Bock Water heaters High Efficiency Condensing Gas Water Heaters User Manual

High Efficiency Condensing
Energy Saver
Gas Water Heaters
Up to 99.1%
Thermal Efficient
60 to 100 gallons/125,000 to 399,999 BTU PVC Conventional, Through-the Wall, or Direct Vent Low NOx Premix Power Burner Non-CFC foam insulation Electronic ignition and controls Zero inch clearance to combustibles Glass-lined storage tank Hand hole cleanout Sediment reduction system Standard and ASME construction NSF kit available 3" Concentric vent kit available Complies with SCAQMD low NOx requirements Design certified by CSA International (formerly AGA/CGA) 3-Year Limited Tank/1-Year Limited Parts Warranties
Whisper Quiet
NOTE: Diagrams are for both the 60 and 100 gallon models
¾” NPT Gas Inlet
1" NPT Space Heating Outlet
1" NPT Space Heating Return
1 ½"NPT Inlet
3" PVC Exhaust
3” PVC Air Inlet
G E
B
D
3" PVC Exhaust
½” NPT Condensate Connection
F
ACH
T & P Valve
Cleanout
Drain
B - 28 ¼
Gas Inlet
Exhaust
Air Intake
2 ⁄”
8 ¼
8 ¼
T & P Valve
1 ½” NPT Outlet
Energy Saver
High Efficiency Condensing
Gas Water Heaters
This product is available from:
MODEL
NUMBER
60 Gallon Models 57 28 1/4 42 13 53 1/2 5 52 1/2 40 1 1/2
100 Gallon Models 77 5/8 28 1/4 63 13 74 3/4 5 74.75 60 1.5
MODEL
NUMBER
60HEC-125 60 125,000 96.0% 187 364 145 104 120 ft 170 ft 570 60HEC-150 60 150,000 93.0% 211 423 169 121 100 ft 150 ft 570
60HEC-199 60 199,999 92.0% 265 558 223 159 80 ft 130 ft 900 100HEC-150 100 150,000 99.1% 250 450 180 129 120 ft 170 ft 900 100HEC-199 100 199,999 98.5% 309 597 239 171 100 ft 150 ft 900 100HEC-250 100 250,000 97.0% 364 735 294 210 80 ft 130 ft 900 100HEC-300 100 300,000 92.0% 405 836 335 239 60 ft 110 ft 900
100-HEC-399 100 399,999 93.0% 521 1127 451 322 50 ft 100 ft 900
STORAGE
(GAL)
A
HT.B DIA.
RATED INPUT
(BTUH)
T&P Valve: Factory Installed Brass Drain Valve: Factory Installed Dielectric Fittings: Factory Installed Magnesium Anode Rods: Factory Installed
Pressures (all): Working Pressure, 150 psi; Tested Pressure, 300 psi
AMP Draw Range: = 1.0 to 1.8 amps and 7.0 amps for 100HEC-399;
115V A.C. required
Warning: Installation on hard surface only. Installation should be in accordance with all national and/or local codes. In the absence of local codes, refer to NFPA 54 or ANSI Z21.10.1.
Caution: The recommended maximum hot water termperature setting for normal residential use is 120°F. Bock recommends a tempering valve or anti-scald valve be installed and used according to the manufacturer’s directions to prevent scalding.
Toll Free 800.794.2491•Phone 608.257.2225●Fax 608.257.5304
110 South Dickinson Street , Madison, Wisconsin 53703
DIMENSIONS IN INCHES
F
E
FL. TO
VENT
OUTLET
DEGREE RISE
INTAKE
THERMAL
EFF %
C HOT OUT
1ST HR DEL GAL. @ 100° F
RISE
D
COLD
GAS
IN
CONN.
RECOVERY GPH @
40° F 100° F 140° F
1. Determine the total length of straight vent pipe (in feet) required for both the intake and the exhaust.
2. Add 5 feet of venting for every 90° elbow.
3. Add 2½ feet of venting for every 45° elbow.
4. Total vent length cannot exceed "Max Length" in the above chart.
5. Air intake cannot exceed exhaust by more than 30 feet in any venting situation.
Do not include the 3" exhaust elbow or vent terminals in determining maximum vent length.
www.bockwaterheaters.com
G
FL. TO
T&P
VALVE
MAX 3”
PVC,
ABS &
CPVC
H
WATER
CONN.
DIA.
MAX 4”
PVC,
ABS &
CPVC
SHIPPING
WT (LBS)
FL. TO
AIR
Determining required vent length
80027 Rev 6/08
Loading...