Bird Technologies 3129 User Manual

Broadcast Power
Monitor Series BPM-E
Model 3129 Digital Display
OPERATING INSTRUCTIONS
©Copyright 2012
Instruction Book P/N 920-7005ABPME Rev. H
Java® is a registered trademark of Sun Microsystems, Inc.
by Bird Electronic Corporation
Thruline® is a registered trademark of
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation
This page is not blank
16
Safety Precautions
The following are general safety precautions that are not necessarily related to any specific part or procedure, and do not necessarily appear elsewhere in this publication. These precautions must be thoroughly understood and apply to all phases of operation and maintenance.
WARNING
Keep Away From Live Circuits
Operating Personnel must at all times observe general safety precautions. Do
not replace components or make adjustments to the inside of the test
equipment with the high voltage supply turned on. To avoid casualties, always
remove power.
WARNING
Shock Hazard
Do not attempt to remove the RF transmission line while RF power is present.
WARNING
Do Not Service Or Adjust Alone
Under no circumstances should any person reach into an enclosure for the
purpose of service or adjustment of equipment except in the presence of
someone who is capable of rendering aid.
WARNING
Safety Earth Ground
An uninterruptible earth safety ground must be supplied from the main power
source to test instruments. Grounding one conductor of a two conductor
power cable is not sufficient protection. Serious injury or death can occur if
this grounding is not properly supplied.
WARNING
Resuscitation
Personnel working with or near high voltages should be familiar with modern
methods of resuscitation.
WARNING
Remove Power
Observe general safety precautions. Do not open the instrument with the
power on.
i
Safety Symbols
WARNING
Warning notes call attention to a procedure, which if not correctly performed,
could result in personal injury.
CAUTION
Caution notes call attention to a procedure, which if not correctly performed,
could result in damage to the instrument.
Note: Calls attention to supplemental information.
The caution symbol appears on the equipment indicating there is important information in the instruction manual regarding that particular area.
This symbol appears on the equipment and indicates that the AC power cord should be removed before servicing the unit.
This symbol appears on the equipment and indicates the requirement for separate collection of discarded electrical and electronic equipment in accordance with the European Union Directive 2002/96/EC. Refer to the Bird web site for more information.
Warning Statements
The following safety warnings appear in the text where there is danger to oper­ating and maintenance personnel, and are repeated here for emphasis.
WAR NING
Leaking RF energy is a potential health hazard. Never attempt to connect or
disconnect equipment from the transmission line while RF power is being applied.
Severe burns, electrical shock, or death can occur.
See page 11.
WAR NING
High RF voltage and energy is always present in the RF Test Port when the system is operating. Do not operate the system if the BPM-E RF Test Port is open. Close the port with a dummy plug or a suitable sampling plug. Failure to comply may result in severe
burns, electrical shock, or death.
See page 12.
ii
WARNING
Dangerous RF voltage. Do not connect or apply an RF signal to the BPM-E
during equipment setup. Failure to comply may result in severe burns, loss of
use of limbs, or death.
See pages 19, 21, and 22.
WARNING
Disconnect the unit from the RF power source and the ac line before any
disassembly. The potential for electrical shock exists.
See page 41.
Caution Statements
The following equipment cautions appear in the text and are repeated here for emphasis.
CAUTION
BPM-E signal sensing couplers are fixed in place. Do not attempt to remove or
rotate the couplers. They are calibrated and oriented at the factory and are not
designed to be rotated or removed by the end user. Failure to comply may
result in loss of calibration and accuracy, and in permanent damage to the unit.
See pages 12 and 27.
CAUTION
The DC voltage provided by the 3129 Digital Display power/alarm port should
only be used to power the BPM-E. Do not use the 3129 DC source to supply
power to anything else.
See page 15.
CAUTION
Network connections require specific address and protocol information. Have a
qualified IT or network professional perform the BPME ethernet setup. Failure to
comply may result in loss of network communication or the inability to
communicate with the BPME.
See page 22.
CAUTION
Do not use harsh or abrasive detergents for cleaning.
See page 41.
iii
Safety Statements
USAGE
ANY USE OF THIS INSTRUMENT IN A MANNER NOT SPECIFIED BY THE MANUFACTURER MAY IMPAIR THE INSTRUMENT’S SAFETY PROTECTION.
USO
EL USO DE ESTE INSTRUMENTO DE MANERA NO ESPECIFICADA POR EL FABRICANTE, PUEDE ANULAR LA PROTECCIÓN DE SEGURIDAD DEL INSTRUMENTO.
BENUTZUNG
WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT BEEINTRÄCHTIGT WERDEN.
UTILISATION
TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS EXPLICITEMENT PRÉVUE PAR LE FABRICANT PEUT ENDOMMAGER LE DISPOSITIF DE PROTECTION DE L’INSTRUMENT.
IMPIEGO
QUALORA QUESTO STRUMENTO VENISSE UTILIZZATO IN MODO DIVERSO DA COME SPECIFICATO DAL PRODUTTORE LA PROZIONE DI SICUREZZA POTREBBE VENIRNE COMPROMESSA.
iv
SERVICE
SERVICING INSTRUCTIONS ARE FOR USE BY SERVICE ­TRAINED PERSONNEL ONLY. TO AVOID DANGEROUS ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO.
SERVICIO
LAS INSTRUCCIONES DE SERVICIO SON PARA USO EXCLUSIVO DEL PERSONAL DE SERVICIO CAPACITADO. PARA EVITAR EL PELIGRO DE DESCARGAS ELÉCTRICAS, NO REALICE NINGÚN SERVICIO A MENOS QUE ESTÉ CAPACITADO PARA HACERIO.
WARTUNG
ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN NUR FÜR GESCHULTES FACHPERSONAL.
ZUR VERMEIDUNG GEFÄHRLICHE, ELEKTRISCHE SCHOCKS, SIND WARTUNGSARBEITEN AUSSCHLIEßLICH VON QUALIFIZIERTEM SERVICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN
L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE RÉSERVÉ AU PERSONNEL FORMÉ AUX OPÉRATIONS D’ENTRETIEN. POUR PRÉVENIR UN CHOC ÉLECTRIQUE DANGEREUX, NE PAS EFFECTUER D’ENTRETIEN SI L’ON N’A PAS ÉTÉ QUALIFIÉ POUR CE FAIRE.
ASSISTENZA TECNICA
LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE ESCLUSIVAMENTE PER IL PERSONALE OPPORTUNAMENTE ADDESTRATO. PER EVITARE PERICOLOSE SCOSSE ELETTRICHE NON EFFETTUARRE ALCUNA RIPARAZIONE A MENO CHE QUALIFICATI A FARLA.
v
RF VOLTAGE MAY BE PRESENT IN RF ELEMENT SOCKET - KEEP ELEMENT IN SOCKET DURING OPERATION.
DE LA TENSION H.F. PEAT ÊTRE PRÉSENTE DANS LA PRISE DE L'ÉLÉMENT H.F. - CONSERVER L'ÉLÉMENT DANS LA PRISE LORS DE L'EMPLOI.
HF-SPANNUNG KANN IN DER HF-ELEMENT-BUCHSE ANSTEHEN ­ELEMENT WÄHREND DES BETRIEBS EINGESTÖPSELT LASSEN.
PUEDE HABER VOL TAJE RF EN EL ENCHUFE DEL ELEMENTO RF ­MANTENGA EL ELEMENTO EN EL ENCHUFE DURANTE LA OPERACION.
IL PORTAELEMENTO RF PUÒ PRESENTARE VOLTAGGIO RF ­TENERE L'ELEMENTO NELLA PRESA DURANTE IL FUNZIONAMENTO.
vi
About This Manual
1 2 3
4
BPME ___ ___ - ___ ___
This manual covers the operating and maintenance instructions for the follow­ing models:
3129 BPME
Figure 1 BPM-E Model Identification
Item Description Options
1 Line Section 1 = 1 - 5/8”
2 Line Interface U = Unflanged, Recessed Center Cond.
3 Frequency Band VL = 45 - 88 MHz
4 Power L = Low
3 = 3 - 1/8” 4 = 4 - 1/16” 4A = 4 - 1/2” 6 = 6 - 1/8”
UF = Unflanged, Flush Center Cond. D = Dielectric Flanged M = Myat Flanged
leave blank = Flanged, EIA standard
V = 88 - 230 MHz U = 470 - 890 MHz
M = Medium H = High X = Extra Low
Refer to power ranges for each line section diam­eter (See “RF Power Ratings” on page 48)
vii
Figure 2 BPM-E7 Model Identification
1 2 3
4 5
6
BPME 7 ___ ___ - ___ ___ ___
Item Description Options
1 Line Section 7 = 7/8” 2 Input Connector A = N (F)
B = N (M) C = LC (F) D = 7/8” EIA H = 7/16 DIN (F) J = 7/16 DIN (M) K = UHF (F) L = UHF (M)
3 Output Connec-
tor
A = N (F) B = N (M) C = LC (F) D = 7/8” EIA H = 7/16 DIN (F) J = 7/16 DIN (M) K = UHF (F) L = UHF (M)
4 Frequency Band VL = 45 - 88 MHz
V = 88 - 230 MHz U = 470 - 890 MHz
5 Power L = Low
M = Medium H = High
refer to power ranges for each line section diameter (See “RF Power Ratings” on page 48)
6 Mounting P = Panel mount (for a 19 in. equip-
ment rack) leave blank = Standard mounting configuration
viii
Changes to this Manual
We have made every effort to ensure this manual is accurate. If you discover any errors, or if you have suggestions for improving this man­ual, please send your comments to our Solon, Ohio factory. This man­ual may be periodically updated. When inquiring about updates to this manual refer to the part number and revision on the title page.
Literature Contents
Chapter Layout
Introduction — Identifies the parts and functions of the BPM-E and the 3129
Display Panel, and lists optional equipment available.
Theory of Operation — Describes the theory and features of the BPM-E and
the Display, including the alarm options.
Installation — Provides information on installing the BPM-E and 3129 Digital
Display at a site, as well as information on the cable connections and installation instructions for the WebTool utility and the PCTool software.
Operating Instructions — Describes operation of the display and use of the
PCTool software and the WebTool software.
Maintenance — Lists basic troubleshooting information, routine maintenance
tasks for the BPM-E and the 3129 digital display, specifications, and parts lists.
ix
x
Table of Contents
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Safety Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Warning Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Caution Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Safety Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Changes to this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Literature Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Chapter Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Chapter 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Broadcast Power Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Items Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Optional Items Available . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2 Theory of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
General Theory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Factors that Affect Power Reading Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . 7
Alarm Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Alarm Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Alarm Latching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VSWR Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Alarm on Zero Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
High Power Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Low Power Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Mounting a BPM-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
BPM-E7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Flanged Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unflanged Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
xi
3129 Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +14
Mounting a 3129 Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
AC Power Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Alarm Interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Remote Computer Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Power/Alarm Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Power ON/OFF Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
BPM-E DC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Setting Up the BPM-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Installing PCTool and Finder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Connecting the BPM-E Using the RS-232 Port . . . . . . . . . . . . . . . . . . . . 20
Connecting the BPM-E Using the Ethernet Port . . . . . . . . . . . . . . . . . . . 22
Chapter 4 Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Couplers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
BPM-E Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3129 Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Power On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Mode Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Units Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Reset Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Alarm LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
WebTool Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Stats Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Config Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Alarm Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Frequency Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Admin Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Network Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Email Alerts Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
SNMP Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Password Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Help Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
PCTool Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Main . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Frequency Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
xii
Chapter 5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Inspection and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3129 Digital Display Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
BPM-E Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3129 Digital Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
RF Power Range, VHF Frequency Band (45-230 MHz) . . . . . . . . . . . . . . 45
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
RF Power Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Line Section Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3129 Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Appendix 1 Reference Information 53
Determining VSWR Alarm Trip Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
xiii
xiv
Chapter 1 Introduction
This chapter contains introductory information including items supplied and component descriptions.
Broadcast Power Monitor
The Enhanced Bird Broadcast Power Monitor (BPM-E) is a compact, micropro­cessor controlled instrument intended for long-term system VSWR and power monitoring. The BPM-E is designed for use only with shielded (grounded) 50 ohm transmission lines. See Figure 31 on page 49 for an outline drawing with dimensions.
Features
Compatible with analog or digital systems
Monitors VSWR and power
Measures forward power from 2.5 W to 200 kW, measurable reflected
power from 0.25 W to 20 kW (actual measurement ranges depend
upon frequency and line diameter size)
Remote monitoring capability
Multiple alarm options
May be used at any point in the transmission line
Available in a variety of line sections
Can send an e-mail when an alarm occurs
Supports ethernet connection
Provides an extra socket for connecting an RF test element
Items Supplied
Broadcast Power Monitor
Instruction Manual
PCTool software (on CD)
1
Optional
3129 Digital Display - Displays the BPM-E status and provides power to the
BMPE electronics. Includes a power cord, a 50 foot 9-pin cable, and a 50 foot 15­pin cable.
DB-15 Power/Alarm Cable - Connects the BPM-E to a power supply and to
external controllers. 50 feet long with male/female connectors. Refer to Figure 7 on page 16 for pin layout.
DB-15 Interface Connector - Allows easy custom data cable connections to
the BPM-E.
DB-9 RS-232 PC Interface Cable - Connects the BPM-E to a PC. Available in
either 10 or 50 foot lengths, with male/female connectors. Refer to Figure 10 on page 18 for pin layout.
Items
Available
Digital Display
The Bird 3129 Digital Display is a remote monitor panel that can be used with the BPM-E.
Features
A single line display divided into two fields.
Note: Displays forward power, and either reflected power or the
match measurement. An indicator in the lower right of the last digit blinks on and off to indicate communication with the BPM-E.
Displays match measurements as VSWR, Rho, Return Loss, or efficiency
Supplies dc power to the BPM-E
Displays the BPM-E alarm status
Provides an electrical interface for the discrete outputs from the BPM-E
Provides a serial interface to connect a PC to the BPM-E
2
Component Description
1
2
3
4
5
6
7
8
9
Figure 1 BPM-E Components
Item
(Fig. 1)
Function Description
1 RF Input Input to BPM-E from transmitter 2 Power/Alarm
Parallel Port
Connects to the 3129 digital display using a 15 pin cable.
Note: Also used for remote
operation.
3 RS-232 Serial
Port
4 Alarm LED Red LED, lights when an alarm is triggered 5 Monitor On
LED
6 Reset Switch Press to reset the alarm. If an alarm trigger
7 Ethernet Port Connects to a network or PC ethernet card 8 RF Output Output from BPM-E to antenna or load 9 RF Test Port Insert a sampling element with an
Connects to a 3129 digital display, a PC, or other display panel using a 9 pin RS-232 cable
Green LED, lights when the unit is powered
is still present, the alarm will reactivate
appropriate connector to connect to a monitor device (e.g. spectrum analyzer, modulation monitor, oscilloscope)
3
Figure 2 3129 Digital Display Components
Electronic Corporation
Model 3129
True Average Power
Mode Units
Alarm
Reset
Remote
Cleveland, Ohio USA
Phone: (440) 248-1200
www.bird-electronic.com
MODEL 3129
S/N
Electronic Corporation
FUSE 1.0A, 250 V
115/230 VAC
50/60 Hz
.6A MAX.
LINE
C
L
O
S
E
D
N
O
A
L
R
M
O
P
E
N
N
O
A
L
R
M
C
O
M
M
O
N
F
O
R
A
L
R
M
A
L
R
M
T
T
L
O
U
T
R
E
M
O
T
E
R
E
S
E
T
G
R
O
U
N
D
RFL
ANALOG OUTPUT
FWD
POWER/ALARM
SENSOR INTERFACE
RS-232
1
2
3
4
5
6
7
8
9
10
11
12
4
Item
(Fig. 2)
Function Description
1 AC Power
Connector
2 Alarm
Interlocks
3 Analog
Output, Forward Power
4 Analog
Output, Reflected Power
5 Power/
Alarm Port
6 RS-232
Serial Port
7 AC Power
Switch
8 Mode
Button
Connect to ac power supply with a power cord
Alarm interlocks are used to shut down transmitter when an alarm condition occurs. Remote reset can be used to reset the BPM-E after the alarm event
0 to 2 V full scale, linear, 200 ohm output impedance, BNC (f) connector
0 to 2 V full scale, linear, 200 ohm output impedance, BNC (f) connector
Connects to the BPM-E using a 15 pin cable. Provides operating power to the BPM-E. Contains analog and digital alarm information.
Connects to the BPM-E using a 9 pin RS-232 cable (ASCII data between the BPM-E and the display)
Turns on the display panel (and BPM­E if connected).
Selects display mode for the right field.
9 Units Button Selects the displayed power units. 10 Alarm LED Red LED, lights when an alarm is
triggered
11 Reset
Switch
Press to reset the alarm. If an alarm trigger is still present, the alarm will reactivate
12 Remote
Computer
Interface with a PC using a 9 pin RS­232 cable
Connector
5
6
Chapter 2 Theory of Operation
Detector Board
Control Board
Alarm LED
Power LED
Reset Button
DB-9 Connector
DB-15 Connector
Rj45 Connector and Xport Ethernet Controller
Forward Coupler
Reflected Coupler
RF IN
RF OUT
Line Section
General Theory
The enhanced Broadcast Power Monitor (BPM-E) is an instrument that is inserted directly into a transmission line to monitor the forward power, reflected power, and VSWR of the system. The BPM-E consists of a line section with for­ward and reflected directional couplers and an additional housing that contains the external circuitry. The external circuitry consists of a detector circuit and a control circuit (Figure 3, page 7).
The directional couplers sample, through a known coupling factor, the forward and reflected wave in the transmission line. The coupled RF signal is passed to the detector board and converted into a dc voltage. The dc voltage, which is propor­tional to the RF power in the line seciton, is then sent to the control circuit.
In the control circuit, an analog-to-digital converter digitizes the incoming signal and passes it to a micro controller that manages input and output processing. The control circuitry comminicates by sending signals to the alarm and power LEDs, receiving a user initiated signal from the reset button, and both sending and receiving signals via the RS-232 connector (DB9), the ethernet connector (RJ45), and the power/alarm connector (DB15).
Factors that Affect Power Reading Accuracy
Many sources can affect the accuracy of any in-line power reading. These sources include directivity of the directional couplers, noise in the system, and the insertion loss of various system components. To more fully understand how these and other sources cause the power readings to be out of specification, consult with a Bird Applications Engineer.
Figure 3 BPM-E Functional Block Diagram
7
Alarm Response
When an alarm is triggered, the Bird Broadcast Power Monitor turns on the alarm LEDs, provides a TTL alarm out signal (low = alarm), and deactivates a form-C dry contact relay. Additionally the BPM-E can latch the alarm condition and notify up to two persons via email if you have set up this option in the WebTool software.
Note: The alarm relay defaults to fail safe. That is, the relay is de-
energized when an alarm activates or when power is lost. If you need to have an alarm relay that energizes on an alarm, contact Bird (see title page of this manual).
Alarm Reset
After an alarm occurs, you can reset it in the following ways:
Press the reset switch on the BPM-E or on the digital display.
Apply a TTL logic low signal (0 to 0.8 Vdc) to the reset pin on the Power/
Alarm connector.
Use the PCTool software to reset the unit through the RS-232 port.
Use the WebTool software to reset the unit through the ethernet port.
Alarm Latching
The alarm defaults to latching operation. In this mode, the alarm will stay active until reset. In non-latching mode, the alarm will reset automatically about forty seconds after the trigger condition is corrected. The latching mode can be changed using the PCTool or the WebTool.
VSWR Alarm
Activating the VSWR also enables all other alarms that have been selected. Con­versely, deactivating the VSWR alarm disables all other alarms that have been selected.
The BPM-E continuously monitors forward and reflected power. From the power measurements, the VSWR is calculated and compared to the allowed maximum (default of 1.8 to 1). Based on the results of the comparison, possible actions include:
No alarms are activated if the VSWR is less than the maximum, or if the
VSWR alarm is disabled.
8
If:
The VSWR is equal to or slightly greater than the maximum, addi-
tional measurements are accumulated to determine a trend.
Reverse power is increasing, an alarm is triggered.
The reverse power is stable, measurements continue until a trend is
established.
An alarm will be set if the VSWR exceeds the maximum for
more than thirty seconds.
If the VSWR is much greater than the maximum then an alarm is trig-
gered immediately.
Alarm on Zero Power
When the forward power is very small (< 2.5% of full scale), the measured VSWR becomes large due to the noise floor of the sensor. Under these conditions, the VSWR level is meaningless. When the zero power alarm is disabled, the VSWR will not be monitored at these low powers.
High Power Alarm
When the high power alarm is enabled, the forward power is continuously moni­tored. The alarm trigger is a percentage of the Monitor’s full scale power, from 0 – 125%. If the forward power is greater than the trigger level, an alarm is triggered.
Low Power Alarm
When the low power alarm is enabled, the forward power is continuously moni­tored. The alarm trigger is a percentage of the Monitor’s full scale power, from 0 – 125%. If the forward power is less than the trigger level, an alarm is triggered.
9
10
Chapter 3 Installation
This chapter provides information for preparing the Bird Broadcast Power Moni­tor for use.
Unpacking and Inspection
1. Carefully inspect the shipping container for signs of damage. If damage is noticed, do not unpack the unit. Immediately notify the shipping carrier and Bird Electronic Corporation.
2. If the shipping container is not damaged, unpack the unit. Save the packing material in case the unit needs to be shipped again.
3. Inspect all of the components for visible signs of damage. Immediately notify the shipping carrier and Bird Electronic Corporation of equipment damage or missing parts.
The Bird BPM-E is shipped complete and ready for use upon receipt. After unpacking and inspecting the unit, it is ready to be installed.
Tools Required
You will need only common hand tools to install the BPM-E and the 3129 Digital Display (if used).
WARNING
Leaking RF energy is a potential health hazard. Never attempt to connect or
disconnect equipment from the transmission line while RF power is being
applied. Severe burns, electrical shock, or death can occur.
Mounting a BPM-E
Make sure that the LEDs and reset button are accessible, and that the connect­ing cables have adequate clearance. Mount the BPM-E in the transmission line between the transmitter and the antenna. “In” or “RF Input” is the signal from your transmitter. “RF Output” is the signal going to the antenna or load. Follow the instructions in this section to mount a BPM-E7 (See “BPM-E7” on page 12), a BPM-E with a flanged connector (See “Flanged Connector” on page 13), or a BPM-E with an unflanged connector (See “Unflanged Connector” on page 13). Be sure to connect the BPM-E to the RF line as described.
11
WARNING
RF INPUT
RF OUTPUT
High RF voltage and energy is always present in the RF Test Port when the
system is operating. Do not operate the system if the BPM-E RF Test Port is
open. Close the port with a dummy plug or a suitable sampling plug. Failure
to comply may result in severe burns, electrical shock, or death.
CAUTION
BPM-E signal sensing couplers are fixed in place. Do not attempt to remove or
rotate the couplers. They are calibrated and oriented at the factory and are not
designed to be rotated or removed by the end user. Failure to comply may result
in loss of calibration and accuracy, and in permanent damage to the unit.
BPM-E7
The BPM-E uses QC-type quick change connectors. Use 50 ohm coaxial cable such as RG-218/U or RG-220/U (-17A or -19A), appropriate for the frequency and power level of operation. Use a cable connector that will mate with both the transmission line and the BPM-E7. Connect the BPM-E7 to the RF line as shown in Figure 4, page 12.
Figure 4 BPM-E 7, RF Direction
12
Flanged Connector
RF INPUT RF OUTPUT
To connect a flanged unit to a flanged RF transmission line, use an appropriate coupling kit. Refer to Figure 5, page 13 for RF input and output orientation.
1. Insert the center connector (bullet).
Note: Push the connector until it is fully seated.
2. Connect the coaxial input in a straight line.
Note: Push carefully to close.
3. Insert the bolt sets.
4. Tighten the bolt sets evenly all around to transmission line manufacturer’s recommended torque.
Note: Use all of the bolts.
Unflanged Connector
To connect an unflanged unit to an unflanged RF line, use an appropriate cou­pling kit.
1. Insert the center connector (bullet).
Note: 1.Push the connector until it is fully seated.
2. Position the outer sleeve, with clamping bands, over the input connector.
3. Set the transmission line snugly against the coupling stops.
4. Position the clamping bands evenly about 3/4” from the ends of the sleeve.
5. Tighten the clamping bands.
Figure 5 BPM-E Flanged Line Sections, RF Direction
13
3129 Digital Display
Cleveland, Ohio USA Phone: (440) 248-1200 www.bird-electronic.com
MODEL 3129 S/N
Electronic Corporation
FUSE 1.0A, 250 V
115/230 VAC
50/60 Hz .6A MAX.
LINE
C
L
O
S
E
D
N
O
A
L
R
M
O
P
E
N
N
O
A
L
R
M
C
O
M
M
O
N
F
O
R
A
L
R
M
A
L
R
M
T
T
L
O
U
T
R
E
M
O
T
E
R
E
S
E
T
G
R
O
U
N
D
RFL
ANALOG OUTPUT
FWD
POWER/ALARM
SENSOR INTERFACE
RS-232
OLD LABEL
NEW LABEL
A
L
R
M
N
O
R
M
C
L
S
D
A
L
R
M
N
O
R
M
O
P
E
N
A
L
R
M
C
O
M
M
O
N
A
L
R
M
T
T
L
O
U
T
R
E
M
O
T
E
R
E
S
E
T
G
R
O
U
N
D
C
L
O
S
E
D
N
O
A
L
R
M
O
P
E
N
N
O
A
L
R
M
C
O
M
M
O
N
F
O
R
A
L
R
M
A
L
R
M
T
T
L
O
U
T
R
E
M
O
T
E
R
E
S
E
T
G
R
O
U
N
D
1 2 3 4 5 6
Note: When using with a BPME, it is recommended to connect the
3129 directly to a universal power source (UPS).
Mounting a 3129 Digital Display
Install the digital display in a standard (1U) rack mount.
AC Power Connector
The AC Power connector (Figure 2 on page 4) provides operating power for the digital display and the BPM-E electronics. The AC power supply cord is also the line disconnect device for this product. You can use any approved power cord to connect to the digital display, such as domestic type SVT, 300 VAC, 18 AWG, 10 A, 3 conductor (including ground) or international type H05VV-F, 300 VAC, 1.00 mm, 10 A, 3 conductor (including ground).
Alarm Interlocks
When an alarm occurs, the 3129 Digital Display utilizes one of the follwing two methods to shut down your system.
A TTL signal (Alarm TTL Out) that goes low on alarm
A relay (alarm relay) that de-energizes on alarm
The alarm interlocks are available at the alarm interlock connector at the rear of the unit (Figure 6, page 14).
Note: The alarm relay label text has been revised for clarity. If you
are connecting to an older Bird 3129 display, the alarm interlock con­nector might have the “old label” text.
Figure 6 Alarm Interlock Connections
14
1
Pin #
(Fig. 6)
1 Ground 2 Remote Reset (reset TTL alarm signal, TTL low = reset) 3 Alrm TTL Out (low = alarm) 4 Common for Alrm (relay contact common) 5 Open No Alrm (relay energized, contacts are open when no
alarm exists)
6 Closed No Alrm (relay energized, contacts are closed when
no alarm exists)
New Label Text and Description
Remote Computer Connector
To communicate with a BPM-E that is connected to the RS-232 port at the rear of the 3129 Digital Display, connect a PC to the Remote Computer connector on the front panel of the display. When connected in this manner, signals are routed directly from the BPM-E through the display to the PC.
To setup a BPM-E connected to the Remote Computer connector (as described above), follow the setup instructions for RS-232 and PC Tool software in "Setting Up the BPM-E" on page 19.
Power/Alarm Connector
The Power/Alarm connector provides operating power to the BPM-E and receives signals and data from the BPM-E. Pin numbers and descriptions are given in Figure 7, page 16 and a typical connection is illustrated in Figure 8 on page 17.
CAUTION
The DC voltage provided by the 3129 Digital Display power/alarm port should
only be used to power the BPM-E. Do not use the 3129 DC source to supply
power to anything else.
Power ON/OFF Switch
The power switch on the front of the display turns the unit ON or OFF.
15
BPM-E DC Power Connections
1
15
8
9
MALE (model ACM-L2-DFDFTL-12SP only)
Connect DC operating power to the BPM-E Power/Alarm 15-pin connector.
The BPM-E requires an isolated +12 to +26 VDC power supply (0.5 A max). This power is available from the Power/Alarms connector at the rear of the 3129 Dig­ital Display.
If your installation does not use a 3129 Digital Display, you must provide the required power and connect it to the BPM-E Power/Alarm 15-pin connector. The BPM-E Power/Alarm connector also provides alarm signals (TTL and relay con­tacts), a reset line, and forward and reflected power information. See Figure 7, page 16 for the connector pin descriptions.
Figure 7 DB-15 Power/Alarm Connector
Pin Description
1 Relay , normally closed contact (closed when relay is
not energized) (open when there is no alarm)
2 Relay, common contact 3 Alarm output, TTL compatible
TTL High ( 4.3 VDC with a 10k load) = no alarm TTL Low (<0.2 VDC) = alarm
4 Forward monitor, 0 to 2 VDC linearly proportional to
forward power, 200 ohm output impedance
5 Reset input, TTL compatible
6-7 No connection 8 Reflected monitor, 0 to 2 VDC linearly proportional
9 Relay, normally open contact (open when relay is
10-11 Reserved 12-13 DC input, +12 to +26 VDC (<0.5 A) 14-15 Ground for DC input and signals
16
TTL Low (<0.5 VDC) resets alarm
to reflected power, 200 ohm output impedance
not energized) (closed when there is no alarm)
BPM-E Data Connections
NETWORK ANALYZER MODULATION MONITOR OSCILLOSCOPE
1
2
3 4
5
6
7
8
Cleveland, Ohio USA Phone: (440) 248-1200 www.bird-electronic.com
MODEL 3129 S/N
Electronic Corporation
FUSE 1.0A, 250 V
115/230 VAC
50/60 Hz .6A MAX.
LINE
C
L
O
S
E
D
N
O
A
L
R
M
O
P
E
N
N
O
A
L
R
M
C
O
M
M
O
N
F
O
R
A
L
R
M
A
L
R
M
T
T
L
O
U
T
R
E
M
O
T
E
R
E
S
E
T
G
R
O
U
N
D
RFL
ANALOG OUTPUT
FWD
POWER/ALARM
SENSOR INTERFACE
RS-232
The BPM-E has an RS-232 connector and an ethernet connector. The RS-232 con­nector conducts ASCII data between the BPM-E and a display panel or a PC. The ethernet connector conducts data between the BPM-E and a network device (hub, router, PC with network capability). Figure 8 on page 17 shows how a BPM-E can be connected to a Bird 3129 Digital Display. RS-232 pin numbers and descriptions are given in Figure 10 on page 18. When you connect using the RS-233 port, you will use the PCTool software utility to communicate with the BPM-E.
If you connect the BPM-E to the rear panel of a 3129 Digital Display (RS-232 con­nection), you can also connect a PC to the RS-232 connector on the front of the display (Remote connector) to communicate with the BPM-E.
The ethernet connector provides a means for you to connect the BPM-E to a network or directly to a computer with ethernet capability that is not connected to a network. When you use the ethernet capability, you will also use the WebT­ool utility to set the IP address, configure the BPM-E, and monitor the power and alarm status of the transmission line.
Figure 8 BPM-E Rear Panel Data Connections
Item Description
1 3129 Digital Display, rear panel 2 RS-232 communication port, 9-pin 3 Power/Alarm connector, 15-pin 4 Ethernet connector (for network or local PC) 5 Computer (for network or local PC) 6 Sampler port 7 Monitor device (network analyzer, modulation monitor,
oscilloscope)
8 BPM-E controller
17
Figure 9 BPM-E Front Panel Data Connections
1
2
3
Electronic Corporation
Model 3129
True Average Power
Mode Units
Alarm
Reset
Remote
Item Description
1 3129 Digital Display, front panel 2 3129 Remote computer connector 3 Computer (PC)
Figure 10 DB-9 RS-232 Connector
Pin Description
1 Carrier Detect, always > +5 C 2 Transmit Output, RS-232 data signal 3 Receive Input, RS-232 data signal 4 Data Set Ready Input, connected but not used 5 Data Signal Ground 6 Data Terminal Ready Output, connected but not
used
7 Clear-To-Send, shorted internally to Ready-T o-Send 8 Ready-To-Send, shorted internally to Clear-To-Send
18
9 Ring Indicator, no connection
Setting Up the BPM-E
Note: It is recommended to connec the BPME directly to a universal
power source (UPS).
If you connect directly to a display instead of a computer or network, you can begin using the BPM-E, as shipped, with the factory default alarm and frequency settings. However, you should change the settings (frequency, alarms, etc.) to fit your applica­tion. To make changes to any of the settings or to set up the BPM-E to communicate with a computer, you need to use either the PCTool (used with RS-232 connection) or the WebTool and the Finder utility (used with ethernet connection).
Note: To use the PCTool software or the WebTool software, your PC
must have the Java runtime environment (java virtual machine v1.4.2 or later) installed prior to connecting the BPM-E. If you do not have the runtime environment, you can find it on the CD that came with your BPM-E or you can download it from the web at www.java.com or from the Bird Technology web site (www.bird-elec­tronic.com). For information about downloading the Java Runtime Environment, refer to the readme.txt file that was provided on the CD shipped with your unit.
Installing PCTool and Finder
WARNING
Dangerous RF voltage. Do not connect or apply an RF signal to the BPM-E
during equipment setup. Failure to comply may result in severe burns, loss of
use of limbs, or death.
1. Make sure that there is NO RF power applied to the BPM-E.
2. Copy the file named SETUP.EXE from the CD that came with your unit to a temporary folder on your hard drive. You can also download SETUP.EXE from the Bird Technology web site (www.bird-electronic.com).
3. Launch SETUP.EXE from your hard drive. Typically if you double-click the file name, the file will launch.
4. Follow the on-screen instructions to complete the installation. When the installation is complete, you will see the PCTool main screen with no data in the fields (Figure 11, page 20).
Note: IF you have an older version of PCTool installed on your
computer, the installation process in this step will uninstall the older version. To install the newer version, you must run SETUP.EXE a second time.
19
Figure 11 PCTool Installation Screen
5. Do one of the following to set up your BPM-E:
If you connect your BPM-E directly to a display panel (such as the Bird 2139 Digital Display) using an RS-232 cable, or you connect it directly
to a PC using an RS-232 cabl, follow the setup instructions described in
See “Connecting the BPM-E Using the RS-232 Port” on page 20.
If you connect your BPM-E directly to a PC or to a network using an ethernet cable, follow the setup instructions described in See “Con-
necting the BPM-E Using the Ethernet Port” on page 22.
Connecting the BPM-E Using the RS-232 Port
The RS-232 communication protocol is fixed in the firmware and cannot be mod­ified.
1. Connect the computer’s serial port, via a DB-9 cable, directly to the BPM-E or to the BPM-E through a 3129 digital display.
Note: Do not use a null modem adapter.
2. Install the Java runtime environment, refer to "Setting Up the BPM-E" on page 19.
Note: Perform this step if it is not already done.
20
WARNING
Dangerous RF voltage. Do not connect or apply an RF signal to the BPM-E
during equipment setup. Failure to comply may result in severe burns, loss of
use of limbs, or death.
WARNING
Do not connect RF power to the unit.
3. Apply operating power to the BPM-E. Refer to "BPM-E Data Connections" on page 17).
4. Launch PCTool from your hard drive.
5. Specify which COM (serial) port the BPM-E will use:
a. On the Menu bar, click on Connection and select New....
b. On the New Connection dialog box, select the computer
COM port to which the BPM-E is connected then click OK (Figure 12, page 21).
Note: When the BPM-E establishes communication with your PC, the
PCTool software will display the COM port being used in the space immediately below the Menu bar.
Note: To use the features of the PCTool software, refer to
Chapter 4 Operating Instructions on page 27.
Figure 12 PCTool, Select a COM Port
21
Connecting the BPM-E Using the Ethernet Port
When you connect to the BPM-E using the ethernet port, you use the WebTool software to setup the BPM-E. You do not need to install the WebTool software because it is part of the BPM-E firmware.
Note: You must have Java runtime installed before you can use the
WebTool software.
CAUTION
Network connections require specific address and protocol information. Have a
qualified IT or network professional perform the BPM-E ethernet setup. Failure to
comply may result in loss of network communication or the inability to
communicate with the BPM-E.
The setup in this section should be performed only by a person who thoroughly understands IP and network setup protocols.
Note: If you are connecting to a network, before you begin, do the
following:
Contact your IT professional to get the subnet mask values for
your network and to determine whether or not your network has a DHCP server.
Inform your network administrator that the BPM-E will use port
10001. The network administrator might need to open this port before you can set up the BPM-E.
1. Install the Java runtime environment (refer to See “Setting Up the BPM-E” on page 19).
Note: Perform this step if it is not already done. Note: To use the WebTool software, your PC must have the Java run-
time environment (java virtual machine v1.4.2 or later) installed prior to connecting the BPM-E to an ethernet device. If you do not have the run­time environment, you can download it from the web at www.java.com or from the Bird Technology web site (www.bird-electronic.com). For information about downloading the Java 2 Runtime Environment, refer to the readme.txt file that was provided with your unit.
WARNING
Dangerous RF voltage. Do not connect or apply an RF signal to the BPM-E
during equipment setup. Failure to comply may result in severe burns, loss of
use of limbs, or death.
WARNING
Do not connect RF power to the unit.
2. Apply operating power to the BPM-E, refer to "BPM-E Data Connections" on page 17).
3. Follow the ethernet setup flowchart (Figure 13, page 23) to complete the installation.
22
Figure 13 Ethernet Connection Flowchart
Change your computer IP to 169.254.x.x and subnet to 255.255.0.0
Record the IP and subnet address of your computer
Use a cross-over Ethernet cable to connect BPM-E to computer
Start the BPMFinder utility on your computer and enter the subnet mask of your network
Does your
network have a
DHCP server?
Connect BPM-E to network with a standard Ethernet cable
Will you
connect directly
to the BPM-E
for setup?
Record the BPM-E serial number
YES
YES
NO
NO
1. Start the BPMEFinder utility on your computer
2. Enter the subnet mask as 255.255.0.0
3. Click the button Find BPMEs On Network
4. On the BPMEFinder list, click on the serial number that matches your unit
A
0
153363 CH 17 XMTR
SITE 7A
Note: The name you enter (at the left of the @ symbol) is also used in
the BPM-E Finder utility. If you use the email option to notify someone that an alarm has occurred, the name of this BPM-E will help identify where the alarm came from.
23
When you click on the serial number that matches your unit, the WebTool starts. If WebTool doesn’t start, your web browser is not in your path. Either add it to your path or open your Web browser and enter the IP address of the BPM-E in the address bar. http://<ip address>
A
B
Click on ‘Email Alerts’ tab and check the ‘Enabled’ box.
Fill out ‘Email From’ field to set the BPM-E’s name on the network (or leave it as is to identify the BPM-E it by serial number).
Uncheck the ‘Enabled’ box to disable email alerts. OR Leave the ‘Enabled’ box checked and fill out the ‘Email Recipient’ fields and SMTP server IP address.
E
D
24
If you access the BPM-E using a static IP or Host name, you can save the webpage address in your Favorites (a dynamic IP may be different each time the BPM-E connects).
When BPM-E is attached to its final destination network or computer, connect to it either by typing its IP address or host name in the address bar of your web browser, or use the BPMEFinder with your network or computer’s subnet mask to find and connect to the BPME.
If computer IP address or subnet mask were changed, restore the original settings.
Click ‘Apply all Changes’
Setup is now
complete
E
Note: To use the features of the WebTool software, refer to
Chapter 4 Operating Instructions on page 27.
25
26
Chapter 4 Operating Instructions
This chapter provides a description of controls and indicators on the BPM-E and the 3129 Digital Display. Read and become familiar with the following instruc­tions before operating the unit.
Couplers
The BPM-E does not use elements to sense the RF signal. It uses couplers. The couplers are fixed in place.
CAUTION
BPM-E signal sensing couplers are fixed in place. Do not attempt to remove or
rotate the couplers. They are calibrated and oriented at the factory and are
not designed to be rotated or removed by the end user. Failure to comply may
result in loss of calibration and accuracy, and in permanent damage to the
unit.
BPM-E Controls
There are two indicators and one control on the BPM-E:
Monitor On LED (green) - Lights when the unit is powered. Alarm LED (red) - Lights when an alarm has been triggered. Reset Switch - Press to reset an alarm. If the alarm trigger condition is still
present, the alarm will reactivate.
3129 Digital Display
Power On
After the AC power switch is set to ON, a message will be displayed. Examples of possible messages are:
‘Digital display ver x.xxx’ Shown at power-up for about 4 seconds.
‘Waiting...’ Shown when no response is received from the BPM-E.
‘Serial Pass Thru...’ Shown when a PC or other remote device is connected to the Remote Computer Connector on the front panel.
27
Mode Button
Press MODE to cycle through the possible display modes for the right half of the display, which are:
Reflected Power
Match Efficiency (%)
Return Loss (dB)
VSWR (SWR)
Reflection Coefficient (ρ)
Units Button
Press UNITS to toggle the display between Watts (W or kW) and dBm. The unit applies to forward power and to reflected power (if it is displayed).
Reset Button
Resets the alarm LED if the alarm condition is no longer present. Directly connected to the Reset Input pin of the BPM-E Power/Alarm connector.
Alarm LED
Indicates the presence of an alarm condition. Directly connected to the Alarm pin on the BPM-E Power/Alarm connector.
WebTool Software
The BPM-E WebTool software is used to monitor the measurement outputs from the BPM-E and to set and change alarm and network configurations. This soft­ware runs in a web browser (such as Microsoft’s Internet Explorer). To use the tool, open a web browser then in the address field, type the address of the BPM-E you wish to access. The software has five buttons at the left side that open the following screens: Main, Stats, Config, Admin, and Help. You can access information about the WebTool software by click on the Help button.
28
Main Screen
The Main screen is the default screen you see when you open the WebTool soft­ware (Figure 14, page 29). The Main screen identifies the BPM-E at the top of the window. The center of the screen displays measurement data that is being received from the BPM-E. You can set the refresh rate from 1 second to 60 sec­onds (how frequently the software updates the data from the BPM-E). At the bottom of the window, the status bar displays various information about the software and uses three alert colors, red - a fatal error (cannot establish connec­tion, connection lost), yellow - a warning (cannot complete a user request, user does not have access permission), gray - normal operation.
For more information about the Main screen features, refer to the help section in the software (click on the Help button).
The alarm condition area (Figure 15, page 30) will display three conditions
No alarm (green text) - no alarm condition exists
Latched (red text) - an alarm condition did occur but its cause has been fixed or the cause no longer exists.
Alarm (red text) - an alarm condition that has occurred and has not gone away or been reset is identified by text (VSWR, High Pwr, Low Pwr,
or any combination of these if more than one alarm exists).
You can reset the alarm at the BPM-E by pressing the reset button or by clicking on the Reset Alarm button on the Web Tool Main screen. If the cause of the alarm is still present, the message cannot be reset.
Figure 14 BPM-E WebTool Software, Main Screen
29
Figure 15 Alarm Active Message
Reset Alarm
Stats Screen
The Stats screen (Figure 16 on page 30) can chart and display historical data stored in the BPM-E memory. You can chart forward and reflected power read­ings and alarm conditions (low power, high power, and VSWR alarm). You can display the data in either a line graph or a bar chart.
The BPM-E keeps data for a 365 day period. You select the starting day (in the Begin field) and the number of days to view. Day 0 is today, day 1 is yesterday, and so on to day 364. Click the Add >> button to add the days to the list to view.
When you click the Chart It button, the WebTool retrieves the data and gener­ates a new chart. Click the Clear button to clear your day selection.
For more information about the Stats screen features, refer to the help section in the software (click on the Help button).
Figure 16 Web Tool Stats Screen
30
Config Screen
The Config (Configure) screen has two tab views, Alarms and Frequency. The administrator of the WebTool can set an optional password requirement to con­trol who can make changes to the Config screen (refer to Admin Screen for pass­word control).
For more information about the Config screen, refer to the help section in the software (click on the Help button).
Alarm Tab
In the Alarms tab (Figure 17, page 32), you specify BPM-E alarm settings. To return to the factory default alarm settings, click on the Factory Default button. After you have set the alarm preferences, click the Apply Changes button to record your settings in memory.
You can select or deselect the following alarm conditions:
Master Alarm Enable - When checked, activates the VSWR alarm and
enables all other alarm conditions that have been selected (boxes checked), dis­ables all alarms when not checked.
VSWR trip point - Specify the VSWR value that will cause an alarm (select val-
ues from the drop-down list). This value is adjustable from 1.3 to 2.5 by incre­ments of 0.1. Check the VSWR Alarm Enabled on Zero Power checkbox to allow the VSWR alarm to trigger at very low forward power (< 2.5% of full scale power). Refer to See “Determining VSWR Alarm Trip Point” on page 53 for addi­tional information about limitations of the VSWR trip point.
High Power Alarm (forward power only) - Check the Enable box and spec-
ify the percentage of full scale at which an alarm will occur. The high power value must be greater than the low power value. The maximum value is 125% of full scale power. The alarm setpoint is entered as a percent of full scale. For example, if you have a 500W full scale unit and would like an alarm when the forward power exceeds 375 W, the alarm setpoint would be 375/500 x 100 or 75%. Enter 75 in the field and check the Enable High Power Alarm checkbox.
Low Power Alarm (forward power only) - Check the Enable box and spec-
ify the percentage of full scale at which an alarm will occur. The low power value must be less than the high power value. The minimum is 0%.
Latch Alarms - Sets whether the alarm will reset automatically in the absence
of an alarm condition. When this checkbox is unchecked, if an alarm trigger is corrected, the alarm will reset after a forty-five second delay. When the box is checked, the alarm must be manually reset.
Trigger Alarm Button - After you have set or made changes to alarm settings,
you can use the Trigger Alarm button to test the alarms (messages, relay, TTL out­puts). If the Config password is enabled, you will be required to enter the password before you can test the alarm settings.
31
Figure 17 WebTool Config Screen, Alarms
Frequency Tab
In the Frequency view (Figure 18 on page 32), you specify monitor frequencies and then apply that configuration to the BPM-E. Click the View Channel List button to display a list of United States television channels and their frequencies (Figure , page 32). To add a frequency to the Selected Frequencies list, type it in the Fre­quency (MHz) field, then click the Add button. To remove a frequency from the list, click on the frequency to select it, then click on the Remove button. After you have set the configuration frequencies, click the Configure button to record your settings to memory. The value shown beside Configuration Frequency is the cen­ter frequency of all of the values in the Selected Frequencies list.
Note: The changed frequencies stored in memory will not take effect
until the BPM-E power has been turned off and then back on.
Figure 18 Web Tool Config Screen, Frequency
32
Admin Screen
The Admin screen has four tabs, Network, Email Alerts, SNMP, and Passwords. After making changes in one or all of the tabs, click the Apply All Changes button to record your settings in memory.
For more information about the Admin screen, refer to the help in the software (click on the Help button).
Network Tab
In the Networking tab (Figure 19 on page 33), you can specify the following infor­mation about the address of the BPM-E: IP address, subnet mask, gateway IP, DHCP host name, and whether or not DHCP is used.
If you use the ethernet connection to communicate with the BPM-E, you need to specify a unique IP address. An IP address is required even if you connect the BPM-E directly to a computer that is not on a network. Contact your IT profes­sional for assistance in determining the IP address, subnet mask, and information about DHCP use and name.
Figure 19 WebTool Admin Screen, Network Setup
Email Alerts Tab
In the Email Alerts tab (Figure 20 on page 34), you can specify the following infor­mation: the SMTP server IP, the SMTP port, whether or not to use the email alerts, the email address of the BPM-E, and the email addresses of two people to notify when an alarm occurs (optional).
You can have the WebTool software contact two specified recipients via email if an alarm occurs. The BPM-E needs to be connected to a computer or server that has email capabilities. Contact your IT professional for assistance in determining the SMTP server IP and port. The text you enter at the left of the @ symbol in the From email address will uniquely identify this BPM-E in all sent emails. Use text that will identify the BPM-E and its location. The text at the right of the @ symbol is the email domain information for your server.
33
Figure 20 WebTool Admin Screen, Email Alerts
SNMP Tab
In the SNMP tab (Figure 21 on page 34), you can specify setup for the SNMP fea­ture if you have chosen to use it. Contact your IT professional for assistance. You can obtain the latest MIB file from the Bird Technologies web site.
Figure 21 WebTool Admin Screen, Set SNMP Email Address
34
Password Tab
In the Password tab (Figure 22 on page 35), you can set the administrator pass­word and the optional configuration access password. When you set or change a password, you must type the password a second time in the appropriate “confirm” field before it will be accepted.
You must have a password to view and edit the Admin screen. The default pass­word is “bird” (lower case without the quotes). After you make changes, click on the Apply All button.
If a configuration access password is set, users can view the Config screen but not edit it. A password must have at least 3 and no more than 49 characters.
Figure 22 Web Tool Admin Screen, Passwords
Help Screen
While you are using the WebTool software, you can get help about the screens and features by clicking on the Help button at the left side of the screen.
35
PCTool Software
The BPM-E PCTool software is used to monitor the measurement outputs from the BPM-E and to set and change alarm configurations. This software is a stand-alone application that must be installed onto your PC. To use the tool, launch it from the computer’s operating system menus or from a shortcut on your desktop.
Note: Your PC must have the Java runtime environment (java vir-
tual machine) installed to run the PCTool software. For Windows operating systems, this is typically installed by default. If you do not have the runtime environment, you can download it from the java.com web site (look for Java Software for Desktop).
The PCTool screen (Figure 23, page 36) is divided into three parts, the Menu bar at the top, the information area in the center, and the status bar at the bottom. The BPM-E identification and the COM port being used appear in the space immediately below the Menu bar. The status bar displays various information about the software and uses three alert colors, red - a fatal error (cannot estab­lish connection, connection lost), yellow - a warning (cannot complete a user request), gray - normal operation. The Menu bar has the following four entries:
File - Contains the command to exit the software Connection - Contains two options, New (select a COM port), and Close (dis-
connect the BPM-E from the PC)
View - Contains two options, Main (open the Main screen) and Config (open
the Config and Alarm screen)
Help - Provides information about the software version and opens the on-line
help screens.
Figure 23 PCTool Screen, Main Screen
36
Connection
The PCTool software must be set to use the correct computer COM port to com­municate with the BPM-E. The default port is COM 1. To change the Com port, select Connection from the Menu bar, then select New. Choose the COM port you want from the drop-down list in the dialog box then click OK (Figure 24, page 37).
Note: The Connection menu also has a Close command. Choosing
the Close command will close (break) the COM port connection to the computer.
For more information about the Connection screen features, refer to the help section in the software (click on Help on the Menu bar).
Figure 24 PCTool Software, New Co nnection Com Menu
View
The View menu has two options, Main and Config.
Main
The “Main” screen (Figure 23, page 36) is the default screen you see when you open the PCTool software. It displays forward and reflected power, VSWR, return loss, Rho, efficiency, and alarm conditions.
37
The alarm condition area displays information in three colors:
No alarm (green text) - No alarm condition exists Latched (red text) - An alarm has happened, but has cleared Alarm (red text) - An alarm has happened and is identified (VSWR, High Pwr,
Low Pwr, or any combination of these if more than one alarm exists)
If an alarm has occurred and has not been reset, the alarm text will be red and will display which alarm (or alarms) occurred (Figure 25, page 38). You can reset the alarm at the BPM-E or by clicking on the Reset Alarm button on the Main screen. If the alarm condition is still present, the message cannot be reset.
You can also set the refresh rate from 1 second to 60 seconds (how frequently the software updates the data from the BPM-E).
For more information about the Main screen features, refer to the help section in the software (click on Help on the Menu bar).
Figure 25 PCTool Main Screen (alarm display)
Config
The Configure (Config) screen has two tab views, Alarms and Frequency.
Alarm Tab - In the Alarms tab (Figure 26, page 39), you specify BPM-E alarm set-
tings. To return to the factory default alarm settings, click on the Factory Default button. After you have set the alarm preferences, click the Apply Changes button to record your settings in memory.
38
Figure 26 Config Screen, Alarm Tab
You can select or deselect the following alarm conditions:
Master Alarm Enable - When checked, activates the VSWR alarm and
enables all other alarm conditions that have been selected (boxes checked), dis­ables all alarms when not checked.
VSWR trip point - Specify the VSWR value that will cause an alarm (select val-
ues from the drop-down list). This value is adjustable from 1.3 to 2.5 by incre­ments of 0.1. Check the VSWR Alarm Enabled on Zero Power checkbox to allow the VSWR alarm to trigger at very low forward power (< 2.5% of full scale power).
High Power Alarm (forward power only) - Check the Enable box and spec-
ify the percentage of full scale at which an alarm will trigger. The high power value must be greater than the low power value. The maximum value is 125% of full scale power. The alarm setpoint is entered as a percent of full scale. For example, if you have a 500W full scale unit and would like an alarm when the forward power exceeds 375 W, the alarm setpoint would be 375/500 x 100 or 75%. Enter 75 in the field and check the Enable High Power Alarm checkbox.
Low Power Alarm (forward power only) - Check the Enable box and specify
the percentage of full scale at which an alarm will trigger. The low power value must be less than the high power value. The minimum is 0%.
Latch Alarms - Sets whether the alarm will reset automatically in the absence
of an alarm condition. When this checkbox is unchecked, if an alarm trigger is corrected, the alarm will reset after a forty-five second delay. When the box is checked, the alarm must be manually reset.
After you have set or made changes to alarm settings, you can test the settings by clicking on the Trigger Alarm button.
39
Frequency Tab
In the Frequency tab (Figure 27 on page 40), you specify monitor frequencies and then apply that configuration the BPM-E. Click the View Channel List button to dis­play a list of United States television channels and their frequencies (Figure 28, page 40). To add a frequency to the Selected Frequencies list, type it in the Fre­quency (MHz) field, then click the Add button. To remove a frequency from the list, click on the frequency to select it, then click on the Remove button. After you have set the configuration frequencies, click the Configure button to record your settings to memory. The value shown beside Configuration Frequency is the cen­ter frequency of all of the values in the Selected Frequencies list.
Figure 27 Config Screen, Frequency Tab
Figure 28 US Television Channel List
40
Chapter 5 Maintenance
This chapter contains cleaning, troubleshooting, specifications, and part infor­mation for the Bird Broadcast Power Monitor and the 3129 Digital Display.
Inspection and Cleaning
This unit requires only simple and routine maintenance.
WARNING
Disconnect the unit from the RF power source and the ac
line before any disassembly. The potential for electrical
shock exists.
CAUTION
Do not use harsh or abrasive detergents for cleaning.
1. Wipe off dust and dirt regularly. Use a soft, clean cloth dampened with mild detergent.
2. Check connectors, connector pins, and cables for damage. If needed, clean the connectors using a self-drying contact cleaner that leaves no residue.
3129 Digital Display Fuses
The 3129 Digital Display contains two time-delayed IEC (5 x 20mm) Type T 1.0A, 250V fuses. These are the only user replaceable parts. Refer to figure Figure 29 on page 42 for fuse location.
41
Figure 29 3129 Digital Display, Fuse Location
1
2
3
Item Description
1 Fuse holder tab, pry outward to remove fuse holder 2 Fuse holder 3Fuse
Specifications
BPM-E Specifications
Frequency Range
VHF low VHF UHF
Dynamic Range, Min 20 dB Max Allowable Peak/
Average Ratio Insertion Loss, Max 0.05 dB Directivity, Min 26 dB min, 30 dB typical
42
45 – 88 MHz 88 - 230 MHz 470-890 MHz
10 dB min. at max RF power
Detection Method T rue Average Power Impedance 50 ohms Accuracy
Power
Calibrated for FM band TV Channels 1-6
TV Channels 7-83 VSWR
Display Resolution RMS Noise
Connectors, RF See See “Line Section Sizes” on
RS-232 Serial Port
Connector Protocol
DC Power Required Analog Outputs
NOTE: Refer to See “Factors that Affect Power Reading Accuracy” on page 7 in the Theory of Operation to learn about factors that can cause power readings to be out of spec.
± 5% of reading ± 5% of reading at calibrated channel ± 1 channel ± 5% of reading at calibrated channel ± 4 channels Calculated from Fwd and Rfl power ± 1 digit
0.1 % of full scale
page 49
Female DB-9 9600 baud, no parity, 8 data bits, 1 stop bit, no handshake +12 to +26 Vdc @ <0.5A 2V full scale, 0 to 2V range, 200 ohm output impedance, linear scale.
Ethernet port
Network Interlace Compatibility Protocols
Left LED Right LED Security Power/Alarm Parallel Port Display Options
Ethernet 10/100 BASE-T (auto sensing) Ethernet version 2.0 / IEEE 802.3 ARP, UDP/IP, TCP/IP, DHCP, BOOTP, AutoIP, and HTTP Amber: 10 Mbps. Green: 100 Mbps Amber: Half-duplex. Green: Full-duplex 128 bit encryption Female DB-15 connector BPM-E-PCTool, 3129 digital display, Site Analyzer, BPM-E-WebTool
43
Alarm
Alarm Relay
Relay Contact Rating VSWR set points
Alarm Stimulus Alarm Response
Alarm Reset
Alarm Power Up
Environmental
Operating Temp Storage Temp Humidity Altitude
CE CE compliant Calibration Cycle > 1 year
Dry, contacts, with common, normally open, and normally closed connections (form C) 100 Vdc @ 0.5 A
1.3 to 2.5:1 by 0.1 steps, measurement limited by max input power VSWR, high forward power, low forward power Turn on red LED; trip relay; set software flag; set alarm line low (<0.2V); Send email Response time is inversely proportional to the overload Push button on BPM-E Push button on 3129 digital display Ethernet or RS-232 command TTL low (Vdc=0 to +0.8 V) Alarm defaults to fail-safe (alarm on when unit is not powered
0 to +50 °C (+32 to 122 °F) –20 to +80 °C (–4 to +176 °F) 95% max. (non-condensing) 3000 m (10,000 ft.) above sea level
Recommended Calibration Cycle Interval
Dimensions See See “Line Section Sizes” on
Weight, Nominal See Figure 31, page 49
3129 Digital Display Specifications
Display 20 character LCD with LED backlight RS-232 Serial Port
Connector Protocol
Power/Alarm Parallel Port Male DB-15 connector
User defined
page 49
Male DB-9 RS-232, 9600 baud, no parity, 8 data bit s, 1 stop bit, no handshake
44
Remote Computer Connector
Connector Protocol
AC Power Requirements 115/230 Vac @ 50/60 Hz, 0.6 A AC Connector
Domestic International
T emperature
Operating Storage
Humidity 95% max. (non-condensing) Altitude 3000 m (10,000 ft.) Dimensions 19" L x 1.75" W x 5" H
Weight, Nominal < 10 lbs
RF Power Range, VHF Frequency Band (45-230 MHz)
Female DB-9 RS-232, 9600 baud, no parity, 8 data bit s, 1 stop bit, no handshake
North American Power Cord Standard Type SVT, 300 Vac, 18 A WG, 10 A, 3 conductor (including ground) Type H05VV-F, 300 Vac, 1.00 mm, 10 A, 3 conductor (including ground)
–10 to +50 °C (+14 to 122 °F) –40 to +80 °C (–40 to +176 °F)
(483 x 44 x 127 mm) (1U EIA)
Line size
7/8” High
1-5/8” High
3-1/8” High
4-1/16” and 4-1/2”
6-1/8” High
Unit power
Med Low
Med Low
Med Low Extra Low
High Med Low
Med Low
range
Measurable Range, Fwd
5000 - 50 W 2000 - 20 W 500 - 5 W
20 - 0.2 kW 8000 - 80 W 2000 - 20 W
50 - 0.5kW 20 - 0.2 kW 5000 - 50 W 1000 - 10 W
100 - 1 kW 40 - 0.4 kW 10 - 0.1 kW
200 - 2 kW 80 - 0.8 kW 20 - 0.2 kW
Measurable
Range, Rfl
500 - 5 W 200 - 2 W 50 - 0.5 W
2000 - 20 W 800 - 8 W 200 - 2 W
5000 - 50 W 2000 - 20 W 500 - 5 W 100 - 1 W
10 - 0.1 kW 4000 - 40 W 1000 - 10 W
20 - 0.2 kW 8000 - 80 W 2000 - 20 W
45
RF Power Range, UHF Frequency Band (470-890 MHz)
Line size Unit power
range
7/8” High
Med Low
1-5/8” High
Med Low
3-1/8” High
Med Low Extra Low
4-1/16” and 4-1/2”
6-1/8” High
High Med Low
Med Low
Measurable
Range, Fwd
2500 - 25 W 1000 - 10 W 250 - 2.5 W
5000 - 50 kW 2000 - 20 W 500 - 5 W
25 - 0.25 kW 10 - 0.1 kW 2500 - 25 W 1000 - 10 W
40 - 0.4 kW 15 - 0.15 kW 4000 - 40 W
75 - 0.75 kW 30 - 0.3 kW 8000 - 80 W
Measurable
Range, Rfl
250 - 2.5 W 100 - 1 W 25 - 0.25 W
500 - 5 W 200 - 2 W 50 - .05 W
2500 - 25 W 1000 - 10 W 250 - 2.5 W 100 - 1 W
4000 - 40 W 1500 - 15 W 4000 - 4 W
7500 - 75 W 3000 - 30 W 800 - 8 W
46
Troubleshooting
The Bird Broadcast Power Monitor has no operator serviceable parts. Any required service must be performed at an authorized service facility.
The table below contains troubleshooting information for problems which can occur during normal operation. This manual cannot list all malfunctions that may occur or their corrective actions. If a problem is not listed or is not cor­rected by the listed actions, notify a qualified service center.
PROBLEM POSSIBLE CAUSE CORRECTION
Monitor On LED does not illuminate
Alarm LED does not illuminate when alarm exists
High VSWR Dirty connectors Clean connectors
Digital display screen does not light
No dc power Check power source, and
15 pin power/alarm cable
Defective LED Return the unit to an
authorized service center
Defective LED Return the unit to an
authorized service center
Defective power/alarm cable
Defective connectors Replace connectors Shorted or open
transmission line Unit is not turned on Set AC Power Switch to
Unit is not plugged in Connect AC power cord Fuse is blown Replace fuse
Repair or replace cable
Have the line serviced.
ON
Replacement Parts
Description Part Number
Digital Display 3129 9 pin RS-232 Interface Cable
50 ft. 10 ft.
DB-15 Interface Cable,
50 ft., male/female 5A2264-15-MF-50
DB-15 Interface Connector SUBCON-15/M-SH Fuse, for 3129 digital display (1
amp, slow blow)
5A2264-09-MF-50 5A2264-09-MF-10
5A2257-16
47
RF Power Ratings
4
-1/16 ”
&
4-
1
/
2
6-1/8 ”
Line Section Max RF Power vs. Frequency
1000
100
10
Max Average Power (kW)
Frequency (Mhz)
10
1
100 1000
3
-1/
8 ”
7
/
8
1
-
5
/
8
For power ratings based upon line sizes, refer to See “Specifications” on page 42.
Note: For a specific frequency and line size, the maximum safe oper-
ating power may be lower than the full scale power measurement capability of the BPME.
48
Line Section Sizes
6.5”
(165 mm)
6 11/64”
(169.9 mm)
3 1/8”
(79.4 mm)
BPM-E7
4.25”
(106 mm)
C
POWER/ALARM RS/232
ALARM
OPR/TEST
RESET
BROADCAST
POWER MONITOR
Cleveland, Ohio USA
Phone: (440) 248-1200
www.bird-electronic.com
B
A
4.5”
114 mm
()
Figure 30 BMPE Dimensions, Model BPM-E7
Figure 31 BPM-E Dimensions, Flanged and Unflanged Models
49
Inner
Conduc
1
Model Connector
BPME1 1-5/8” EIA
Flanged
BPME1U 1-5/8” EIA
BPME1UF 1-5/8” EIA
BPME3 3-1/8” EIA
BPME3U 3-1/8” EIA
BPME3UF 3-1/8” EIA
BPME4AUF 4-1/2” IEC
BPME4D 4-1/16”
BPME4M 4-1/16”
BPME6 6-1/8” EIA
BPME6U 6-1/8” EIA
BPME7 7/8” line,
1
For unflanged units, this dimension is the outer diameter of the transmission line.
Unflanged
Unflanged, Flush Center
Flanged
Unflanged
Unflanged, Flush Center
Unflanged
Flanged, Dielectric Standard
Flanged, Myat Standard
Flanged
Unflanged
Type N connectors
Dim. A
3.50” (89 mm)
1-5/8” (41.3 mm)
1-5/8” (41.28 mm)
5.19” (132 mm)
3-1/8” (79.4 mm)
3-1/8” (79.4 mm)
4.17” (106 mm)
6.19” (157 mm)
6.19” (157 mm)
8.13” (206 mm)
6-1/8” (155.6 mm)
1.25” (318 mm)
Dim. B Dim. C
6.75” (171.5 mm)
6.38” (162 mm)
6.38” (162 mm)
7.03” (178.6 mm)
6.5” (165.1 mm)
6.5” (165.1 mm)
7.5” (190.5 mm)
8.38” (212.8 mm)
8.38” (212.8 mm)
10.22” (259.6 mm)
9.63” (244.6 mm)
n/a n/a n/a 1.25 lbs.
2.98“ (75.7 mm)
2.98“ (75.6 mm)
2.98“ (75.6 mm)
3.4“ (86.4 mm)
3.4“ (86.4 mm)
3.4“ (86.4 mm)
3.96” (100.7 mm)
3.87“ (98.2 mm)
3.87“ (98.2 mm)
4.96“ (126 mm)
4.96“ (126 mm)
tor
Setback
EIA 3.25 lbs.
0.438” (11.1 mm)
0 1.5 lbs.
EIA 7.25 lbs.
0.688” (17.5 mm)
0 4.25 lbs.
0.06” (1.5 mm)
1.22” (31 mm)
1.375” (35 mm)
EIA 17 lbs.
0.968” (24.6 mm)
Weight
(1.5 kg)
1.5 lbs. (0.68 kg)
(0.68 kg)
(3.3 kg)
4.25 lbs. (1.93 kg)
(1.93 kg)
10 lbs. (4.55 kg)
8.88 lbs. (4 kg)
8.88 lbs. (4 kg)
(4 kg)
12.75 lbs. (5.78 kg)
(0.57 kg)
50
3129 Digital Display
Electronic Corporation
Model 3129
True Average Power
Mode Units
Alarm
Reset
Remote
1.75 ” (44 mm)
0.25 ”
(6 mm)
1/8 ”
(3 mm)
19 ”
(483 mm)
(432 mm)
4.92 ” (125 mm)
WARNING
SHOCK HAZARD
REMOVE AC POWER BEFORE ATTEMPTING
TO SERVICE THIS INSTRUMENT
Figure 32 3129 Digital Display Dimensions
51
Customer Service
Any maintenance or service procedure beyond the scope of those in this chapter should be referred to a qualified service center.
If you need to return the unit for any reason, request an RMA through the Bird Technologies website (link shown below). All instruments returned must be shipped prepaid and to the attention of the RMA number.
Bird Service Center
30303 Aurora Road Cleveland (Solon), Ohio 44139-2794 Fax: (440) 248-5426 E-mail: bsc@bird-technologies.com
For the location of the Sales Office nearest you, visit our website at:
http://www.bird-technologies.com
52
Appendix 3 Reference Information
Determining VSWR Alarm Trip Point
Even though the VSWR trip point can be set to 2.5, the instrument cannot always measure VSWR above 1.9. This is due to the large amount of reflected power caused at higher VSWRs. The maximum VSWR that can be physically measured is determined by the ratio of the forward and reflected couplers at full scale. This ratio is 10:1. The maximum measurable VSWR occurs when the reflected channel is near its limit. The following table shows the maximum mea­surable VSWR as a function of percentage of full scale forward input power. Use this table as a guide to determine the VSWR trip point. For example, using a BPM-E 1 for the VHF low band, the full scale power measurement is 2 kW. If you are measuring a transmitter that delivers 1.7 kW (1.7 Kw is 85% of the 2 kW full scale), the maximum measurable VSWR is 2.24. If the transmitter power is reduced to 1 kW (50 % of the 2 kW full scale), then the maximum measurable VSWR is 3.00.
Percentage Full
Scale
50% 3.00 55% 2.82 60% 2.68 65% 2.56 70% 2.46 75% 2.38 80% 2.31 85% 2.24 90% 2.19 95% 2.14
100% 2.09
Max VSWR
53
54
Limited Warranty
All products manufactured by Seller are warranted to be free from defects in material and workmanship for a period of one (1) year, unless otherwise speci­fied, from date of shipment and to conform to applicable specifications, draw­ings, blueprints and/or samples. Seller’s sole obligation under these warranties shall be to issue credit, repair or replace any item or part thereof which is proved to be other than as warranted; no allowance shall be made for any labor charges of Buyer for replacement of parts, adjustment or repairs, or any other work, unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or not to conform to specifications, drawings, blueprints and/or samples, Seller shall, upon prompt notice thereof, either examine the products where they are located or issue shipping instructions for return to Seller (transportation-charges prepaid by Buyer). In the event any of our products are proved to be other than as warranted, transportation costs (cheapest way) to and from Seller’s plant, will be borne by Seller and reimbursement or credit will be made for amounts so expended by Buyer. Every such claim for breach of these warranties shall be deemed to be waived by Buyer unless made in writing within ten (10) days from the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof which have been subjected to any misuse or neglect, damaged by accident, rendered defective by reason of improper installation or by the performance of repairs or alterations outside of our plant, and shall not apply to any goods or parts thereof furnished by Buyer or acquired from others at Buyer’s request and/or to Buyer’s specifications. Routine (regularly required) calibration is not covered under this limited warranty. In addition, Seller’s warranties do not extend to the failure of tubes, transistors, fuses and batteries, or to other equipment and parts manufactured by others except to the extent of the original manufacturer’s war­ranty to Seller.
The obligations under the foregoing warranties are limited to the precise terms thereof. These warranties provide exclusive remedies, expressly in lieu of all other remedies including claims for special or consequential damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER WARRANTY WHATSOEVER, WHETHER EXPRESS, STATUTORY, OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT­NESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR SELLER ANY OBLIGATION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
Bird Technologies
56
Loading...