Bohn H-IM-65B Installation Manual

Air Cooled
Condenser
Installation
Bulletin No. H-IM-65B December 1999 Part Number 90800701
Replaces H-IM-65A, August 1996
Angle Leg Models
Channel Legs Models
Air-Cooled
Condensers
21 - 212 Tons
Installation and
Maintenance Data
Table of Contents
Sound Vibration . . . . . . . . . . . . . . . . . . . . . . . . 2
Rigging Instructions . . . . . . . . . . . . . . . . . . . . . 3
Space and Location Requirements . . . . . . . . . 4
Typical Arrangements
Installation, Refrigerant Piping . . . . . . . . . . . . . 5
Line Sizing Discharge Lines
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Wiring Diagrams . . . . . . . . . .. . . . . . . 7-8
Start-Up Discharge Gas Pulsation Operation Winter Operation Head Pressure Control
Fan Cycling . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fan Cycling Head Pressure Controls Flooding Head Pressure Controls
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . 10
Minimum Ambient for Fan Cycling Mechanical Fan Cycling Thermostat Settings. . 11 Electronic Fan Cycling Thermostat Settings
Pressure Chart . . . . . . . . . . . . . . . . . . . . . . . . . 12
Additional Refrigerant Charges Maintenance
Cleaning Instructions . . . . . . . . . . . . . . . . . . . . 13
In-Warranty Return Material Procedure
Replacement Parts . . . . . . . .. . . . . . . . . . . . . 14
Installation Check List . . . . . . . . . . . . . . . . . 15
1
Inspection
Responsibility should be assigned to a dependable individual at the job site to receive material. Each shipment should be carefully checked against the bill of lading. The shipping receipt should not be signed until all items listed on the bill of lading have been accounted for.
Check carefully for concealed damage. Any shortage or damages should be reported to the delivering carrier.
Damaged material becomes the delivering carrier's responsibility, and should not be returned to the manufacturer unless prior approval is given to do so. When uncrating, care should be taken to prevent damage. Heavy equipment should be left on units shipping base until it has been moved to the nal location.
System Warranty
This equipment is designed to operate properly and produce rated capacity when installed in accordance with accepted industry standards. Failure to meet the following conditions may result in voiding of the system warranty:
1. System piping must be installed following industry standards for good piping practices.
2. Inert gas must be charged into piping during welding.
3. System must be thoroughly leak checked and evacuated before initial charging. High vacuum gauge capable of reading microns is mandatory. Dial indicating pressure gauges are not acceptable.
4. Power supply to system must meet the following conditions:
a. Voltage for 208/230 motors not less than 195 volts or more than 253 volts.
b. All other voltages must not exceed +/- 10% of nameplate ratings.
c. Phase imbalance not to exceed 2%.
5. All controls and safety switch circuits properly connected per wiring diagram.
6. Factory installed wiring must not be changed without written factory approval.
Installation
Note: Installation and maintenance to be performed onlybyqualiedpersonnelwhoarefamiliarwith local codes and regulations, and experienced withthistypeofequipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard.
Avoidcontactwiththem.
Unit Location
Units are designed for outdoor application and may be mounted on a roof or concrete slab (ground level installation). Roof mounted units should be installed level on steel channels or an I-beam frame to support the unit above the roof. Use of vibration pads or isolators is recommended. The roof must be strong enough to support the weight of the unit. Concrete slabs used for unit mounting should be installed level and be properly supported to prevent settling. A one­piece concrete slab with footings extending below the frost line is recommended.
The condenser should be located far enough away from any
wall or other obstruction to provide sufcient clearance for air
entrance. Do not attach ductwork to the coil inlet or fan outlet. Care should be taken to avoid air recirculation conditions that can be caused by sight screening, walls, etc. Also keep unit fan discharge away from any building air intakes. See page 4 for space and location requirements.
Sound Vibration
Units should be installed away from occupied spaces and above or outside of utility areas, corridors and auxiliary spaces to reduce the transmission of sound and vibration to
occupied spaces. The refrigerant piping should be exible
enough to prevent the transmission of noise and vibration from the unit into the building. If the refrigerant lines are to be suspended from the structure of the building, isolation hangers should be
used to prevent the transmission of vibration. Where piping
passes through a wall, it is advisable to pack berglass and
sealing compound around the lines to minimize vibration and
retain exibility in the lines.
The unit needs to be secured in its nal location. Holes are
provided in the base runner for this purpose.
Warning: This equipment may contain a substance whichharmsthepublichealthand environment by destroying ozone in the upper atmosphere. Venting of certain refrigerants to the atmosphere is illegal. Refrigerant recovery devices must be used wheninstallingorservicingthisproduct. Consult your local codes for requirements in your location.
Warning: There may be more than one source of electrical current in this unit. Do not servicebeforedisconnectingallpower supplies.
2
© 2004, Heatcraft Refrigeration Products LLC
Drawing1.RiggingInstructions
3
Space and Location Requirements
The most important consideration which must be taken into account when deciding upon the location of air-cooled equipment is the provision for a supply of ambient air to the condenser, and removal of heated air from the condenser area. Where this essential requirement is not adhered to, it will result in higher head pressures, which cause poor operation and possible eventual failure of equipment. Units must not be located in the vicinity of steam, hot air or fume exhausts.
Walls or Obstructions
The unit should be located so that air may circulate freely and
not be recirculated. For proper air ow and access all sides
of the unit should be a minimum of “W” away from any wall or obstruction. It is preferred that this distance be increased whenever possible. Care should be taken to see that ample room is left for maintenance work through access doors and panels. Overhead obstructions are not permitted. When the unit is in an area where it is enclosed by three walls the unit must be installed as indicated for units in a pit.
Another consideration which must be taken is that the unit should be mounted away from noise sensitive spaces and must have adequate support to avoid vibration and noise transmission into the building. Units should be mounted over corridors, utility areas, rest rooms and other auxiliary areas where high levels of sound are not an important factor. Sound and structural consultants should be retained for recommendations.
Multiple Units
For units placed side by side, the minimum distance between units is the width of the largest unit. If units are placed end to end, the minimum distance between units is 4 feet.
Units in Pits
The top of the unit should be level with the top of the pit, and side distance increased to “2W”.
If the top of the unit is not level with the top of pit, discharge cones or stacks must be used to raise discharge air to the top of the pit. This is a minimum requirement.
Decorative Fences
Fences must have 50% free area, with 1 foot undercut, a “W” minimum clearance, and must not exceed the top of unit. If these requirements are not met, unit must be installed as indicated for “Units in pits”.
* “W” = Total width of the condenser.
4
Typical Arrangements
Notes:
Figure 1 illustrates a typical piping arrangement involving a remote condenser located at a higher elevation, as commonly encountered when the condenser is on a roof and the compressor and receiver are on grade level or in a basement equipment room.
In this case, the design of the discharge line is very critical. If properly sized for full load condition, the gas velocity might be too low at reduced loads to carry oil up through the discharge line and condenser coil. Reducing the discharge
line size would increase the gas velocity sufciently at
reduced load conditions; however, when operating at full load, the line would be greatly undersized, and thereby create an excessive refrigerant pressure drop. This condition can be overcome in one of two following ways:
1.The discharge line may be properly sized for the desired pressure drop at full load conditions and an oil separator installed at the bottom of the trap in the discharge line from the compressor.
2. A double riser discharge line may be used as shown in Figure 2. Line “A” should be sized to carry the oil at mini­ mum load conditions and the line “B” should be sized so that at the full load conditions both lines would have suf­ cient ow velocity to carry the oil to the condenser.
For more complete information, refer to the ASHRAE Handbook on Systems.
Figure 1
1. All oil traps are to be as short in radius as possible. Common practice is to fabricate the trap using three 90 degrees ells.
2. Pressure relief valves are recommended at the condenser for protection of the coil.
3. A drain line check valve is recommended for applications where the condenser may be at a lower temperature than the receiver.
Installation, Refrigerant Piping
Install piping according to standard accepted refrigeration practice. The following recommendations should be adhered to:
1. See Tables 1 and 2 for discharge and liquid drain line sizes for remote condenser connections.
2. Use only refrigeration grade copper tubing.
3. Soft solder joints are not acceptable.
4. Put dry nitrogen through lines while brazing.
5. Do not leave dehydrated piping or components open to the atmosphere any longer than is absolutely necessary.
Figure 2
5
Loading...
+ 11 hidden pages