Block HLD310-500/250 Catalog Page

Radio interference suppression filter, three-phase, low leakage current
HLD 310-500/250
Advantages
For enhanced requirements
Low leakage current
Single-stage filter concept
Increase in the interference immunity of the connected consumer
Applications
Radio interference suppression filter for line-side interference suppression of single devices, frequency converters or as group interference suppression.
Sample application
Picture shows HLD 310-500/30
Standards Z
Radio interference suppression filter complying with DIN EN 60939-2, UL 1283, CSA C22.2 No.8
Approvals W Z
UL 1283 5th edition, CSA 22.2 No 8
Radio interference suppression filter, three-phase, low leakage
450 .0
220 .0
435 .0
525 .0
155 .0
125 .0
+
-
30
current
HLD 310-500/250
Type HLD 310-500/250
Special features
Characteristics
Operating data
Rated voltage Voltage range Rated current Leakage current (50 Hz)* Leakage current (50 Hz)** Power loss Overrating Capacity
Input
Rated frequency
Approvals
Approvals
Environment
Ambient temperature max.
Climatic category
Safety and protection
SCCR*** Protection index Type Safety class (prepared) Test voltage
Notes
*
** ***
Order numbers
Order Number
Suitable for the medical field
3 x 520 Vac 0 - 3 x 520 Vac 3 x 250 A <0.40 mA <3.50 mA
180.0 W 150 %, shortly
50 - 60 Hz
cURus, UL 1283 5th edition, CSA 22.2 No.8
50 °C 25/085/21
[in accordance with EN 60068-1]
100 kA IP 20 Metal enclosure I 2150 Vdc Phase/Phase, 2700 Vdc Phase/PE
Leakage current measured against the maximum permissible input voltage fluctuation in accordance with IEC 38 ±10 %
Leakage current by loss of two phases with corresponding preliminary fuse
HLD 310-500/250
Type HLD 310-500/250
Terminal and mounting
Terminals phase Terminals PE Fixing method Fixing screws
Measures and weights
Weight
Screw clamp, 150 mm² Bolt, M10 Mounting lugs M6
12.20 kg