Beckhoff KL5151-0000, KS5151, KL5151-0021, KL5151-0050, KS5152 Documentation

...
Documentation
KL5151/KS5151, KL5152/KS5152
Incremental Encoder Terminals
2.0.0 2016-03-15
Version: Date:
Product overview: incremental encoder interface
1 Product overview: incremental encoder interface
KL5151-0000 [}8]: single-channel incremental encoder terminal
KL5151-0021 [}9]: single-channel incremental encoder terminal with comparator output
KL5151-0050 [}10]: two-channel incremental encoder terminal
KL5152-0000 [}10]: two-channel incremental encoder terminal
KL5151/KS5151, KL5152/KS5152 3Version: 2.0.0
Table of contents
Table of contents
1 Product overview: incremental encoder interface .................................................................................3
2 Foreword ....................................................................................................................................................5
2.1 Notes on the documentation............................................................................................................. 5
2.2 Safety instructions ............................................................................................................................ 6
2.3 Documentation issue status.............................................................................................................. 7
3 Product overview.......................................................................................................................................8
3.1 KL5151-0000 - Introduction .............................................................................................................. 8
3.2 KL5151-0021 - Introduction .............................................................................................................. 9
3.3 KL5152-0000 (KL5151-0050) - Introduction ................................................................................... 10
3.4 Technical data ................................................................................................................................ 11
4 Mounting and wiring ...............................................................................................................................12
4.1 Installation on mounting rails .......................................................................................................... 12
4.2 Connection system ......................................................................................................................... 14
4.3 KL5151-0000 - Connection............................................................................................................. 18
4.4 KL5151-0021 - Connection............................................................................................................. 19
4.5 KL5152-0000 (KL5151-0050) - Connection.................................................................................... 20
4.6 ATEX - Special conditions .............................................................................................................. 21
4.7 ATEX Documentation ..................................................................................................................... 22
5 Configuration software KS2000 .............................................................................................................23
5.1 KS2000 - Introduction ..................................................................................................................... 23
5.2 Parameterization with KS2000 ....................................................................................................... 25
5.3 Settings........................................................................................................................................... 26
6 Access from the user program ..............................................................................................................28
6.1 KL5151-0000 .................................................................................................................................. 28
6.1.1 Process image ....................................................................................................................28
6.1.2 Control and status bytes .....................................................................................................29
6.1.3 Mapping ..............................................................................................................................31
6.2 KL5151-0021 .................................................................................................................................. 33
6.2.1 Process image ....................................................................................................................33
6.2.2 Control and status bytes .....................................................................................................33
6.3 KL5152-0000 (KL5150-0050) ......................................................................................................... 35
6.3.1 Process image ....................................................................................................................35
6.3.2 Control and status bytes .....................................................................................................38
6.3.3 Mapping ..............................................................................................................................40
6.4 Register .......................................................................................................................................... 44
6.4.1 Register overview ...............................................................................................................44
6.4.2 Register description ............................................................................................................45
6.4.3 Examples of Register Communication................................................................................48
7 Appendix ..................................................................................................................................................51
7.1 Support and Service ....................................................................................................................... 51
KL5151/KS5151, KL5152/KS51524 Version: 2.0.0
Foreword
2 Foreword
2.1 Notes on the documentation
Intended audience
This description is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards. It is essential that the following notes and explanations are followed when installing and commissioning these components.
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under development. For that reason the documentation is not in every case checked for consistency with performance data, standards or other characteristics. In the event that it contains technical or editorial errors, we retain the right to make alterations at any time and without warning. No claims for the modification of products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with corresponding applications or registrations in various other countries.
The TwinCAT Technology is covered, including but not limited to the following patent applications and patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany
Copyright
© Beckhoff Automation GmbH & Co. KG, Germany. The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization are prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
KL5151/KS5151, KL5152/KS5152 5Version: 2.0.0
Foreword
2.2 Safety instructions
Safety regulations
Please note the following safety instructions and explanations! Product-specific safety instructions can be found on following pages or in the areas mounting, wiring, commissioning etc.
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
Description of symbols
In this documentation the following symbols are used with an accompanying safety instruction or note. The safety instructions must be read carefully and followed without fail!
DANGER
Serious risk of injury!
Failure to follow the safety instructions associated with this symbol directly endangers the life and health of persons.
WARNING
Risk of injury!
Failure to follow the safety instructions associated with this symbol endangers the life and health of persons.
CAUTION
Personal injuries!
Failure to follow the safety instructions associated with this symbol can lead to injuries to persons.
Attention
Damage to the environment or devices
Failure to follow the instructions associated with this symbol can lead to damage to the en­vironment or equipment.
Note
Tip or pointer
This symbol indicates information that contributes to better understanding.
KL5151/KS5151, KL5152/KS51526 Version: 2.0.0
Foreword
2.3 Documentation issue status
Version Comment
2.0.0 • Migration
• Update revision status
1.3.0 • Technical data updated
• ATEX notes added
• Extended temperature range for KL5151-0000
• Description of control and status bytes of the KL5151-0021 corrected
1.2.0 • Introduction updated
• Description of the parameterization of the KL5151 by means of KS2000 configuration software updated.
• Register description updated
• Mounting description expanded
• KL5151-0021 added
• KL5151-0050 now available as KL5152-0000
1.1.0 • Description of the process images expanded
• Mapping tables added
1.0 • KL5151-0050 added
• Description of the parameterization of the KL5151 by means of KS2000 configuration software added.
0.1 Preliminary version (KL5151-0000 only)
Firmware and hardware versions
Documentation Version
KL5151-0000 KL5151-0021 KL5152-0000 (KL5151-0050)
Firmware Hardware Firmware Hardware Firmware Hardware
2.0.0 4E 09 14 08 4E 09
1.3.0 4C 07 13 07 4C 07
1.2.0 4C 07 13 07 4C 07
1.1.0 3A 02 - - 3A 02
1.0 3A 02 3A 02
0.1 3A 00 - -
The firmware and hardware versions (delivery state) can be taken from the serial number printed on the side of the terminal.
Syntax of the serial number
Structure of the serial number: WWYYFFHH
WW - week of production (calendar week) YY - year of production FF - firmware version HH - hardware version
Example with ser. no.: 35 04 3A 02:
35 - week of production 35 04 - year of production 2004 3A - firmware version 3A 02 - hardware version 02
KL5151/KS5151, KL5152/KS5152 7Version: 2.0.0
Product overview
3 Product overview
3.1 KL5151-0000 - Introduction
Fig.1: KL5151
The KL5151-0000 Bus Terminal is an interface with 24 V inputs for the direct connection of incremental encoders. A 32 bit counter with a quadrature decoder and a 32 bit latch for the zero pulse can be read, set or enabled.
The KL5151-0000 Bus Terminal can also be used as a 32-bit up/down counter.
Table1: LED indicators
LED Function
Ch. A Lights up when a signal is present at input A.
Ch. B Lights up when a signal is present at input B.
Ch. C Lights up when a signal is present at input C (zero input).
Gate / Latch Lights up when a signal is present at the gate/latch input.
KL5151/KS5151, KL5152/KS51528 Version: 2.0.0
Product overview
3.2 KL5151-0021 - Introduction
Fig.2: KL5151-0021
The KL5151-0021 Bus Terminal is an interface with 24 V inputs for the direct connection of incremental encoders. A 32 bit counter with a quadrature decoder and a 32 bit latch for the zero pulse can be read, set or enabled.
The KL5151-0021 Bus Terminal has an additional comparator output.
Table2: LED indicators
LED Function
Ch. A Lights up when a signal is present at input A.
Output Lights up when the comparator output is switched on.
Ch. B Lights up when a signal is present at input B.
Ch. C Lights up when a signal is present at input C (zero input).
Gate / Latch Lights up when a signal is present at the gate/latch input.
Operation
Referencing
Enter the reference value for referencing via the output double word DataOUT1 [}33] and set bits CB1.0 [}33] (EnLatchC) and CB1.2 [}33] (SetCnt) in the control byte. The reference value is now adopted by the
counter on a rising edge at input C.
Measuring the workpiece
At the beginning of the measurement the filter value is preset in the filter register R0 [}45]. Then set the release bit CB1.1 [}33] (EnMeas) in the control byte. If a plate has been successfully measured, the terminal sets bit SB1.1 [}34] (MeasDone) in the status byte.
The measurement begins on an appropriate edge. If the level already exists, only the position of the end of the board is determined. The start of the measurement is then taken as the start of the board.
Post-forming sawing
The output has a rise time of 10 µs and a 40 µs delay due to the optocoupler.
KL5151/KS5151, KL5152/KS5152 9Version: 2.0.0
Product overview
3.3 KL5152-0000 (KL5151-0050) - Introduction
Fig.3: KL5151-0050
The KL5152-0000 (KL5151-0050) Bus Terminal is an interface with 24 V inputs for the direct connection of two incremental encoders. The terminal can optionally be used as a single-channel or two-channel device.
Table3: LED indicators
Signal LED Function Encoder
Ch. A1 Lights up when a signal is present at input A1. 1
Ch. B1 Lights up when a signal is present at input B1.
Ch. A2 Lights up when a signal is present at input A2. 2
Ch. B2 Lights up when a signal is present at input B2.
KL5151/KS5151, KL5152/KS515210 Version: 2.0.0
Product overview
3.4 Technical data
Technical data KL5151-0000 KL5151-0021 KL5152-0000 (KL5151-0050)
Sensor inputs (channels) 1 2
Encoder connection A, B, C, Gate, 24 V Channel 1: A1, B1
Channel 2: A2, B2
Encoder operating voltage 24 V
DC
Counter 1 x 32 bit binary 2 x 32 bit binary
Limit frequency 100 kHz
Quadrature decoder 4-fold evaluation
Commands read, set, latching,
Compare function for setting the output (KL5151-0021 only)
Supply voltage 24VDC (-15%/+20%)
Comparator output 0 1 0
Current consumption from the power contacts
Typically 100 mA (without sensor load current)
Bit width in the K-bus I/O 4 x 16 bit user data, 1 x 8 bit control/status
Bit width in the input process image
2 data words, 1 status byte
compact [}36] complete [}36]
4 data words 4 data words,
2 status bytes
Bit width in the output process image
2 data words, 1 control byte
2 data words, 2 control bytes, 2 filler bytes
4 data words, 2 control bytes
Power supply for electronic via the K-bus
Current consumption from K-bus
typically 50 mA
Weight approx. 50 g
Dimensions (W x H x D) approx. 15 mm x 100 mm x 70 mm
Mountin [}12]g
on 35 mm mounting rail conforms to EN 60715
Pluggable wiring [}14]
at all KSxxxx series terminals
Permissible ambient temperature range during operation
-25°C ... +60°C* 0°C ... +55°C (UL)
0°C ... +55°C (ATEX [}21])
0°C ... + 55°C
Permissible ambient temperature range during storage
-40°C ... + 85°C -25°C ... + 85°C
Permissible relative humidity
95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Protection class IP20
Installation position variable
Approval
CE, cULus, ATEX [}21]
*) -25°C ... +60°C (extended temperature range) 0°C ... +55°C (according to cULus for Canada and the USA) 0°C ... +55°C (according to ATEX, see special conditions)
KL5151/KS5151, KL5152/KS5152 11Version: 2.0.0
Mounting and wiring
4 Mounting and wiring
4.1 Installation on mounting rails
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the Bus Terminals!
Assembly
Fig.4: Attaching on mounting rail
The Bus Coupler and Bus Terminals are attached to commercially available 35mm mounting rails (DIN rails according to EN60715) by applying slight pressure:
1. First attach the Fieldbus Coupler to the mounting rail.
2. The Bus Terminals are now attached on the right-hand side of the Fieldbus Coupler. Join the components with tongue and groove and push the terminals against the mounting rail, until the lock clicks onto the mounting rail. If the Terminals are clipped onto the mounting rail first and then pushed together without tongue and groove, the connection will not be operational! When correctly assembled, no significant gap should be visible between the housings.
Note
Fixing of mounting rails
The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At the installation, the locking mechanism of the components must not come into con­flict with the fixing bolts of the mounting rail. To mount the mounting rails with a height of
7.5mm under the terminals and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).
KL5151/KS5151, KL5152/KS515212 Version: 2.0.0
Mounting and wiring
Disassembly
Fig.5: Disassembling of terminal
Each terminal is secured by a lock on the mounting rail, which must be released for disassembly:
1. Pull the terminal by its orange-colored lugs approximately 1cm away from the mounting rail. In doing so for this terminal the mounting rail lock is released automatically and you can pull the terminal out of the bus terminal block easily without excessive force.
2. Grasp the released terminal with thumb and index finger simultaneous at the upper and lower grooved housing surfaces and pull the terminal out of the bus terminal block.
Connections within a bus terminal block
The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by joining the components:
• The six spring contacts of the K-Bus/E-Bus deal with the transfer of the data and the supply of the Bus Terminal electronics.
• The power contacts deal with the supply for the field electronics and thus represent a supply rail within the bus terminal block. The power contacts are supplied via terminals on the Bus Coupler (up to 24V) or for higher voltages via power feed terminals.
Note
Power Contacts
During the design of a bus terminal block, the pin assignment of the individual Bus Termi­nals must be taken account of, since some types (e.g. analog Bus Terminals or digital 4­channel Bus Terminals) do not or not fully loop through the power contacts. Power Feed Terminals (KL91xx, KL92xx or EL91xx, EL92xx) interrupt the power contacts and thus rep­resent the start of a new supply rail.
PE power contact
The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first when plugging together, and can ground short-circuit currents of up to 125A.
KL5151/KS5151, KL5152/KS5152 13Version: 2.0.0
Mounting and wiring
Fig.6: Power contact on left side
Attention
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g. disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230V). For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In order to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at least 10mm from the group of terminals.
WARNING
Risk of electric shock!
The PE power contact must not be used for other potentials!
4.2 Connection system
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the Bus Terminals!
Overview
The Bus Terminal system offers different connection options for optimum adaptation to the respective application:
• The terminals of KLxxxx and ELxxxx series with standard wiring include electronics and connection level in a single enclosure.
• The terminals of KSxxxx and ESxxxx series feature a pluggable connection level and enable steady wiring while replacing.
• The High Density Terminals (HD Terminals) include electronics and connection level in a single enclosure and have advanced packaging density.
KL5151/KS5151, KL5152/KS515214 Version: 2.0.0
Mounting and wiring
Standard wiring
Fig.7: Standard wiring
The terminals of KLxxxx and ELxxxx series have been tried and tested for years. They feature integrated screwless spring force technology for fast and simple assembly.
Pluggable wiring
Fig.8: Pluggable wiring
The terminals of KSxxxx and ESxxxx series feature a pluggable connection level. The assembly and wiring procedure for the KS series is the same as for the KLxxxx and ELxxxx series. The KS/ES series terminals enable the complete wiring to be removed as a plug connector from the top of the housing for servicing. The lower section can be removed from the terminal block by pulling the unlocking tab. Insert the new component and plug in the connector with the wiring. This reduces the installation time and eliminates the risk of wires being mixed up.
The familiar dimensions of the terminal only had to be changed slightly. The new connector adds about 3 mm. The maximum height of the terminal remains unchanged.
A tab for strain relief of the cable simplifies assembly in many applications and prevents tangling of individual connection wires when the connector is removed.
Conductor cross sections between 0.08mm2 and 2.5mm2 can continue to be used with the proven spring force technology.
The overview and nomenclature of the product names for KSxxxx and ESxxxx series has been retained as known from KLxxxx and ELxxxx series.
High Density Terminals (HD Terminals)
Fig.9: High Density Terminals
The Bus Terminals from these series with 16 connection points are distinguished by a particularly compact design, as the packaging density is twice as large as that of the standard 12mm Bus Terminals. Massive conductors and conductors with a wire end sleeve can be inserted directly into the spring loaded terminal point without tools.
KL5151/KS5151, KL5152/KS5152 15Version: 2.0.0
Mounting and wiring
Note
Wiring HD Terminals
The High Density (HD) Terminals of the KLx8xx and ELx8xx series doesn't support steady wiring.
Ultrasonically "bonded" (ultrasonically welded) conductors
Note
Ultrasonically “bonded" conductors
It is also possible to connect the Standard and High Density Terminals with ultrasonically "bonded" (ultrasonically welded) conductors. In this case, please note the tables concern-
ing the wire-size width [}16] below!
Wiring
Terminals for standard wiring ELxxxx / KLxxxx and terminals for steady wiring ESxxxx / KSxxxx
Fig.10: Mounting a cable on a terminal connection
Up to eight connections enable the connection of solid or finely stranded cables to the Bus Terminals. The terminals are implemented in spring force technology. Connect the cables as follows:
1. Open a spring-loaded terminal by slightly pushing with a screwdriver or a rod into the square opening above the terminal.
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal closes automatically when the pressure is released, holding the wire securely and permanently.
Terminal housing ELxxxx, KLxxxx ESxxxx, KSxxxx
Wire size width 0.08 ... 2,5mm
2
0.08 ... 2.5mm
2
Wire stripping length 8 ... 9mm 9 ... 10mm
KL5151/KS5151, KL5152/KS515216 Version: 2.0.0