Block HLD103-500/750 Catalog Page

Radio interference suppression filter, three-phase
HLD 103-500/750
Advantages
For enhanced requirements
Single-stage filter concept
Efficient filter effect against line-bound interference emissions
Applications
Radio interference suppression filter for line-side interference suppression of single devices, frequency inverters or as group interference suppression.
Sample application
Picture shows HLD 103-500/1000
Standards Z
Radio interference suppression filter to DIN EN 60939-2
Approvals Z
Radio interference suppression filter, three-phase
H
H
235. 0
120. 0
10.0
9.0
260. 0
210. 0
110. 0
12.0
390. 0
300. 0
45.0
15.0
+
-
30
HLD 103-500/750
Type HLD 103-500/750
Operating data
Rated voltage Voltage range Rated current Leakage current (50 Hz)* Leakage current (50 Hz)** Rated frequency Overrating Capacity
Environment
Ambient temperature max.
Climatic category
Safety and protection
Protection index Type Safety class (prepared) Test voltage
Notes
*
**
Order numbers
Order Number
3 x 520 Vac 3 x 0 - 520 Vac 3 x 750 A
570.00 mA
60.00 mA 50 - 60 Hz 150 %, shortly
50 °C 25/085/21
[in accordance with EN 60068-1]
IP 00 Metal enclosure I 2121 Vdc Phase/Phase, 2700 Vdc Phase/PE
Leakage current measured against the maximum permissible input voltage fluctuation in accordance with IEC 38 ±10 %
Leakage current by loss of two phases
HLD 103-500/750
Type HLD 103-500/750
Terminal and mounting
Terminals phase Terminals PE Fixing method Fixing screws
Measures and weights
Weight
Flat copper, 30 x 10 mm Bolt, M12 Mounting lugs M8
15.80 kg