Thank you for purchasing the Sonic-Pro series S4 ultrasonic flowmeter.
This instruction manual provides important information regarding the safe installation,
operation and maintenance of the flowmeter. Please read it carefully before attempting to
install or operate the meter. A copy of this manual should be kept by the operator. Extra
copies of this manual are available from your supplier or directly from the manufacturer.
The following important symbols are used throughout this manual and on labeling affixed to
the flowmeter:
CAUTION
risk of electric shock
Sonic-Pro
This symbol identifies a risk of electric shock where the possibility of injury or
death is present.
!
!
CAUTION
risk of danger
CAUTION
risk of danger
QUESTIONS REGARDING THE SAFE USE OF THIS PRODUCT AND OTHER TECHNICAL
ASSISTANCE MAY BE DIRECTED TO:
!
This symbol identifies a risk of injury or death is present.
In all cases, when this symbol is used on labeling affixed to the flowmeter, the
documentation needs to be consulted to find out the nature of the potential
HAZARD and any actions which have to be taken.
If the equipment is used in a manner not specified by this instruction manual,
the protection provided by the equipment may be impaired.
Blue-White Industries
714-893-8529
techsupport @blue-white.com
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
d
Sonic-Pro
Page 2
1.0 Product Overview
The Sonic-Pro series S4 Ultrasonic Flow Meter can measure fluid flow in water and many
other clean fluids with sound speeds that are similar to water. The meter measures fluid flow
using the Transit Time method. The S4 ultrasonic sound transducers do not touch the
process fluid and there are no moving parts. This method of flow measurement is safe, nonintrusive and requires little to no maintenance.
The fluid being measured must be relatively “clean” to enable the sound waves to complete
their circuit. The maximum amount of particles should not exceed . The 5% (50,000 ppm)
meter cannot measure through air. Air bubbles and excessive turbulence will disrupt the
sound beam.
The angle of the sound beam, as it travels through a material, is effected by the speed that
sound travels through that material. As the sound speed changes, the angle changes. Sound
travels through 68 F clean water at a speed of 1,481 meters per sec. The S4 ultrasonic
sound transducers are factory positioned for a fluid sound speed of 1,500 m/sec +/- 100.
They cannot be adjusted in the field.
Water that contains concentrations of other chemicals, or other chemicals entirely, may be
acceptable provided the chemical does not change the sound speed (SOS) more than
approximately +/- 100 meters per second and provided the fluid allows the sound beam to
pass through unimpeded. Note that the speed that sound travels through the fluid is effected
by changes in the fluid’s density.
O
The S4 includes a 6-button user interface that can be used to configure the meter. The
optimum sound speed setpoint can be adjusted by the user within the range of 1,500 m/sec
+/- 100 m/sec.
TRANSIT TIME MEASUREMENT PRINCIPLE
During operation in the Transit Time measurement method, a short ultrasonic signal burst
passes first in one direction and then in the other between two transducers separated along
the length of the pipe. When traveling in the same direction as fluid flow, the burst is carried
along by the fluid and arrives earlier as a result. When traveling against fluid flow, the burst is
held back by the fluid and arrives later. The SPU (measures this Signal Processing Unit)
difference in time-of-flight in the two directions. From this, the actual time-of-flights, the
distance traveled in the fluid and the angle of the ultrasonic signal path, it calculates the fluid
velocity.
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
d
Page 3
Sonic-Pro
2.0 Flowmeter SPU Installation
2.1
Unpacking
2.2
Mounting
Location
!
risk of danger
The Sonic-Pro Flowmeter is shipped with the following items:
!Sonic-Pro Flowmeter SPU (Signal Processing Unit)
!Sonic-Pro Inline Pipe Fitting
!Enclosure Mounting Hardware (not included in sensor mounted units)
The Sonic-Pro was designed to be installed and operated by qualified personnel only. Do not
attempt to install or operate the meter if you are unsure. Seek qualified assistance. Please
note that warranty coverage does not include damage due to misuse or improper
installation.
If remote mounting the SPU, select a mounting location that is within reach of the transducer
cables and power supply. The transducer cable must not be cut or modified. Note that the
Sonic-Pro can accurately measure flow from either direction.
The SPU can be mounted on a wall or on a horizontal or vertical run of pipe. Although the
Sonic-Pro is designed to withstand outdoor conditions. A cool, dry location, where the unit
can be easily monitored is recommended. Special ventilation is not required.
CAUTION
Do not position the equipment so that it is difficult to disconnect the power
supply cord.
2.3
Wall or Pipe
Mounting
When the SPU is not mounted directly to the Inline Fitting, the SPU must be installed on a
solid, secure surface such as a solid wall, panel, wall studs, etc. DO NOT install the meter
on drywall with anchor bolts.
8.00 in
[20.3 cm]
The SPU can be mounted on horizontal or vertical pipe. The pipe must be secure and of
sufficient strength to support the weight of the SPU.
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
d
Sonic-Pro
Page 4
3.0 Ultrasonic Transducer Installation
3.1
Pipe Fitting/
Transducer
Installation
Minimum Straight Pipe Length Requirements
The Sonic-Pro’s sound wave beam is only affected by fluid that actually passes through the
beam and therefore, the meter will not measure with high accuracy if the fluid velocity is not
consistent across the entire pipe diameter. Flow disturbances such as pumps, elbows, tees,
and valves in the flow stream can cause swirl patterns and vortices that will affect the
measurement accuracy or disrupt flow measurement capability. Install the transducers on a
straight run of pipe as far as possible from any disturbances. The distance required for high
accuracy will depend on the type of disturbance.
Type of Disturbance
Flange
Reducer
o
90 Elbow
o
Two 90 Elbows - 1 Direction
o
Two 90 Elbows - 2 Directions
Gate valve or Pump
Upstream from Transducers
5 x Nominal Pipe Size
7 x Nominal Pipe Size5 x Nominal Pipe Size
10 x Nominal Pipe Size5 x Nominal Pipe Size
15 x Nominal Pipe Size5 x Nominal Pipe Size
20 x Nominal Pipe Size5 x Nominal Pipe Size
25 x Nominal Pipe Size5 x Nominal Pipe Size
Straight Lengths of Pipe Required
Downstream from Transducers
5 x Nominal Pipe Size
Transducer Mounting Requirements
!
The meter can be mounted on horizontal or vertical runs of pipe.
!
Mounting anywhere around the diameter of vertical pipe is acceptable, however, the pipe
must be completely full of fluid at all times.
!
Back pressure is required on downward flows to ensure a full pipe.
!
See the minimum straight length of pipe requirement chart above.
!
Related piping must be independently supported. The meter should not be allowed to
support the weight of related piping.
NO
Pipe must be full
NO
Air could be trapped
Down flows
must have
back pressure
OK
!
160° F (71° C)
150° F (65° C)
140° F (60° C)
130° F (54° C)
120° F (49° C)
110° F (43° C)
100° F (38° C)
TEMPERATURE F (C)
90° F (32° C)
80° F (27° C)
70° F (21° C)
OK
L >= 5DL >= 10D
See minimum straight length requirements above
INLINE PIPE FITTING
TEMPERATURE VS PRESSURE
HDPE and 316SS Adapters
PVC Adapters
0
50100
WORKING PRESSURE (PSI/g)
150
200250
300
OK
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
d
Page 5
Sonic-Pro
4.0 Wiring Installation
4.1
Electrical
Connections
4.2
Cable Gland
Liquid-Tight
Connections
The meter must be powered by 15 to 28 volts DC. Depending on the model ordered, an
AC/DC plug-in transformer may have been be supplied for this purpose. See the diagram
below for wiring of output signals, communications signals and process control relays.
The transducer cable length is factory fixed. Do not attempt to modify the length of these cables. Various cable lengths are available from the factory. Contact the factory if you need
assistance.
Shielded cable is recommended for signal output connections.
The Sonic-Pro SPU wiring compartment is equipped with:
Ÿ Three liquid-tight cable gland connectors for cable diameter from .200 to .394 inches (5.1
to 10.0 mm).
Ÿ Two liquid-tight cable gland connectors cable for diameters from .118 to .255 inches (3.0 to
6.5 mm).
Ÿ One communications cable liquid-tight cable gland grommet for cable diameters from .190
to .205 inches. It is provided for any one of the following cable types:
Ethernet Cable
RS-232 serial cable
Note that the blank grommet plug should be used when the communications cable grommet
is not required.
4.3
Wiring
Compartment
Back-up
Battery
Compartment
(4 D cells -
not included)
Communications
Cable Grommet
Optional
Communications
Circuitry
Wiring Terminals
Main PCB
Transducer A Transducer B
USB
Connection
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
Communications
Circuitry
Input Socket
d
Touchpad
Connection
Sonic-Pro
4.4
Wiring
Terminals
The terminal blocks are plug type capable of accepting 14 to 30 AWG wire.
FUNCTIONTERM PIN #DESCRIPTION
POWER INPUT:
Primary power
Chassis Ground
POWER INPUT:
Battery Back-up power
PULSE FREQUENCY
OUTPUT:
Open Collector
PADDLEWHEEL
SENSOR INPUT:
AC Sine wave
RELAY ‘A’ OUTPUT
RELAY ‘B’ OUTPUT
Chassis Ground
ANALOG OUTPUT:
4-20 mA
TRANSDUCER
INPUT:
Transducer A
TRANSDUCER
INPUT:
Transducer B
T1
T1
T1
T2
T2
T2
T2
T2
T2
T3
T4
1
2
3
4
5
1
2
3
4
5
6
7
8
9
10
11
12
13
1
2
3
1
2
3
RATING
(+) 15-28 Vdc
(-) 15-28 Vdc
Ground
(+) Positive
(-) Negative
(+) Positive
(-) Negative
(+) Positive
(-) Negative
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
Ground
(+) Positive
(-) Negative
(+) Red
(-) Black
Green or Bare
(+) Red
(-) Black
Green or Bare
15-28Vdc, 400mA max
4 D cell size batteries
(Alkaline batteries only are acceptable)
Type: Open collector w/ internal 1 K pull-up to 5V.
Can be pulled up to 30V @ 10mA (3K pull-up)
Type: FORM C
Load capacity: 30V, 100mA max (ext. supplied)
Type: FORM C
Load capacity: 30V, 100mA max (ext. supplied)
Current output: 4-20 mADC, isolated.
Max Load Impedance: 1K ohm
Power: Internal
Resolution: 12 bits
Accuracy: Less than 0.1% F.S.
Update Rate: 1.0 s
Page 6
Analog Out (+)
Chassis
Analog Out (-)
V Bat (+)
V Bat (-)
5 4 3 2 110 9 8 7 6 5 4 3 2 13 2 13 2 1131211
Battery
T1T2T3T4
WARNING
INPUT POWER LIMITS
DC INPUT
15~28 Vdc-15W
ANYBUS
COMMUNICATIONS
DC (-)
DC PWR
POWER
INPUTS
DC (+)
4-20 mA
Relay B (n/c)
Relay B (n/o)
Relay B (com)
Relay A (n/c)
Relay A (com)
Chassis
Relay B
USER INTERFACE
CONNECTIONS
Relay A
Relay A (n/o)
Pulse In (-)
Paddle
Pulse Out (-)
Pulse Out (+)
Pulse In (+)
Pulse
RED (+)
GRN
BLK (-)
Transducer A
TRANSDUCER
INPUTS
RED (+)
GRN
BLK (-)
Transducer B
USB
TOUCHPAD
INPUT
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
d
Page 7
Sonic-Pro
5.0 Operation
5.1
Power On
5.1.1
Battery Powered
operation
1. If power is present on Terminal T1 pins 1 & 2, the meter is always powered on.
2. If power is removed from Terminal T1 pins 1 & 2, and 4 D-Cell batteries are installed on
Terminal T1 pins 4 & 5, the meter will stay on (battery back-up). Under these conditions, the
meter can be turned on/off by pressing and holding the front panel ENTER button for three
seconds.
3. If power is only present on the battery Terminal T1 pins 4 & 5, then the meter can be
turned on/off by pressing and holding the front panel ENTER button for three seconds.
Operating time is limited when powered by batteries only.
While the batteries pack is provided primarily as back-up power, the S4 meter can be
operated solely with 4 D-cell batteries (not included). The meter can be configured to sleep
between measurements in order to conserve power. The approximate battery life is .....
Continuous Running
The following meter features are disabled during battery operation:
Ÿ Communications Module
Ÿ Analog output
Ÿ Pulse Frequency Output
10 / 10
128 Hr72 Hr310 Hr377 Hr450 Hr
On / Sleep Time (seconds)
10 / 1005 / 1003 / 268
5.2
Run Screen
5.2.1
Fault Screen
When the S4 is factory ordered with a pipe fitting/transducer, the pipe fitting data and the
default display feature parameters are pre-configured. When power is applied and there is
water in the pipe fitting, the following RUN display screen will be displayed.
Transducer Separation
Distance
Flow Direction
Flow Rate Units
0.28”
U.S Gallons/Min
25
Total Units
Ÿ Press the ENTER button to enter the menu system.
Ÿ Press the ESC button to clear the flow total to zero (if enabled in configuration).
Ÿ Press the up arrow p to toggle the flow rate to linear Feet/Sec., Meters/sec and back to
the configured user units of measure.
There are three possible FAULT indicator screens.
Ÿ FAULT 11 - Transducers are not connected or there is no fluid in the pipe.
Ÿ FAULT 12 - The allowable SOS (Speed Of Sound) error set-point has been exceeded.
Ÿ FAULT 21 - The configuration data is not valid.
U.S Gallons
0.28”
U.S Gallons/Min
XDCR Disc.
U.S Gallons
F-11
105
.
.
0”
1482
05469
Measurement Reliability
Battery Life
Measured Sound Speed
Flow rate
Flow Total
(press and hold ESC to clear)
Error Code
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
0
d
Sonic-Pro
5.3
Menu
Navigation
Page 8
The Configuration Menu
From the RUN mode, press and release the ENTER button to enter the CONFIGURATION
menu. The following menu will be displayed:
5.3.1
Selecting and
Entering Menus
5.3.2
Selecting Optional
Items
Ÿ Press up arrow p or down arrow q to select menu items.
The selected item will be highlighted.
Ÿ Press right arrow u or ENTER to enter the selected menu.
Ÿ Press left arrow t to go back one menu.
Ÿ Notice the gray area. These menu items are hidden from
view. Press the up arrow p or down arrow q to display
hidden menu items.
Ÿ Press up arrow p or down arrow q to select optional
configuration items. The selected item will be highlighted.
Ÿ Press left arrow t or ENTER to choose the selected
optional item and return to the menu heading.
Paddle Wheel
XDCR Settings
Meter Settings
Output Settings
Clock
Calibration
Global Config.
About
U.S. Gallons
Ounces
U.S. Barrels Liq.
U.S. Barrels Oil
Cubic Feet
Acre Feet
Imperial Gallons
Cubic Meters
Liters
Milliliters
FR Custom V/Gal
5.3.3
Inputting Data
5.3.4
Save Configuration
Ÿ Press right arrow u or left arrow t to select a digit to
modify. Pressing the left arrow t will create additional
numbers to the left.
Ÿ Press up arrow p to increase or down arrow q to
decrease the value.
Ÿ Press ENTER to confirm the modifications and return to
the menu heading.
Ÿ Press ESC to cancel the modifications and return to the
menu heading.
Ÿ Press left arrow t to exit to the main menu.
Ÿ Press down arrow q to Highlight Save Config.
Ÿ Press right arrow u or ENTER to save the configuration
changes.
Ÿ Press ENTER to confirm the configuration changes have
been saved.
Ÿ Press up arrow p to RUN.
Ÿ Press right arrow u or ENTER to enter the RUN mode,
Enter Value
9.1000
0
Configuration
XDCR Settings
Save Config.
Configuration
XDCR Settings
Save Config.
Configuration
Configuration Saved!
OK
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
d
Page 9
Sonic-Pro
6.0 Configuration
The S4’s SPU can be used with a Paddle Wheel type sensor that outputs an AC Sine wave or
an Ultrasonic type sensor.
6.1
Configure the
SPU for a
Paddle Wheel
Sensor
6.2
Configure the
SPU for an
Ultrasonic
Inline Pipe
Fitting
Configuration
Paddle Wheel
When using an AC Sine wave Paddle Wheel type flow sensor and pipe fitting, the installer
must input the pipe fitting K-factor. The K-Factor is the total number of pulses output by the
sensor per gallon of fluid flow for a specific pipe fitting. The K-factor is different for each pipe
fitting. See the paddle wheel sensor’s instruction manual for a list of pipe fitting K-factors.
Configuration
Run
Save Config
Paddle Wheel
K-Factor
Enter Value
0.0000
When using Ultrasonic Transducers (XDCR), if the SPU and the Ultrasonic Inline Pipe
Fitting was shipped from the factory as a single model number, the SPU is pre-configured
with the proper model number and calibration constants shown on the calibration label
attached to the pipe fitting. If the pipe fitting was sold separately, the SPU will need to be configured with the following data shown on the calibration label:
1. Measurement Units. The default value for all inline fittings is ENGLISH.
2. Model. The default value for all inline fittings is “C”.
3. Mount Method. The default value for all inline fittings is “V”.
4. Cable Length. Enter the length in feet. The available cable lengths are: 1 foot (SPU
mounted directly on the pipe fitting), 10, 25, 50 or 100 feet.
5. Flow Direction -> Direction. The default value for all inline fittings is “A -> B”.
6. Flow Direction -> Settings. Each flow direction has a unique SCALING and ZERO
VALUE number shown on the pipe fitting calibration label. Note that the ZERO number
may be POSITIVE or NEGATIVE.
7. Pipe Outside Diameter. Shown on the pipe fitting calibration label. Do not use your
inlet/outlet pipe size.
8. Pipe Wall Thickness. Shown on the pipe fitting calibration label. Do not use your
nominal pipe size.
9. Pipe Material. Shown on the pipe fitting calibration label. Do not use your inlet/outlet pipe
material.
10. Fluid Type. Select WATER or CUSTOM.
11. Fluid SOS. If WATER is selected, it is not necessary to input a fluid SOS. If “CUSTOM”
fluid type is selected, the Speed of Sound (SOS) for the custom fluid must be entered
manually. Note that the SOS must be within the pipe fitting’s SOS range.
Run
Save Config
ProSeries
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.
XDCR Settings
d
Meas. Units
Transducer
Pipe
FluidFluid Type
ENGLISH
Mount Method
Cable Length(ft)
Flow Direction
Pipe Outside Dia.
Pipe Wall Thick.
Pipe Material
Pipe SOS
Fluid SOS
METRIC
Model
C
I
J
V
W
Enter Value
Direction
Settings
Enter Value
0.0000
Enter Value
0.0000
Enter Value
0.0000
Enter Value
10
0000
A -> B
B -> A
A -> B
B -> A
Custom
HDPE
Custom
Water
Enter Value
0.00000.0000
Scaling(A->B)
Zero(A->B)
Scaling(B->A)
Zero(B->A)
Zero Value(B->A)
Sign(B->A)
Positive
Negative
Enter Value
Zero Value(A->B)
Sign(A->B)
Positive
Negative
Enter Value
0.0000
Enter Value
0.0000
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.