Berko 2500 Installation Manual

Mechanical & Electrical Accessories
for 1800, 1900, 2500, 2600, C1800 & C2500
Installation Instructions
NOTE: Accessories described in this instruction manual are intended for use with Marley Engineered Products 1800, 1900, 2500, 2600, C1800 and C2500 Series Model C baseboard heaters only.
!
This instruction sheet contains vital information for the proper installation and use of the accessories described herein. Carefully read this manual before installation, operation, or ser­vice of the accessory. Failure to follow these instructions could result in fire, electric shock, death, serious personal injury, or property damage. Save these instructions for reference by future users.
WARNING: HAZARD OF FIRE OR ELECTRIC SHOCK.
1. Be sure electric power is disconnected at main fuse or circuit breaker distribution panel before installation or servicing.
2. The installation must comply with all Local and National Electrical Codes and utility requirements.
3. Refer to installation instructions provided with the heater when installing these accessories.
4. Check accessory and heater nameplate to verify power requirements match power supply coming to heater and accessory. Make sure total power requirements do not exceed ratings of accessory.
5. When using RSA transformer relay accessory, supply wires must be minimum 90° C.
Series Baseboard Heaters
RA1
FS
DSW2
PR
HCA
RSA
MODEL NO.
HCA121520 ** HCA241520 ** DSW2 * RA1 ** RSA1224C RSA2024C RSA2424C RSA2724C RSA3724C RSA6024C PR24C PR120C FS * FSJ2 *
* Followed by WCA or NWCA suffix ** Followed by WC or NWC suffix
Suffix should match heater suffix
ECR 40406 / 40495 3/15 5200-2206-007
Heat/Cool Switch w/Receptacle Heat/Cool Switch w/ Receptacle Power ON/OFF Switch DPST Duplex Receptacle Low Voltage Relay w/Transformer 120/24V Low Voltage Relay w/Transformer 208/24V Low Voltage Relay w/Transformer 240/24V Low Voltage Relay w/Transformer 277/24V Low Voltage Relay w/Transformer Low Voltage Relay w/Transformer Power Relay SPST 24V Coil Power Relay SPST 120V Filler Section Joiner Section
DESCRIPTION
20 Amps @ 120 VAC 20 Amps @ 250 VAC 20 Amps @ 120 - 177 VAC 15 Amps @ 120 VAC 25 Amps @ 120 VAC 25 Amps @ 208 VAC 25 Amps @ 240 VAC 22 Amps @ 277 VAC 17 Amps @ 347 VAC 12 Amps @ 600 VAC 30 Amps @ 120 - 240 VAC
23 Amps @ 277 VAC 10 Amps @ 347 & 600 VAC
RATINGS
WIRING DIAGRAM
Figure 1
Figure 2 Figure 3
Figure 4
Figure 5
ELEMENT
B
ASEBOARD
H
EATER
W
ALL THERMOSTAT
(OPTIONAL)
B
LACK
S
WITCH
B
LUE
W
HITE
WHITE WITH
BLACK TAP E
GROUND
R
ECEPTACLE
AC ACCESSORY
L
1
L2
HIGH LIMIT
L1
L2
HIGH LIMIT
E
LEMENT
SWITCH
HIGH LIMIT
E
LEMENT
BASEBOARD HEATER
LVR ACCESSORY
G
ROUND
TRANSFORMER RELAY
TO 24 VOLT
THERMOSTAT
R
ED
WHITE
L1
L
2
BLACK
YELLOW
BLUE
LVR ACCESSORY
GROUND
BASEBOARD HEATER
ELEMENT
HIGH LIMIT
BLUE
YELLOW
BLACK
TRANSFORMER RELAY
TO 24 VOLT
THERMOSTAT
RED
WHITE
L1
L
2
H
IGH LIMIT
H
IGH LIMIT
BASEBOARD HEATER
B
ASEBOARD HEATER
ELEMENT
ELEMENT
TRANSFORMER RELAY
TO 24 VOLT
T
HERMOSTAT
LV R
BLUE
YELLOW
BLACK
L
1
L2
RED
W
HITE
HIGH LIMIT
ELEMENT
L1 L2
GROUND
POWER RELAY
TO EXTERNAL CONTROL
VOLTAGE SOURCE
HIGH LIMIT
ELEMENT
TO EXTERNAL CONTROL
VOLTAGE SOURCE
GROUND
L1 L2
POWER RELAY
POWER RELAY
TO EXTERNAL CONTROL
VOLTAGE SOURCE
ELEMENT
ELEMENT
GROUND
L1 L2
HIGH LIMIT
HIGH LIMIT
L1
D
BLACK
WHITE
GROUND
Figure 1. HCA Heat/Cool Switch w/Receptacle
Figure 2. DSW2 Power ON/OFF Switch Figure 4. RSA Transformer Relay
5A
5B
5C
Figure 3. RA1 120 Volt Duplex Receptacle Figure 5. PR Power Relay
HCA121520 and HCA242520
Do not use Heat-Cool Transfer Switch as an “OFF/ON” switch. Operation of baseboard should be regulated by a wall mounted thermostat. Operation of air conditioner should be regulated by the thermostat provided in the air conditioner.
1. Plug air conditioner into receptacle. Set heat-cool transfer switch to “OFF” position. Turn heating thermostat to highest position. If heater or air conditioners are energized, turn off power supply and have wiring rechecked.
2. Set heat-cool transfer switch to “HEAT” position. If baseboard heater does not operate, turn off power supply and have wiring rechecked.
3. Set heat-cool transfer switch to “COOL” position. If air condi­tioner does not operate, turn off power supply and have wiring rechecked.
2
1. All electrical work must conform to Local and National Electrical Codes. This unit must be connected with a 20 amp. maximum branch circuit. The minimum wire size allowable is No. 12AWG Copper. NOTE: The use of UL Listed connectors of the proper size is required.
2. The transfer switch must be installed in the wiring compart-
3. Connect center switch leads (black for switches rated 240V,
4. Fold wires carefully and install transfer switch in place of wiring
5. Reconnect power at main fuse or circuit breaker distribution
ment where the power wiring has been brought in. Remove that wiring compartment cover and discard.
one white and one black for switches rated 120V), to the power supply wires and connect the blue leads through the thermostat to the heater wire as shown in the wiring diagram, (Figure 1).
compartment cover.
panel.
OPERATION
CAUTION
!
DSW2
1. All electrical work must conform to Local and National Electrical Codes. The minimum wire size allowable is No. 12AWG Copper. NOTE: The use of UL Listed connectors of the proper size is required.
2. The Power ON/OFF switch is intended to be installed in the wiring compartment where the power wiring has been brought in. Remove wiring compartment cover and discard.
3. Connect the Power ON/OFF switch leads to the heater and power leads as shown in the wiring diagram, (Figure 2).
4. Fold wires carefully and install Power ON/OFF in place of wiring compartment cover.
5. Reconnect power at main fuse or circuit breaker distribution panel.
7. For left end connection, remove wire nut connecting crossover wire and limit control wires together. Connect power supply wire (L2), the larger yellow wire, and crossover wire together. The blue wire is to be connected to the high limit wire. Connect power supply wire (L1) to larger black wire.
8. After all electrical power connections are completed, install the thermostat as described in the Thermostat Owners Manual. Connect wires from the thermostat to the red and white wires (refer to paragraph 5) with suitable UL Listed wire nuts. If more heaters are to be connected to the same thermostat, refer to wiring diagram in Figure 5.
9. Once wiring is complete, peel off the back of the conductor label included in this kit and attach it to the back of the control box cover. Reinstall cover.
RA1
1. All electrical work must conform to Local and National Electrical Codes. This unit must be connected to a separate 15 amp maximum branch circuit. The minimum wire size allowable is No. 14AWG Copper. NOTE: The use of UL Listed connectors of the proper size is required.
2. The duplex receptacle may be installed in either the left or right wiring compartment. Remove the desired wiring compartment cover and discard.
3. Drill hole through floor or wall at knockout location where branch circuit supply will enter the wiring compartment. (This may require removing the heater).
4. Feed branch circuit supply wire through drilled hole and knock­out in heater. Install cable connector (not supplied).
5. Connect branch circuit supply to duplex receptacle as shown in wiring diagram, (Figure 3).
6. Reconnect power at main fuse or circuit breaker distribution panel for the heater and duplex receptacle.
RSA1224C, RSA2024C, RSA2424C,
RSA2724C, RSA3424C and RSA6024C
INSTALLATION
1. All electrical work must conform to Local and National Electrical Codes. The use of UL Listed connectors of the proper size is required. Supply wiring must be suitable for 90° C.
2. Remove the control box cover where the power supply leads are. Remove small knockout in back of baseboard and make aligning hole in wall (See Figures 6 and 7). Fish thermostat wires through this hole.
3. Loosely install both transfer relay screws. Attach baseplate as shown in Figures 6 or 7.
4. Slide transformer/relay under loosely installed screws in base plate and tighten screws. NOTE: For left end installation transformer/relay is mounted upside down.
5. Push the red and white transformer wires through the hole in the top of the baseplate. Make 24V thermostat connections in the compartment formed by the baseplate and the top of the wiring compartment. (See wiring diagram Figure 4).
6. For right end connection remove wire nut and connect power supply wire (L2) to the larger yellow wire and to the element lead wire. Connect power supply wire (L1) to larger black wire and connect blue wire to return wire. (See wiring diagram Figure 4).
TRANSFORMER RELAY
BASEPLATE SCREWS
TRANSFORMER/RELAY
CREWS
S
POWER SUPPLY WIRES
Figure 6. Left End
TRANSFORMER RELAY
BASEPLATE
RETURN WIRE
SMALL KNOCKOUT
BASEBOARD HEATER
ELEMENT WIRE
GROUND WIRE
Figure 7. Right End
ASEPLATE
B
POWER SUPPLY WIRES
RETURN WIRE
LIMIT CONTROL WIRE
SMALL KNOCKOUT
ELEMENT WIRE
LIMIT CONTROL
IRE
W
GROUND WIRE
BASEPLATE SCREWS
TRANSFORMER/RELAY SCREWS
3
CHECK OPERATION
1. Before connecting power supply, be sure all thermostats are turned to “LOW” or “NO HEAT”.
2. Connect power supply at distribution box. Wait 3 to 5 minutes and check to see that none of the heaters are operating. Should any of the heaters be operating, disconnect power sup­ply and check wiring.
3. If none are operating, turn the thermostats to the highest posi­tion and wait 3 to 5 minutes. Check to see that all heaters are operating. If any are not operating, disconnect power supply and check wiring.
PR24C and PR120C
1. All electrical work must conform to Local and National Electrical Codes. The use of UL Listed connectors of proper size is required.
2. On PR24 model, using 24 volt class 2 control circuit wiring, remove small knockout in back of baseboard and make align­ing hole in wall (See Figures 8 or 9). Route 24 volt class 2 external control circuit wires through this hole. On PR120 model, the control circuit wiring connections may be made in the heater wiring compartment.
3. Attach baseplate to back of wiring compartment with screws provided. (See Figure 8 or 9). Insert snap bushing in appro­priate hole in baseplate top.
4. Mount power relay on baseplate and securely fasten with screw provided. See Figure 8 or 9 for proper mounting location on baseplate.
5. On PR24 model, using 24 volt class 2 control circuit wiring, push the two red relay wires up through the hole in the top of the baseplate. Make all external 24 volt class 2 control circuit wiring connections in the compartment formed by the baseplate and the top of the wiring compartment. On the PR120 model, connect external 120 volt control circuit wiring in the heater wiring compartment by connecting to the red control wire. The compartment formed by the base plate and top of the heater wiring compartment is not used on the PR120 Model.
6. For right end connection, remove wire nut and connect return wire to one black lead on power relay. Connect power sup­ply wire (L1) to other black lead on power relay. Connect power supply wire (L2 or N) to element lead wire. (See wiring diagram, Figure 5A).
7. For left end connection, remove wire nut connecting the limit control and connect limit control wire to one black lead on power relay. Connect power supply wire (L1) to other black lead on power relay. Connect power supply (L2 or N) to crossover wire. (See wiring diagram, Figure 5B).
8. If more heaters are to be connected to same power relay, refer to wiring diagram Figure 5C. Do not exceed ampacity rating of power relay.
FSJ2 and FS
The FS Filler Sections provide for a uniform appearance by cov­ering open space between heaters or between the end of a heater and the wall. If heaters are butted together, Marley Model Number FSJ2 Joiner Strip should be used. These instructions are provided to assist you in the installation and prevent unnecessary problems that you may encounter. Read and study these instructions as well as the instructions pro­vided with the heaters before installing.
SMALL
NOCKOUT
K
RETURN WIRE
LEMENT
E WIRE
ASEPLATE
B SCREW
GROUND SCREW
GROMMET
BASEPLATE SCREW
OWER
P
ELAY
R
RELAY SCREW
ASEPLATE
B
BASEBOARD
EATER
H
Figure 8. Right End Wiring Compartment
USHING
B
BASEPLATE
CREW
S
POWER RELAY
RELAY SCREW
BASEPLATE SCREW
BASEPLATE
BASEBOARD HEATER
SMALL KNOCKOUT
ETURN
R WIRE
ELEMENT WIRE
THERMAL CUT OUT
GROUND SCREW
Figure 9. Left End Wiring Compartment
CAUTION
!
To prevent possible damage to internal wiring, prior to installing the filler section, remove the heater junction box cover(s) at the end of the heater(s) where the filler is to be installed. Position all wiring in the junction boxes so it is not in the area where the self-tapping screw (Step 4) will be installed.
1. Mount the heaters on the wall in accordance with the heater installation instructions. Make sure the heaters are at the same mounting height from the floor to assure a level mount­ing of the filler section.
2. Position the filler section on top of the heater(s) and press down toward the bottom of the filler to assure a tight fit. The section will snap into place. Do not mount over the junction box screw.
3. If the filler section is to be mounted between a heater and a wall, a block of wood to support one end of the filler should be attached to the wall, level with the top of the heater.
4. Attach filler sections with sheet metal screw, supplied by others, in the bottom of the filler and into the baseboard.
4
LIMITED WARRANTY
All products covered by this instruction sheet are warranted against defects in workmanship and materials for one year from date of installation. This warranty does not apply to damage from accident, misuse, or alteration; nor where the connected voltage is more than 5% above the nameplate voltage; nor to equipment improperly installed or wired or maintained in violation of this instruction sheet. All claims for warranty work must be accompanied by proof of the date of installation. The customer shall be responsible for all costs incurred in the removal or reinstallation of products, including labor costs, and shipping costs incurred to return products to a Marley Engineered Products Service Center, and we will repair or replace, at our option, at no charge to you with return freight paid by Marley. It is agreed that such repair or replacement is the exclusive remedy available from Marley Engineered Products. THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, AND ALL IMPLIED WAR­RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT. MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT, WHETHER BASED UPON NEGLIGENCE, TORT, STRICT LIABILITY, OR CONTRACT. Some states do not allow the exclusion on limitation of incidental or consequential damages, so the above exclusion or limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state. For the address of your nearest authorized service center, contact Marley Engineered Products, 470 Beauty Spot Road East, Bennettsville, SC 29512 USA. Merchandise returned to the factory must be accompanied by a return authorization and service identi­fication tag, both available from the above location. When requesting return authorization, include all catalog numbers shown on the products.
HOW TO OBTAIN WARRANTY SERVICE AND WARRANTY PARTS PLUS GENERAL INFORMATION
1. Warranty Service or Parts 1-800-642-4328
2. Purchase Replacement Parts 1-800-654-3545
3. General Product Information www.marleymep.com
Note: When obtaining service always have the following:
1. Model number of the product
2. Date of manufacture
3. Part number or description
470 Beauty Spot Rd. East Bennettsville, SC 29512 USA
5
Loading...
+ 10 hidden pages