Improper installation, adjustment, alteration, service
or maintenance can cause serious injury or property damage. Refer to this manual. For assistance
or additional information, consult a qualified installer
or service agency.
WARNING:
If the information in these instructions is not followed exactly, fire or explosion may result and can
cause property damage, personal injury or death.
WARNING:
Follow minimum combustible clearance as noted
on water heater label. Do not install on combustible
flooring (see Figure 2, Page 3). Install in accordance with all local codes. In the absence of local
codes, refer to NFPA 31 or ANSI Z21.10.1.
CAUTION:
The recommended temperature for normal residential use is 120°F. The dial on the aquastat does not
always reflect the outcoming water temperature,
which could occasionally exceed 120°F. The variation in outcoming temperature could be based on
factors including but not limited to usage patterns
and type of installation. Test your water at the tap
nearest to the water heater. (See page 5 for measuring the outcoming water temperature).
WARNING:
Hotter water increases the risk of scald injury. Before changing the temperature setting, read the
instruction manual. Temperatures at which injury occurs vary with the individual’s age and length of
exposure.
The slower reaction times of children, elderly and
physically or mentally impaired persons increases
the scalding hazard to them. It is recommended lower
water temperatures be used where these situations
exist.
Households with small children or invalids may require a temperature setting less than 120°F to prevent
accidental contact with hot water.
To lower water temperature use point-of-use temperature limiting devices.
WARNING:
Flammable vapors may be drawn to this water heater from other areas of the structure by air currents.
Do not store or use any flammable liquids in the
vicinity of this heater.
WARNING:
Water heater blankets may restrict air flow to the
heater and cause fire, asphyxiation, personal injury
or death.
#23420Rev 7 (7/11)
110 South Dickinson Street • P.O. Box 8632 • Madison, WI 53708-8632
FAILURE TO FOLLOW
THESE INSTRUCTIONS
OR ALL APPLICABLE
UILDING CODES AND
B
REGULATIONS VOIDS
THE WARRANTY ON THIS
WATER HEATER.
THIS MANUAL HAS BEEN PREPARED TO ACQUAINT YOU WITH THE INSTAL-
ATION, OPERATION, AND MAINTENANCE OF YOUR WATER HEATER AND
L
TO PROVIDE IMPORTANT SAFETY INFORMATION.
ead all instructions thoroughly before attempting installation or operation of the
R
water heater. Keep these and all component instructions for future reference.
The manufacturer of this water heater will not be liable for any damages caused
by failure to comply with the installation and operating instructions outlined on the
following pages. These instructions are a guide for the correct installation of the
water heater.
If the installer lacks the necessary skills or has difficulty following the
directions, do not proceed but get help from a qualified person for that part of the
installation that is not understood.
Local plumbing and electrical codes must be followed in the installation of this
water heater. In the absence of a local code use the UNIFORM PLUMBING
CODE and the NFPA Code. Local codes may supersede instructions in this installation manual.
MULTIPLE BURNER
INSTALLATION
SELECT THE RIGHT
LOCATION
Check for exhaust fans in
the heater room or adjacent areas which draw
combustion air away from
heater.THEHEATER
MUST HAVE COMBUSTION AIR TO OPERATE.
When two or more burners are used, each unit should have a separate
supply line to the fuel pump to prevent nuisance lockouts caused by one or both
pumps starving for oil. If this is not possible, the use of a priority
control is recommended.
Check new equipment to see if all components are in good condition.
The water heater and oil burner may be shipped as separate units. The aquastat
and immersion well may be packed with the oil burner.
The new water heater requires fuel (#I or #2 heating oil), electricity and should be
close to the chimney and water supply. Locate the heater near a floor drain if possible for easy maintenance and protection if trouble should occur. Allow ample
space around the heater for servicing (see combustible clearance warning, page
1). Adequate air for combustion must be available. NOTE: Locate the heater so it
is not subject to physical damage by moving vehicles or possible flooding.
FIGURE 1
WHEN THE WATER HEATER IS USED IN A COMBINEDAPPLIANCEAPPLICATION,PLEASE
CONTACT THE LOCAL DISTRIBUTOR OR THE FACTORY FOR INSTALLATION INSTRUCTIONS ON
“SYSTEM PLUS”.
– 2 –
DO NOT INSTALL THE WATER HEATER ON COMBUSTIBLE FLOORING (see Figure 2).
31 or contact Bock Water Heaters with questions concerning proper flooring materials.
Minimum clearance to combustible construction is:
SIDES 6"; BACK 6"; FRONT 24". The installation of
this water heater must conform with local codes and
ordinances. In the absence of local codes, the installation must comply with the National Fire Protection
Association (NFPA 31) Code.
Refer to NFPA
CONNECT WATER
NOTE: INDEX LINE ON INLET NIPPLE
MUST BE ALIGNED WITH ARROW ON
DECAL. HOLD INLET NIPPLE WHEN
TIGHTENING FITTINGS. ROTATI NG
NIPPLE COULD DRASTICALLY REDUCE
PERFORMANCE.
PIPING
Connect the water piping, being careful not to apply heat to the heater
ipples. Install dielectric unions and shut off valves on both hot and cold water
n
lines.
Hot water outlet
(“HOT”) is on tank
top. Cold water inlet
is on right front
bottom of 33E and
40E. On all other
models, cold water
inlet is on tank top.
The 40E and all “C” models (example: 32EC, 51PPC) have a 1” NPT tapping located on the front left side of the tank. This is an alternate outlet for use with combined
appliance applications. If this fitting is not used, plug it with a fitting suitable for
potable water.
A 1” NPT fitting is also located behind the drain valve on the 40E and all
“C” models. This is for use as an alternate inlet or a combined appliance return.
Yourheaterisshippedwithareducerinthislocationtomount
the drain valve.
Models 33E and 40E are equipped with an inlet flow diverter installed in the tank. Heaters equipped with this diverter
are labeled with a decal next to the inlet (shown to the left).
The purpose of this diverter is to help keep the tank bottom
free of sediment by aiding tank flushing. The index line on
the diverter nipple must be aligned with the arrow on the
decal (left) to function properly. Do not allow the diverter to
rotate out of position when tightening the inlet fittings.
The drain valve fitting may be used as an alternate cold water inlet on heaters
equipped with a dip tube, as shown in Figure 3. By plumbing a “T” into the drain
fitting, the cold water inlet can be relocated to this point. The dip tube must be
removed and its fitting plugged. Figure 3 also shows a copper loop heat trap
installed on the hot water outlet to reduce standby losses.
FIGURE 2
The drain valve fitting may be used as
an alternate cold water inlet on heaters
equipped with a dip tube, as shown in
Figure 3. By plumbing a “T” into the drain
fitting, the cold water inlet can be
relocated to this point. The dip tube
must be removed and its fitting plugged.
Figure 3 also shows a copper loop heat
trap installed on the hot water outlet to
reduce standby losses.
Note: When converting to this configuration on an existing heater, visually
inspect the heater and make certain it
does not have scale buildup on the
bottom of the tank. Scale can restrict the flow
of water into the tank.
CAUTION!! Scalding injury and/or water
damage can occur from either the manual
lifting of the lever or the normal operation of the
T&P valve if it is not piped to a proper drain. If
the valve fails to flow water or reseat, call
a plumber.
FIGURE 3
– 3 –
Inspect the incoming water line for check valves or water pressure reducing
alves. Any type of check valve may cause pressure to build up in the heater and
v
cause tank failure. If the heater is installed in a closed system or if backflow preventers and pressure regulators are installed, add an expansion tank. Do not try
o heat hard water. Install a water softener if the heater is being used in a hard
t
water area (water hardness more than 7 grains).
An approved temperature and pressure (T&P) relief valve is factory installed in
the opening provided in the upper right hand side of the heater. Pipe the T&P to
within 6" of the floor or to a floor drain with a free flowing drain pipe. Do not install
a check valve in the cold water line.
CONNECT TO
CHIMNEY
MOUNT THE OIL
BURNER
Using “L” or “A” type venting, connect the heater to the chimney. Use the same
size smoke pipe as the heater flue pipe (on models 20e, 20pp, 32E, 32PP and
33E, you may use 4" with a reducer if needed).
WARNING: On Models 40E, 5OES, 50ESC, 51E, 51EC, 51PP, 51PPC. 71E and
120E, do not reduce the smoke pipe diameter. Run a separate smoke pipe from
the water heater to the chimney wherever possible.
If it is necessary to tee into an existing smoke pipe, be sure the connector being
teed into is large enough to accommodate the products of combustion of all units
attached to it. When teeing into another connector, run in at 45° angle (see Figure
1). Install a draft regulator control only if necessary. Overfire draft should not be
positive. Stack draft should be -.02” W.C. minimum to -.05” W.C. maximum; CO2
should be a minimum of 11%. If a draft control is installed on the chimney,
another one on the heater is not needed.
The oil burner is equipped with a primary relay. An aquastat with immersion
well is packed with the burner. The thermostat is factory set at 120°F for residential use (see caution on page 1 regarding temperature variations). Install the
immersion well with the aquastat and check the bulb length (see “Burner &
Controls” section, page 10).
Remove the cardboard core from the burner opening. Mount the burner on stud
bolts and place the gasket (supplied) between the burner flange and the heater.
Secure the burner to the heater with 1/4 -20 nuts (supplied). Open the inspection
door on the heater and check the burner tube with a mirror before firing to
be sure the opening is not blocked (see Maintenance and Service sections on
pages 6 and 7 for troubleshooting).
CONNECT THE
ELECTRICITY
All wiring must comply with applicable codes and ordinances. The primary relay
is wired to the burner at the factory. Install the aquastat well in the 3/4" tapping at
the front of the heater. Be sure the sensing bulb is inserted all the way into the
well. For Honeywell aquastats, tighten the screw on top of the aquastat to secure
the control to the well. For Carlin EZ-Temp aquastats, refer to the pre-packaged
installation guide for proper set-up procedure. Refer to drawings for correct models. Connect the power supply to the aquastat and run through a fused disconnect switch (attached to heater in field). See Figure 1.
CONNECT THE OIL
LINE
A properly sized and rated oil filter or strainer shall be installed in the oil
supply line (NFPA 31, 4.5.4). In addition, for models 20e and 20pp, a secondary means of filtration before the fuel oil pump is recommended. Bock
WARNING!! WHEN YOU
INSTALL THE BYPASS
PLUG YOU MUST RUN A
TWO-LINE SYSTEM.
recommends the Delavan Line Filter (25 micron) for secondary filtration.
Gravity System: The oil burner is normally equipped with a single-stage pumpequipped for one line (gravity) flow. Use 1/2" O.D. soft copper tubing and attach
with flared fittings. DO NOT USE COMPRESSION FITTINGS. Install the shut
off valve and oil filter in the oil line. Follow the pump manufacturer’s instructions
– 4 –
(attached to the pump).
ift System: The burner should be ordered with a 2-stage pump. Run a 2-line
L
system (suction and
eturn lines). Install the bypass plug according to the
r
instructions attached to pump (plug is in a bag with an instruction sheet).
or any horizontal run exceeding the maximum length specified in Figure 4, or
F
any lift of more than 10 feet, a booster pump must be used. Booster pumps may
be obtained from Sun Tec Hydraulics, Rockford, Illinois. Booster pumps must be
installed as close to the oil supply tank as possible. Suction and return lines
should be the same diameter and both go within 6” of the bottom of the tank. The
return line should stop slightly above the suction line. Use a minimum of fittings.
Make bends in the tubing with as large a radius as possible. DO NOT USE COMPRESSION FITTINGS. Caution must be used in the final connection to the burner
so as not to strain the fuel unit. Before attaching the tubing to the burner, form a
coil in the tubing to minimize any vibration. Bury the oil lines in the floor for quiet
operation, making sure there are NO CONNECTIONS OR FITTINGS UNDER
THE FLOOR.
1. Fill the tank with water, opening a hot water faucet to allow trapped air to
escape from the heater. Open the cold water inlet valve. Shut off each faucet as
it delivers water that is free of air. Inspect for leaks. Never operate an empty or
partially full heater.
2. Be sure the oil tank is filled with #1 or #2 heating oil. Remove the transformer
hold down screw and swing the transformer back open on the hinge. Rotate the
blower wheel a few times to loosen the pump shaft. Swing the transformer closed
and fasten.
3. Bleed air from the oil line by opening the bleed valve on the fuel pump. Attach
a small plastic tube to the bleed valve fitting on the pump and run to a gallon
container. Turn on the electricity and set the thermostat so the burner motor runs.
The heater will not ignite when the bleed valve is open. Bleed the line until the oil
is completely clear, not milky or opaque. The oil must be transparent and free of
air bubbles and froth. To keep the burner control from locking out while bleeding
the pump, attach a jumper between the flame detector terminals after starting the
burner. Remove the jumper when finished. Shut the bleed valve and the burner
will ignite. Remove the plastic tubing. Set the pump pressure to 100 PSI for
Wayne, Carlin and Beckett burners and 150 PSI for Riello burners.
– 5 –
4. Adjust the burner combustion air in accordance with the burner manufacturer’s
instructions. Using combustion instruments, check the C02 and smoke. The C02
hould be at least 10 1/2% minimum with 0-to-trace smoke on the Bacharach
s
scale.
. While the burner is operating, disconnect one of the yellow cad cell wires.
5
Check to see that the burner control locks out in the time specified on the control.
Reattach the wire and reset the control. The burner should restart. Note: You may
have to wait a minute before resetting the control.
MEASURING THE
OUTCOMING
WATER
TEMPERATURE
MAINTENANCE
Have the oil burner
serviced once each
year by a qualified
oil burner service
person. Service
should comply with
the burner manufacturerʼs recommendations and include:
6. The thermostat is factory set at 120°F for residential use. (See caution on
page 1 regarding temperature variations. It is the responsibility of the homeowner and installer to verify that the installer follows the recommended quantitative
testing for measuring the outcoming water temperature. To make sure that the
system works properly after installation and in the future, it is recommended that
the heater’s performance be measured and monitored. Run water out of the tap
nearest the heater until it comes out warm. Using a calibrated thermometer, take
a measurement. If the water is not at a suitable temperature for the installation,
have a qualified service person adjust the aquastat. Contact Bock for further
information on the thermometer if needed.
WARNING: Hydrogen gas can be produced in a hot water system served by
a heater that has not been used for a long period of time (generally two
weeks or more.) Hydrogen gas is extremely flammable. To reduce the risk
of injury, open the hot water faucet at the highest location in the house for
several minutes before using any electrical appliance connected to the hot
water system. If hydrogen is present, there may be an unusual sound such
as air escaping through the pipe as the water begins to flow. Do not smoke
or allow an open flame near the faucet at the time it is open.
1. Oil the burner motor (5-10 drops) with #10 SAE motor oil (if applicable).
2. Install a new burner nozzle of the correct rate and angle. (See Chart A, page 11).
3. Clean and adjust the electrodes and inspect for cracks in the porcelain. Check
for corrosion on the buss bars and ignitor terminals.
4. Change the fuel oil filter and have the oil tank checked for sediment. Clean the
tank if necessary.
5. Keep the oil tank full to prevent water vapor from collecting inside the tank,
especially during the summer.
6. Check the smoke pipe and chimney. Clean and repair if necessary.
7. EVERY SIX to 12 MONTHS. Drain water from the heater tank and inspect for
sediment or lime accumulation. Flush out if necessary. If lime has accumulated,
remove with a commercial compound for dissolving lime or by scraping through
the hand hole opening (if supplied). Check water softening equipment if lime is
found in the tank. DO NOT ATTEMPT TO HEAT HARD WATER. (See maintenance label on heater.)
8. Change the magnesium anode rods every six to 12 months or when theyare reduced to 3/8” diameter (see maintenance label on heater). We recommend the installer use PermaBond LH-050. Teflon tape should not be used when
installing magnesium or aluminum anode rods.
9. Open the relief valve test lever to flush out the tank. Make sure it reseats itself.
– 6 –
10. If the heater is to be shut off in cold weather, drain the tank to prevent freezing.
SERVICE
1. Check the fuel supply, electrical wiring and fuses, and make sure temperature
control is calling for heat.
. If the motor runs but there is no flame, remove the electrode assembly, clean,
2
readjust to the burner manufacturer’s specifications, check the electrode porcelain for cracks and replace if necessary. Check the transformer to see if it is pro-
ucing a strong spark. (Use extreme CAUTION: The transformer has a 10,000
d
volt output). Check that the coupling between the motor and pump shaft is not
slipping. Check the set screw on the blower wheel for tightness. Clean or replace
the nozzle with the correct size and spray angle (see Chart A, page 11).
3. Bleed the pump and check for clear, air-free oil. If the oil is milky or frothy, check
the line for air leaks at fittings. Tighten all fittings again. Check the filter gaskets
and make sure cartridge is clean.
4. If the burner motor does not run, check the motor thermal overload button (red
button on end of motor). Reset the primary control by pushing the reset button on
the control. If the burner motor still does not run after resetting the control, turn off
the electricity and replace the flame detector (with the same make) located in the
burnercompartment.Resettheprimarycontrol.Ifthemotorstill
does not run, replace the control.
5. If the burner ignites and runs a short time (30-40 seconds), then goes out on
safety, replace the flame detector. If the burner still runs only a short time, replace
the control.
6. If there is a smell of oil or combustion products, remove and clean the electrode
assembly (see No. 2 above). Check the draft in the stack above the heater. Stack
draft (pull in) should be -.02” W.C. minimum to -.05” W.C. maximum.
Check for exhaust fans in the heater room or adjacent areas which draw combustion air away from heater. THE HEATER MUST HAVE COMBUSTION AIR TO
OPERATE.
For more information, contact your installer, the nearest Bock distributor, or write,
call or fax:
BOCK WATER HEATERS, INC.
110 South Dickinson Street, Madison, WI 53703
Phone: 608/257-2225 • Fax: 608/257-5304
– 7 –
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.