Beijer Electronics EXTER T60, EXTER T60m Installation Manual

0 (0)
EXTER T60/T60m
Installation Manual
English
MAEN809F, 2014-11
Foreword
Installation manual for EXTER T60/T60m
All EXTER operator panels are developed to satisfy the demands of human-machine communication. Built-in functions such as displaying and controlling text, dynamic indication, time channels, alarm and recipe handling are included.
The operator panel works primarily in an object-oriented way,making it easy to understand and use. Configuration is carried out on a PC using the configuration tool. The project can then be transferred and stored in the operator panel itself.
Various types of automation equipment such PLCs, servosor drives can be connected to the EXTER operator panels. In this manual, the term “the controller” refers to the connected equipment.
This manual explains how to install the operator panel. Please refer to the reference manual for further information.
Order no: MAEN809F
Copyright © 2014-11 Beijer Electronics AB. All rights reserved.
The information in this document is subject to changewithoutnoticeandisprovidedasavailableatthe
time of printing. Beijer ElectronicsAB reserves the right to change any information without updatingthis
publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document.
Read the entire installation manual prior to installing and using this equipment. Only qualified personnel
may install, operate or repair this equipment. Beijer Electronics AB is not responsible for modified, altered
or renovated equipment. Because the equipment has a widerangeofapplications,usersmustacquirethe
appropriate knowledge to use the equipment properly in their specificapplications. Personsresponsible
for the application and the equipment must themselves ensure that each application is in compliancewith
all relevant requirements, standards and legislationinrespecttoconfigurationandsafety. Onlypartsand
accessories manufactured according to specifications set by Beijer Electronics AB may be used.
BEIJER ELECTRONICS AB SHALL NOT BE LIABLE TO ANYONE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTALOR CONSEQUENTIAL DAMAGES RESULTING FROMTHE INSTALLATION, USE OR REPAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT, CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDYSHALL BE THE REPAIR,REPLACEMENT, OR REFUND OF PURCHASEPRICE, AND THE CHOICE OF THE APPLICABLE REMEDYSHALLBEATTHESOLEDISCRETIONOFBEIJER ELECTRONICSAB .
Beijer Electronics, MAEN809F
Contents
Contents
1 Safety Precautions ....................................................... 4
1.1 General ...........................................................
4
1.2 UL and cUL Installation .........................................
4
1.3 DuringInstallation ..............................................
6
1.4 DuringUse .......................................................
6
1.5 Service and Maintenance ........................................
6
1.6 Dismantling and Scrapping .....................................
6
2 Installation ............................................................... 7
2.1 SpaceRequirements .............................................
7
2.2 InstallationProcess ..............................................
7
2.2.1 ModeSwitches ...................................................
10
2.2.2 ConnectionstotheController ..................................
10
2.2.3 OtherConnectionsandPeripherals .............................
10
3 Technical Data ........................................................... 11
4 ChemicalResistance .................................................... 13
4.1 MetalCasing .....................................................
13
4.2 Touch Screen and Overlay Material ............................
13
4.2.1 AutotexF157/207 ...............................................
13
4.2.2 TouchScreenSurface ............................................
14
4.2.3 TouchScreenProtector ..........................................
15
5 Operator PanelDrawings .............................................. 16
5.1 CommunicationPorts ...........................................
16
5.2 EXTER T60/T60m Outline ....................................
17
6 Additional Installation Tips ............................................ 18
6.1 Grounding the Operator Panel .................................
18
6.2 Ethernet Connection in the Panel ..............................
19
6.3 To Achieve Better EMC Protection .............................
20
6.4 AmbientTemperature ...........................................
21
6.5 Safety .............................................................
22
6.6 GalvanicIsolation ................................................
23
6.7 Cable and Bus Termination RS485 .............................
24
Beijer Electronics, MAEN809F
Safety Precautions
1SafetyPrecautions
Both the installer and the owner and/oroperator of the operator panel must read and understand this installation manual.
1.1 General
Read the safety precautions carefully.
Check the delivery for transportation damage. If damage is found, notify the
supplier as soon as possible.
The supplier is not responsible for modified, altered or reconstructed
equipment.
Use only parts and accessories manufactured according to specifications of
the supplier.
Read the installation and operating instructions carefully before installing,
using or repairing the operator panel.
Neverallowfluids,metalfilingsorwiringdebristoenteranyopeningsinthe
operator panel. This may cause fire or electrical shock.
Only qualified personnel may operate the operator panel.
Storing the operator panel where the temperature is lower/higher than
recommended in this manual can cause the LCD display liquid to congeal/become isotopic.
The LCD display liquid contains a powerful irritant. In case of skin contact,
wash immediately with plenty of water. In case of eye contact, hold the eye open,flushwithplentyofwaterandgetmedicalattention.
Thefiguresinthismanualservesanillustrativepurpose. Becauseofthemany
variables associated with any particular installation, the supplier cannot assume responsibility for actual use based on the figures.
The supplier neither guarantees that the operator panel is suitable for your
particular application, nor assumes responsibility for your product design, installation or operation.
It is recommended to turn on and shut down the operator panel at least once
before installing any components/cards or beforeconnecting the operator panel to external devices, like for example serial devices.
1.2 ULandcULInstallation
Caution:
This section is only valid for UL labeled EXTER T60/T60m panels.
This equipment is suitable for use in non-hazardous locations only.
[Combinations of equipment in your system are subject to investigation by the local authority having jurisdiction at the time of installation].
All devices have to be supplied by a Class 2 power supply.
Beijer Electronics, MAEN809F
4
Safety Precautions
Warning:
Do not disconnect equipment unless powerhasbeen removed or the area is knownto be non-hazardous AVANTDEDECONNECTER L’EQUIPEMENT, COUPER LE COURANT OUS’ASSURER QUE L‘EMPLACEMENT EST DESIGNE NON DANGEREU X.
Warning:
Only UL and cUL approved expansion units are allowed to be connected to the port designated “EXPANSION”. At themoment there are no such units evaluated or allowed. SEULES LES UNITÉSD'EXTENSION CERTIFIÉESUL ET cUL PEUVENT ÊTRE RACCORDÉES AU PORT DÉSIGNÉ « EXPANSION ». À L'HEURE ACTUELLE, AUCUNE UNITÉ DE CE TYPE N'A ÉTÉ TESTÉE OU AUTORISÉE.
Warning:
Do not replace expansion unit unless power has been switched off or the area is known to benon-hazardous. NE REMPLACEZ L'UNITÉ D'EXTENSION QUE SI LE COURANT A ÉTÉ COUPÉ OU SI LA ZONE EST JUGÉE NON DANGEREUSE.
This product contains a battery; this must only be cha
nged in an area known
to be non-hazardous.
Replace the battery with a CR2450 battery. Us
e of another type of battery
may present a risk of fire orexplosion.
Warning:
Batterymay explode if mistreated. Do not recharge, disassemble or dispose of in re. LA BATTERIEPEUTEXPLOSER EN CAS DE MAUVAISE MANIPULATION. NE LA RECHARGEZ PAS,NE LA DÉMONTEZPAS ET NE LA JETEZ PAS D A N S LE F E U .
Foruse on a flat surface of a type 4X enclosure indoor use only.
Use minimum 75°C copper conductors only.
To make wiring connections to the power supply connector, follow the table
with cable and torque specifications below:
Terminal Block Connector Wire Size TQ Lb.In.
X1/X100 Phoenix connectors AWG 30–12 5–7
X1/X100 Anytek connectors AWG 24–12 3.5
These dev
ices are Class 2 supplied programmable controllers (industrial PCs)
for the u
se in industrial control equipment and are intended to be (front)
panel mo
unted (Type 1 and 4x for indoor use only).
Beijer Electronics, MAEN809F
5
Safety Precautions
Caution:
TheenclosureprovidesadegreeofprotectionofatleastIP20,butwheninstalledinan apparatus,it should meet IP54. LE BOÎTIER OFFRE UN DEGRÉ DE PROTECTION D'AU MOINS IP20, MAIS LORSQU'IL EST INSTALLÉ DANS UN APPAREIL,ILDOIT ÊTRE DE CLASSE IP54.
1.3 During Installation
The operator panel is designed for stationary installation on a plane surface,
where the following conditions are fulfilled:
no high explosive risks no strong magnetic fields no direct sunlight no large, sudden temperature changes
Install the product according to the accompanying installation instructions.
Ground the product according to the accompanying installation instructions.
Only qualified personnel may install the operator panel.
Separate the high voltage, signal and supply cables.
Make sure that the voltage and polarity of the power source is correct before
connecting the product to the power outlet.
Peripheralequipment must be appropriate for the application and location.
1.4 During Use
Keep the operator panel clean.
Emergency stopand other safety functions
may notbe controlled from the
operator panel.
Do not use excessive force or sharp objec
ts when operating the touchscreen.
1.5 Service and Maintenance
Only qualified personnel should carry out repairs.
The agreed warranty applies.
Before carrying out any cleaning or maintenance operations, disconnect the
equipment from the electrical supply.
Clean the display and surrounding front cover with a soft cloth and mild
detergent.
Replacing thebattery incorrectly may result in explosion. Only use batteries
recommended by the supplier. During the warranty period, the battery needs to be replaced by an authorized Beijer Electronics service center.
1.6 Dismantling and
Scrapping
The operator p
anel or parts thereof shall be recycled according to local
regulations.
The followin
g components contain substances that might be hazardous
to health a
nd the environment: lithium battery,electrolytic capacitor and
display.
Beijer Electronics, MAEN809F
6
Installation
2Installation
2.1 Space Requirements
Installation plate thickness: 1.5 - 7.5 mm (0.06 - 0.3 inch)
Space requirements when installingthe operator panel:
50 mm
152 mm
202 mm
(2.0 inch)
50 mm
(2.0 inch)
100 mm (4.0 inch)
100 mm (4.0 inch)
100 mm (4.0 inch)
57 mm
(2.24 inch)
(7.95 inch)
(5.98 inch)
Caution:
The openings on the enclosure are for air conve
ction. Do not cover these openings.
2.2 Installation Process
1.
Unpack and check the delivery. If dama
ge is found, notify the supplier.
x 4
Panel cut out 180 x 130 mm
(7.09 x 5.12 inch)
Note:
Place the operator panel on a stable surface during installation. Droppingit or lettingit fall may cause damage.
Beijer Electronics, MAEN809F
7
Installation
2.
Place the panel cut out where the operator panel is to be situated, draw along the outer sides of the holes andcut according to the markings.
3.
Secure the operator panel in position, using all the fastening holes and the provided brackets and screws:
x 4
0.5 - 1.0 Nm
Beijer Electronics, MAEN809F