Bohn BMA 850 User Manual

BN-LUC | NOVEMBER 2020
Replaces September 2020
LARGE UNIT COOLER
EVAPORATOR
Technical Guide
Now including models meeting minimum AWEF
TABLE OF CONTENTS
3 4 5
6

14
22
36
50 53
55
58 61
Features & Benefits Nomenclatures Preferred Option Packages
Models Meet Minimum DOE AWEF
Air Defrost
6 Performance Data
6 Application Capacity: Air Defrost - 60 Hz
7 Unit Specifications
Electric Defrost
8 Performance Data
8 Application Capacity: Low Temp. Electric Defrost - 60 Hz
9 Application Capacity: Medium Temp. Electric Defrost - 60 Hz
10 Unit Specifications
Hot Gas Defrost
11 Performance Data
11 Application Capacity: Low Temp. Hot Gas Defrost - 60 Hz
12 Application Capacity: Medium Temp. Hot Gas Defrost - 60 Hz
13 Unit Specifications
Models Do Not Meet Minimum DOE AWEF
Air Defrost
14 Performance Data
14 Application Capacity: Air Defrost - 60 Hz
15 Fan Data: Air Defrost - 60 Hz
16 Application Capacity: Air Defrost - 50 Hz
17 Fan Data: Air Defrost - 50 Hz
18 Unit Specifications
Electric Defrost
22 Performance Data
22 Application Capacity: Low Temp. Electric Defrost - 60 Hz
23 Fan Data: Low Temp. Electric Defrost - 60 Hz
24 Application Capacity: Electric Defrost - 50 Hz
25 Fan Data: Electric Defrost - 50 Hz
26 Application Capacity: Electric Defrost High CFM - 60 Hz
27 Fan Data: Electric Defrost High CFM - 60 Hz
28 Unit Specifications
Hot Gas Defrost
36 Performance Data
36 Application Capacity: Low Temp. Hot Gas Defrost - 60 Hz
37 Fan Data: Low Temp. Hot Gas Defrost - 60 Hz
38 Application Capacity: Hot Gas Defrost - 50 Hz
39 Fan Data: Hot Gas Defrost - 50 Hz
40 Application Capacity: Hot Gas Defrost High CFM - 60 Hz
41 Fan Data: Hot Gas Defrost High CFM - 60 Hz
42 Unit Specifications
Physical Data Dimensional Drawings DOE Rated AWEF
55 AWEF Data
55 Air Defrost 56 Electric Defrost
57 Hot Gas Defrost
Standard Nozzle Selection Replacement Parts
2
FEATURES & BENEFITS
GENERAL FEATURES
Mill finish aluminum provides an attractive design and
structurally sound cabinet
Thermo-Flex (with five-year limited warranty) is innovative,
eliminates leaks, and reduces risk of refrigerant loss
Liquid line solenoid wiring harness for faster installation
Suction Schrader fitting for easier suction temperature
measurement
Hinged drain pan and access panels for easy servicing
Adjustable defrost control can be customized per
application
Long air throw is ideal for large warehouse and industrial
applications
Standardized terminal board for easier field wiring
Improved wire management and routing for easier
installation and service
Complete hot gas defrost model oering meets more
applications
Quick reference QR code providing access to relevant
product documentation
ADDITIONAL FEATURES  MODELS MEETING MINIMUM AWEF
2 Speed EC motor, totally enclosed
850 RPM lower noise motor
Balance heater load for electric defrost
Air defrost terminal block
OPTIONS
High CFM motor and fan combinations (208-230/3/60
and 460/3/60) *
Totally enclosed motors (208-230/3/60 and 460/3/60)
Low temperature motors for blast cooling and freezing
(for room temps -31°F to -50°F) *
Units available with Bronze-Glow coil coating (air,
electric and hot gas)
Units available with copper fins (6 FPI models only)
Air defrost units available with polyester coated fins or
various coil coating options
Long air throw collars for large warehouse and
industrial applications
Insulated drain pan
Factory installed mounted components are available in
these configurations:
Pre-assembled units come with mounted TXV,
liquid line solenoid valve and room thermostat
Mounted TXV Mounted TXV and solenoid valve Mounted room thermostat
Defrost termination control
Mounted fusing for motors and heaters
More factory mounted features for easier field
installation available, consult factory for details
2-Speed EC motor
improves eciency and provides more energy savings
OUTSTANDING FEATUR ES
Hinged Access Panels allow for
easy access to components
Balance Heater Load improves
reliability and generates more energy savings
Hinged Drain Pan
improves access to service and clean the drain pan and coil
3
NOMENCLATURE
Table 1 : 24” Fan (Meeting and Not Meeting DOE Minimum AWEF)
BTUH CAPACITY
MODELS MEET MINIMUM AWEF*
0480 = 48,000 0540 = 53,800 0565 = 56,400
PRODUCT IDENTIFIER
E = Evaporator
B
BRAND
B = Bohn
* Models meet minimum AWEF have a model capacity digit that ends with “0” or “5”. ** Models do not meet minimum AWEF have a model capacity digit ending with “3”
+
Call factory for Glycol and CO2 models, special process required.
E H A B0000C S 6 A M0630
0630 = 63,000 0700 = 69,800 0730 = 72,700
...
EVAPORATOR STYLE
H = LUC (Large
Unit Cooler)
MODELS DO NOT MEET MINIMUM AWEF**
0373 = 40,000 0423 = 45,000 0473 = 48,000 0513 = 56,000
...
VOLTAGE
B = 208-230/1/60 C = 208-230/3/60 D = 460/3/60 M = 460/1/60 E = 575/3/60 X = 380-400/3/50
APPLICATION
S = Standard
Refrigerants
C = CO G = Glycol
FINS PER INCH FPI
6 4
DEFROST STYLE
A = Air Defrost E = Electric
+
2
+
Defrost H = Hot Gas Defrost
MOTOR TYPE
M = 2-Speed EC V = Variable speed
EC Rail Mount H = High CFM Rail Mount P = PSC Open Drip Proof Rail Mount T = 3 Phase AC Totally Enclosed Rail Mount Y = 3 Phase AC Open Drip Proof Rail Mount
VINTAGE
FACTORY INSTALLED OPTION PACKAGES
B#### =
Preferred Option Packages D#### = A la Carte Options Y#### = Custom Option Packages
NOMENCLATURE (LEGACY MODELS)
Table 2 : 30” Fan Legacy Models
FINS PER INCH/ DEFROST
A = 6 or 8 FPI Air Defrost E = 6 FPI Electric Defrost L = 4 FPI Electric Defrost G = 6 FPI Hot Gas Defrost F = 4 FPI Hot Gas Defrost
BH
MODEL SERIES
B = Bohn Large
Profile Unit Cooler
* Legacy models do not meet minimum AWEF
4
A
850
(Standard/Motor Fan Blade)
VOLTAGE
B = 208-230/1/60 C = 208-230/3/60 D = 460/3/60 E = 575/3/60 M = 460/1/60 X = 380-400/3/50 Y = 200-220/1/50 S = Configurable
C
G
CONTROL OPTION
G = intelliGen™
OPTIONAL MOTOR
T = Totally
Enclosed Motors V = High CFM Option P = 3 Phase Motor
P
A
VINTAGECAPACITY x 100
PREFERRED OPTION PACKAGES
↑ Package
B0150 Standard base + Beacon II R404A
B0151 Standard base + Beacon II R448A/R449A
B0152 Standard base + Beacon II R407A/F
B0153 Standard base + Beacon II R407C
B0250 Standard base + intelliGen™ (R404)
B0251 Standard base + intelliGen™ (R448A/R449A)
B0252 Standard base + intelliGen™ (R407A/F)
B0253 Standard base + intelliGen™ (R407C)
B0350 Standard base + QRC (R404)
B0351 Standard base + QRC (R448A/R449A)
B0352 Standard base + QRC (R407A/F)
B0353 Standard base + QRC (R407C)
B0450 Standard base + Mounted TXV (404A)
B0451 Standard base + Mounted TXV + Solenoid (404A)
B0452 Standard base + Mounted TXV + Solenoid + T-Stat (404A)
(standard base model features + indicated options below)
Description
B0453 Standard base + Mounted TXV (407A)
B0454 Standard base + Mounted TXV + Solenoid (407A)
B0455 Standard base + Mounted TXV + Solenoid + T-Stat (407A)
B0456 Standard base + Mounted TXV (448A)
B0457 Standard base + Mounted TXV + Solenoid (448A)
B0458 Standard base + Mounted TXV + Solenoid + T-Stat (448A)
↑Applicable only for 24” Fan size models Refer Nomenclature Table 1 for details
Capacity Correction Factors
Electric and Hot Gas Defrost Unit Only
Saturated Suction Temperature °F
Saturated Suction Temperature °C
20 -10 -20 -30 -40
-7 -23 -29 -34 -40
Multiply Capacity By
1.15 1.04 1.00 0.9 0.8
5
Models Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Air Defrost - 60 Hz
Please consult AWEF table on page 55 to confirm model meets DOE minimum AWEF
R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
1
Application Capacity
Application Capacity1Application Capacity1Application Capacity
1
Model
FPI
6 BEH0570*S6AMA 1 BHA520 - - 57,000 16,700 56,200 16,500 57,60 0 16,900
6 BEH0700*S6AMA 1 BHA520 - - 69,800 20,500 68,800 20,200 70,500 20,700
6 BEH0755*S6AMA 1 BHA630 - - 75,300 22,100 73,800 21,600 80,400 23,600
6 BEH0900*S6AMA 1 BHA750 - - 90,000 26,400 87,60 0 25,700 91,300 26,800
6 BEH1080*S6AMA 1 BHA750 - - 108,000 31,700 105,100 30,800 109,500 32,100
6 BEH1245*S6AMA 1 BHA850 - - 124,400 36,500 121,000 35,500 126,200 37,000
6 BEH1445*S6AMA 1 BHA930 - - 144,500 42,300 141,000 41,300 143,300 42,000
6 BEH1655*S6AMA 1 BHA1100 - - 165,200 48,400 163,000 47, 8 0 0
Model
FPI
6 BEH0570*S6AMA 1 BHA520 2 6,850 11,638 24 610 65 20 80 24
6 BEH0700*S6AMA 1 BHA520 2 6,850 11,638 24 610 65 20 80 24
6 BEH0755*S6AMA 1 BHA630 2 6,850 11,638 24 610 65 20 80 24
6 BEH0900*S6AMA 1 BHA750 3 10,800 18,349 24 610 65 20 80 24
6 BEH1080*S6AMA 1 BHA750 3 10,800 18,349 24 610 65 20 80 24
6 BEH1245*S6AMA 1 BHA850 3 10,800 18,349 24 610 65 20 80 24
6 BEH1445*S6AMA 1 BHA930 4 14,400 24,4 66 24 610 65 20 80 24
6 BEH1655*S6AMA 1 BHA1100 4 14,400 24,466 24 610 65 20 80 24
Legacy
Model
Nomenclature
Legacy
Model
Nomenclature
10°F TD
25°F SST
BTUH Watts BTUH Watts BTUH Watts BTUH Watts
No. of
Fans
6°C TD
-4°C SST
CFM
10°F TD
25°F SST
Fan Data Air Throw
m3H
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
166,000 48,600
Diameter Standard With Collar
in mm ft m ft m
6°C TD
-4°C SST
Notes:
1
= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the
Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov * = Electrical Code Designator (see Nomenclature details) Net Capacity is available upon request
6
Models Meeting DOE Minimum AWEF
SPECIFICATIONS– R-407A/R-407F
Air Defrost - 60 Hz
Please consult AWEF table on page 55 to confirm model meets DOE minimum AWEF
2-Speed EC Motors
Model HP
FPI Amps Watts MCA MOPD Amps Watts MCA MOPD
6 BEH0570*S6AMA 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15
6 BEH0700*S6AMA 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15
6 BEH0755*S6AMA 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15
6 BEH0900*S6AMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15
6 BEH1080*S6AMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15
6 BEH1245*S6AMA 1 3/4 6.6 1,679 7. 2 15 3.3 1,679 3.6 15
6 BEH1445*S6AMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15
6 BEH1655*S6AMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15
Nomenclature
208-230/3/60 460/3/60
Notes:
* = Electrical Code Designator (see Nomenclature Table 1 for details)
7
Models Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Low Temperature Electric Defrost - 60 Hz
Please consult AWEF table on page 56 to confirm model meets DOE minimum AWEF
R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
1
Application Capacity
Application Capacity1Application Capacity1Application Capacity
1
Model
Legacy
Model
FPI
Nomenclature
6 BEH0540*S6EMA 1 BHE450 - - 53,800 15,800 52,900 15,500 - -
6 BEH0630*S6EMA 1 BHE550 - - 63,000 18,500 61,600 18,100 - -
6 BEH0805*S6EMA 1 BHE640 - - 80,100 23,500 79,300 23,200 - -
6 BEH0925*S6EMA 1 BHE740 - - 92,300 27,100 91,400 26,800 - -
6 BEH1125*S6EMA 1 BHE810 - - 112,200 32,900 109,300 32,000 - -
6 BEH1210*S6EMA 1 BHE950 - - 120,700 35,400 11 7, 5 0 0 34,400 - -
4 BEH0480*S4EMA 1 BHL400 - - 48,000 14,100 47,600 14,000 - -
4 BEH0565*S4EMA 1 BHL480 - - 56,400 16,500 55,900 16,400
4 BEH0730*S4EMA 1 BHL560 - - 72,700 21,300 71,400 20,900 - -
4 BEH0845*S4EMA 1 BHL650 - - 84,300 24,70 0 83,100 24,400 - -
4 BEH1010*S4EMA 1 BHL710 - - 100,800 29,500 98,000 28,700 - -
4 BEH1085*S4EMA 1 BHL840 - - 108,300 31,700 106,600 31,200 - -
10°F TD
-20°F SST
BTUH Watts BTUH Watts BTUH Watts BTUH Watts
6°C TD
-29°C SST
10°F TD
-20°F SST
6°C TD
-29°C SST
10°F TD
-20°F SST
6°C TD
-29°C SST
10°F TD
-20°F SST
- -
6°C TD
-29°C SST
Fan Data Air Throw
Model
FPI
6 BEH0540*S6EMA 1 BHE450 2 6,850 11,638 24 610 65 20 80 24
6 BEH0630*S6EMA 1 BHE550 2 6,850 11,638 24 610 65 20 80 24
6 BEH0805*S6EMA 1 BHE640 3 10,800 18,349 24 610 65 20 80 24
6 BEH0925*S6EMA 1 BHE740 3 10,800 18,349 24 610 65 20 80 24
6 BEH1125*S6EMA 1 BHE810 4 14,400 24,466 24 610 65 20 80 24
6 BEH1210*S6EMA 1 BHE950 4 14,400 24,466 24 610 65 20 80 24
4 BEH0480*S4EMA 1 BHL400 2 7,0 50 11,978 24 610 65 20 80 24
4 BEH0565*S4EMA 1 BHL480 2 7, 0 50 11,978 24 610 65 20 80 24
4 BEH0730*S4EMA 1 BHL560 3 11,200 19,029 24 610
4 BEH0845*S4EMA 1 BHL650 3 11,200 19,029 24 610 65 20 80 24
4 BEH1010*S4EMA 1 BHL710 4 15,000 25,485 24 610 65 20 80 24
4 BEH1085*S4EMA 1 BHL840 4 15,000 25,485 24 610 65 20 80 24
Legacy
Model
Nomenclature
No. of
Fans
CFM
m3H
Diameter Standard With Collar
in mm ft m ft m
65 20 80 24
Notes:
1
= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the
Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov * = Electrical Code Designator (see Nomenclature details) Net Capacity is available upon request
8
Models Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-448A/R-449A
Application Capacity: Medium Temperature Electric Defrost - 60 Hz
Please consult AWEF table on page 56 to confirm model meets DOE minimum AWEF
R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
1
Application Capacity
Application Capacity1Application Capacity1Application Capacity
1
Model
Legacy
Model
FPI
Nomenclature
6 BEH0540*S6EMA 1 BHE450 - - 62,400 18,300 61,400 18,000 - -
6 BEH0630*S6EMA 1 BHE550 - - 73,100 21,400 71,500 21,000 - -
6 BEH0805*S6EMA 1 BHE640 - - 92,900 27,20 0 92,000 27,000 - -
6 BEH0925*S6EMA 1 BHE740 - - 107,100 31,400 106,000 31,100 - -
6 BEH1125*S6EMA 1 BHE810 - - 130,200 38,200 126,800 37, 2 0 0 - -
6 BEH1210*S6EMA 1 BHE950 - - 140,000 41,000 136,300 39,900 - -
4 BEH0480*S4EMA 1 BHL400 - - 55,700 16,300 55,200 16,200 - -
4 BEH0565*S4EMA 1 BHL480 - - 65,400 19,200 64,800 19,000
4 BEH0730*S4EMA 1 BHL560 - - 84,300 24,700 82,800 24,300 - -
4 BEH0845*S4EMA 1 BHL650 - - 97, 8 0 0 28,700 96,400 28,300 - -
4 BEH1010*S4EMA 1 BHL710 - - 116,900 34,300 113,700 33,300 - -
4 BEH1085*S4EMA 1 BHL840 - - 125,600 36,800 123,700 36,300 - -
10°F TD
25°F SST
BTUH Watts BTUH Watts BTUH Watts BTUH Watts
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
- -
6°C TD
-4°C SST
Fan Data Air Throw
Model
FPI
6 BEH0540*S6EMA 1 BHE450 2 6,850 11,638 24 610 65 20 80 24
6 BEH0630*S6EMA 1 BHE550 2 6,850 11,638 24 610 65 20 80 24
6 BEH0805*S6EMA 1 BHE640 3 10,800 18,349 24 610 65 20 80 24
6 BEH0925*S6EMA 1 BHE740 3 10,800 18,349 24 610 65 20 80 24
6 BEH1125*S6EMA 1 BHE810 4 14,400 24,466 24 610 65 20 80 24
6 BEH1210*S6EMA 1 BHE950 4 14,400 24,466 24 610 65 20 80 24
4 BEH0480*S4EMA 1 BHL400 2 7,0 50 11,978 24 610 65 20 80 24
4 BEH0565*S4EMA 1 BHL480 2 7, 0 50 11,978 24 610 65 20 80 24
4 BEH0730*S4EMA 1 BHL560 3 11,200 19,029 24 610
4 BEH0845*S4EMA 1 BHL650 3 11,200 19,029 24 610 65 20 80 24
4 BEH1010*S4EMA 1 BHL710 4 15,000 25,485 24 610 65 20 80 24
4 BEH1085*S4EMA 1 BHL840 4 15,000 25,485 24 610 65 20 80 24
Legacy
Model
Nomenclature
No. of
Fans
CFM
m3H
Diameter Standard With Collar
in mm ft m ft m
65 20 80 24
Notes:
1
= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the
Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov * = Electrical Code Designator (see Nomenclature details) Net Capacity is available upon request
9
Models Meeting DOE Minimum AWEF
SPECIFICATIONS– R-407A/R-407F
Electric Defrost - 60 Hz
Please consult AWEF table on page 56 to confirm model meets DOE minimum AWEF
2-Speed EC Defrost Heaters
Model HP
FPI Amps Watts MCA MOPD Amps Watts MCA MOPD
BEH0540*S6EMA 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15 15,100 42.0 21.1
6
BEH0630*S6EMA 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15 15,100 42.0 21.1
6
BEH0805*S6EMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15 19,700 54.7 2 7. 5
6
BEH0925*S6EMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15 19,700 54.7 27.5
6
BEH1125*S6EMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15 27,000 75.0 3 7.7
6
BEH1210*S6EMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15 27,000 75.0 3 7. 7
6
BEH0480*S4EMA 1 3/4 4.4 1,1 19 5.0 15 2.2 1,119 2.5 15 15,100 42.0 21.1
4
BEH0565*S4EMA 1 3/4 4.4
4
BEH0730*S4EMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15 19,700 54.7 27.5
4
BEH0845*S4EMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15 19,700 54.7 2 7. 5
4
BEH1010*S4EMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15 27,000 75.0 38.0
4
BEH1085*S4EMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15 27,000 75.0 3 7.7
4
Nomenclature
208-230/3/60 460/3/60
Watts
1,119 5.0 15 2.2 1 ,119 2.5 15 15,100 42.0 21.1
208­230/ 3/60
Total Amps
460/ 3/60
Notes:
* = Electrical Code Designator (see Nomenclature details)
10
Models Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-448A/R-449A
Application Capacity: Low Temperature Hot Gas Defrost - 60 Hz
Please consult AWEF table on page 57 to confirm model meets DOE minimum AWEF
R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
1
Application Capacity
Application Capacity1Application Capacity1Application Capacity
1
Model
Legacy
Model
FPI
Nomenclature
6 BEH0540*S6HMA 1 BHG450 - - 53,800 15,800 52,900 15,500 - -
6 BEH0630*S6HMA 1 BHG550 - - 63,000 18,500 61,600 18,100 - -
6 BEH0805*S6HMA 1 BHG640 - - 80,100 23,500 79,300 23,200 - -
6 BEH0925*S6HMA 1 BH G74 0 - - 92,300 27,100 91,400 26,800 - -
6 BEH1125*S6HMA 1 BHG810 - - 112,200 32,900 109,300 32,000 - -
6 BEH1210*S6HMA 1 BHG950 - - 120,700 35,400 11 7, 5 0 0 34,400 - -
4 BEH0480*S4HMA 1 BHF400 - - 48,000 14,100 47,600 14,000 - -
4 BEH0565*S4HMA 1 BHF480 - - 56,400 16,500 55,900 16,400
4 BEH0730*S4HMA 1 BHF560 - - 72,700 21,300 71,400 20,900 - -
4 BEH0845*S4HMA 1 BHF650 - - 84,300 24,700 83,100 24,400 - -
4 BEH1010*S4HMA 1 BHF710 - - 100,800 29,500 98,000 28,700 - -
4 BEH1085*S4HMA 1 BHF840 - - 108,300 31,700 106,600 31,200 - -
10°F TD
-20°F SST
BTUH Watts BTUH Watts BTUH Watts BTUH Watts
6°C TD
-29°C SST
10°F TD
-20°F SST
6°C TD
-29°C SST
10°F TD
-20°F SST
6°C TD
-29°C SST
10°F TD
-20°F SST
- -
6°C TD
-29°C SST
Fan Data Air Throw
Model
FPI
6 BEH0540*S6HMA 1 BHG450 2 6,850 11,638 24 610 65 20 80 24
6 BEH0630*S6HMA 1 BHG550 2 6,850 11,638 24 610 65 20 80 24
6 BEH0805*S6HMA 1 BHG640 3 10,800 18,349 24 610 65 20 80 24
6 BEH0925*S6HMA 1 BHG 740 3 10,800 18,349 24 610 65 20 80 24
6 BEH1125*S6HMA 1 BHG810 4 14,400 24,466 24 610 65 20 80 24
6 BEH1210*S6HMA 1 BHG950 4 14,400 24,466 24 610 65 20 80 24
4 BEH0480*S4HMA 1 BHF400 2 7,0 5 0 11,978 24 610 65 20 80 24
4 BEH0565*S4HMA 1 BHF480 2 7,0 5 0 11,978 24 610 65 20 80 24
4 BEH0730*S4HMA 1 BHF560 3 11,200 19,029 24 610
4 BEH0845*S4HMA 1 BHF650 3 11,200 19,029 24 610 65 20 80 24
4 BEH1010*S4HMA 1 BHF710 4 15,000 25,485 24 610 65 20 80 24
4 BEH1085*S4HMA 1 BHF840 4 15,000 25,485 24 610 65 20 80 24
Legacy
Model
Nomenclature
No. of
Fans
CFM
m3H
Diameter Standard With Collar
in mm ft m ft m
65 20 80 24
Notes:
1
= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the
Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov * = Electrical Code Designator (see Nomenclature details) Net Capacity is available upon request
11
Models Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-448A/R-449A
Application Capacity: Medium Temperature Hot Gas Defrost - 60 Hz
Please consult AWEF table on page 57 to confirm model meets DOE minimum AWEF
R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
1
Application Capacity
Application Capacity1Application Capacity1Application Capacity
1
Model
Legacy
Model
FPI
Nomenclature
6 BEH0540*S6HMA 1 BHG450 - - 62,400 18,300 61,400 18,000 - -
6 BEH0630*S6HMA 1 BHG550 - - 73,100 21,400 71,500 21,000 - -
6 BEH0805*S6HMA 1 BHG640 - - 92,900 27, 2 00 92,000 27,000 - -
6 BEH0925*S6HMA 1 BH G74 0 - - 107,100 31,400 106,000 31,100 - -
6 BEH1125*S6HMA 1 BHG810 - - 130,200 38,200 126,800 37, 200 - -
6 BEH1210*S6HMA 1 BHG950 - - 140,000 41,000 136,300 39,900 - -
4 BEH0480*S4HMA 1 BHF400 - - 55,700 16,300 55,200 16,200 - -
4 BEH0565*S4HMA 1 BHF480 - - 65,400 19,200 64,800 19,000
4 BEH0730*S4HMA 1 BHF560 - - 84,300 24,700 82,800 24,300 - -
4 BEH0845*S4HMA 1 BHF650 - - 97,80 0 28,700 96,400 28,300 - -
4 BEH1010*S4HMA 1 BHF710 - - 116,900 34,300 113,700 33,300 - -
4 BEH1085*S4HMA 1 BHF840 - - 125,600 36,800 123,700 36,300 - -
10°F TD
25°F SST
BTUH Watts BTUH Watts BTUH Watts BTUH Watts
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
- -
6°C TD
-4°C SST
Fan Data Air Throw
Model
FPI
6 BEH0540*S6HMA 1 BHG450 2 6,850 11,638 24 610 65 20 80 24
6 BEH0630*S6HMA 1 BHG550 2 6,850 11,638 24 610 65 20 80 24
6 BEH0805*S6HMA 1 BHG640 3 10,800 18,349 24 610 65 20 80 24
6 BEH0925*S6HMA 1 BHG 740 3 10,800 18,349 24 610 65 20 80 24
6 BEH1125*S6HMA 1 BHG810 4 14,400 24,466 24 610 65 20 80 24
6 BEH1210*S6HMA 1 BHG950 4 14,400 24,466 24 610 65 20 80 24
4 BEH0480*S4HMA 1 BHF400 2 7,0 5 0 11,978 24 610 65 20 80 24
4 BEH0565*S4HMA 1 BHF480 2 7,0 5 0 11,978 24 610 65 20 80 24
4 BEH0730*S4HMA 1 BHF560 3 11,200 19,029 24 610
4 BEH0845*S4HMA 1 BHF650 3 11,200 19,029 24 610 65 20 80 24
4 BEH1010*S4HMA 1 BHF710 4 15,000 25,485 24 610 65 20 80 24
4 BEH1085*S4HMA 1 BHF840 4 15,000 25,485 24 610 65 20 80 24
Legacy
Model
Nomenclature
No. of
Fans
CFM
m3H
Diameter Standard With Collar
in mm ft m ft m
65 20 80 24
Notes:
1
= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the
Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov * = Electrical Code Designator (see Nomenclature details) Net Capacity is available upon request
12
Models Meeting DOE Minimum AWEF
SPECIFICATIONS– R-407A/R-407F
Hot Gas Defrost - 60 Hz
Please consult AWEF table on page 57 to confirm model meets DOE minimum AWEF
2-Speed EC Motor Drain Pan Heaters
Model HP
FPI Amps Watts MCA MOPD Amps Watts MCA MOPD
6 BEH0540*S6HMA 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15 2,100 9.2 4.6
6 BEH0630*S6HMA 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15 2,100 9.2 4.6
6 BEH0805*S6HMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15 2,700 11.8 5.9
6 BEH0925*S6HMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15 2,700 11.8 5.9
6 BEH1125*S6HMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15 4,000 17.4 8.7
6 BEH1210*S6HMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15 4,000 17.4 8.7
4 BEH0480*S4HMA 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15 2,100 9.2 4.6
4 BEH0565*S4HMA 1 3/4
4 BEH0730*S4HMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15 2,700 11.8 5.9
4 BEH0845*S4HMA 1 3/4 6.6 1,679 7.2 15 3.3 1,679 3.6 15 2,700 11.8 5.9
4 BEH1010*S4HMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15 4,000 1 7.4 8.7
4 BEH1085*S4HMA 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15 4,000 1 7.4 8.7
Nomenclature
208-230/3/60 460/3/60
Watts
4.4 1,119 5.0 15 2.2 1,119 2.5 15 2,100 9.2 4.6
Total Amps
208­230/
1/60
2
460/
1/60
Notes:
* = Electrical Code Designator (see Nomenclature Table 1 for details)
2
Hot gas drain pan available
13
Models Not Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Air Defrost - 60 Hz
R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
1
Application Capacity
Application Capacity1Application Capacity1Application Capacity
1
4 Fin Per Inch
Model
FPI
6 BEH0553*S6A^A 1 BHA520 52,000 15,200 58,000 17,000 58,000 17,000 58,000 17,000
6 BEH0723*S6A^A 1 BHA630 63,000 18,500 72,000 21,100 72,000 21,100 72,000 21,100
6 BEH0743*S6A^A 1 BHA750 75,000 22,000 86,000 25,200 86,000 25,200 86,000 25,200
6 BEH0933*S6A^A 1 BHA850 85,000 24,90 0 97,000 28,400 97,000 28,400 97,000 28,400
6 BEH1053*S6A^A 1 BHA930 93,000 2 7, 3 0 0 104,000 30,500 104,000 30,500 104,000 30,500
6 BEH1313*S6A^A 1 BHA1100 110,000 32,200 125,000 36,600 125,000 36,600 125,000 36,600
6 BHA1170 2 BHA1170 117,000 34,300 133,000 39,000 133,000 39,000 133,000 39,000
6 BHA1400 2 BHA1400 140,000 41,000 162,000 47, 5 0 0 162,000 47,50 0
6 BHA1610 2 BHA1610 161,000 47, 2 0 0 187,000 54,800 187,000 54,800 187,000 54,800
6 BHA1900 2 BHA1900 190,000 55,700 220,000 64,500 220,000 64,500 220,000 64,500
6 BHA2200 2 BHA2200 220,000 64,500 255,000 74,700 255,000 74,700 255,000 74,700
6 BHA2440 2 BHA2440 244,000 71,500 288,000 84,400 288,000 84,400 288,000 84,400
8 BHA2160 2 BHA2160 216,000 63,300 251,000 73,600 251,000 73,600 251,000 73,600
8 BHA2500 2 BHA2500 250,000 73,300 295,000 86,500 295,000 86,500 295,000 86,500
8 BHA2780 2 BHA2780 278,000 81,500 328,000 96,100 328,000 96,100 328,000 96,100
Legacy
Model
Nomenclature
10°F TD
25°F SST
BTUH Watts BTUH Watts BTUH Watts BTUH Watts
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
162,000 47, 5 00
6°C TD
-4°C SST
Notes:
1
= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the
Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov * = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature Table 1 for details)
14
Models Not Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-404A/R-507A
Fan Data: Air Defrost - 60 Hz
Fan Data Air Throw
Model
FPI
6 BEH0553*S6A^A 1 BHA520 2 9,000 15,291 24 610 70 21 85 26
6 BEH0723*S6A^A 1 BHA630 2 9,000 15,291 24 610 70 21 85 26
6 BEH0743*S6A^A 1 BHA750 3 12,600 21,408 24 610 70 21 85 26
6 BEH0933*S6A^A 1 BHA850 3 12,600 21,408 24 610 70 21 85 26
6 BEH1053*S6A^A 1 BHA930 4 16,800 28,543 24 610 70 21 85 26
6 BEH1313*S6A^A 1 BHA1100 4 16,800 28,543 24 610 70 21 85 26
6 B HA1 170 2 BHA1170 3 20,700 35,170 30 763 100 30 115 35
6 BHA1400 2 BHA1400 3 20,700 35,170 30 763 100 30 115 35
6 BHA1610 2 BHA1610 3 24, 30 0 41, 286 30 763
6 BHA1900 2 BHA1900 3 26,550 45,1 09 30 763 120 37 140 43
6 BHA2200 2 BHA2200 4 30,400 51,650 30 763 120 37 140 43
6 BHA2440 2 BHA2440 4 35,400 60,145 30 763 120 37 140 43
8 BHA2160 2 BHA2160 3 25,950 44,089 30 763 120 37 140 43
8 BHA2500 2 BHA2500 4 29,600 50,291 30 763 120 37 140 43
8 BHA2780 2 BHA2780 4 34,600 58,786 30 763 120 37 140 43
Legacy
Model
Nomenclature
No. of
Fans
CFM
m3H
Diameter Standard With Collar
in mm ft m ft m
100 30 115 35
Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature Table 1 for details)
15
Models Not Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Air Defrost - 50 Hz
R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
1
Application Capacity
Application Capacity1Application Capacity1Application Capacity
1
Model
FPI
6 BEH0553*S6A^A 1 BHA520 47,800 14,000 53,400 15,600 53,400 15,600 53,400 15,600
6 BEH0723*S6A^A 1 BHA630 58,000 17,000 66,200 19,400 66,200 19,400 66,200 19,400
6 BEH0743*S6A^A 1 BHA750 69,000 20,200 79,100 23,200 79,100 23,200 79,100 23,200
6 BEH0933*S6A^A 1 BHA850 78,200 22,900 89,200 26,100 89,200 26,100 89,200 26,100
6 BEH1053*S6A^A 1 BHA930 85,600 25,100 95,700 28,000 95,700 28,000 95,700 28,000
6 BEH1313*S6A^A 1 BHA1100 101,200 29,700 115,000 33,700 115,000 33,700 115,000 33,700
6 BHA1170 2 BHA1170 107,600 31,500 122,400 35,900 122,400 35,900 122,400 35,900
6 BHA1400 2 BHA1400 128,800 3 7,70 0 149,000 43,700 149,000 43,700
6 BHA1610 2 BHA1610 148,100 43,400 172,000 50,400 172,000 50,400 172,000 50,400
6 BHA1900 2 BHA1900 174,8 00 51,200 202,400 59,300 202,400 59,300 202,400 59,300
6 BHA2200 2 BHA2200 198,700 58,200 230,900 67,7 0 0 230,900 67,70 0 230,900 67,700
6 BHA2440 2 BHA2440 202,400 59,300 234,600 68,800 234,600 68,800 234,600 68,800
8 BHA2160 2 BHA2160 224,500 65,800 265,000 7 7, 700 265,000 77, 700 265,000 7 7,70 0
8 BHA2500 2 BHA2500 230,000 67,400 271,400 79,500 271,400 79,500 271,400 79,500
8 BHA2780 2 BHA2780 255,800 75,000 301,800 88,400 301,800 88,400 301,800 88,400
Legacy
Model
Nomenclature
10°F TD
25°F SST
BTUH Watts BTUH Watts BTUH Watts BTUH Watts
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
6°C TD
-4°C SST
10°F TD
25°F SST
149,000 43,700
6°C TD
-4°C SST
Notes:
1
= Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the
Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov * = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature Table 1 for details)
16
Models Not Meeting DOE Minimum AWEF
PERFORMANCE DATA – R-404A/R-507A
Fan Data: Air Defrost - 50 Hz
Fan Data Air Throw
Model
FPI
6 BEH0553*S6A^A 1 BHA520 2 8,100 13,762 24 610 70 21 85 26
6 BEH0723*S6A^A 1 BHA630 2 8,100 13,762 24 610 70 21 85 26
6 BEH0743*S6A^A 1 BHA750 3 11,300 19,199 24 610 70 21 85 26
6 BEH0933*S6A^A 1 BHA850 3 11,300 19,199 24 610 70 21 85 26
6 BEH1053*S6A^A 1 BHA930 4 15,100 25,655 24 610 70 21 85 26
6 BEH1313*S6A^A 1 BHA1100 4 15,100 25,655 24 610 70 21 85 26
6 B HA1 170 2 BHA1170 3 18,600 31,602 30 763 90 27 100 30
6 BHA1400 2 BHA1400 3 18,600 31,602 30 763 90 27 100 30
6 BHA1610 2 BHA1610 3 21,900 37, 2 0 8 30 763
6 BHA1900 2 BHA1900 3 23,900 40,606 30 763 110 34 130 40
6 BHA2200 2 BHA2200 4 27,400 46,553 30 763 110 34 130 40
6 BHA2440 2 BHA2440 4 31,900 5 4,198 30 763 110 34 130 40
8 BHA2160 2 BHA2160 3 23,400 39,757 30 763 110 34 130 40
8 BHA2500 2 BHA2500 4 26,700 45,364 30 763 110 34 130 40
8 BHA2780 2 BHA2780 4 31,200 53,009 30 763 110 34 130 40
Legacy
Model
Nomenclature
No. of
Fans
CFM
m3H
Diameter Standard With Collar
in mm ft m ft m
90 27 100 30
Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature Table 1 for details)
17
Models Not Meeting DOE Minimum AWEF
SPECIFICATIONS– R-407A/R-407F
Air Defrost - 60 Hz
2-Speed EC Motors
Model HP
FPI Amps Watts MCA MOPD Amps Watts MCA MOPD
6 BEH0553*S6A^A 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15
6 BEH0723*S6A^A 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15
6 BEH0743*S6A^A 1 3/4 6.6 1,679 7. 2 15 3.3 1,679 3.6 15
6 BEH0933*S6A^A 1 3/4 6.6 1,679 7. 2 15 3.3 1,679 3.6 15
6 BEH1053*S6A^A 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15
6 BEH1313*S6A^A 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15
Model HP
FPI Amps Watts MCA MOPD Amps Watts MCA MOPD
6 BEH0553*S6A^A 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15
6 BEH0723*S6A^A 1 3/4 4.4 1,119 5.0 15 2.2 1,119 2.5 15
6 BEH0743*S6A^A 1 3/4 6.6 1,679 7. 2 15 3.3 1,679 3.6 15
6 BEH0933*S6A^A 1 3/4 6.6 1,679 7. 2 15 3.3 1,679 3.6 15
6 BEH1053*S6A^A 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15
6 BEH1313*S6A^A 1 3/4 8.8 2,238 9.4 15 4.4 2,238 4.7 15
6 BHA1170 2 1-1/2 11.1 3,356 12.0 20 5.7 3,356 6.2 15
6 BHA1400 2 1-1/2 11.1 3,356 12.0 20 5.7 3,356 6.2 15
6 BHA1610 2 1-1/2 11.1 3,356 12.0 20 5.7 3,356 6.2 15
6 BHA1900 2 1-1/2 11.1 3,356 12.0 20 5.7 3,356 6.2 15
6 BHA2200 2 1-1/2 14.8 4,474 15.7 25 7. 6 4,474 8.1 15
6 BHA2440 2 1-1/2 14.8 4,474 15.7 25 7. 6 4,474 8.1 15
8 BHA2160 2 1-1/2 11.1 3,356 12.0 20 5.7 3,356 6.2 15
8 BHA2500 2 1-1/2 14.8 4,474 15.7 25 7.6 4,474 8.1 15
8 BHA2780 2 1-1/2 14.8 4,474 15.7 25 7. 6 4,474 8.1 15
Nomenclature
Nomenclature
208-230/3/60 460/3/60
Variable Speed EC
208-230/3/60 460/3/60
Notes:
* = Electrical Code Designator (see Nomenclature Table 1 for details) ^ = Motor Code Designator (see Nomenclature Table 1 for details)
18
Models Not Meeting DOE Minimum AWEF
SPECIFICATIONS– R-407A/R-407F
Air Defrost - 60 Hz
3 Phase AC Open Drip Proof Rail Mount
Model HP
FPI Amps Watts MCA MOPD Amps Watts MCA MOPD
6 BEH0553*S6A^A 1 3/4 8.0 1,119 9.0 20 4.0 1,119 4.5 15
6 BEH0723*S6A^A 1 3/4 8.0 1,119 9.0 20 4.0 1,119 4.5 15
6 BEH0743*S6A^A 1 3/4 12.0 1,679 13.0 25 6.0 1,679 6.5 15
6 BEH0933*S6A^A 1 3/4 12.0 1,679 13.0 25 6.0 1,679 6.5 15
6 BEH1053*S6A^A 1 3/4 16.0 2,238 1 7. 0 30 8.0 2,238 8.5 15
6 BEH1313*S6A^A 1 3/4 16.0 2,238 17.0 30 8.0 2,238 8.5 15
6 BHA1170 2 1 13.8 2,237 15.0 25 6.9 2,237 7.5 15
6 BHA1400 2 1 13.8 2,237 15.0 25 6.9 2,237 7.5 15
6 BHA1610 2 1-1/2 19.8 3,356 21.5 40 9.9 3,356 10.7 20
6 BHA1900 2 1-1/2 21.0 3,356 22.8 40 10.5 3,356 11.4 20
6 BHA2200 2 1-1/2 26.4 4 ,474 28.1 45 10.5 4,474 11.2 15
6 BHA2440 2 1-1/2 28.0 4, 474 29.8 45 13.2 4,474 14.0 20
8 BHA2160 2 1-1/2 21.0 3,356 22.8 40 14.0 3,356 15.2 25
8 BHA2500 2 1-1/2 26.4 4 ,474 28.1 45 13.2 4,474 14.0 20
8 BHA2780 2 1-1/2 28.0 4,474 29.8 45 14.0 4,474 14.9 25
Model HP
Nomenclature
208-230/3/60 460/3/60
3 Phase AC Totally Enclosed Rail Mount
208-230/3/60 460/3/60
FPI Amps Watts MCA MOPD Amps Watts MCA MOPD
6 BEH0553*S6A^A 1 1 6.0 1,492 6.8 20 3.0 1,492 3.4 15
6 BEH0723*S6A^A 1 1 6.0 1,492 6.8 20 3.0 1,492 3.4 15
6 BEH0743*S6A^A 1 1 9.0 2,238 9.8 20 4.5 2,238 4.9 15
6 BEH0933*S6A^A 1 1 9.0 2,238 9.8 20 4.5 2,238 4.9 15
6 BEH1053*S6A^A 1 1 12.0 2,984 12.8 20 6.0 2,984 6.4 15
6 BEH1313*S6A^A 1 1 12.0 2,984 12.8 20 6.0 2,984 6.4 15
6 BHA1170 2 1-1/2 19.8 3,356 21.5 40 9.9 3,356 10.7 20
6 BHA1400 2 1-1/2 19.8 3,356 21.5 40 9.9 3,356 10.7 20
6 BHA1610 2 1-1/2 19.8 3,356 21.5 40 9.9 3,356 10.7 20
6 BHA1900 2 1-1/2 19.8 3,356 21.5 40 9.9 3,356 10.7 20
6 BHA2200 2 1-1/2 26.4 4 ,474 28.1 45 13.2 4,474 14.0 20
6 BHA2440 2 1-1/2 26.4 4 ,474 28.1 45 13.2 4,474 14.0 20
8 BHA2160 2 1-1/2 19.8 3,356 21.5 40 9.9 3,356 10.7 20
8 BHA2500 2 1-1/2 26.4 4 ,474 28.1 45 13.2 4,474 14.0 20
8 BHA2780 2 1-1/2 26.4 4,474 28.1 45 13.2 4,474 14.0 20
Notes:
* = Electrical Code Designator (see Nomenclature Table 1 for details) ^ = Motor Code Designator (see Nomenclature Table 1 for details)
Nomenclature
19
Models Not Meeting DOE Minimum AWEF
SPECIFICATIONS– R-407A/R-407F
Air Defrost - 60 Hz
3 Phase AC Totally Enclosed Rail Mount
Model HP
FPI Amps Watts MCA MOPD
6 BEH0553*S6A^A 1 1/2 1.8 746 2.0 15
6 BEH0723*S6A^A 1 1/2 1.8 746 2.0 15
6 BEH0743*S6A^A 1 1/2 2.7 1,119 2.9 15
6 BEH0933*S6A^A 1 1/2 2.7 1,119 2.9 15
6 BEH1053*S6A^A 1 1/2 3.6 1,492 3.8 15
6 BEH1313*S6A^A 1 1/2 3.6 1,492 3.8 15
6 BHA1170 2 1 7. 8 2,237 8.5 15
6 BHA1400 2 1 7. 8 2,237 8.5 15
6 BHA1610 2 1-1/2 7. 8 3,356 8.5 15
6 BHA1900 2 1-1/2 8.4 3,356 9.1 15
6 BHA2200 2 1-1/2 10.4 4,474 11.1 15
6 BHA2440 2 1-1/2 11.2 4,474 11.9 20
8 BHA2160 2 1-1/2 8.4 3,356 9.1 15
8 BHA2500 2 1-1/2 10.4 4,474 11 .1 15
8 BHA2780 2 1-1/2 11.2 4,474 11.9 20
Nomenclature
PSC Open Drip Proof Rail Mount
575/3/60
Model HP
FPI Amps Watts MCA MOPD Amps Watts MCA MOPD
6 BEH0553*S6A^A 1 1/2 6.4 74 6 7. 2 20 3.4 746 3.8 15
6 BEH0723*S6A^A 1 1/2 6.4 74 6 7. 2 20 3.4 74 6 3.8 15
6 BEH0743*S6A^A 1 1/2 9.6 1119 10.4 20 5.1 1119 5.5 15
6 BEH0933*S6A^A 1 1/2 9.6 1119 10.4 20 5.1 1119 5.5 15
6 BEH1053*S6A^A 1 1/2 12.8 1492 13.6 20 6.8 1492 7. 2 15
6 BEH1313*S6A^A 1 1/2 12.8 1492 13.6 20 6.8 1492 7.2 15
Notes:
* = Electrical Code Designator (see Nomenclature Table 1 for details) ^ = Motor Code Designator (see Nomenclature Table 1 for details)
Nomenclature
208-230/1/60 460/1/60
20