Blue Sea Systems m-ACR 7601 User Manual

5 (1)
Blue Sea Systems m-ACR 7601 User Manual

Features and Specifications for m-ACR 7601 and Mini Add-A-Battery 7649

m-ACR Automatic Charging Relay Features

Automatically combines batteries during charging, isolates batteries when discharging

The Start Isolation option protects electronics from voltage sags and spikes during engine cranking

Supports alternators up to 65 Amps

Ignition protected—safe for installation aboard gasoline powered boats

For 12 or 24 volt systems

Dual Sensing—senses charging on either battery bank

LED Status Chart

LED

BATTERY STATUS

REASON

Solid ON

Combined

Charging

Single Flash (15 sec.)

Isolated

Standby

Double Flash

Isolated (Start Isolation)

Start Isolation wire is energized

Triple Flash

Isolated (Under Voltage Lockout)

One or both batteries are below

 

 

9.5V (12V System) 19V (24V System)

Specifications

Intermittent Rating (5 min.)

115A

Continuous Rating

65A

Operating Current (Combine)

90mA

Operating Current (Open)

15mA

Cable Size (to meet current ratings)

6 AWG (16mm²)

Maximum Cable Size

1/0 AWG (50mm²)

Terminal Stud Size

1/4"-20

Maximum Torque

60 in-lbs (6.8 Nm)

Relay Contact Position

12V DC

24V DC

Combine

(30 sec.)

13.6V DC

27.2V DC

 

(2 min.)

13.0 V DC

26.0V DC

Open Low

(10 sec.)

12.35V DC

24.7V DC

 

(30 sec.)

12.75V DC

25.5V DC

Over Voltage Lockout

 

16.0V DC

--

Under Voltage Lockout

9.5V DC

19.0V DC

Under Voltage Reset

 

10.0V DC

20.0V DC

Regulatory

E marked for Ignition Protection, Meets ISO 8846 and SAE J1171 external ignition protection requirements Rated IP67----temporary immersion up to 1 meter for 30 minutes

m-Series, Dual Circuit Plus™ Battery Switch 6011 (Included with 7649 Mini Add-A-Battery) Features

Switches two battery banks simultaneously with one ON/OFF switch while maintaining battery bank isolation, minimizing the risk of a dead start battery

The COMBINE BATTERIES function parallels two battery banks in the event of a low battery

Ignition protected—safe for installation aboard gasoline powered boats

Specifications

Cranking Rating (10 sec.)

1,000 Amps

Cranking Rating (1 min.)

650 Amps

Intermittent Rating (5 min.)

450 Amps

Continuous Rating

300 Amps

Maximum Voltage

32 Volts

Cable Size to Meet Ratings

4/0 AWG (120mm²)

Terminal Stud Size

3/8"-16 (M10)

Maximum Torque

120 in-lbs (13.56 Nm)

Regulatory

E marked for ignition protection, meets UL1500 and SAE J1171 external ignition protection requirements

Rated IP66---protected against powerful water jets

Installation Instructions

m-ACR Automatic Charging Relay 7601

m-ACR Mounting

To avoid corrosion to connecting wires and terminals, mount in a dry and protected location if possible. Avoid locations directly above the battery banks.

m-ACR Electrical Connections

The wiring diagrams illustrated on the back page represent common installations and are not meant to be a guide for wiring a specific vessel.

The 7601 m-ACR is not intended to carry starting currents. Use a battery switching system with a combine batteries/parallel function if batteries may need to be combined for emergency starting. Caution: Disconnect battery connections before beginning the installation.

m-ACR Voltage Sensing

• The 7601 m-ACR will sense a charge being applied to either battery bank.

Use the wire sizing chart below to select the appropriate wire sizes to prevent overheating the m-ACR.

 

Wire Size and Fuse Rating Chart

 

Charging Amps

Min. Wire Size* (AWG)

Fuse Rating

Min. Wire Size* (Metric)

≤30

#10

40A-50A

6 mm²

≤50

#8

60A-65A

10 mm²

≤65

#6

90A-100A

16 mm²

* Larger wire sizes may be required to minimize voltage drop in long wire runs.

For more information please use the Circuit Wizard at www.circuitwizard.bluesea.com m-ACR minimum connections for operation:

Connect one battery bank positive to one of the 1/4”-20 studs.

Connect the other battery bank positive to the other 1/4”-20 stud.

Both positive connections should be made through appropriately sized circuit protection to meet ABYC recommendations. See “Wire Size and Fuse Rating” chart, above, for suggested fuse ratings.

Connect the quick connect terminal marked GND (ground) to the DC system ground through a 10A in-line fuse to prevent fault currents from flowing in this wire.

m-ACR optional connection:

To enable start isolation:

Connect a wire from the quick connect terminal marked SI (starting isolation) to the terminal or wire running from the start key switch to the starter solenoid (see back for wiring diagram). This connection can be made at the start key switch or at the starter solenoid, but must be to the line that is positive only when cranking. Connection to a line that is positive while the engine is normally running will prevent the charging relay from working properly.

Installation Instructions

m-Series, Dual Circuit Plus™ Battery Switch 6011 (Included with 7649 Mini Add-A-Battery)

Turn all loads off before turning the battery switch to OFF.

Do not switch to OFF while the engine is running.

Mount the battery switch in an easily accessible location close to the batteries.

Attach one 4/0 AWG cable per terminal to meet ratings.

Terminals must be attached under nut and lock washer. Torque to 120 in-lb (13.56 Nm)

980014350 Rev.001