NOTE: Accessories described in this instruction manual are
intended for use with Marley Engineered Products 1800, 1900,
2500, 2600, C1800 and C2500 Series Model C baseboard
heaters only.
WARNING
!
This instruction sheet contains vital information for the proper
installation and use of the accessories described herein.
Carefully read this manual before installation, operation, or service of the accessory. Failure to follow these instructions could
result in fire, electric shock, death, serious personal injury, or
property damage. Save these instructions for reference by future
users.
WARNING: HAZARD OF FIRE OR ELECTRIC SHOCK.
1.Be sure electric power is disconnected at main fuse or circuit
breaker distribution panel before installation or servicing.
2.The installation must comply with all Local and National
Electrical Codes and utility requirements.
3.Refer to installation instructions provided with the heater
when installing these accessories.
4.Check accessory and heater nameplate to verify power
requirements match power supply coming to heater and
accessory. Make sure total power requirements do not
exceed ratings of accessory.
5.When using RSA transformer relay accessory, supply wires
must be minimum 90° C.
Figure 3. RA1 120 Volt Duplex ReceptacleFigure 5. PR Power Relay
HCA121520 and HCA242520
Do not use Heat-Cool Transfer Switch as an “OFF/ON” switch.
Operation of baseboard should be regulated by a wall mounted
thermostat. Operation of air conditioner should be regulated by
the thermostat provided in the air conditioner.
1. Plug air conditioner into receptacle. Set heat-cool transfer switch
to “OFF” position. Turn heating thermostat to highest position.
If heater or air conditioners are energized, turn off power
supply and have wiring rechecked.
2. Set heat-cool transfer switch to “HEAT” position. If baseboard
heater does not operate, turn off power supply and have wiring
rechecked.
3. Set heat-cool transfer switch to “COOL” position. If air conditioner does not operate, turn off power supply and have wiring
rechecked.
2
1. All electrical work must conform to Local and National Electrical
Codes. This unit must be connected with a 20 amp. maximum
branch circuit. The minimum wire size allowable is No.
12AWG Copper. NOTE: The use of UL Listed connectors of
the proper size is required.
2. The transfer switch must be installed in the wiring compart-
3. Connect center switch leads (black for switches rated 240V,
4. Fold wires carefully and install transfer switch in place of wiring
5. Reconnect power at main fuse or circuit breaker distribution
ment where the power wiring has been brought in. Remove
that wiring compartment cover and discard.
one white and one black for switches rated 120V), to the power
supply wires and connect the blue leads through the thermostat
to the heater wire as shown in the wiring diagram, (Figure 1).
compartment cover.
panel.
OPERATION
CAUTION
!
DSW2
1. All electrical work must conform to Local and National Electrical
Codes. The minimum wire size allowable is No. 12AWG Copper.
NOTE: The use of UL Listed connectors of the proper size
is required.
2. The Power ON/OFF switch is intended to be installed in the
wiring compartment where the power wiring has been brought
in. Remove wiring compartment cover and discard.
3. Connect the Power ON/OFF switch leads to the heater and
power leads as shown in the wiring diagram, (Figure 2).
4. Fold wires carefully and install Power ON/OFF in place of
wiring compartment cover.
5. Reconnect power at main fuse or circuit breaker distribution
panel.
7. For left end connection, remove wire nut connecting crossover
wire and limit control wires together. Connect power supply
wire (L2), the larger yellow wire, and crossover wire together.
The blue wire is to be connected to the high limit wire.
Connect power supply wire (L1) to larger black wire.
8. After all electrical power connections are completed, install the
thermostat as described in the Thermostat Owners Manual.
Connect wires from the thermostat to the red and white
wires (refer to paragraph 5) with suitable UL Listed wire
nuts. If more heaters are to be connected to the same
thermostat, refer to wiring diagram in Figure 5.
9. Once wiring is complete, peel off the back of the conductor
label included in this kit and attach it to the back of the control
box cover. Reinstall cover.
RA1
1. All electrical work must conform to Local and National Electrical
Codes. This unit must be connected to a separate 15 amp
maximum branch circuit. The minimum wire size allowable is
No. 14AWG Copper.
NOTE: The use of UL Listed connectors of the proper size
is required.
2. The duplex receptacle may be installed in either the left or right
wiring compartment. Remove the desired wiring compartment
cover and discard.
3. Drill hole through floor or wall at knockout location where
branch circuit supply will enter the wiring compartment. (This
may require removing the heater).
4. Feed branch circuit supply wire through drilled hole and knockout in heater. Install cable connector (not supplied).
5. Connect branch circuit supply to duplex receptacle as shown
in wiring diagram, (Figure 3).
6. Reconnect power at main fuse or circuit breaker distribution
panel for the heater and duplex receptacle.
RSA1224C, RSA2024C, RSA2424C,
RSA2724C, RSA3424C and RSA6024C
INSTALLATION
1. All electrical work must conform to Local and National Electrical
Codes. The use of UL Listed connectors of the proper size
is required. Supply wiring must be suitable for 90° C.
2. Remove the control box cover where the power supply leads
are. Remove small knockout in back of baseboard and make
aligning hole in wall (See Figures 6 and 7). Fish thermostat
wires through this hole.
3. Loosely install both transfer relay screws. Attach baseplate as
shown in Figures 6 or 7.
4. Slide transformer/relay under loosely installed screws in base
plate and tighten screws. NOTE: For left end installation
transformer/relay is mounted upside down.
5. Push the red and white transformer wires through the hole in
the top of the baseplate. Make 24V thermostat connections in
the compartment formed by the baseplate and the top of the
wiring compartment. (See wiring diagram Figure 4).
6. For right end connection remove wire nut and connect power
supply wire (L2) to the larger yellow wire and to the element
lead wire. Connect power supply wire (L1) to larger black wire
and connect blue wire to return wire. (See wiring diagram
Figure 4).
TRANSFORMER RELAY
BASEPLATE SCREWS
TRANSFORMER/RELAY
CREWS
S
POWER SUPPLY WIRES
Figure 6. Left End
TRANSFORMER RELAY
BASEPLATE
RETURN
WIRE
SMALL KNOCKOUT
BASEBOARD
HEATER
ELEMENT WIRE
GROUND WIRE
Figure 7. Right End
ASEPLATE
B
POWER SUPPLY WIRES
RETURN WIRE
LIMIT CONTROL WIRE
SMALL KNOCKOUT
ELEMENT WIRE
LIMIT CONTROL
IRE
W
GROUND WIRE
BASEPLATE SCREWS
TRANSFORMER/RELAY
SCREWS
3
CHECK OPERATION
1. Before connecting power supply, be sure all thermostats are
turned to “LOW” or “NO HEAT”.
2. Connect power supply at distribution box. Wait 3 to 5 minutes
and check to see that none of the heaters are operating.
Should any of the heaters be operating, disconnect power supply and check wiring.
3. If none are operating, turn the thermostats to the highest position and wait 3 to 5 minutes. Check to see that all heaters are
operating. If any are not operating, disconnect power supply
and check wiring.
PR24C and PR120C
1. All electrical work must conform to Local and National Electrical
Codes. The use of UL Listed connectors of proper size is
required.
2. On PR24 model, using 24 volt class 2 control circuit wiring,
remove small knockout in back of baseboard and make aligning hole in wall (See Figures 8 or 9). Route 24 volt class 2
external control circuit wires through this hole. On PR120
model, the control circuit wiring connections may be made in
the heater wiring compartment.
3. Attach baseplate to back of wiring compartment with screws
provided. (See Figure 8 or 9). Insert snap bushing in appropriate hole in baseplate top.
4. Mount power relay on baseplate and securely fasten with screw
provided. See Figure 8 or 9 for proper mounting location on
baseplate.
5. On PR24 model, using 24 volt class 2 control circuit wiring,
push the two red relay wires up through the hole in the top of
the baseplate. Make all external 24 volt class 2 control circuit
wiring connections in the compartment formed by the
baseplate and the top of the wiring compartment. On the
PR120 model, connect external 120 volt control circuit
wiring in the heater wiring compartment by connecting to
the red control wire. The compartment formed by the base
plate and top of the heater wiring compartment is not used on
the PR120 Model.
6. For right end connection, remove wire nut and connect return
wire to one black lead on power relay. Connect power supply wire (L1) to other black lead on power relay. Connect
power supply wire (L2 or N) to element lead wire. (See wiring
diagram, Figure 5A).
7. For left end connection, remove wire nut connecting the limit
control and connect limit control wire to one black lead on
power relay. Connect power supply wire (L1) to other black
lead on power relay. Connect power supply (L2 or N) to
crossover wire. (See wiring diagram, Figure 5B).
8. If more heaters are to be connected to same power relay, refer
to wiring diagram Figure 5C. Do not exceed ampacity rating of
power relay.
FSJ2 and FS
The FS Filler Sections provide for a uniform appearance by covering open space between heaters or between the end of a heater
and the wall. If heaters are butted together, Marley Model Number
FSJ2 Joiner Strip should be used.
These instructions are provided to assist you in the installation
and prevent unnecessary problems that you may encounter.
Read and study these instructions as well as the instructions provided with the heaters before installing.
SMALL
NOCKOUT
K
RETURN
WIRE
LEMENT
E
WIRE
ASEPLATE
B
SCREW
GROUND
SCREW
GROMMET
BASEPLATE
SCREW
OWER
P
ELAY
R
RELAY
SCREW
ASEPLATE
B
BASEBOARD
EATER
H
Figure 8. Right End Wiring Compartment
USHING
B
BASEPLATE
CREW
S
POWER RELAY
RELAY SCREW
BASEPLATE
SCREW
BASEPLATE
BASEBOARD
HEATER
SMALL
KNOCKOUT
ETURN
R
WIRE
ELEMENT
WIRE
THERMAL
CUT OUT
GROUND
SCREW
Figure 9. Left End Wiring Compartment
CAUTION
!
To prevent possible damage to internal wiring, prior to installing
the filler section, remove the heater junction box cover(s) at the
end of the heater(s) where the filler is to be installed. Position
all wiring in the junction boxes so it is not in the area where the
self-tapping screw (Step 4) will be installed.
1. Mount the heaters on the wall in accordance with the heater
installation instructions. Make sure the heaters are at the
same mounting height from the floor to assure a level mounting of the filler section.
2. Position the filler section on top of the heater(s) and press
down toward the bottom of the filler to assure a tight fit. The
section will snap into place. Do not mount over the junction
box screw.
3. If the filler section is to be mounted between a heater and a
wall, a block of wood to support one end of the filler should be
attached to the wall, level with the top of the heater.
4. Attach filler sections with sheet metal screw, supplied by others,
in the bottom of the filler and into the baseboard.
4
LIMITED WARRANTY
All products covered by this instruction sheet are warranted against defects in workmanship and materials for one year from date of
installation. This warranty does not apply to damage from accident, misuse, or alteration; nor where the connected voltage is more than
5% above the nameplate voltage; nor to equipment improperly installed or wired or maintained in violation of this instruction sheet. All
claims for warranty work must be accompanied by proof of the date of installation.
The customer shall be responsible for all costs incurred in the removal or reinstallation of products, including labor costs, and shipping
costs incurred to return products to a Marley Engineered Products Service Center, and we will repair or replace, at our option, at no
charge to you with return freight paid by Marley. It is agreed that such repair or replacement is the exclusive remedy available from Marley
Engineered Products.
THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED
WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT. MARLEY ENGINEERED PRODUCTS
SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT, WHETHER BASED
UPON NEGLIGENCE, TORT, STRICT LIABILITY, OR CONTRACT.
Some states do not allow the exclusion on limitation of incidental or consequential damages, so the above exclusion or limitation may
not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state.
For the address of your nearest authorized service center, contact Marley Engineered Products, 470 Beauty Spot Road East,
Bennettsville, SC 29512 USA. Merchandise returned to the factory must be accompanied by a return authorization and service identification tag, both available from the above location. When requesting return authorization, include all catalog numbers shown on the
products.
HOW TO OBTAIN WARRANTY SERVICE AND
WARRANTY PARTS PLUS GENERAL INFORMATION
1. Warranty Service or Parts1-800-642-4328
2. Purchase Replacement Parts1-800-654-3545
3. General Product Informationwww.marleymep.com
Note: When obtaining service always have the following:
1. Model number of the product
2. Date of manufacture
3. Part number or description
470 Beauty Spot Rd. East
Bennettsville, SC 29512 USA
5
Loading...
+ 10 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.