Radio interference suppression filter, three-phase, low leakage current
HLD 310-500/16
Advantages
For enhanced requirements
Low leakage current
Single-stage filter concept
Efficient filter effect against line-bound interference emissions
Increase in the interference immunity of the connected consumer
Applications
Radio interference suppression filter for line-side interference suppression of
single devices, frequency converters or as group interference suppression.
Sample application
Picture shows HLD 310-500/30
Standards Z
Radio interference suppression filter complying with
DIN EN 60939-2, UL 1283, CSA C22.2 No.8
Approvals W Z
UL 1283 5th edition, CSA 22.2 No 8

Radio interference suppression filter, three-phase, low leakage
current
HLD 310-500/16
Type HLD 310-500/16
Special features
Characteristics
Operating data
Rated voltage
Voltage range
Rated current
Leakage current (50 Hz)*
Leakage current (50 Hz)**
Power loss
Overrating Capacity
Input
Rated frequency
Approvals
Approvals
Environment
Ambient temperature max.
Climatic category
Safety and protection
SCCR***
Protection index
Type
Safety class (prepared)
Test voltage
Notes
*
**
***
Order numbers
Order Number
Suitable for the medical field
3 x 520 Vac
0 - 3 x 520 Vac
3 x 16 A
<0.40 mA
<3.50 mA
12.0 W
150 %, shortly
50 - 60 Hz
cURus, UL 1283 5th edition, CSA 22.2 No.8
50 °C
25/085/21
[in accordance with EN 60068-1]
100 kA
IP 20
Metal enclosure
I
2150 Vdc Phase/Phase, 2700 Vdc Phase/PE
Leakage current measured against the
maximum permissible input voltage fluctuation in
accordance with IEC 38 ±10 %
Leakage current by loss of two phases
with corresponding preliminary fuse
HLD 310-500/16
Type HLD 310-500/16
Terminal and mounting
Terminals phase
Terminals PE
Fixing method
Fixing screws
Measures and weights
Weight
Screw clamp, 4 mm²
Bolt, M5
Mounting lugs
M5
1.20 kg