Bohn BVF050 User Manual

7160.1
March 2000
Replaces 7170
BELT DRIVE AIR COOLED
BELT DRIVE AIR COOLED
CONDENSERS
CONDENSERS
Model BVF
45-228 Nominal Tons
Vertical Discharge
DESIGN FEATURES
• Wide range of sizes, all with quiet, efficient 4 pole moters
• Multicirculating at no extra cost
• Control paner with disconnect interlock
• Zinc plated, iridite dipped corrosion proof fan guards
• Access paners on each fan section for ease of maintenance
• Each fan has pillow block ball bearings with lubrica tion fittings
AVAILABLE OPTIONS
• Connection manifold kits
• Limitizer® head pressure control
• Fan cycling control packages
• Optional coils, including Heresite® and Bohnguard™ coatings, all copper coil
• Extended lube lines to fan bearings
• Sealtite wiring
SPECIFICATIONS - BELT DRIVE UNITS
Model @ 30º TD Circuits Charge Motor Full Load Amps
BVF R-22* Available R-22‡ HP 208 230 460
045 693 (2) 19 32 1.5 11 10 5 050 776 (2) 19 32 2 13.4 12 6 054 822 (2) 19 32 2 13.4 12 6 057 868 (2) 19 32 5 29.2 26.4 13.2 059 899 (2) 26 42.8 2 13.4 12 6 062 944 (2) 19 32 5 29.2 26.4 13.2 065 990 (2) 19 32 5 29.2 26.4 13.2 069 1055 (2) 19 48.1 1.5 16.5 15 7.5 073 1112 (2) 26 42.8 5 29.2 26.4 13.2 081 1234 (2) 19 48.1 2 20.1 18 9 086 1309 (2) 19 48.1 5 43.8 39.6 19.8 088 1340 (2) 26 63.5 2 20.1 18 9 096 1462 (2) 26 63.5 3 27.9 25.2 12.6 097 1477 (2) 19 48.1 5 43.8 39.6 19.8 101 1538 (2) 32 78.4 3 27.9 25.2 12.6 106 1614 (2) 26 63.5 5 43.8 39.6 19.8
111 1697 (2) 26 84.5 2 26.8 24 12 114 1736 (2) 32 78.4 5 43.8 39.6 19.8 121 1849 (2) 26 84.5 3 37.2 33.6 16.8 136 2071 (2) 32 103.3 3 37.2 33.6 16.8 139 2117 (2) 26 84.5 5 58.4 52.8 26.4 145 2209 (2) 26 105.6 2 33.5 30 15 151 2300 (2) 32 103.3 5 58.4 52.8 26.4 159 2416 (2) 26 105.6 3 46.5 42 21 167 2545 (2) 26 126.7 2 40.2 36 18 179 2726 (2) 26 105.6 5 73 66 33 182 2773 (2) 26 126.7 3 55.8 50.4 25.2 200 3044 (2) 32 155 3 55.8 50.4 25.2 209 3183 (2) 26 126.7 5 - 79.2 39.6 228 3471 (2) 32 155 5 - 79.2 39.6
* MBH x 1000 = BTUH ‡ For summer operation above 60ºF without Limitizer
PHYSICAL/DIMENSIONAL DATA
Optional
Manifold Kit
Unit Conn. O.D.
Size Inlet Outlet 045-097 2 101-159 2 167-228 3
1
/8 21/8
5
/8 25/8
1
/8 31/8
BVF 045-228
48” Coil Approx. Unit Fans Conn. Net Wt. Size A D E F G J K L M R S Y Qty. RPM CFM In Out (Lbs.)
045 1 14 110 - - 31 050 1 14 110 - - 31 054 1 14 110 - - 31 057 1 14 110 - - 31 059 1 14 110 - - 30 062 1 14 110 - - 31 065 1 14 110 - - 31 069 169 165 82 83 31 073 1 14 110 - - 30 081 169 165 82 83 31 086 169 165 82 83 31 088 169 165 82 83 30 096 169 165 82 83 30 097 169 165 82 83 31 101 169 165 82 83 28 106 169 165 82 83 30 111 224 220 109 114 169 165 82 83 28 121 224 220 109 136 224 220 109 139 224 220 109 145 279 275 82 151 224 220 109 159 279 275 82 167 334 330 109 179 279 275 82 182 334 330 109 200 334 330 109 209 334 330 109 228 334 330 109
Dimensions in inches All units have two circuits
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 611/16 23/16 - 4 470 7200 21/8 21/8 2910
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 611/16 23/16 - 4 545 78000 21/8 21/8 2970
1
/2 1101/2 287/8 2113/16 2113/16 421/4 421/4 615/16 27/16 - 4 545 82400 21/8 21/8 3370
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 611/16 23/16 - 4 600 99200 21/8 21/8 3050
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 615/16 27/16 821/2 5 470 81500 21/8 21/8 3850
1
/2 1101/2 287/8 2113/16 2113/16 421/4 421/4 615/16 27/16 - 4 600 100400 21/8 21/8 3450
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 615/16 27/16 821/2 5 545 94000 21/8 21/8 3900
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 615/16 27/16 110 6 470 101400 25/8 25/8 4525
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 615/16 27/16 821/2 5 600 114500 21/8 21/8 3950
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 615/16 27/16 110 6 545 117000 25/8 25/8 4575
1
/2 1101/2 299/16 2113/16 2113/16 421/4 421/4 615/16 27/16 110 6 545 123600 25/8 25/8 4995
1
/2 1101/2 301/4 2113/16 2113/16 421/4 421/4 615/16 27/16 110 6 600 142200 25/8 25/8 4695
1
/2 1101/2 299/16 2113/16 2113/16 421/4 421/4 615/16 27/16 110 6 600 150600 25/8 25/8 5115
5
/8 2113/16 237/16 417/16 417/16 61/2 115/16 - 2 415 32800 13/8 13/8 1280
5
/8 2113/16 237/16 417/16 417/16 61/2 115/16 - 2 470 35000 13/8 13/8 1340
5
/8 2113/16 237/16 417/16 417/16 61/2 115/16 - 2 470 34400 13/8 13/8 1380
5
/8 2113/16 237/16 417/16 417/16 61/2 115/16 - 2 600 51200 13/8 13/8 1370
1
/4 225/8 237/16 3913/16 3513/16 61/2 115/16 - 2 470 31200 15/8 15/8 1540
5
/8 2113/16 237/16 417/16 417/16 61/2 115/16 - 2 600 50100 13/8 13/8 1420
5
/8 2113/16 237/16 417/16 417/16 61/2 115/16 - 2 600 48200 13/8 13/8 1450
5
/8 2113/16 237/16 417/16 3913/16 61/2 115/16 - 3 415 44000 15/8 15/8 1960
1
/4 225/8 237/16 3913/16 3513/16 61/2 115/16 - 2 600 49200 15/8 15/8 1610
5
/8 2113/16 237/16 417/16 3913/16 61/2 115/16 - 3 470 51600 15/8 15/8 2110
5
/8 2113/16 237/16 417/16 3913/16 61/2 115/16 - 3 600 76800 15/8 15/8 2095
1
/4 2113/16 2113/16 421/4 421/4 61/2 115/16 - 3 470 46800 15/8 15/8 2335
1
/4 2113/16 2113/16 421/4 421/4 61/2 115/16 - 3 545 54300 15/8 15/8 2380
5
/8 2113/16 237/16 417/16 3913/16 61/2 115/16 - 3 600 72300 15/8 15/8 2395
7
/8 2113/16 2113/16 421/4 421/4 615/16 27/16 - 3 545 58800 21/8 21/8 2460
1
/4 2113/16 2113/16 421/4 421/4 61/2 115/16 - 3 600 66000 15/8 15/8 2440
7
/8 2113/16 2113/16 421/4 421/4 615/16 27/16 - 3 600 67600 21/8 21/8 2580
ENGINEERING SPECIFICATIONS - BELT DRIVE UNITS
UNIT CABINET - Casings shall be constructed of heavy gauge corrosion resistant aluminum, or galva­nized steel, thoroughly reinforced with bolted gussets. Full width baffles shall divide the individual fan sections. Morot access panels shall be provided in each fan section. Cabinet mounting frames and mounting legs shall be constructructed of heavy galvanized steel. The legs shall be shipped with the unit for field installation.
CONDENSER COIL- Coil shall be constructed of plate type, die formed, aluminum fins mechanically bonded to copper tubes; fins shall employ full height, self-spacing collars which completely cover tube surface. Coil shall be pressure and leak tested at 425 PSIG air under warm water, evacuated, dehydrated, and sealed with caps on connections.
FANS - Fans, each driven by its own motor, shall be selected to cover a large percentage of the coil face area. Fans shall be statistically and dynamically balanced before shipment. Low tip speeds shall provide quiet operation.
UL LISTING - All 60 Hz models (except 575V) shall be UL listed.
DRIVES & BEARINGS - Each fan shall be equipped with a heavy duty, weather protected, pillow block bearing with lubricating fitting accessible through the motor access panel. Fan shaftes shall be polished steel, precision machined and coated with corrosion resistant dressing. V-belt and cast iron drive pulleys shall be matched for heavy duty continuous operation.
FAN MOTORS - Motors shall be NEMA typpe “T” frame, open drip-proof with grease lubricated ball bearings. They shall be thermally protected against burn-out (except 575 volt). Motors shall be factory wired with leads marked and terminated in a weather­proof junction box located on the outside of the unit. They shall be positioned within unit casing for weather protection. Adjustable motor mount bases and large, easy access motor compartment panels. Available in 208V, 230V, 460V, and 575V, three phase 60 Hz models; and 200V, 380V, and 415V three phase 50 Hz models.
FAN GUARDS - Guards shall be constructed of heavy gauge, close meshed steel wire that is zinc plated and iridite dipped to prevent corrosion.
Bohn is a product line of
Heatcraft Refrigeration Products
2175 W. Park Place Blvd. Stone Mountain, GA 30087
770.465.5600 fax: 770.465.5990 www.heatcraftrpd.com