BFT LEO Instruction Manual

Page 1
LEO
CONTROL UNIT
FOR ICARO
D80000
00-00-99 Vers. 00
Page 2
346
LEO
LEO
GND terminal
2-3 Single-phase mains supply 230V±10% 50Hz (2=N) (3=L)
JP2
4-5 Blinker connection (mains voltage) 40W Max. 6-7-8-9 Motor connection:
6 operation 1 + capacitor 7 common (blue) 8 operation 2 9 capacitor
JP3
10-11 Output 24V~ 1A max – power supply for photocells or other
devices.
12-13 Gate-open warning light output (24V 3W max)
JP5 Encoder connection
WARNING! The maximum length of the connection cable of
the encoder should not exceed 3.00 mt.
JP8
21-22 Open-Close button (N.O. Start), key selector. 21-23 Block button (N.C. Stop). If not used, leave jumped. 21-24 Photocell input (N.C.). If not used, leave jumped. 21-25 Opening limit switch connection (N.C. SWO). If not used,
leave jumped.
21-26 Closing limit switch connection (N.C. SWC). If not used, leave
jumped. 21-27 Pedestrian button connection (N.O. Ped) 21-28 Open-Button connection (N.O. Open) 21-29 Close-Button connection (N.O. Close) 21-30 Rubber edge connection (N.C.). If not used, leave jumped. 21-31 Timer input connection (N.O.). If the contact is open the leaves
close and the gate is ready for normal operation. If the contact
is closed (N.C.), the leaves open and remain open until the
contact is opened.
JP9
34 TX1 serial output 35 TX2 serial output 36 RX1 serial imput 37 RX2 serial input 38-39 Antenna input for snap-in radio receiver board (38 signal - 39
braid). Cable RG58 40-41 Second radio channel output of twin-channel receiver board
D811327_03
CONTROL UNITS
CONTROL UNITS
Page 3
347
5) PROGRAMMING
The control panel provided with a microprocessor is supplied with function parameters preset by the manufacturer, suitable for standard installations. The predefined parameters can be altered by means of either the incorporated display programmer or UNIPRO. In the case where programming is carried out by means of UNIPRO, carefully read the instructions relating to UNIPRO, and proceed in the following way. Connect the UNIPRO programmer to the control unit through the UNIFLAT accessory (See fig. 5). Enter the CONTROL UNITS menu, and the
PARAMETERS submenu, then scroll the display screenfuls using the up/ down arrows, and set the numerical values of the parameters listed below. For the function logics, refer to the LOGIC submenu. In the case where programming is carried out by means of the incorporated programmer, refer to Fig. A and B and to the configuration paragraph.
6) CONFIGURATION
The display programmer is used to set all the LEO control panel functions. The programmer is provided with three pushbuttons for menu scrolling and function parameter configurations (Fig. 2): + menu scrolling/value increment key
- menu scrolling/value reduction key OK Enter (confirm) key The simultaneous pressure of the + and
– keys is used to exit the active menu and move to the preceding menu. If the + and – keys are pressed simultaneously at the main menu level (parameters, logics, radio, language, autosetting, self-diagnosis), programming is exited and the display is switched off (the OK message is displayed). The modifications made are only set if the OK key is subsequently pressed. When the OK key is pressed for the first time, the programming mode is entered. The following pieces of information appear on the display at first:
- Display Software version
- Control unit Software version
- Number of total manoeuvres carried out (the value is expressed in
thousands, therefore the display constantly shows 0000 during the first thousand manoeuvres)
- Number of manoeuvres carried out since the latest maintenance operation
(the value is expressed in thousands, therefore the display constantly shows 0000 during the first thousand manoeuvres)
- Number of memorised radio control devices. When the OK key is pressed during the initial presentation phase, the first menu (parameters) can be accessed directly. Here follows a list of the main menus and the respective submenus available. The predefined parameter is shown between square brackets [ 0 ]. The writing appearing on the display is indicated between round brackets. Refer to Figures A and B for the control unit configuration procedure.
6.1) Parameter Menu (PARAM) 1- Pedestrian opening (Mt. ped) [ 001.0 m ]
Set the numerical value of the pedestrian opening from 10 cm (000.1) to 6m (006.0).
2- Automatic Closing Time (TCA) (tca) [ 40s ]
Set the numerical value of the automatic closing time from 1 to 180 seconds.
3- Encoder (Encoder) [ 80 ]
Set the encoder sensitivity value from 1 to 99. A higher value corresponds to greater sensitivity, whereas a lower value corresponds to lesser sensitivity.
WARNING: Check that the impact force value measured at the points established by the EN 12445 standard is lower than that specified in the EN 12453 standard.
Incorrect sensitivity setting can cause injuries to persons or animals, or damage to things.
4- Opening torque (open torque) [ 50% ]
Set the motor opening torque value between 1% and 99%.
5- Closing torque (cls. torque) [ 50% ]
Set the motor closing torque value between 1% and 99%.
6- Brake (Brake) [ 0% ]
Set the required brake value between 0 and 99%, compatibly with the weight of the gate and the existing stresses.
7- Zone (zone) [ 0 ]
Set the zone number between a minimum value of 0 and a maximum value of 127. See paragraph 7 on Serial connection.
6.2) Logic Menu (logic.)
- TCA ( tca ) [ ON ]
ON Activates automatic closing OFF Excludes automatic closing
- 3 Steps (3 step) [ OFF ]
ON Enables 3-step logic. A start impulse has the following effects:
door closed: ............................................................................ opens
on opening: ............................ stops and enters TCA (if configured)
door open: .............................................................................. closes
on closing: ....................................... stops and reverses movement
after stopping: ......................................................................... opens
OFF Disables 3-step logic
- Opening Impulse lock (Ibl open) [ OFF ]
ON The Start impulse has no effect during the opening phase. OFF The Start impulse becomes effective during the opening phase.
- Impulse lock TCA (ibl TCA ) [ OFF ]
ON The Start impulse has no effect during the TCA dwell period. OFF The Start impulse becomes effective during the TCA dwell period.
- Pre alarm (pre-alarM) [ OFF ]
ON The blinker comes on about 3 seconds before the motor starts. OFF The blinker comes on at the same time as the motor starts.
- Hold-to-run (hold-to-run ) [ OFF ]
ON Hold-to-run operation: the manoeuvre continues as long as the
command key is kept pressed.
OFF Impulse operation: one impulse opens the gate if closed, and closes
it if open.
- Rapid closing (fast cls ) [ OFF ]
ON Closes the gate after photocell disengagement, before waiting for
the end of the TCA (automatic closing time) set.
OFF Command not entered.
- Photocells on opening (photc. open ) [ OFF ]
ON: In case of obscuring, this excludes photocell operation on opening.
During the closing phase, it immediately reverses the motion.
OFF: In case of obscuring, the photocells are active both on opening and
on closing. When a photocell is obscured on closing, it reverses the motion only after the photocell is disengaged.
- Master/Slave (Master) [ OFF ]
ON The control panel is set as Master in a centralised connection (see
Paragraph 7).
OFF The control panel is set as Slave in a centralised connection (see
Paragraph 7).
- Loop (loop) [ OFF ]
ON In the case of a closed loop centralised connection (Fig.5), set the
control unit to ON.
OFF In the case of an open centralised connection (Fig.5), set the control
unit to OFF.
6.3) Radio Menu (radio)
- Add (add)
Allows you to add one key of a radio control device to the receiver memory; after storage it displays a message showing the transmitter number in the memory location (from 01 to 64). NOTE: When using transmitters with two or more channels, the first push­button which has been stored is associated to the START function. If a second push-button is stored, it will be associated to the pedestrian function.
- Read (read)
Checks one key of a receiver; if stored it displays a message showing the receiver number in the memory location (from 01 to 64), and the key number (T1, T2, T3 or T4).
- Delete (erase 1)
Removes one single key of a transmitter from the receiver memory; after deletion it displays a message showing the receiver number in the memory location (from 01 to 64).
- Eliminate list (erase 64) WARNING! Completely removes all memorised radio control devices from
the receiver memory.
6.4) Language Menu (Language)
Allows you to set the language on the display programmer. 5 languages are available:
- ITALIAN (TA)
- FRENCH (FRA)
- GERMAN (DEU)
- ENGLISH (ENG)
- SPANISH (ESP)
6.5) DEFAULT MENU (default)
Restores the preset default values on the control unit.
D811327_03
LEO
LEO
CONTROL UNITS
CONTROL UNITS
Page 4
348
6.6) Self-diagnosis Menu (selftest)
Allows you to carry out control unit self-diagnosis. If, at the end of the diagnosis, the answer is OK, it means that the control unit and connected devices operate correctly. In case of error, the display indicates the number of the terminal which does not operate correctly; thus proceed to checking the devices connected to this, making reference to the following table: 22 Start error 23 Stop error 24 Photocell error 25 Opening limit-switch error 26 Closing limit-switch error 27 Pedestrian input error 28 Open error 29 Close error 30 Electric edge error 31 Clock error
6.7) Autoset Menu (Autoset )
Allows you to automatically set the following parameters: Opening torque Closing torque Encoder Brake To carry out autosetting, connect two N.O. pushbuttons, if not provided, to inputs 21-28 (Open) and 21-29 (Close). WARNING!! The autoset operation is only to be carried out after checking the exact leaf (opening/closing) movement, and correct limit-switch activation.
Therefore, during display of the (.... .... ....) message, carry out about fifteen
opening and closing manoeuvres in Hold-to-run mode, by pressing and keeping the OPEN or CLOSE pushbutton alternatively pressed until the opening or closing limit switches are activated. During this phase, the control panel carries out tests with various levels of opening/closing torque, encoder sensitivity and brake value. Moreover, during autosetting, the leaf may be stopped, due to the checks which are being carried out by the control panel. After this, if autosetting is successfully completed, the control unit
automatically exits the (.... .... ....) phase, and displays the OK message
which indicates correct autoset execution.
If, on the other hand, the control unit remains in the (.... .... ....) phase after
the 15 expected manoeuvres, it means that there are certain resistance points along the gate which do not allow the control unit to set optimum operation values. Proceed to find out whether there are any mechanical obstructions which might prevent regular leaf movement.
WARNING! About 10 manoeuvres are carried out in “Hold-to-run mode in the course of the autoset phase, during which the installer must control the automation movement and prevent persons or things from approaching or standing within the automation working range.
WARNING: Check that the impact force value measured at the points established by the EN 12445 standard is lower than that specified in the EN 12453 standard.
Incorrect sensitivity setting can cause injuries to persons or animals, or damage to things.
6.8) Statistics
Having connected the UNIPRO programmer to the control unit, enter the CONTROL UNIT / STATISTICS menu and scroll the screenful showing the statistical parameters:
- Board microprocessor software version.
- Number of cycles carried out. If motors are replaced, count the number
of manoeuvres carried out up to that time.
- Number of cycles carried out from the latest maintenance operation.
It is automatically set to zero after each self-diagnosis or parameter writing.
- Date of latest maintenance operation. To be updated manually from the
appropriate menu Update maintenance date.
- Installation description. 16 characters can be entered for installation
identification.
7) SERIAL CONNECTION (Fig.5)
The LEO control panel allows several automation units to be connected in a centralised way by means of appropriate serial inputs and outputs. This makes it possible to use one single command to open and close all the automation units connected.
Following the diagram in Fig. 5, proceed to connecting all the LEO control panels, exclusively using a telephone-type line. Should a telephone cable with more than one pair be needed, it is indispensable to use wires from the same pair. The length of the telephone cable between one appliance and the next must not exceed 250 m. At this point, each of the LEO control panels must be appropriately configured, by setting a MASTER unit first of all, which will have control over all the others, to be necessarily set as SLAVE (see logic menu). Also set the Zone number (see parameter menu) between 0 and 127.
The zone number allows you to create groups of automation units, each one answering to the Zone Master unit. Each zone can only be
assigned one Master unit, the Master unit in zone 0 also controls the Slave units in the other zones. Loop closing of the serial connection (indicated by a dotted line in Fig.5) is only needed if you require to check the no. of the connected devices by means of UNIPRO.
7.1) Opposite sliding leaves (Fig. 6)
Serial connection also provides centralized control of two opposite sliding gates (Fig. 6a). In this case, the Master M1 control board will perform closing and opening of Slave M2 control board simultaneously. In case of opposite sliding leaves, the M1 (master) control board and the M2 (slave) control board should bear the same area number without other devices being connected in such area. If the opening direction of one of the two motors is incorrect, invert the connection 6 and 8 of the motor as well as the connections 25 and 26 of the opening and closing limiting devices. The safety devices (photocells and sensing edges) should be connected according to the diagram in Fig. 6b. The Start, Open, Close, push-buttons and the Timer contact should be normally connected to the M1 (master) control board. The pedestrian command is to be connected to the M2 panel (slave). The Stop command provides greater safety and is generated by a double contact NC push-button connected to both control boards as shown in Fig. 6b.
NOTE: Disable the TCA function from the M2 (slave) panel.
8) SCRAPPING Warning: This operation should only be carried out by qualified personnel. Materials must be disposed of in conformity with the current
regulations. In case of scrapping, the automation devices do not entail any particular risks or danger. In case of materials to be recycled, these should be sorted out by type (electrical components, copper, aluminium, plastic etc.).
9) DISMANTLING Warning: This operation should only be carried out by qualified personnel. When the control unit is disassembled to be reassembled on another site, proceed as follows:
Disconnect the power supply and the entire electrical installation.
In the case where some of the components cannot be removed or are
damaged, they must be replaced.
The descriptions and illustrations contained in the present manual are not binding. The Company reserves the right to make any alterations deemed appropriate for the technical, manufacturing and commercial improvement of the product, while leaving the essential product features unchanged, at any time and without undertaking to update the present publication.
D811327_03
LEO
LEO
CONTROL UNITS
CONTROL UNITS
Page 5
349
LEGENDA
Fig. A
OK
Press the OK key
BFT Disp 1.0 LEO 1.0 0000 0000 00
PARAM.
LOGIC.
[00]
Parameter increment/reduction or ON/OFF commutation
Menu scrolling (+ = preceding - = following)
Press OK key (Enter/confirm)
OK! message (confirms modification made)
Mt.ped
PRG
PRG
[
001.0
]
ENCOder
OK
OK OK
OK
OK OK
OK OK
OK OK
OK OK
OK
OK
OK
OK
+/-
+/-
+/-
OK
brake
[
000
]
PRG
cls torque
[
050
]
PRG
open torque
[
050
]
PRG
[
080
]
PRG
TCA
[
040
]
PRG
ZONe
[
000
]
PRG
ACCESS TO MENUS
FOLLOWING MENUS
FIG. B
-
+
/ON
/OFF
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
Display software version
Control unit software version No. total manoeuvres
(in thousands) No. manoeuvres since latest
maintenance(in thousands) No. radio control devices
memorised
KO! message (value or function error)
PRG
ÒWaitÓ message (enter value or function)
OK
8 8 8 8
PARAMETER MENU
Pedestrian opening
- value expressed in m
(default 001.0=1m, min 000.1=0,1m, max
006.0=6m)
TCA -
value expressed in seconds (default
40=40s, min 1=1s, max 180=180s)
Encoder
Ð value expressed in % (default
80%, min 1%, max 99%)
Opening torque
Ð value expressed in %
(default 50%, min 1%, max 99%)
Closing torque Ð
value expressed in %
(default 50%, min 0%, max 99%)
Brake Ð
value expressed in % (default 0%,
min 1%, max 99%)
Zone Ð
numerical value (default 0, min 0,
max 127)
+/-
Simultaneously press the + and - keys. Simultaneous pressure of the + and Ð keys allows you to exit the active menu and return to the preceding menu; if this takes place at the main menu level, programming is exited and the display switched off. The modifications made are only confirmed if the OK key is subsequently pressed.
Preset value
PRG
OK
+/-
OK
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
PRG
OK
PRG
OK
PRG
OK
PRG
OK
PRG
OK
PRG
OK
PRG
OK
PRG
OK
PRG
OK
OK
photoc. open
ON OFF
[
off
]
OK
Mast
er
ON OFF
[
off
]
OK
LOOP
ON OFF
[
off
]
OK
fast cls
ON OFF
[
off
]
OK
hold-to-run
ON OFF
[
off
]
OK
PRE-ALarm
ON OFF
[
off
]
OK
ibl
tca
ON OFF
[
off
]
OK
ON OFF
[
off
]
iblopen
OK
3 step
ON OFF
[
off
]
OK
TCA
ON OFF
[on]
D811327_03
LEO
LEO
CONTROL UNITS
CONTROL UNITS
Page 6
350
Fig. B
22 . .. 31
language
P1
T1 T2
T1 T2 T3 T4
TRC 1-2
TRC 4
FIG. 1A
FIG. 2A
TRC 1-2
TRC 4
MITTO 2-4
T1T2T1
T2
T3
T4
P1
RADIO
Press P1 (pushbutton) on radio
control device Ð see Fig. 1A
Press the required T (key) on radio control device Ð see Fig. 2A
Press the required T (key) on radio control device Ð see Fig. 2A
Release P1 on radio control device
ADD hidden button release
desired button
01
erase 1
PRG.
read
SELF-DIAGNOSIS MENU
OK = No error 22 = Start error 23 = Stop error 24 = Photocell error 25 = Opening limit-switch error 26 = Closing limit-switch error 27 = Pedestrian input error 28 = Open error 29 = Close error 30 = Electric edge error 31 = Clock error
Chec k cor r ect opera tion of th e de vice whic h is connected to the terminal having its number displayed.
AUTOSET MENU
(See Paragraph 6.5) Automatically sets: Opening torque Ð Closing torque Ð Encoder Ð Brake
WARNING!
The control unit carries out about ten manoeuvres in Òhold-to-runÓ mode in the course of the autoset phase, during which the installer must control the automation movement and prevent persons or things from appro a ching or st andin g with i n the automation operating range.
RADIO MENU ADD
- Allows you to add one key of a radio control device to the receiver memory; after storage it displays a me s sage showi n g th e rec e iver numbe r in the memory location (from 01 to 64).
NOTE:
When using transmitters with two or more channels, the first push-button which has been stored is associated to the START function. If a second push- button is stored, it will be associated to the pedestrian function.
READ
- Checks one key on a receiver, if stored it displays a message showing the receiver number in the memory locat ion (from 01 to 64), a nd the key number (T1, T2, T3 or T4).
ERASE 1
- Removes one single key of a transmitter from the receiver memory; after deletion it displays a message showing the receiver number in the memory location (from 01 to 64).
ERASE 64 WARNING!
Completely removes all memorised radio
control devices from the receiver memory.
ITA
01
FRA
DEU
ENG
esp
PRECEDING MENUS
FIG. A
OK
OK
OK
Press P1 (pushbutton) on radio
control device Ð see Fig. 1A
Press the required T (key) on radio control device Ð see Fig. 2A
Release P1 on radio control device
hidden butto
n release
desired button
OK
OK
OK OK
OK
OK
OK
OK
OK
OK
PRG
+/-
-
+
-
+
-
+
-
+
-
+
. . . . . . . .
OK
AUTOset
selftest
test
ERASE 64
+/-
+/-
+/-
+/-
+/-
DEFAULT
-
+
-
+
-
+
-
+
-
+
-
+
-
+
01 t1
D811327_03
LEO
LEO
CONTROL UNITS
CONTROL UNITS
Page 7
351
Fig. 2
Fig. 3
Fig. 1
JP1 JP2
1 2 3
C
4 5 6 7 8 9
21 22 23 24 25 26 27 28 29 30 31
L
N
GND
1
2
3
JP8
START
COM
NO
NC NC
NO
NC
NO NO NO
NC
NO
STOP
M
ANT.
SWC
PED
OPEN
CLOSE
TIMER
COSTA
II¡CH.R
24 V~
PHOT
SW0
10 11 12 13
JP3
ANT
SHIELD
24 V~
40W max.
34 35 36 37 38 39 40 41
JP9
4 5 6 7 8 9
21 22 23 24 25 26 27 28 29 30 31
34 35 36 37 38 39 40 41
+
OK Enter
8 8 8 8
236
194
100
LEO
SD
88 8 8
24V
3W max.
SCA
TX1
RX1
RX2
TX2
Fig. 5
10 11 12 13
6,3 AF
0,315 AT
2AT
D811327_03
LEO
LEO
CONTROL UNITS
CONTROL UNITS
Page 8
352
Fig. 4
Fig. 5
LEO
UNIPRO
TX1
RX1
RX2
TX2
TX1
RX1
RX2
TX2
TX1
RX1
RX2
TX2
TX1
RX1
RX2
TX2
Max. 250m
UNIFLAT
8 8 8 8
21 22 23 24 25 26 27 28 29 30 31
34 35 36 37 38 39 40 41
21 22 23 24 25 26 27 28 29 30 31
34 35 36 37 38 39 40 41
21 22 23 24 25 26 27 28 29 30 31
34 35 36 37 38 39 40 41
21 22 23 24 25 26 27 28 29 30 31
34 35 36 37 38 39 40 41
D811327_03
LEO
LEO
CONTROL UNITS
CONTROL UNITS
Page 9
353
Fig. 6
TX1
TX2
RX1
RX2
SWO1
SWC1
CC1
TX1
RX1 CC1 CC2
TX2
RX2
1
2
3
4 5 6 7 8 9
21 22 23 24 25 26 27 28 29 30 31
34 35 36 37 38 39 40 41
10 11 12 13
5 AF
0,315 AT
2AT
M2
SLAVE
M1
MASTER
FIG. 6a
FIG. 6b
LEO
M1 (MASTER)
1
2
3
4 5 6 7 8 9
21 22 23 24 25 26 27 28 29 30 31
34 35 36 37 38 39 40 41
10 11 12 13
5 AF
0,315 AT
2AT
LEO
M2 (SLAVE)
TCA OFF
STOP
SWO2
SWC2
CC2
NC
PHOT
NC
NC
NC
NC NC NC
D811327_03
LEO
LEO
CONTROL UNITS
CONTROL UNITS
Loading...