever a system is added, removed or
29
Initialization of Beacon II Smart Controller
INITIALIZATION of BEACON II SMART CONTROLLER
When power is first applied to the Beacon II Smart Controller it checks the configuration of
the system to which it is connected and stores this in its memory. Beacon II Smart
Controller checks how many condensing units there are and how many evaporators are
connected to each condensing unit. This is called Initialization.
added, removed or modified (changing the number of evaporators on a condensing
unit), while connected to the Beacon II Smart Controller, Beacon II Smart Controller
must be re-initialized.
Make sure all wiring changes to the system and Beacon II Smart Controller are complete
before initializing the Beacon II Smart Controller.
INITIALIZATION STEPS (for version 1.2)
• Put all systems in “SERVICE” using the service switch, before turning on power.
• Turn power on and program any “SLAVE” evaporators as slave.
• Press and Hold both the “ENTER” and “CLEAR” buttons on Smart Controller.
• Hold both the “ENTER” and “CLEAR” buttons down until the LCD screen of the
Smart Controller displays “EEROM?”
• When “EEROM?” is displayed, release both buttons and press the “ENTER” button.
• The Smart Controller LCD screen will display “WAIT.”
After “WAIT” is displayed it may take up to 2 minutes for the initialization to be completed
and the normal LCD screen is displayed.
Whenever a system is
• CLOCK (+ -)This is used to set the time of day on the display.
• Depress the + button to move the clock forward
• Depress the - button to move the clock backward
• When in PROG Mode, these are used to step through values for setting superheat etc.
• COOLING: Depressing this button will start the system in the cooling cycle immediately
(The 4 minutes “Hold Off” is bypassed). This button will illuminate to indicate that the
Cooling function is “ON”. System operation will be as described under
REFRIGERATION MODE in the Beacon II installation manual.
Pressing the COOLING button while the system is cooling, and the button illuminated,
will pumpdown the system and turn it off.
• DEFROST: Depressing this button will force the system into defrost immediately (The
“Hold Off/Hold On” times are bypassed). This button will illuminate to indicate that the
Defrost function is “ON”. When in Defrost, pressing this button twice will end defrost.
30
Programming Beacon II Smart Controller
• MONITOR: Depressing the MONITOR button will display the setpoints shown on page 10.
If one Beacon II Smart Controller is controlling two or more independent systems, you
must press the
monitor.
• PROG REVIEW: This button allows stepping through each of the setpoints for initial
setup and to make changes.
If one Beacon II Smart Controller is controlling two or more independent systems, you
must press the
make program changes.
• CLEAR: Used to clear incorrect entries while programming or to return to the System
display when monitoring.
• TIME: Slide-bar is used to set the thermostat clock for Defrost times.
• SETPOINT: Slide-bar is used to change settings while programming.
• ENTER: To enter new settings into the program. NOTE: Settings are recorded in memory
even if power fails.
SELECTION BAR
SELECTION BAR
to display information on the system you want to
to display information on the system you want to
PROGRAMMING BEACON II SMART CONTROLLER
To make a change, press the PROG REVIEW3 button until the setpoint that needs
changing is displayed. The SETPOINT Slide-bar is then used to change to the desired new
setting. When the new desired setting is displayed, press the “ENTER” button. The new
setting is now programmed into the Beacon II Smart Controller memory.
Press the PROG REVIEW button and follow the steps below:
•
DEFTYP
This selection will automatically set the defaults for Air and Electric Defrost. Important:
This will set the refrigerant type to R22 for Air and R404A for Electric. You must change
to the refrigerant you are using in your application.
•
REFTYP
•
BOXTMP
then press “ENTER”)
•
SUPRHT
superheat temp., then press “ENTER”.
•
SMT DFT
then press “ENTER” (for version 1.2. When Smart Defrost is turned on, 8 defrost periods
per day will automatically be programmed. These will be at 12:00 am, 3:00 am, 6:00 am,
9:00 am, 12:00 pm, 3:00 pm, 6:00 pm, and 9:00 pm. Also, the defrost fail safe time will be
set to 60 minutes, and the defrost termination temperature will be set to 55°F. The user
can change these as needed for the application).
•
DEF ST
bar to select first defrost time, then press “ENTER”. Use + button to scroll to next defrost
period, dF 2, use “TIME” slide-bar to select second defrost time and press “ENTER”.
Repeat steps for each required defrost period). If defrost times are notprogrammed the system will use the defaults: Electric Defrost - four per day at
4:00 AM, 10:00 PM, 4:00 PM, 10:00 AM. Air Defrost - two per day at 9:00 AM, 9:00 PM.
– ELE or AIR: Select for Electric Defrost or Air Defrost then press “ENTER”.
– 22, 404, 507
– Box Temp: -30º F to 70º F. Use “SETPOINT” slide-bar to get desired temp.,
– Superheat: 4 to 20 º F. Use “SETPOINT” slide-bar to select desired
: Smart Defrost: On/Off. Use “SETPOINT” slide-bar to turn it ON or OFF,
- Defrost Start time: Up to 12 settings per day (For dF 1, use the “TIME” slide-
31
Monitoring with Beacon II Smart Controller
•
DEFSAF
elapsed, the defrost cycle will end, even if the programmed Defrost Termination
temperature was not achieved. Use “SETPOINT” slide-bar to select desired time,
•
DEFTMP
•
ALR HI
select desired temp., then press “ENTER”.
•
ALR LO
select desired temp., then press “ENTER”.
ALRMIN
•
indicated: 2 to 120 min. Use “SETPOINT” slide-bar to select desired time, then press
“ENTER”.
•
º F / º C
•
12/24H
“SETPOINT” slide-bar to select, then press “ENTER”.
•
TEST
cycle each output at 10 second intervals. Use “SETPOINT” slide-bar to select, then
press “ENTER”. Return to “OFF” and then press “ENTER” to end the test.
•
SERVIC
down and shut it off. The system will not restart until
OFF mode.
– Defrost Fail Safe Time: 10 to 200 minutes. When this time has
then press “ENTER”.
– Defrost Termination Temperature: 40 to 100º F. Use “SETPOINT”
slide-bar to select desired temp., then press “ENTER”.
– Alarm High Temperature. -40 to 90º F. Use “SETPOINT” slide-bar to
– Alarm Low Temperature -40 to 90º F. Use “SETPOINT” slide-bar to
– Alarm Time, in minutes. Condition must exceed before alarm is
– º F or º C. Use “SETPOINT” slide-bar to select then press “ENTER”.
– Clock: 12H is for standard time. 24H is for international time. Use
: OFF or ON: Puts all evaporators in TEST mode. Use with Caution. This will
– ON or OFF: When placed in the ON mode this will pump the system
SERVIC
is placed back in the
MONITORING with BEACON II SMART CONTROLLER
The Monitoring function can be used to monitor live system data. The information
displayed, such as superheat, is the actual superheat of the system as it is changing.
Press the MONITOR button and follow the steps below:
•
SUPRHT
•
EXVSET
+ button to check other evaporators if Master/slave)
•
SUCTMP
•
SSVTMP
•
SUCPRE
•
OD TMP
•
DEFTMP
•
DEFTIM
•
CMPCYC
•
CMPRUN
•
SPRTMP
– Superheat (use + button to check superheat of other evaporators, if
Master/slave)
- Expansion valve step setting (Stepper motor setting 0 to 255 steps: use
– Evaporator Suction temperature (Measured by the Suction sensor)
– Saturated Suction temperature at the Evaporator
– Evaporator Suction Pressure
– Actual outdoor ambient temperature (Measured at the condensing
unit)
– Evaporator coil temperature (Used to terminate defrost)
- Defrost Time: Length of last defrost
- Comp Cycles: No of Compressor Cycles since 12:00 midnight
- Comp run time (Measured since 12:00 midnight)
– Spare sensor temperature input
32
Locking Beacon II Smart Controller
•
VERSON
evaporators, if Master/slave)
•
VERSON
When multiple evaporators are connected as master/slave depressing the + or - button
will display information specific to each evaporator. Units in a master/slave connection
are numbered 1 through 4.
The first evaporator connected to the SMART CONTROLLER
Terminals is Evaporator # 1.
LOCKING BEACON II SMART CONTROLLER
BEACON II SMART CONTROLLER is lockable to prevent programmed settings to be
changed by unauthorized personnel. When the Controller is Locked, all the Buttons, except
for the Monitor and Prog Review Buttons, are disabled.
To LOCK the settings, do the following:
– Software Version: For each controller (use + button to check other
- Software Version: for Beacon II Smart Controller
MULTI-OUT
• Press “PROG REVIEW” button.
• Press and hold “MONITOR” button
• While holding “MONITOR” button, Press “ENTER” button.
• The LCD will display LOCK
This will prevent unauthorized persons from changing any settings.
To UNLOCK the Controller, repeat these steps.
ERROR CODES
•
BXSEN -
•
DFSEN -
•
STSEN -
•
SPSEN -
•
ODSEN -
•
SUPLO -
•
SHTDN -
The error code will flash alternately with the normal display information. When the error
condition is corrected, the error code will no longer be displayed and only the normal
information will be displayed.
Room temperature sensor shorted, open or not installed
Defrost temperature sensor shorted, open or not installed
Suction Temperature sensor shorted, open or not installed
Suction pressure transducer shorted, open or not installed
Outdoor temperature sensor shorted
Superheat too low
Compressor shutdown (High or low refrigerant pressure or low oil pressure)
WIRING ERROR
If the Beacon II Smart Controller LCD displays
error in the communication wiring or that the wiring is broken or disconnected.
+COMM+
, this indicates that there is an
The communication wiring is the MULTI IN and MULTI OUT connections. Check to make
sure the OUT is connected to IN. Never connect OUT to OUT or IN to IN.
33
Alarm Codes
ALARM CODES
•
*BOXHI
•
*BOXLO
•
*STRUP
•
*INFLT
Power failure
•
When an ALARM condition occurs, the BEACON II SMART CONTROLLER will display
“CALL FOR SERVICE”, the ALARM code, the SYSTEM Number and will sound an internal
buzzer.
The alarm code will flash alternately with the normal display information. When the alarm
condition is corrected, the alarm code will no longer be displayed and only the normal
information will be displayed.
The system will pumpdown and cycle off and will
not restart until the fault is cleared for the following conditions:
: Box temperature too high
: Box temperature too low
:System Start-up failureCompressor pumps down and tries to restart
after 4 minutes.
: Input fault(Box Temp., Suction Temp., Pressure
Transducer open or not installed)
Suction sensor shorted, open or not installed
Room temperature sensor shorted, open or not installed
Pressure Transducer open or not installed
The system will pumpdown, cycle off and try to restartfor three consecutive times. Each
try will be after the 4 minutes “Hold Off” period, for the following fault conditions.
Oil pressure
High pressure or low pressure cutout
After the fourth try, the Alarm contacts will be closed and an alarm message displayed on
the LCD screen. To clear this condition, the system should be cycled through the “Service”
mode after correction is complete.
On Multiple systems the Alarm contacts on each of the Master Evaporator will announce
Alarms for that system.
ALARM BUZZER
The ALARM buzzer will sound when an Alarm condition occurs. This buzzer will turn off
when the Alarm condition is cleared. The buzzer can also be silenced at any time by
pressing the “CLEAR” button.
34
Smart Defrost
DATA LOGGING
Beacon II Smart Controller logs system data in its memory every 15 minutes. The length of
time it records data is dependent on how many systems are being controlled by the Beacon
II Smart Controller. It keeps writing data to its memory until the memory is full. When the
memory is full it will overwrite its oldest stored data in memory with newly recorded data.
Data recorded:System Mode, Box Temperature, AUX Temperature, Superheat,
Suction Pressure and the Number of Compressor cycles since
midnight.
Errors and Alarms recorded: Date, Time, System #, Unit #, Error type, Alarm type, Error
duration and Alarm duration
Length of data recorded:One System = 30 days
Two Independent Systems = 15 days
Three Independent Systems = 10 days
Four Independent Systems =7 days
Recording intervals:Every 15 minutes
All recorded data will have a date/time stamp.
On multiple evaporator systems, the data recorded is from the master evaporator only. This
data is available via connection to a PC through the Smart Controller’s RS232 serial port.
The data can be viewed on a PC using our Windows based SMART II software and can be
imported into an Excel spreadsheet.
Real-time data can also be recorded and stored on a Desktop PC while the PC is
connected to the Smart Controller. The PC will continuously request information from the
Smart Controller regarding system operation and setup and record this data every minute,
in an Excel Spreadsheet. This information is stored to the PC hard drive, which depending
on the size of the hard drive, would allows for many days of recording. This data may also
be periodically saved on a disk by the user.
The SMART II software is sold separately from the Beacon II Smart Controller.
SMART DEFROST
The Beacon II Smart Controller continuously monitors the system performance to
determine the need for defrost. It uses a variety of data such as the outdoor ambient and
box temperature in it’s decision making process.
Activating Smart Defrost:
You must program multiple defrost times into the Smart Controller to provide
flexibility for the system to defrost the coil properly. Smart Defrost will only allow the
system to defrost at a programmed defrost time. The system will not defrost in
between programmed defrost times. Hence, we recommend that a minimum of
35
PC and Modem Access
8 defrost periods be programmed when Smart Defrost is turned on. The system
will not defrost eight times per day but with this many defrost periods it will have
better options to keep the coil clear.
After programming the minimum 8 defrost periods, all that’s needed to activate
Smart Defrost is to press the
button until “
SMT DFT
” is displayed.
“PROG REVIEW”
Move the “
return to the main screen.
For version 1.2., when Smart Defrost is turned on, 8 defrost periods per day will
automatically be programmed. These will be at 12:00 am, 3:00 am, 6:00 am, 9:00
am, 12:00 pm, 3:00 pm, 6:00 pm, and 9:00 pm. Also, the defrost fail safe time will be
set to 60 minutes, and the defrost termination temperature will be set to 55°F. The
user can change these as needed for the application.
Deactivating Smart Defrost:
To turn Smart Defrost off move the “
“
ENTER
SETPOINT
”. Press “
” slide-bar to “ON” then press “
SETPOINT
CLEAR
” to return to the main screen.
ENTER
” slid-bar to “
”. Press “
OFF
” then press
CLEAR
” to
PC & MODEM ACCESS
For access to the system from a PC directly or via a modem, the SMART II Software must
be purchased and installed on your PC. With PC access, ALL system settings can be
monitored, changed or logged from a remote location. The stored data can be viewed in an
Excel spreadsheet.
36
Operational Checkout
After the system has been charged and has operated for at least 2 hours at normal operating conditions
without any indication of malfunction, it should be allowed to operate overnight on automatic controls. Then a
thorough recheck of the entire system operation should be made as follows:
(a) Check compressor discharge and suction pressures. If not within system design limits, determine why
and take corrective action.
(b) Check liquid line sight glass and expansion valve operation. If there are indications that more
refrigerant is required, leak test all connections and system components and repair any leaks before
adding refrigerant.
(c) Using suitable instruments, carefully check line voltage and amperage at the compressor terminals.
Voltage must be within 10% of that indicated on the condensing unit nameplate. If high or low voltage
is indicated, notify the power company. If amperage draw is excessive, immediately determine the
cause and take corrective action. On 3 phase motor compressors, check to see that a balanced load
is drawn by each phase.
(d) The maximum approved settings for high pressure controls on Bohn/Heatcraft air cooled condensing
equipment is 400 psig. On air cooled systems, check as follows:
• Disconnect the fan motors or block the condenser inlet air.
• Watch high pressure gauge for cutout point.
• Recheck all safety & operating controls for proper operation and adjust if necessary.
(e) Check head pressure controls for pressure setting.
(f)Check crankcase heater operation if used.
(g) Install instruction card and control system diagram for use of building manager or owner.
Check-Out & Start-Up
After the installation has been completed, the following points should be covered before the system is placed
in operation:
(a) Check all electrical and refrigerant connections. Be sure they are all correct and tight.
(b) Check voltage taps on transformer. The transformer is shipped wired to 240 voltage tap/connection. If your
supply voltage is 208 volt systems, change to 208 voltage tap.
(b) Check setting of time delay relay for low pressure switch in condensing unit. It should be set at one minute
(the second marker).
(c) Check high and low pressure controls, pressure regulating valves, oil pressure safety controls, and all
other safety controls and adjust them, if necessary.
(d) On freezers only, check the low pressure switch setting. It must be set to 0 PSIG cut out, 10 PSIG cut in,
to allow start and operation, especially in cold ambients.
(e) Liquid line should always be insulated.
(f) Wiring diagrams, instruction bulletins, etc. attached to the condensing units should be read and filed for
future reference.
(g) All fan motors on air cooled condensers, evaporators, etc. should be checked for proper rotation. Fan
motor mounts should be carefully checked for tightness and proper alignment.
(h) Observe system pressures during charging and initial operation. Do not add oil while the system is short of
refrigerant unless oil level is dangerously low.
(i) Continue charging until system has sufficient refrigerant for proper operation. Do not overcharge.
Remember that bubbles in a sight glass may be caused by a restriction as well as a shortage of refrigerant.
(j) Do not leave unit unattended until the system has reached normal operating conditions and the oil charge
has been properly adjusted to maintain the oil level at the center of the sight glass.
(k) At initial start-up, the system may cycle off at 2 minutes and display a low superheat error, then restart
itself. This cycle may be repeated a few times. Do not shut the system off. Let the system run, as it may take
a few cycles for the electric expansion valve to attain the correct setting for the desired superheat.
CAUTION: Extreme care must be taken in starting compressors for the first time after system
charging. At this time, all of the oil and most of the refrigerant might be in the compressor creating a
condition which could cause compressor damage due to slugging. Activating the crankcase heater
for 24 hours prior to start-up is recommended. If no crankcase heater is present, then directing a
500 watt heat lamp or other safe heat source on the lower shell of the compressor for approximately
thirty minutes will be beneficial in eliminating this condition which might never reoccur.
37
Preventive Maintenance
Routine preventive maintenance of any mechanical equipment is critical to its long term
reliability. During even normal operation all equipment will experience some deterioration
during its lifetime caused by wear and environmental influences. For that reason, regularly
scheduled maintenance of your refrigeration equipment is required in order to keep it
operating to its maximum efficiency while avoiding potentially costly repairs of a premature
failure due to equipment neglect. The following is Bohn/Heatcraft’s minimum
recommendations for regularly scheduled preventive maintenance of your McDonald’s
refrigeration system. Qualified and licensed refrigeration companies only should perform all
preventive and corrective maintenance on refrigeration equipment. While we cannot
guarantee that close adherence to these recommendations will eliminate all equipment
problems, it will greatly reduce the potential for mechanical and electrical failures thus
providing increased reliability.
38
Preventive Maintenance
CONDENSING UNIT
QUARTERLYSEMI-ANNUALLYDATEDATEDATEDATE
Visually inspect unit✔✔
1
Look for signs of oil stains on interconnection piping and condenser coil. Pay close attention to
areas around solder joints, building penetrations and pipe clamps. Check any suspect areas with an
electronic leak detector
✔✔
2
Check condition of moisture indicator in the sight glass of all systems. Look for indication of moisture
or flash gas.
✔✔
3 Check condition of condenser. Look for accumulation of dirt and debris. Clean as required.✔✔
4 Check for unusual noise or vibration. Take corrective action as required.✔✔
5
Inspect wiring for signs of wear or discoloration
✔✔
Clean condenser coil and blades
✔
1
Periodic cleaning can be accomplished by using a brush, pressurized water and a commercially
available foam coil cleaner. If foam cleaner is used, it should not be an acid based cleaner. Follow
label directions for appropriate use
✔
2 Rinse until no residue remains✔
Check operation of condenser fans✔
1
Check that each fan rotates freely and quietly. Replace any fan motor that does not rotate smoothly
or makes excessive noise.
✔
2 Check all fan blade set screws and tighten as required✔
3
Check all fan blades for signs of cracks, wear or stress. Pay close attention to the hub and spider.
Replace blades as required.
✔
4 Verify that all motors are mounted securely✔
Inspect electrical wiring and components✔
1 Verify that all electrical and ground connections are secure, tighten as required.✔
2
Check condition of compressor, defrost heater and condenser fan contactors. Look for
discoloration and pitting. Replace as required
✔
3 Check operation and calibration of all timers, relays pressure controls and safety controls✔
4
Clean electrical cabinet. Look for signs of moisture, dirt, debris, insects and wildlife. Take corrective
action as required
✔
5
Verify operation of crankcase heaters by measuring amp draw
✔
Check refrigeration cycle for all systems✔
1 Check suction and discharge temperatures & pressures. If abnormal take appropriate action✔
2 Check operation of liquid injection on freezer system✔
3 Check pressure drop across all filters and driers. Replace as required.✔
4 Verify that superheat at the compressor conforms to specification. (30F to 45F)✔
Inspect suction accumulators✔
1 Inspect all accumulators for signs of leaks and corrosion.✔
2 Pay close attention to all copper to steel brazed connections✔
3 Wire brush all corroded areas and peeling paint.✔
4 Apply an anticorrosion primer and paint as required. ✔
5 Re-attach insulation and replace any damaged sections
39
Preventive Maintenance
UNIT COOLERS
QUARTERLYSEMI-ANNUALLYDATEDATEDATEDATE
Visually inspect unit✔✔
1 Look for signs of corrosion on fins, cabinet, copper tubing and solder joints✔✔
2
Look for excessive or unusual vibration for fan blades or sheet metal panels when in operation.
Identify fan cell(s) causing vibration and check motor and blade carefully.
✔✔
3
Look for oil stains on headers, return bends, and coil fins. Check any suspect areas with an
electronic leak detector.
✔✔
4
Check drain pan to insure that drain is clear of debris, obstructions or ice build-up and is free
draining.
✔✔
5
Insure that there is sufficient clearance free of obstructions around unit coolers to allow proper
airflow through coils
✔✔
6 Verify Box setpoint temperature is being met✔✔
Clean Evaporator coil and blades✔
1
Periodic cleaning can be accomplished by using a brush, pressurized water or a commercially
available Evaporator Coil Cleaner or mild detergent.
Never
use an acid based cleaner. Always
follow label directions for appropriate use. Be sure the product you use is approved for use in food
service applications.
✔
2 Flush and rinse coil until no residue remains.✔
3 Pay close attention to drain pan, drain line and trap.
Check the operation of all fans and ensure airflow is unobstructed✔
1
Check that each fan rotates freely and quietly. Replace any fan motor that does not rotate
smoothly or makes an unusual noise.
✔
2 Check all fan set screws and tighten if needed.✔
3
Check all fan blades for signs of stress or wear. Replace any blades that are worn, cracked or bent.✔
4
Verify that all fan motors are securely fastened.
✔
Inspect electrical wiring and components✔
1
Visually inspect all wiring for wear, kinks, bare areas and discoloration. Replace any wiring found to
be damaged
✔
2 Verify that all electrical and ground connections are secure, tighten if necessary.✔
3 Check operation/calibration of all fan cycle and defrost controls when used.✔
4 Look for abnormal accumulation of ice patterns and adjust defrost cycles accordingly✔
5 Compare actual defrost heater amp draw against unit data plate. (freezer only)✔
6
Visually inspect heaters to ensure even surface contact with the coil. If heaters have creeped
decrease defrost termination temperature and be sure you have even coil frost patterns. (freezer
only)
✔
7 Check low voltage wiring at Beacon board for broken wires✔
8 Check voltage at Beacon board. Should be between 18 to 30 Volts✔
Check Beacon sensors✔
1 Press MONITOR button to display sensor reading for Box Temp., Suction Temp. and Defrost Temp.✔
2 Use an accurate Thermometer to measure temperatures at the same locations as the sensors.✔
3 LED readings should match measured values, within 3 °F at same locations as sensors.✔
Check Beacon Pressure Transducer✔
1 Press MONITOR button to display Suction Pressure reading at the Evaporator✔
2 Use an accurate Gauge Set to measure Evaporator Pressure.✔
3 Measured suction pressure should match LED displayed value within 2 Psig.✔
Check Drain Line Heater✔
1 Check heater amps✔
2
Check that heater is wrapped around entire length of drain line inside the walk-in freezer
✔
Refrigeration Cycle✔
1 Check unit cooler superheat and compare reading for your specific application✔
2 Visually inspect coil for even refrigerant distribution✔
40
Diagnostics
Beacon II Troubleshooting Guide
PROBLEMStep ACTION ITEMIF OKIF NOT OK
1.Check Primary Power Supply Disconnect1. Check fuses and circuit breakers
LED is not lit.3.Check Transformer Secondary Output Voltsnext step3. Replace if necessary
LED shows
compressor will not run.3.Check Compressor Contactor Coil Voltagenext step3. Check internal condensing unit wiring
ERROR CODES:
E1
E2
E3
E4
E5 Outdoor SensorCheck Sensor, wiring and Board ConnectionReplace or remove
E6
During Cooling4.Check Electric Expansion Valve ClosureGo to4. Pumpdown system see if LPS opens or if it
(0°F for 2 minutes)next step times out (EEV is bad or LPS is set
Coo
, but(24 Volts across “COMP” and “C” at board)Go to primary) and wiring of 208V power taps.
Room SensorCheck Sensor and Board ConnectionReplace as needed
Defrost SensorCheck Sensor and Board ConnectionReplace as needed
Suction SensorCheck Sensor and Board ConnectionReplace as needed
Suction TransducerCheck Transducer and Board ConnectionReplace as needed
Low Superheat3.Check Control Board step position from board LED3. Replace board if EEV steps not at 2.
2.Check Voltage to Evaporator TransformerGo to2. Check field wiring for breaks
4.Check Voltage at Control Board (24V and C)4. Check factory wiring and connections
5.Replace Control Board
1.Check Compressor internal overloads1. Wait for reset
2.Check Control Power to Condensing Unit2. Check transformer voltage (secondary and
4.Check Compressor Contactor “pulled in”4. Replace as needed
1.Check Refrigerant Type1. Compare board setpoint and refrigerant
2.Check coil for ice2. Defrost coil and check defrost cycle
settings/setpoints, defrost sensor and
heater amps.
incorrectly, if times out) – See Pumpdown.
5.Compressor Not Operating5. Check overloads and contactor.
6.Check Suction Temperature Sensor6. Compare board sensor reading against
actual suction line temperature.
7.Check Suction Pressure Transducer7. Compare pressure reading against gauges.
41
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEMStep ACTION ITEMIF OKIF NOT OK
1.Check wiring connection to the board• Correct field wiring to the board
2.Low Pressure Safety (LPS) Tripped:
• Check for correct refrigerant type• Change setpoint to match refrigerant
• Check refrigerant charge• Add more refrigerant to proper charge
• Check LPS setting• Correct LPS setting
• Check LPS wiring• Correct LSP wiring
• Check EEV operation (stuck?)• Clean or replace EEV
• Check coil for icing• Defrost coil (see
• Check for correct superheat reading• Check/replace sensor or transducer
• Check for correct nozzle selection• Replace distributor nozzle
• Check for clogged EEV inlet screen• Replace EEV
• Check line sizing• Correct line sizing
• Check LPS time delay relay setting• Reset to 1 minute
• Check operation of LPS• Replace Low Pressure Safety Switch
3.High Pressure Safety (HPS) Tripped:
• Check for system overcharge• Reclaim/recover excess charge
• Check for non-condensables• Remove all non-condensables
• Check condenser fan motor and blade• Repair or replace motor and/or blade
• Check for dirty condenser coil• Clean condenser coil
• Check head pressure controls• Adjust or replace faulty controls
• Check fan cycling controls• Adjust or replace faulty controls
• Check liquid line sizing• Correct line sizing
• Check for liquid line restrictions• Repair line or remove restrictions
• Check operation of HPS• Replace HPS if necessary
E6
, step 2)
E7
Compressor4.Oil Pressure Safety (OPS) Tripped:
Shutdown• Check oil level in compressor• Add oil to crankcase to minimum level
8.Check compressor relay on board• Replace board if relay is faulty
E6
42
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEMStep ACTION ITEMIF OKIF NOT OK
E9
Multi-out to Multi-in1.Check for 24 volts power to the board1. If no voltage, see “LED is not lit” above
Communication Wiring for low voltage, see “88888 LED display”
(only shows after initial 2.Check for crossed communication wiringGo to
successful connection)(multi-out not wired to multi-in terminals)next step
3.Check for broken communication wiring
Break in the designated
lines will cause errors
as follows:
[With SMART
Controller II]
Line #SMARTCooler or Freezer
1+COMM+E9
2+COMM+no error
SMART II
in out
Cooler or Freezer
in out
1
2
PROBLEMStep ACTION ITEMIF OKIF NOT OK
88888 LED display1.Check Voltage to Evaporator Transformer1. Check field wiring for breaks or shorts
(power is below 18V and2.Check Transformer Secondary Output VoltsGo to2. Replace if necessary
appears at initial power)3.Check Voltage at Control Board (24 and C)next step3. Check factory wiring and connections
LED displays
then
displayed errorsboard to condensing unit terminal connection compressor contactor.
dLy
oFF
with no2.Check for short in field wiring from “comp” onnext step.2. Check internal factory wiring to
4.Check Voltage at SMART Controller II4. Check field wiring from board
1.Check for low voltage1. Check all steps for “88888 LED display”
Go to Voltage could drop off too fast to show.
3.Replace defective contactor (holding coil)
43
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEMStep ACTION ITEMIF OKIF NOT OK
1.Check system operation: Is it running?1. Check power to condensing unit
2.Check system charge2. Add or remove refrigerant to proper charge
3.Check for proper operating superheat3. Check EEV operation
4.Check for high superheat and EEV wide open4. Check EEV inlet screen and restrictions
Cannot get to box6.Compare equipment capacity with requirementsGo to6. Add or replace with more/larger equipment
temperature7.Check box temperature setpointnext step7. Correct setpoint to proper value
Service Mode*ONLY Master board on multiple evaporator systems Mode, all must be “open” to terminate the mode.)
3.Connection between “Ser” and “C” on board*3. Open connection between “Ser” and “C”
(all are wired in parallel; all will activate mode) (Note: If multiple switches were placed in Service
(with Beacon II Smart Controller) (with Beacon II Smart Controller)
1.Use Remote Service Switch in condensing unit1. Must terminate using same switch
2.Connection between “Ser” and “C” on board*2. Open connection between “Ser” and “C”
3.From program menu of Beacon II Smart Controller,3. From program menu of Beacon II Smart
Change SERVICE setpoint to “On”. Change SERVICE setpoint to “Off”
[all are wired in parallel; any/all will activate mode.] [Note: If multiple switches were placed in Service
*ONLY Master board on multiple evaporator systems Mode, all must be “open” to terminate the mode.)
Check position of Service Mode switches
Check compressor overloads and contactor
Check control board EEV signal
Check suction sensor and transducer
Check liquid line sizing
Check head pressure controls
Check integrity of compressor operation
(impaired, worn or damaged components)
switch or make corrective adjustments.
settings/setpoints and defrost sensor
(frequency and termination of defrosts)
44
Parts
Table 7. Condensing Unit Parts List
CONDENSING UNITS
PART DESCRIPTION
Compressor - FreezerZF09K4EZF13K4EZF15K4EZF13K4EZF15K4E
Compressor - CoolerRS64C1ECS10K6ECS10K6ERS43C1ERS43C1E
Disconnect Fuses2251011022510112225101132251011122510113
Start Relay - Cooler100764710076601007647
Start Capacitor - Cooler707695670769577076959
Run Capacitor - Cooler707695170758587076950
Compr Contactor - Cooler2254304
Compr Contactor - Freezer2255845
Condenser Fan Motor25399101
Condenser Fan Blade22999901
Fan Guard23104401
Head Pressure Valve:
Cooler29317401
Freezer2931730329317304293173042931730429317303
High Pressure Control28903201
Lo Pressure Control - Freezer2891402
Lo Pressure Control - Cooler2890099
Lo Pressure Time Delay22536801
Crankcase Htr - Freezer24701301
Fan Cycling Thermostat2890019
Ambient Temperature Sensor*88904902
Evaporator Fuses - Freezer22510002
Evaporator Fuses - Cooler22510001
Fan Relay (R3, R4 - 240v)22505201
Fan Relay (R1, R2 - 24v)22521901
Terminal Block2251423
MAC3X
MAC7XMAC8X
MAC4XMAC5X
Table 8. Evaporator Parts List
PART DESCRIPTIONPART NUMBEREVAPORATORS
Fan Motor25308601ALL
Fan Blade5140CALL
Fan Guard37000701ALL
29320007LET160BHB2N6MK
Expansion Valve Controller22515201ALL
Beacon II Control Board28910101ALL
Temperature Sensor Kit*89904902ALL
Transformer (240/24 - 40 VA)22529602ALL
Pressure Transducer28911201ALL
Pressure Transducer Harness22515101ALL
*Only the sensor with white leads is shipped as a Service Replacement Part.
45
Beacon II Smart Controller
Table 9. Beacon II Smart Controller Parts List
PART DESCRIPTIONNUMBER
Beacon II Smart Controller89704301
*Smart Controller Software Package89704101
*Smart Controller Software Package is sold separately.
Table 10. Beacon II Operational Limits
OPERATIONAL LIMITS
Voltage18 VAC to 30 VAC
Controlling Box Temp. Range-30°F to 70°F
Box Temp. Dead-Band+/-1°F
Cold Ambient LimitsStart and operate to -20°F
PART
46
Startup Checklist
Date of Start-up
Store Address
CONDENSING UNIT
MODEL #
SERIAL #
COOLER UNIT
MODEL #
SERIAL #
FREEZER UNIT
MODEL #
SERIAL #
ELECTRICAL
• Check Primary Supply voltage.
If 208 V, change transformer wiring in the
Cooler and Freezer to the 208 V tap
YES
• Check Compressor Amps for COOLER and
FREEZER compressors. Should match
nameplate.
YESNO
PIPING
• Is suction line trapped at the Cooler?
YESNO
• Is suction line trapped at the Freezer?
YESNO
DRAIN LINES
• Are drain lines sloped properly?
YESNO
• Is drain line trapped outside the Cooler?
YESNO
• Is drain line trapped outside the Freezer?
YESNO
• Is heat tape wrapped along entire length of
the drain line in the Freezer?
YESNO
• Is heat tape plugged in and heating the drain
line?
YESNO
INSULATION
• Are Liquid lines fully insulated?
YESNO
• Are Suction lines fully insulated?
YESNO
SETTINGS
• Check Beacon II board settings for the
following:
FREEZER
Refrigerant TypeR404A
Box Setpoint Temp.-10°F.
Superheat8°F.
No. of Defrost/Day4
Defrost End Temp.65°F.
COOLER
Refrigerant TypeR404A
Box Setpoint Temp.35°F.
Superheat8°F.
No. of Defrost/Day2
Defrost End Temp.50°F.
SYSTEM CHECKS
• Check Compressor Superheat for the
COOLER (Should be between 20°F. & 30°F.)
YESNO
• Check Compressor Superheat for the
FREEZER (Should be between 20°F. & 30°F.)
YESNO
• Force unit into a Defrost Check heater amps.
Should match nameplate amps.
YESNO
• Check LPS Time Delay Relays. Should be
set at 1 minute for both the COOLER and
FREEZER.
YESNO
• Check Low Pressure Switch on FREEZER. Should
be set at 0 psig Cut-out/10 psig Cut-in.
YESNO
• Did FREEZER and COOLER cycle off on LPS at
Set-point Temperature?
YESNO
• Is the sight glass free of bubbles?
YESNO
• Are the COOLER and FREEZER fans at proper
speeds?
YESNO
• Check system for refrigerant leaks. Are there any
leaks on the COOLER, FREEZER, CONDENSING
UNIT or INTERCONNECTING PIPING?
YESNO
• Check system piping for unusual vibration or noise.
Is there any unusual vibration or noise on the
COOLER, FREEZER, CONDENSING UNIT or
INTERCONNECTING PIPING?
YESNO
• Start the FREEZER only. Does the compressor
start and evaporator fans run for this FREEZER?