Bock Water heaters Commercial Oil-Fired Water Heaters User Manual

Oil-Fired
Commercial Water Heaters
Featuring Bock’s Legendary
The heat exchanger with
hundreds of turbons to
boost heat transfer --
with less fuel.
Standard & ASME Construction
3-Year limited warranty on commercial installations
68 to 113 Gallon Capacities
155,000 to 623,000 BTU
Cobalt-enriched Glass-Lined Tank
Dual Magnesium Anode Rods to Inhibit Corrosion
Oil-Fired
71E 72E, 73E, 120E, 541E
Outlet
Auxiliary Outlet: 32EC/BCS, 71EC, 51EC/BCS
Inlet
T&P Relief Valve
D C
B
E
A
Drain Valve/ Return: 32E, 50ES, 51E
Aquastat Connection
Drain Valve/ Return: 71E
Hand-Hole: 50ES
Hand-Hole: 71E
Outlet
Auxiliary Outlet
Inlet
T&P Relief Valve
D C
B
E
A
Drain Valve/ Return
Aquastat Connection
Hand-Hole
Return: 120E, 190E, 241E, 361E
Outlet
High Limit
Inlet/ Return
T&P Relief Valve
C
B
E
A
Drain Valve
Aquastat Connection
Hand-Hole
190E, 241E, 361E
Shipping Weight
(lbs)***
Model
Storage
(gal)
Rated Input
BTH/HR GPH A B C D E Standard ASME
Recovery
@ ∆ 90°F
(GPH)
Max. Temp
Setting
(°F)
Inlet
Pipe
Dia.
Outlet
Pipe
Dia.
Return
Pipe
Dia.
Dimensions
71E 68 173,000 1.25 177 160** 1” 1 1/2”* 1 1/2” 66” 26” 6” 13 1/2” 22” 438 N/A 72E 67 199,000 1.50 212 160** 1” 1 1/2”* 1 1/2” 58” 28” 8” 16” N/A 503 N/A
73E 67 242,000 1.75 258 180 1” 1 1/2”* 1 1/2” 58” 28” 8” 16” N/A 503 N/A 120E 113 155,000 1.10 163 180 1” 2”* 2” 67” 31 1/2” 6” 19” 22” 709 N/A 190E 113 190,000 1.35 199 180 1” 2”* 2” 67” 31 1/2” 6” 19” 22” 709 N/A 241E 109 277,000 2.00 286 180 1” 2”* 2”* 67” 31 1/2” 8” 19” 22” 856 912 361E 91 415,000 3.00 443 180 1”
2”* 2”* 67” 31 1/2” 9” 23” 26” 1014 1050
541E 83 623000 4.5 648 180 2” 2”* 2”* 66” 34” 10” N/A 30 1/2” 1232 1258
*Nipple not included **Optional setting, contact factory ***Weight does not include burner and controls
T&P Valve: Factory Installed Drain Valve: Factory Installed Brass Valve Standard Voltage (all): 120V, 60 Hz, 1P Pressures (all): Working Pressure, 150 psi; Testing Pressure, 300 psi
ASHRAE: All Bock Products Meet or Exceed Current ASHRAE Standards.
Warning: Do not install on combustible ooring. Installation should be in accordance with all national and/or local codes. In the absence of local
codes, refer to NFPA 31 or ANSI Z.21.10.1.
(on selected models)
Caution: The recommended maximum hot water termperature setting for normal residential use is 120°F. Bock recommends a tempering valve or anti-scald valve be installed and used according to the manufacturer’s directions to prevent scalding.