Beckhoff EM7004 Documentation

Documentation
EM7004
4 Axis Interface, 16 Digital Inputs, 16 Digital Outputs, 4 Analog Outputs, 4 Encoder Inputs
Version: Date:
2.0 2016-09-21
Table of contents
1 Foreword ....................................................................................................................................................4
1.1 Notes on the documentation............................................................................................................... 4
1.2 Safety instructions .............................................................................................................................. 5
1.3 Documentation issue status................................................................................................................ 6
1.4 Version identification of EtherCAT devices......................................................................................... 6
2 Product overview.....................................................................................................................................10
2.1 Terminal Modules – System Overview ............................................................................................. 10
2.2 Introduction ....................................................................................................................................... 13
2.3 Technical data .................................................................................................................................. 14
2.4 Basic function principles ................................................................................................................... 14
2.4.1 Analog process data ..............................................................................................................15
2.4.2 Process data equations .........................................................................................................15
3 Mounting and wiring ...............................................................................................................................19
3.1 Recommended mounting rails .......................................................................................................... 19
3.2 Dimensions ....................................................................................................................................... 19
3.3 Mounting and demounting - terminals with traction lever unlocking ................................................. 19
3.4 Installation positions ......................................................................................................................... 21
3.5 Wiring................................................................................................................................................ 24
3.6 Connection technology ..................................................................................................................... 28
4 Commissioning........................................................................................................................................30
4.1 TwinCAT Quick Start ........................................................................................................................ 30
4.1.1 TwinCAT2 .............................................................................................................................32
4.1.2 TwinCAT 3 .............................................................................................................................42
4.2 TwinCAT Development Environment................................................................................................ 54
4.2.1 Installation of the TwinCAT real-time driver ...........................................................................54
4.2.2 Notes regarding ESI device description................................................................................. 60
4.2.3 TwinCAT ESI Updater............................................................................................................ 64
4.2.4 Distinction between Online and Offline ..................................................................................64
4.2.5 OFFLINE configuration creation ............................................................................................65
4.2.6 ONLINE configuration creation ..............................................................................................70
4.2.7 EtherCAT subscriber configuration ........................................................................................78
4.3 General Notes - EtherCAT Slave Application ................................................................................... 88
5 Object description and parameterization..............................................................................................96
5.1 Objects for commissioning................................................................................................................ 97
5.2 Objects for regular operation ............................................................................................................ 98
5.3 Standard objects (0x1000-0x1FFF) .................................................................................................. 98
5.4 Profile-specific objects (0x6000-0xFFFF) ....................................................................................... 107
6 Appendix ................................................................................................................................................113
6.1 Ordering information for EM7004 modules and EM/KM connectors .............................................. 113
6.2 EtherCAT AL Status Codes ............................................................................................................ 114
6.3 Firmware compatibility .................................................................................................................... 114
6.4 Firmware Update EL/ES/EM/EPxxxx.............................................................................................. 114
6.5 Restoring the delivery state ............................................................................................................ 125
6.6 Support and Service ....................................................................................................................... 126
EM7004 3Version: 2.0
Foreword

1 Foreword

1.1 Notes on the documentation

Intended audience
This description is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards. It is essential that the following notes and explanations are followed when installing and commissioning these components.
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under development. For that reason the documentation is not in every case checked for consistency with performance data, standards or other characteristics. In the event that it contains technical or editorial errors, we retain the right to make alterations at any time and without warning. No claims for the modification of products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with corresponding applications or registrations in various other countries.
The TwinCAT Technology is covered, including but not limited to the following patent applications and patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany
Copyright
© Beckhoff Automation GmbH & Co. KG, Germany. The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization are prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
EM70044 Version: 2.0
Foreword

1.2 Safety instructions

Safety regulations
Please note the following safety instructions and explanations! Product-specific safety instructions can be found on following pages or in the areas mounting, wiring, commissioning etc.
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
Description of symbols
In this documentation the following symbols are used with an accompanying safety instruction or note. The safety instructions must be read carefully and followed without fail!
Serious risk of injury!
Failure to follow the safety instructions associated with this symbol directly endangers the
DANGER
life and health of persons.
Risk of injury!
Failure to follow the safety instructions associated with this symbol endangers the life and
WARNING
health of persons.
Personal injuries!
Failure to follow the safety instructions associated with this symbol can lead to injuries to
CAUTION
persons.
Damage to the environment or devices
Failure to follow the instructions associated with this symbol can lead to damage to the en-
Attention
vironment or equipment.
Tip or pointer
This symbol indicates information that contributes to better understanding.
Note
EM7004 5Version: 2.0
Foreword

1.3 Documentation issue status

Version Comment
2.0 • Migration
• Update structure
1.9 • Update chapter "Basic function principles"
1.8 • Update chapter "Wiring"
1.7 • Update chapter "Firmware"
1.6 • New safety and trademark notes added
1.5 • Object description added
1.4 • Technical data added
1.3 • Correction wiring description
1.2 • Update description added
1.1 • Technical data added
1.0 • Object description added, PLS function added
0.2 • Object description added
0.1 • First preliminary documentation for EM7004

1.4 Version identification of EtherCAT devices

Designation
A Beckhoff EtherCAT device has a 14-digit designation, made up of
• family key
• type
• version
• revision
Example Family Type Version Revision
EL3314-0000-0016 EL terminal
(12 mm, non­pluggable connection level)
CU2008-0000-0000CU device 2008 (8-port fast
ES3602-0010-0017 ES terminal
(12 mm, pluggable connection level)
Notes
• The elements mentioned above result in the technical designation. EL3314-0000-0016 is used in the example below.
• EL3314-0000 is the order identifier, in the case of “-0000” usually abbreviated to EL3314. “-0016” is the EtherCAT revision.
• The order identifier is made up of
- family key (EL, EP, CU, ES, KL, CX, etc.)
- type (3314)
- version (-0000)
• The revision -0016 shows the technical progress, such as the extension of features with regard to the EtherCAT communication, and is managed by Beckhoff. In principle, a device with a higher revision can replace a device with a lower revision, unless specified otherwise, e.g. in the documentation.
3314 (4-channel thermocouple terminal)
ethernet switch) 3602 (2-channel
voltage measurement)
0000 (basic type) 0016
0000 (basic type) 0000
0010 (high­precision version)
0017
EM70046 Version: 2.0
Foreword
Associated and synonymous with each revision there is usually a description (ESI, EtherCAT Slave Information) in the form of an XML file, which is available for download from the Beckhoff website. From 2014/01 the revision is shown on the outside of the IP20 terminals, see Fig. “EL5021 EL terminal, standard IP20 IO device with batch number and revision ID (since 2014/01)”.
• The type, version and revision are read as decimal numbers, even if they are technically saved in hexadecimal.
Identification number
Beckhoff EtherCAT devices from the different lines have different kinds of identification numbers:
Production lot/batch number/serial number/date code/D number
The serial number for Beckhoff IO devices is usually the 8-digit number printed on the device or on a sticker. The serial number indicates the configuration in delivery state and therefore refers to a whole production batch, without distinguishing the individual modules of a batch.
Structure of the serial number: KKYYFFHH
KK - week of production (CW, calendar week) YY - year of production FF - firmware version HH - hardware version
Example with Ser. no.: 12063A02: 12 - production week 12 06 - production year 2006 3A - firmware version 3A 02 ­hardware version 02
Exceptions can occur in the IP67 area, where the following syntax can be used (see respective device documentation):
Syntax: D ww yy x y z u
D - prefix designation ww - calendar week yy - year x - firmware version of the bus PCB y - hardware version of the bus PCB z - firmware version of the I/O PCB u - hardware version of the I/O PCB
Example: D.22081501 calendar week 22 of the year 2008 firmware version of bus PCB: 1 hardware version of bus PCB: 5 firmware version of I/O PCB: 0 (no firmware necessary for this PCB) hardware version of I/O PCB: 1
Unique serial number/ID, ID number
In addition, in some series each individual module has its own unique serial number.
See also the further documentation in the area
• IP67: EtherCAT Box
• Safety: TwinSafe
• Terminals with factory calibration certificate and other measuring terminals
EM7004 7Version: 2.0
Foreword
Examples of markings:
Fig.1: EL5021 EL terminal, standard IP20 IO device with batch number and revision ID (since 2014/01)
Fig.2: EK1100 EtherCAT coupler, standard IP20 IO device with batch number
Fig.3: CU2016 switch with batch number
EM70048 Version: 2.0
Fig.4: EL3202-0020 with batch numbers 26131006 and unique ID-number 204418
Foreword
Fig.5: EP1258-00001 IP67 EtherCAT Box with batch number 22090101 and unique serial number 158102
Fig.6: EP1908-0002 IP76 EtherCAT Safety Box with batch number 071201FF and unique serial number
00346070
Fig.7: EL2904 IP20 safety terminal with batch number/date code 50110302 and unique serial number 00331701
EM7004 9Version: 2.0
Product overview

2 Product overview

2.1 Terminal Modules – System Overview

Fig.8: Terminal Modules – System Overview
Better sensor and actuator functionality makes machines and systems more and more powerful. The Bus Terminal reliably meets increased requirements for I/O signals through its modularity and compact design. The existing Beckhoff Bus Terminal system is complemented by the new version of the EMxxxx / KMxxxx Terminal Modules with increased packing density. In many areas of application, cost benefits can be realized through lower overall installed size and application-specific signal mix.
The new Terminal Modules are fully system-compatible. Like the Bus Terminals, they are bus-neutral and can therefore be operated with any Beckhoff Bus Coupler and Bus Terminal Controller. Like the standard Bus Terminals, the EM / KM modules are integrated in the I/O system and connected with the internal terminal bus (K-bus). Bus Terminals and terminal modules can be combined without restriction.
Connector
Like for the Bus Terminals, no tools are required for the wiring. Spring-loaded technology is used, however the connection layer is pluggable (fixed wiring).
Fig.9: Terminal modules - pluggable connection
Connection technology
Plug connectors are available for single and triple conductor connection methods.
EM700410 Version: 2.0
Product overview
Fig.10: Terminal module with plug connector for single conductor connection method (ZS2001-0002)
Fig.11: Terminal module with connector for three-wire connection (ZS2001-0004)
Packing density
The Terminal Modules combine 16, 32 or 64 digital inputs or outputs on a very small area. This compact and slimline design enables very high packing densities, leading to smaller control cabinets and terminal boxes.
EM7004 11Version: 2.0
Product overview
Fig.12: Terminal module with 16 channels
Fig.13: Terminal module with 32 channels
Fig.14: Terminal module with 64 channels
EM700412 Version: 2.0

2.2 Introduction

Product overview
Fig.15: EM7004
Terminal module axis interface
The EtherCAT module EM7004 is an interface that is optimized for direct connection of 4 servo drives, whose "encoder simulation" feeds the module with RS485 signals. The compact module features 4 integrated incremental encoders, 16 digital 24VDC inputs and outputs, and 4 analog ±10 V outputs. For fast preprocessing the digital outputs can be connected directly via the 4 encoders (PLS). This function is parameterizable. All inputs and outputs operate with a 24 V supply. Connectors X4, X5, X6 and X7 each feature an encoder input and an analog output. The connectors are galvanically isolated from each other and from the supply voltage. Connectors X0 and X1 with 16 digital inputs and X2 and X3 with 16 digital outputs enable 3-wire connection.
See also section Ordering information for EM/KM connector [}113].
EM7004 13Version: 2.0
Product overview

2.3 Technical data

Technical data EM7004
Digital inputs 16, 24V Digital outputs 16, 24V Max. output current
Digital outputs
Max. sum current (24 V supply voltage) 10 A Analog outputs 4 x ±10V (2mA) Encoder inputs 4x(A,/A,B,/B,gate,latch,ground); A B – insulated
Minimum cycle time 1ms Power supply for the electronics via the E-bus Current consumption via E-bus typ. 280 mA Electrical isolation 500 V (E-bus/signal voltage) Dimensions with connector (W x H x D) approx. 147 mm x 100 mm x 55 mm (width aligned:
Weight (without connector) approx. 260 g Weight of a connector ZS2001-0004 (three-pole) approx. 20 g Weight of a connector ZS2001-0005 (single-pole) approx. 10 g Permissible ambient temperature range during
operation Permissible ambient temperature range during
storage Permissible relative humidity 95%, no condensation
Mounting [}19]
Vibration/shock resistance conforms to EN60068-2-6/ EN60068-2-27 EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4 Protection class IP20 Installation position variable Approval CE
X2.0 - X2.3: 0.5 A X2.4 - X2.7: 1.5 A X3.0 - X3.3: 0.5 A X3.4 - X3.7: 1.5 A
RS485 inputs (RS422); 4 x 16bit, quadrature encoder; < 400kHz
PLS function (Programmable Limit Switch) [}14]
145 mm), see dimensional drawing [}19]
0°C ... + 55°C
-25°C ... + 85°C
on 35 mm mounting rail conforms to EN 60715
DC
DC

2.4 Basic function principles

The 4-axis interface terminal module EM7004 integrates 4 Incremental encoder, 4 analog outputs with +/-10V and 16 digital 24V inputs and outputs. The digital inputs and outputs can be connected in single, two or three wire connection mode. For the incremental encoder a 16-bit counter with quadrature decoder and a 16-bit latch can be read, set or enabled. In addition to encoder inputs A, /A, B, /B, an additional latch input L (24V) and a gate input G (24V) for disabling the counter are available. The "Value" input value represents a 16-bit "position counter". The PLS function (Programmable Limit Switch) can be used to control digital outputs automatically depending on the encoder counter value (up to 75 entries).
Reference
An object description and an overview of adjustable encoder parameters can be found in chapter "TwinCAT System Manager - Object overview [}96]".
EM700414 Version: 2.0

2.4.1 Analog process data

Product overview
In the delivery state the process data are shown in two's complement form (-1
corresponds to 0xFFFF).
dez
The feature object 0x8020:02 [}97] (channel 1), 0x8030:02 [}97] (channel 2), 0x8040:02 [}97] (channel
3), 0x8050:02 [}97] (channel 4) can be used to select other presentation types (e.g. magnitude sign format, absolute value).
Output value Output voltage
hexadecimal decimal
0x8001 -32769 -10V 0xC001 -16383 -5V 0x0000 0 0V 0x3FFF +16383 +5V 0x7FFF +32767 +10V

2.4.2 Process data equations

Calculation
The process data, which are transferred to the Bus Terminal, are calculated based on the following equations:
YH = X x AK + B
K
YA = YH x AW x 2
-16
+ B
Output value after manufacturer calibration (the feature object user scaling [0x8020:01 [}97] (channel 1), 0x8030:01 [}97] (channel 2), 0x8040:01 [}97] (channel 3), 0x8050:01 [}97] (channel 4) is inactive]
Output value following user scaling
W
EM7004 15Version: 2.0
Product overview
Legend
Name Name Object index
Y
H
Y
A
X Controller process data ­B
K
A
K
B
W
A
W
Process data to D/A converter after manufacturer calibration ­Process data to D/A converter after user scaling -
Manufacturer calibration offset (can only be changed if the producer code word (object 0xF008 [}112]) is set)
Manufacturer calibration gain (can only be changed if the Producer codeword (object 0xF008 [}112]) is set)
User scaling offset (can be activated via feature object user scaling [0x8020:01 [}97] (channel1), 0x8030:01 [}97] (channel 2), 0x8040:01 [}97] (channel
3), 0x8050:01 [}97] (channel 4)]
User scaling gain (can be activated via feature object user scaling [0x8020:01 [}97] (channel1), 0x8030:01 [}97] (channel 2), 0x8040:01 [}97] (channel
3), 0x8050:01 [}97] (channel 4)]
0x802F:01 [}98], 0x803F:01 [}98], 0x804F:01 [}98], 0x805F:01 [}98]
0x802F:02 [}98], 0x803F:02 [}98], 0x804F:02 [}98], 0x805F:02 [}98]
0x8020:11 [}97], 0x8030:11 [}97], 0x8040:11 [}97], 0x8050:11 [}97]
0x8020:12 [}97], 0x8030:12 [}97], 0x8040:12 [}97], 0x8050:12 [}97]
EM700416 Version: 2.0
Product overview
Sample: Limitation of the output range from -5V to +5V, calculation of the user scaling GAIN factor
YA = 16383
dec
corresponds to the desired upper limit value of +5 V
YH = 32767 BW = 0
YA = YH x AW x 2
Û (YA - BW ) / (YH x 2
dec
dec
-16
+ B
-16
(16383 - 0) / 32767 x 2
W
) =A
-16
corresponds to the upper limit value of +10 V corresponds to the offset of the user scaling
Calculation of the GAIN value for an upper limit value of +5V (corresponds to a lower limit value of -5V through cancelling the sign)
W
corresponds to the user scaling gain factor (factor 0.5)
=A W =32767
Sample: Shifting of the output range from -3V to +10V, calculation of the user scaling OFFSET value
YA = (- 9831 YH = (-32769 AW = 65536
YA = YH x AW x 2
Û YA - YH x AW x 2
) corresponds to the desired lower limit value of -3 V
dec
) corresponds to the lower limit value of -10 V
dec
dec
-16
+ B
-16
W
= B
W
corresponds to the gain factor of the user scaling (factor 1)
Calculation of the OFFSET value for the shifting of the lower limit value to -3 V
(- 9831) - (- 32769 x 65536 x 2
-16
)
corresponds to the offset value of the user scaling of +7 V
= B W = 22938
OFFSET value
Shifting of the output value through the OFFSET is linear up to the lower (- 10V) or upper limit value (+ 10V).
Note
User-specific output value (user default output)
The analog output value can, e.g. in the case of a failure of communication with the controller, be set to a user-specific value. The objects 0x8020:06 [}97] (channel 1), 0x8030:06 [}97] (channel 2), 0x8040:06 [}97] (channel 3), 0x8050:06 [}97] (channel 4) activate this option (value: TRUE); the output values are determined with the objects 0x8020:13 [}97] (channel 1), 0x8030:13 [}97] (channel 2), 0x8040:13 [}97] (channel 3), 0x8050:13 [}97] (channel 4). If this function is disabled (value of object 0x8020:06 [}97] (channel 1), 0x8030:06 [}97] (channel 2), 0x8040:06 [}97] (channel 3), 0x8050:06 [}97] (channel 4) is
FALSE), the manufacturer default value (0V) is output. If the watchdog timer is deactivated (value of object 0x8020:05 [}97] (channel 1), 0x8030:05 [}97] (channel 2), 0x8040:05 [}97] (channel 3), 0x8050:05 [}97] (channel 4) is TRUE), no default value is
output.
PLS function (Programmable Limit Switch)
The PLS function enables a certain value ("PLS output data", object 0x80A2 [}111]) to be assigned to the digital outputs when the assigned encoder ("Encoder as PLS source", object 0x80A0:01 [}98]) has reached a particular switch value ("PLS switch value", object 0x80A1 [}111]). Object 0x80A0:11 [}98] ("output
mask") is used to specify which of the digital outputs are allocated to the PLS function.
EM7004 17Version: 2.0
Product overview
Sample
Value in object 0x80A0:11 [}98] = 0x00FF, outputs 0-7 are assigned to the PLS function, outputs 8-15 are not linked to the function.
If no valid table entry is available (counter reading >=0, but less than the first table entry), the value in object 0x80A0:12 [}98] ("default output") is output. Object 0x80A1 [}111] contains up to 75 switch values ("PLS switch values"); object 0x80A2 [}111] contains
up to 75 output data ("PLS output data"). The PLS function can only be activated if the subindex :0 (number of following subindices) for objects 0x80A1 [}111] and 0x80A2 [}111] is identical.
PLS function: Response time for triggering the outputs
The internal processing time of the terminal from reaching the PLS switch value to switch-
Note
ing of the digital outputs is specified with less than 365µs.
Code Word
Code word
The vendor reserves the authority for the basic calibration of the terminals. The code word
Note
is therefore at present reserved.
EM700418 Version: 2.0
Mounting and wiring

3 Mounting and wiring

3.1 Recommended mounting rails

Terminal Modules and EtherCAT Modules of KMxxxx and EMxxxx series, same as the terminals of the EL66xx and EL67xx series can be snapped onto the following recommended mounting rails:
• DIN Rail TH 35-7.5 with 1 mm material thickness (according to EN 60715)
• DIN Rail TH 35-15 with 1,5 mm material thickness
Pay attention to the material thickness of the DIN Rail
Terminal Modules und EtherCAT Modules of KMxxxx and EMxxxx series, same as the ter-
Note

3.2 Dimensions

EM7004
minals of the EL66xx and EL67xx series does not fit to the DIN Rail TH 35-15 with 2,2 to 2,5 mm material thickness (according to EN 60715)!
Fig.16: EM7004 dimensions

3.3 Mounting and demounting - terminals with traction lever unlocking

The terminal modules are fastened to the assembly surface with the aid of a 35 mm mounting rail (e.g. mounting rail TH 35-15).
Fixing of mounting rails
The locking mechanism of the terminals and couplers extends to the profile of the mounting
Note
EM7004 19Version: 2.0
rail. At the installation, the locking mechanism of the components must not come into con­flict with the fixing bolts of the mounting rail. To mount the recommended mounting rails un­der the terminals and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).
Mounting and wiring
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation,
WARNING
disassembly or wiring of the Bus Terminals!
Mounting
• Fit the mounting rail to the planned assembly location.
and press (1) the terminal module against the mounting rail until it latches in place on the mounting rail (2).
• Attach the cables.
Demounting
• Remove all the cables. Thanks to the KM/EM connector, it is not necessary to remove all the cables separately for this, but for each KM/EM connector simply undo 2 screws so that you can pull them off (fixed wiring)!
• Lever the unlatching hook on the left-hand side of the terminal module upwards with a screwdriver (3). As you do this
◦ an internal mechanism pulls the two latching lugs (3a) from the top hat rail back into the
terminal module,
◦ the unlatching hook moves forwards (3b) and engages
EM700420 Version: 2.0
Mounting and wiring
• In the case 32 and 64 channel terminal modules (KMxxx4 and KMxxx8 or EMxxx4 and EMxxx8) you now lever the second unlatching hook on the right-hand side of the terminal module upwards in the same way.
• Pull (4) the terminal module away from the mounting surface.

3.4 Installation positions

Constraints regarding installation position and operating temperature range
Please refer to the technical data for a terminal to ascertain whether any restrictions re-
Attention
EM7004 21Version: 2.0
garding the installation position and/or the operating temperature range have been speci­fied. When installing high power dissipation terminals ensure that an adequate spacing is maintained between other components above and below the terminal in order to guarantee adequate ventilation!
Mounting and wiring
Optimum installation position (standard)
The optimum installation position requires the mounting rail to be installed horizontally and the connection surfaces of the EL/KL terminals to face forward (see Fig. “Recommended distances for standard installation position”). The terminals are ventilated from below, which enables optimum cooling of the electronics through convection. "From below" is relative to the acceleration of gravity.
Fig.17: Recommended distances for standard installation position
Compliance with the distances shown in Fig. “Recommended distances for standard installation position” is recommended.
Other installation positions
All other installation positions are characterized by different spatial arrangement of the mounting rail - see Fig “Other installation positions”.
The minimum distances to ambient specified above also apply to these installation positions.
EM700422 Version: 2.0
Mounting and wiring
Fig.18: Other installation positions
EM7004 23Version: 2.0
Mounting and wiring

3.5 Wiring

Otherwise the device may be damaged
Bring the bus system into a safe, de-energized state before starting installation, disassem-
Attention
Connection of the supply voltages and pin assignment
Version 1: 24Vsupply voltage via clamped joint X8
For power supply of the EM module, connect the clamped joint X8 (see Fig. Clamped joint for power supply) with the 24V supply voltage.
bly or wiring of the terminal modules!
Fig.19: Clamped joint for power supply
Risk of damage to the module; note sum current!
Regardless of the maximum output current of the individual module channels, the maxi-
Attention
mum sum current flowing via the clamped joint X8 must not exceed 10A (see Technical data [}14])!
Version 2: Alternative 24V module supply
The diagram shows the alternative connection of the supply voltage for the digital inputs and outputs, and the further connection of the module.
EM700424 Version: 2.0
Mounting and wiring
Fig.20: Connection of the module with alternative power supply
Alternative 24 V power supply of the EM module
For alternative supply (US) of the EM module, connect connectors X0-X3 (see Fig. Connec-
Note
tion of the module with alternative power supply)
• the positive supply voltage to terminal location +24V
• the negative supply voltage to terminal location 0V
Connection for clamped joints X0 - X1
Digital inputs, channel 0 - 15 (16 channels)
(with connector ZS2001-0002 or ZS2001-0004)
EM7004 25Version: 2.0
Mounting and wiring
Connection Terminal point on EM/KM plug connector
24V 24 X0 Input 0 0 X0 Input 1 1 X0 Input 2 2 X0 Input 3 3 X0 Input 4 4 X0 Input 5 5 X0 Input 6 6 X0 Input 7 7 X0 0V 0V X0 24V 24 X1 Input 8 0 X1 Input 9 1 X1 Input 10 2 X1 Input 11 3 X1 Input 12 4 X1 Input 13 5 X1 Input 14 6 X1 Input 15 7 X1 0V 0V X1
Connection for clamped joints X2 – X3
Digital outputs, channel 0 - 15 (16 channels)
(with connector ZS2001-0002 or ZS2001-0004)
Connection Terminal point on EM/KM plug connector
24V 24 X2 Output 0 0 X2 Output 1 1 X2 Output 2 2 X2 Output 3 3 X2 Output 4 4 X2 Output 5 5 X2 Output 6 6 X2 Output 7 7 X2 0V 0V X2 24V 24 X3 Output 8 8 X3 Output 9 9 X3 Output 10 10 X3 Output 11 11 X3 Output 12 12 X3 Output 13 13 X3 Output 14 14 X3 Output 15 15 X3 0V 0V X3
EM700426 Version: 2.0
Mounting and wiring
Connection for clamped joints X4 – X7
Incremental encoder and analog outputs
(with connector ZS2001-0005)
Connection Terminal point on EM/KM plug connector
Encoder 1, input A 1 X4 Encoder 1, input /A 2 X4 Encoder 1, input B 3 X4 Encoder 1, input /B 4 X4 Encoder 1, Gate 5 X4 Encoder 1, Latch 6 X4 Ground 7 X4 Analog output 1, +10V 8 X4 Analog output 1, -10 V 9 X4 Shield 10 X4 Encoder 2, input A 1 X5 Encoder 2, input /A 2 X5 Encoder 2, input B 3 X5 Encoder 2, input /B 4 X5 Encoder 2, Gate 5 X5 Encoder 2, Latch 6 X5 Ground 7 X5 Analog output 2, +10 V 8 X5 Analog output 2, -10 V 9 X5 Shield 10 X5 Encoder 3, input A 1 X6 Encoder 3, input /A 2 X6 Encoder 3, input B 3 X6 Encoder 3, input /B 4 X6 Encoder 3, Gate 5 X6 Encoder 3, Latch 6 X6 Ground 7 X6 Analog output 3, +10 V 8 X6 Analog output 3, -10 V 9 X6 Shield 10 X6 Encoder 4, input A 1 X7 Encoder 4, input /A 2 X7 Encoder 4, input B 3 X7 Encoder 4, input /B 4 X7 Encoder 4, Gate 5 X7 Encoder 4, Latch 6 X7 Ground 7 X7 Analog output 4, +10 V 8 X7 Analog output 4, -10 V 9 X7 Shield 10 X7
EM7004 27Version: 2.0
Mounting and wiring

3.6 Connection technology

The digital inputs and outputs can be connected in
• single-conductor (see example, terminal point 0),
• two-conductor (see example, terminal point 3), or
• three-conductor mode (see example, terminal point 6)
.
Input circuits
Fig.21: Input circuits single-, two- and three-conductor mode
EM700428 Version: 2.0
Output circuits
Mounting and wiring
Fig.22: Output circuits single-, two- and three-conductor mode
EM7004 29Version: 2.0
Commissioning

4 Commissioning

4.1 TwinCAT Quick Start

TwinCAT is a development environment for real-time control including multi-PLC system, NC axis control, programming and operation. The whole system is mapped through this environment and enables access to a programming environment (including compilation) for the controller. Individual digital or analog inputs or outputs can also be read or written directly, in order to verify their functionality, for example.
For further information please refer to http://infosys.beckhoff.com:
EtherCAT Systemmanual: Fieldbus Components → EtherCAT Terminals → EtherCAT System Documentation → Setup in the TwinCAT System Manager
TwinCAT2 → TwinCAT System Manager → I/O - Configuration
• In particular, TwinCAT driver installation: Fieldbus components → Fieldbus Cards and Switches → FC900x – PCI Cards for Ethernet → Installation
Devices contain the terminals for the actual configuration. All configuration data can be entered directly via editor functions (offline) or via the "Scan" function (online):
"offline": The configuration can be customized by adding and positioning individual components. These can be selected from a directory and configured.
◦ The procedure for offline mode can be found under http://infosys.beckhoff.com:
TwinCAT2 → TwinCAT System Manager → IO - Configuration → Adding an I/O Device
"online": The existing hardware configuration is read
◦ See also http://infosys.beckhoff.com:
Fieldbus components → Fieldbus cards and switches → FC900x – PCI Cards for Ethernet → Installation → Searching for devices
The following relationship is envisaged from user PC to the individual control elements:
EM700430 Version: 2.0
Commissioning
Fig.23: Relationship between user side (commissioning) and installation
The user inserting of certain components (I/O device, terminal, box...) is the same in TwinCAT2 and TwinCAT3. The descriptions below relate to the online procedure.
Sample configuration (actual configuration)
Based on the following sample configuration, the subsequent subsections describe the procedure for TwinCAT2 and TwinCAT3:
• Control system (PLC) CX2040 including CX2100-0004 power supply unit
• Connected to the CX2040 on the right (E-bus): EL1004 (4-channel analog input terminal -10…+10V)
• Linked via the X001 port (RJ-45): EK1100 EtherCAT Coupler
• Connected to the EK1100 EtherCAT coupler on the right (E-bus): EL2008 (8-channel digital output terminal 24VDC;0.5A)
• (Optional via X000: a link to an external PC for the user interface)
EM7004 31Version: 2.0
Commissioning
Fig.24: Control configuration with an Embedded PC and input (EL1004) and output (EL2008)
Note that all combinations of a configuration are possible; for example, the EL1004 terminal could also be connected after the coupler, or the EL2008 terminal could additionally be connected to the CX2040 on the right, in which case the EK1100 coupler wouldn’t be necessary.
4.1.1 TwinCAT2
Startup
TwinCAT basically uses two user interfaces: the TwinCAT System Manager for communication with the electromechanical components and TwinCAT PLC Control for the development and compilation of a controller. The starting point is the TwinCAT System Manager.
After successful installation of the TwinCAT system on the PC to be used for development, the TwinCAT2 System Manager displays the following user interface after startup:
Fig.25: Initial TwinCAT2 user interface
EM700432 Version: 2.0
Commissioning
Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is "Insert Device [}34]".
If the intention is to address the TwinCAT runtime environment installed on a PLC as development environment remotely from another system, the target system must be made known first. In the menu under
"Actions" → "Choose Target System...", via the symbol " " or the "F8" key, open the following window:
Fig.26: Selection of the target system
Use "Search (Ethernet)..." to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after "Enter Host Name / IP:" (as shown in red)
• perform a "Broadcast Search" (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.
Fig.27: Specify the PLC for access by the TwinCAT System Manager: selection of the target system
Once the target system has been entered, it is available for selection as follows (a password may have to be entered):
EM7004 33Version: 2.0
Commissioning
After confirmation with "OK" the target system can be accessed via the System Manager.
Adding devices
In the configuration tree of the TwinCAT2 System Manager user interface on the left, select "I/ODevices” and then right-click to open a context menu and select "ScanDevices…", or start the action in the menu bar
via . The TwinCAT System Manager may first have to be set to "Configmode" via or via menu “Actions" → "Set/Reset TwinCAT to Config Mode…" (Shift + F4).
Fig.28: Select "Scan Devices..."
Confirm the warning message, which follows, and select "EtherCAT" in the dialog:
Fig.29: Automatic detection of I/O devices: selection the devices to be integrated
Confirm the message "Find new boxes", in order to determine the terminals connected to the devices. "Free Run" enables manipulation of input and output values in "Config mode" and should also be acknowledged.
Based on the sample configuration [}31] described at the beginning of this section, the result is as follows:
EM700434 Version: 2.0
Commissioning
Fig.30: Mapping of the configuration in the TwinCAT2 System Manager
The whole process consists of two stages, which may be performed separately (first determine the devices, then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by selecting "Device ..." from the context menu, which then reads the elements present in the configuration below:
Fig.31: Reading of individual terminals connected to a device
This functionality is useful if the actual configuration is modified at short notice.
Programming and integrating the PLC
TwinCAT PLC Control is the development environment for the creation of the controller in different program environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two text­based languages and three graphical languages.
Text-based languages
◦ Instruction List (IL)
EM7004 35Version: 2.0
Commissioning
◦ Structured Text (ST)
Graphical languages
◦ Function Block Diagram (FBD) ◦ Ladder Diagram (LD) ◦ The Continuous Function Chart Editor (CFC) ◦ Sequential Function Chart (SFC)
The following section refers to Structured Text (ST).
After starting TwinCAT PLC Control, the following user interface is shown for an initial project:
Fig.32: TwinCAT PLC Control after startup
Sample variables and a sample program have been created and stored under the name "PLC_example.pro":
EM700436 Version: 2.0
Commissioning
Fig.33: Sample program with variables after a compile process (without variable integration)
Warning 1990 (missing "VAR_CONFIG") after a compile process indicates that the variables defined as external (with the ID "AT%I*" or "AT%Q*") have not been assigned. After successful compilation, TwinCAT PLC Control creates a "*.tpy" file in the directory in which the project was stored. This file (*.tpy) contains variable assignments and is not known to the System Manager, hence the warning. Once the System Manager has been notified, the warning no longer appears.
First, integrate the TwinCAT PLC Control project in the System Manager via the context menu of the PLC configuration; right-click and select "Append PLC Project…":
Fig.34: Appending the TwinCAT PLC Control project
EM7004 37Version: 2.0
Commissioning
Select the PLC configuration "PLC_example.tpy" in the browser window that opens. The project including the two variables identified with "AT" are then integrated in the configuration tree of the System Manager:
Fig.35: PLC project integrated in the PLC configuration of the System Manager
The two variables "bEL1004_Ch4" and "nEL2008_value" can now be assigned to certain process objects of the I/O configuration.
Assigning variables
Open a window for selecting a suitable process object (PDO) via the context menu of a variable of the integrated project "PLC_example" and via "Modify Link..." "Standard":
Fig.36: Creating the links between PLC variables and process objects
In the window that opens, the process object for the variable “bEL1004_Ch4” of type BOOL can be selected from the PLC configuration tree:
EM700438 Version: 2.0
Commissioning
Fig.37: Selecting PDO of type BOOL
According to the default setting, certain PDO objects are now available for selection. In this sample the input of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox "All types" must be ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a byte variable. The following diagram shows the whole process:
Fig.38: Selecting several PDOs simultaneously: activate "Continuous" and "All types"
Note that the "Continuous" checkbox was also activated. This is designed to allocate the bits contained in the byte of the variable "nEL2008_value" sequentially to all eight selected output bits of the EL2008 terminal. In this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol ( ) at the yellow or red object of the variable indicates that a link exists. The links can also be checked by selecting a "Goto Link Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically selected:
EM7004 39Version: 2.0
Commissioning
Fig.39: Application of a "Goto Link" variable, using "MAIN.bEL1004_Ch4" as a sample
The process of assigning variables to the PDO is completed via the menu selection "Actions" → "Generate
Mappings”, key Ctrl+M or by clicking on the symbol in the menu.
This can be visualized in the configuration:
The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs to variable. However, in this example it would then not be possible to select all output bits for the EL2008, since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or similar PDO, it is possible to allocate this a set of bit-standardised variables (type "BOOL"). Here, too, a "Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the respective PLC instance can then be selected.
Activation of the configuration
The allocation of PDO to PLC variables has now established the connection from the controller to the inputs and outputs of the terminals. The configuration can now be activated. First, the configuration can be verified
via (or via "Actions" → "Check Configuration”). If no error is present, the configuration can be
activated via (or via "Actions" → "Activate Configuration…") to transfer the System Manager settings to the runtime system. Confirm the messages "Old configurations are overwritten!" and "Restart TwinCAT system in Run mode" with "OK".
A few seconds later the real-time status is displayed at the bottom right in the System Manager. The PLC system can then be started as described below.
Starting the controller
Starting from a remote system, the PLC control has to be linked with the Embedded PC over Ethernet via "Online" → “Choose Run-Time System…":
EM700440 Version: 2.0
Commissioning
Fig.40: Choose target system (remote)
In this sample "Runtime system 1 (port 801)" is selected and confirmed. Link the PLC with the real-time
system via menu option "Online" → "Login", the F11 key or by clicking on the symbol .The control program can then be loaded for execution. This results in the message "No program on the controller! Should the new program be loaded?", which should be acknowledged with "Yes". The runtime environment is ready for the program start:
EM7004 41Version: 2.0
Commissioning
Fig.41: PLC Control logged in, ready for program startup
The PLC can now be started via "Online" → "Run", F5 key or .

4.1.2 TwinCAT 3

Startup
TwinCAT makes the development environment areas available together with Microsoft Visual Studio: after startup, the project folder explorer appears on the left in the general window area (cf. "TwinCAT System Manager" of TwinCAT2) for communication with the electromechanical components.
After successful installation of the TwinCAT system on the PC to be used for development, TwinCAT3 (shell) displays the following user interface after startup:
EM700442 Version: 2.0
Commissioning
Fig.42: Initial TwinCAT3 user interface
First create a new project via (or under "File"→“New"→ "Project…"). In the following dialog make the corresponding entries as required (as shown in the diagram):
Fig.43: Create new TwinCAT project
The new project is then available in the project folder explorer:
EM7004 43Version: 2.0
Commissioning
Fig.44: New TwinCAT3 project in the project folder explorer
Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is "Insert Device [}45]".
If the intention is to address the TwinCAT runtime environment installed on a PLC as development environment remotely from another system, the target system must be made known first. Via the symbol in the menu bar:
expand the pull-down menu:
and open the following window:
Fig.45: Selection dialog: Choose the target system
EM700444 Version: 2.0
Use "Search (Ethernet)..." to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after "Enter Host Name / IP:" (as shown in red)
• perform a "Broadcast Search" (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.
Commissioning
Fig.46: Specify the PLC for access by the TwinCAT System Manager: selection of the target system
Once the target system has been entered, it is available for selection as follows (a password may have to be entered):
After confirmation with "OK" the target system can be accessed via the Visual Studio shell.
Adding devices
In the project folder explorer of the Visual Studio shell user interface on the left, select "Devices" within
element “I/O”, then right-click to open a context menu and select "Scan" or start the action via in the
menu bar. The TwinCAT System Manager may first have to be set to "Config mode" via or via the menu "TwinCAT" → "Restart TwinCAT (Config mode)".
Fig.47: Select "Scan"
Confirm the warning message, which follows, and select "EtherCAT" in the dialog:
EM7004 45Version: 2.0
Commissioning
Fig.48: Automatic detection of I/O devices: selection the devices to be integrated
Confirm the message "Find new boxes", in order to determine the terminals connected to the devices. "Free Run" enables manipulation of input and output values in "Config mode" and should also be acknowledged.
Based on the sample configuration [}31] described at the beginning of this section, the result is as follows:
Fig.49: Mapping of the configuration in VS shell of the TwinCAT3 environment
The whole process consists of two stages, which may be performed separately (first determine the devices, then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by selecting "Device ..." from the context menu, which then reads the elements present in the configuration below:
EM700446 Version: 2.0
Commissioning
Fig.50: Reading of individual terminals connected to a device
This functionality is useful if the actual configuration is modified at short notice.
Programming the PLC
TwinCAT PLC Control is the development environment for the creation of the controller in different program environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two text­based languages and three graphical languages.
Text-based languages
◦ Instruction List (IL) ◦ Structured Text (ST)
Graphical languages
◦ Function Block Diagram (FBD) ◦ Ladder Diagram (LD) ◦ The Continuous Function Chart Editor (CFC) ◦ Sequential Function Chart (SFC)
The following section refers to Structured Text (ST).
In order to create a programming environment, a PLC subproject is added to the project sample via the context menu of "PLC" in the project folder explorer by selecting "Add New Item….":
EM7004 47Version: 2.0
Commissioning
Fig.51: Adding the programming environment in "PLC"
In the dialog that opens select "Standard PLC project" and enter "PLC_example" as project name, for example, and select a corresponding directory:
Fig.52: Specifying the name and directory for the PLC programming environment
The "Main" program, which already exists by selecting "Standard PLC project", can be opened by double­clicking on "PLC_example_project" in "POUs”. The following user interface is shown for an initial project:
EM700448 Version: 2.0
Commissioning
Fig.53: Initial "Main" program of the standard PLC project
To continue, sample variables and a sample program have now been created:
EM7004 49Version: 2.0
Commissioning
Fig.54: Sample program with variables after a compile process (without variable integration)
The control program is now created as a project folder, followed by the compile process:
Fig.55: Start program compilation
The following variables, identified in the ST/ PLC program with "AT%", are then available in under "Assignments" in the project folder explorer:
Assigning variables
Via the menu of an instance - variables in the "PLC” context, use the "Modify Link…" option to open a window for selecting a suitable process object (PDO) for linking:
EM700450 Version: 2.0
Commissioning
Fig.56: Creating the links between PLC variables and process objects
In the window that opens, the process object for the variable "bEL1004_Ch4" of type BOOL can be selected from the PLC configuration tree:
Fig.57: Selecting PDO of type BOOL
According to the default setting, certain PDO objects are now available for selection. In this sample the input of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox "All types" must be ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a byte variable. The following diagram shows the whole process:
EM7004 51Version: 2.0
Commissioning
Fig.58: Selecting several PDOs simultaneously: activate "Continuous" and "All types"
Note that the "Continuous" checkbox was also activated. This is designed to allocate the bits contained in the byte of the variable "nEL2008_value" sequentially to all eight selected output bits of the EL2008 terminal. In this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol ( ) at the yellow or red object of the variable indicates that a link exists. The links can also be checked by selecting a "Goto Link Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically selected:
Fig.59: Application of a "Goto Link" variable, using "MAIN.bEL1004_Ch4" as a sample
The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs to variable. However, in this example it would then not be possible to select all output bits for the EL2008, since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or similar PDO, it is possible to allocate this a set of bit-standardised variables (type "BOOL"). Here, too, a "Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the respective PLC instance can then be selected.
EM700452 Version: 2.0
Commissioning
Activation of the configuration
The allocation of PDO to PLC variables has now established the connection from the controller to the inputs
and outputs of the terminals. The configuration can now be activated with or via the menu under "TwinCAT" in order to transfer settings of the development environment to the runtime system. Confirm the messages "Old configurations are overwritten!" and "Restart TwinCAT system in Run mode" with "OK". The corresponding assignments can be seen in the project folder explorer:
A few seconds later the corresponding status of the Run mode is displayed in the form of a rotating symbol
at the bottom right of the VS shell development environment. The PLC system can then be started as
described below.
Starting the controller
Select the menu option "PLC" → "Login" or click on to link the PLC with the real-time system and load the control program for execution. This results in the message "No program on the controller! Should the new program be loaded?", which should be acknowledged with "Yes". The runtime environment is ready for
program start by click on symbol , the "F5" key or via "PLC" in the menu selecting “Start”. The started programming environment shows the runtime values of individual variables:
Fig.60: TwinCAT development environment (VS shell): logged-in, after program startup
The two operator control elements for stopping and logout result in the required action (accordingly also for stop "Shift + F5", or both actions can be selected via the PLC menu).
EM7004 53Version: 2.0
Commissioning

4.2 TwinCAT Development Environment

The Software for automation TwinCAT (The Windows Control and Automation Technology) will be distinguished into:
• TwinCAT2: System Manager (Configuration) & PLC Control (Programming)
• TwinCAT3: Enhancement of TwinCAT2 (Programming and Configuration takes place via a common Development Environment)
Details:
TwinCAT2:
◦ Connects I/O devices to tasks in a variable-oriented manner ◦ Connects tasks to tasks in a variable-oriented manner ◦ Supports units at the bit level ◦ Supports synchronous or asynchronous relationships ◦ Exchange of consistent data areas and process images ◦ Datalink on NT - Programs by open Microsoft Standards (OLE, OCX, ActiveX, DCOM+, etc.) ◦ Integration of IEC 61131-3-Software-SPS, Software- NC and Software-CNC within Windows
NT/2000/XP/Vista, Windows 7, NT/XP Embedded, CE
◦ Interconnection to all common fieldbusses ◦ More…
Additional features:
TwinCAT3 (eXtended Automation):
◦ Visual-Studio®-Integration ◦ Choice of the programming language ◦ Supports object orientated extension of IEC 61131-3 ◦ Usage of C/C++ as programming language for real time applications ◦ Connection to MATLAB®/Simulink® ◦ Open interface for expandability ◦ Flexible run-time environment ◦ Active support of Multi-Core- und 64-Bit-Operatingsystem ◦ Automatic code generation and project creation with the TwinCAT Automation Interface
More…
Within the following sections commissioning of the TwinCAT Development Environment on a PC System for the control and also the basically functions of unique control elements will be explained.
Please see further information to TwinCAT2 and TwinCAT3 at http://infosys.beckhoff.com.

4.2.1 Installation of the TwinCAT real-time driver

In order to assign real-time capability to a standard Ethernet port of an IPC controller, the Beckhoff real-time driver has to be installed on this port under Windows.
This can be done in several ways. One option is described here.
In the System Manager call up the TwinCAT overview of the local network interfaces via Options → Show Real Time Ethernet Compatible Devices.
EM700454 Version: 2.0
Fig.61: System Manager “Options” (TwinCAT2)
This have to be called up by the Menü “TwinCAT” within the TwinCAT3 environment:
Commissioning
Fig.62: Call up under VS Shell (TwinCAT3)
The following dialog appears:
Fig.63: Overview of network interfaces
Interfaces listed under “Compatible devices” can be assigned a driver via the “Install” button. A driver should only be installed on compatible devices.
A Windows warning regarding the unsigned driver can be ignored.
Alternatively an EtherCAT-device can be inserted first of all as described in chapter Offline configuration creation, section “Creating the EtherCAT device” [}65] in order to view the compatible ethernet ports via its
EtherCAT properties (tab „Adapter“, button „Compatible Devices…“):
EM7004 55Version: 2.0
Commissioning
Fig.64: EtherCAT device properties(TwinCAT2): click on Compatible Devices…“ of tab Adapter
TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)” within the Solution Explorer under “I/O”:
After the installation the driver appears activated in the Windows overview for the network interface (Windows Start → System Properties → Network)
Fig.65: Windows properties of the network interface
A correct setting of the driver could be:
EM700456 Version: 2.0
Fig.66: Exemplary correct driver setting for the Ethernet port
Other possible settings have to be avoided:
Commissioning
EM7004 57Version: 2.0
Commissioning
Fig.67: Incorrect driver settings for the Ethernet port
IP address of the port used
IP address/DHCP
In most cases an Ethernet port that is configured as an EtherCAT device will not transport
Note
general IP packets. For this reason and in cases where an EL6601 or similar devices are used it is useful to specify a fixed IP address for this port via the “Internet Protocol TCP/IP” driver setting and to disable DHCP. In this way the delay associated with the DHCP client for the Ethernet port assigning itself a default IP address in the absence of a DHCP server is avoided. A suitable address space is 192.168.x.x, for example.
EM700458 Version: 2.0
Commissioning
Fig.68: TCP/IP setting for the Ethernet port
EM7004 59Version: 2.0
Commissioning

4.2.2 Notes regarding ESI device description

Installation of the latest ESI device description
The TwinCAT EtherCAT master/System Manager needs the device description files for the devices to be used in order to generate the configuration in online or offline mode. The device descriptions are contained in the so-called ESI files (EtherCAT Slave Information) in XML format. These files can be requested from the respective manufacturer and are made available for download. An *.xml file may contain several device descriptions.
The ESI files for Beckhoff EtherCAT devices are available on the Beckhoff website.
The ESI files should be stored in the TwinCAT installation directory.
Default settings:
TwinCAT2: C:\TwinCAT\IO\EtherCAT
TwinCAT3: C:\TwinCAT\3.1\Config\Io\EtherCAT
The files are read (once) when a new System Manager window is opened, if they have changed since the last time the System Manager window was opened.
A TwinCAT installation includes the set of Beckhoff ESI files that was current at the time when the TwinCAT build was created.
For TwinCAT2.11/TwinCAT3 and higher, the ESI directory can be updated from the System Manager, if the programming PC is connected to the Internet; by
TwinCAT2: Option → “Update EtherCAT Device Descriptions”
TwinCAT3: TwinCAT → EtherCAT Devices → “Update Device Descriptions (via ETG Website)…”
The TwinCAT ESI Updater [}64] is available for this purpose.
ESI
The *.xml files are associated with *.xsd files, which describe the structure of the ESI XML
Note
files. To update the ESI device descriptions, both file types should therefore be updated.
Device differentiation
EtherCAT devices/slaves are distinguished by four properties, which determine the full device identifier. For example, the device identifier EL2521-0025-1018 consists of:
• family key “EL”
• name “2521”
• type “0025”
• and revision “1018”
Fig.69: Identifier structure
The order identifier consisting of name + type (here: EL2521-0010) describes the device function. The revision indicates the technical progress and is managed by Beckhoff. In principle, a device with a higher revision can replace a device with a lower revision, unless specified otherwise, e.g. in the documentation.
Each revision has its own ESI description. See further notes [}6].
EM700460 Version: 2.0
Commissioning
Online description
If the EtherCAT configuration is created online through scanning of real devices (see section Online setup) and no ESI descriptions are available for a slave (specified by name and revision) that was found, the System Manager asks whether the description stored in the device should be used. In any case, the System Manager needs this information for setting up the cyclic and acyclic communication with the slave correctly.
Fig.70: OnlineDescription information window (TwinCAT2)
In TwinCAT3 a similar window appears, which also offers the Web update:
Fig.71: Information window OnlineDescription (TwinCAT3)
If possible, the Yes is to be rejected and the required ESI is to be requested from the device manufacturer. After installation of the XML/XSD file the configuration process should be repeated.
Changing the ‘usual’ configuration through a scan
ü If a scan discovers a device that is not yet known to TwinCAT, distinction has to be
Attention
Refer in particular to the chapter ‘General notes on the use of Beckhoff EtherCAT IO components’ and for manual configuration to the chapter ‘Offline configuration creation’ [}65].
If the OnlineDescription is used regardless, the System Manager reads a copy of the device description from the EEPROM in the EtherCAT slave. In complex slaves the size of the EEPROM may not be sufficient for the complete ESI, in which case the ESI would be incomplete in the configurator. Therefore it’s recommended using an offline ESI file with priority in such a case.
made between two cases. Taking the example here of the EL2521-0000 in the revision 1019
a) no ESI is present for the EL2521-0000 device at all, either for the revision 1019 or for
an older revision. The ESI must then be requested from the manufacturer (in this case Beckhoff).
b) an ESI is present for the EL2521-0000 device, but only in an older revision, e.g. 1018 or
1017. In this case an in-house check should first be performed to determine whether the spare parts stock allows the integration of the increased revision into the configuration at all. A new/higher revision usually also brings along new features. If these are not to be used, work can continue without reservations with the previous revision 1018 in the configuration. This is also stated by the Beckhoff compatibility rule.
The System Manager creates for online recorded device descriptions a new file “OnlineDescription0000...xml” in its ESI directory, which contains all ESI descriptions that were read online.
EM7004 61Version: 2.0
Commissioning
Fig.72: File OnlineDescription.xml created by the System Manager
Is a slave desired to be added manually to the configuration at a later stage, online created slaves are indicated by a prepended symbol “>” in the selection list (see Figure “Indication of an online recorded ESI of EL2521 as an example”).
Fig.73: Indication of an online recorded ESI of EL2521 as an example
If such ESI files are used and the manufacturer's files become available later, the file OnlineDescription.xml should be deleted as follows:
• close all System Manager windows
• restart TwinCAT in Config mode
• delete "OnlineDescription0000...xml"
• restart TwinCAT System Manager
This file should not be visible after this procedure, if necessary press <F5> to update
OnlineDescription for TwinCAT3.x
In addition to the file described above "OnlineDescription0000...xml" , a so called EtherCAT
Note
cache with new discovered devices is created by TwinCAT3.x, e.g. under Windows 7:
(Please note the language settings of the OS!) You have to delete this file, too.
Faulty ESI file
If an ESI file is faulty and the System Manager is unable to read it, the System Manager brings up an information window.
Fig.74: Information window for faulty ESI file (left: TwinCAT2; right: TwinCAT3)
EM700462 Version: 2.0
Reasons may include:
• Structure of the *.xml does not correspond to the associated *.xsd file → check your schematics
• Contents cannot be translated into a device description → contact the file manufacturer
Commissioning
EM7004 63Version: 2.0
Commissioning

4.2.3 TwinCAT ESI Updater

For TwinCAT2.11 and higher, the System Manager can search for current Beckhoff ESI files automatically, if an online connection is available:
Fig.75: Using the ESI Updater (>= TwinCAT2.11)
The call up takes place under: “Options” → "Update EtherCAT Device Descriptions"
Selection under TwinCAT3:
Fig.76: Using the ESI Updater (TwinCAT3)
The ESI Updater (TwinCAT3) is a convenient option for automatic downloading of ESI data provided by EtherCAT manufacturers via the Internet into the TwinCAT directory (ESI = EtherCAT slave information). TwinCAT accesses the central ESI ULR directory list stored at ETG; the entries can then be viewed in the Updater dialog, although they cannot be changed there.
The call up takes place under: “TwinCAT“ → „EtherCAT Devices“ → “Update Device Description (via ETG Website)…“.

4.2.4 Distinction between Online and Offline

The distinction between online and offline refers to the presence of the actual I/O environment (drives, terminals, EJ-modules). If the configuration is to be prepared in advance of the system configuration as a programming system, e.g. on a laptop, this is only possible in “Offline configuration” mode. In this case all components have to be entered manually in the configuration, e.g. based on the electrical design.
If the designed control system is already connected to the EtherCAT system and all components are energised and the infrastructure is ready for operation, the TwinCAT configuration can simply be generated through “scanning” from the runtime system. This is referred to as online configuration.
In any case, during each startup the EtherCAT master checks whether the slaves it finds match the configuration. This test can be parameterised in the extended slave settings. Refer to note “Installation of the latest ESI-XML device description” [}60].
For preparation of a configuration:
• the real EtherCAT hardware (devices, couplers, drives) must be present and installed
• the devices/modules must be connected via EtherCAT cables or in the terminal/ module strand in the same way as they are intended to be used later
EM700464 Version: 2.0
Commissioning
• the devices/modules be connected to the power supply and ready for communication
• TwinCAT must be in CONFIG mode on the target system.
The online scan process consists of:
detecting the EtherCAT device [}70] (Ethernet port at the IPC)
detecting the connected EtherCAT devices [}71]. This step can be carried out independent of the preceding step
troubleshooting [}74]
The scan with existing configuration [}75] can also be carried out for comparison.

4.2.5 OFFLINE configuration creation

Creating the EtherCAT device
Create an EtherCAT device in an empty System Manager window.
Fig.77: Append EtherCAT device (left: TwinCAT2; right: TwinCAT3)
Select type ‘EtherCAT’ for an EtherCAT I/O application with EtherCAT slaves. For the present publisher/ subscriber service in combination with an EL6601/EL6614 terminal select “EtherCAT Automation Protocol via EL6601”.
Fig.78: Selecting the EtherCAT connection (TwinCAT2.11, TwinCAT3)
Then assign a real Ethernet port to this virtual device in the runtime system.
Fig.79: Selecting the Ethernet port
EM7004 65Version: 2.0
Commissioning
This query may appear automatically when the EtherCAT device is created, or the assignment can be set/ modified later in the properties dialog; see Fig. “EtherCAT device properties (TwinCAT2)”.
Fig.80: EtherCAT device properties (TwinCAT2)
TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)” within the Solution Explorer under “I/O”:
Selecting the Ethernet port
Ethernet ports can only be selected for EtherCAT devices for which the TwinCAT real-time
Note
driver is installed. This has to be done separately for each port. Please refer to the respec­tive installation page [}54].
Defining EtherCAT slaves
Further devices can be appended by right-clicking on a device in the configuration tree.
Fig.81: Appending EtherCAT devices (left: TwinCAT2; right: TwinCAT3)
The dialog for selecting a new device opens. Only devices for which ESI files are available are displayed.
Only devices are offered for selection that can be appended to the previously selected device. Therefore the physical layer available for this port is also displayed (Fig. “Selection dialog for new EtherCAT device”, A). In the case of cable-based Fast-Ethernet physical layer with PHY transfer, then also only cable-based devices are available, as shown in Fig. “Selection dialog for new EtherCAT device”. If the preceding device has several free ports (e.g. EK1122 or EK1100), the required port can be selected on the right-hand side (A).
Overview of physical layer
• “Ethernet”: cable-based 100BASE-TX: EK couplers, EP boxes, devices with RJ45/M8/M12 connector
EM700466 Version: 2.0
• “E-Bus”: LVDS “terminal bus”, “EJ-module”: EL/ES terminals, various modular modules
The search field facilitates finding specific devices (since TwinCAT2.11 or TwinCAT3).
Commissioning
Fig.82: Selection dialog for new EtherCAT device
By default only the name/device type is used as selection criterion. For selecting a specific revision of the device the revision can be displayed as “Extended Information”.
Fig.83: Display of device revision
In many cases several device revisions were created for historic or functional reasons, e.g. through technological advancement. For simplification purposes (see Fig. “Selection dialog for new EtherCAT device”) only the last (i.e. highest) revision and therefore the latest state of production is displayed in the selection dialog for Beckhoff devices. To show all device revisions available in the system as ESI descriptions tick the “Show Hidden Devices” check box, see Fig. “Display of previous revisions”.
EM7004 67Version: 2.0
Commissioning
Fig.84: Display of previous revisions
Device selection based on revision, compatibility
The ESI description also defines the process image, the communication type between mas-
Note
ter and slave/device and the device functions, if applicable. The physical device (firmware, if available) has to support the communication queries/settings of the master. This is back­ward compatible, i.e. newer devices (higher revision) should be supported if the EtherCAT master addresses them as an older revision. The following compatibility rule of thumb is to be assumed for Beckhoff EtherCAT Terminals/ Boxes/ EJ-modules:
device revision in the system >= device revision in the configuration
This also enables subsequent replacement of devices without changing the configuration (different specifications are possible for drives).
Example:
If an EL2521-0025-1018 is specified in the configuration, an EL2521-0025-1018 or higher (-1019, -1020) can be used in practice.
Fig.85: Name/revision of the terminal
If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection dialog matches the Beckhoff state of production. It is recommended to use the last device revision when creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions should only be used if older devices from stock are to be used in the application.
In this case the process image of the device is shown in the configuration tree and can be parameterised as follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...
EM700468 Version: 2.0
Commissioning
Fig.86: EtherCAT terminal in the TwinCAT tree (left: TwinCAT2; right: TwinCAT3)
EM7004 69Version: 2.0
Commissioning

4.2.6 ONLINE configuration creation

Detecting/scanning of the EtherCAT device
The online device search can be used if the TwinCAT system is in CONFIG mode. This can be indicated by a symbol right below in the information bar:
• on TwinCAT2 by a blue display “Config Mode” within the System Manager window: .
• on TwinCAT3 within the user interface of the development environment by a symbol .
TwinCAT can be set into this mode:
• TwinCAT2: by selection of in the Menubar or by “Actions” → “Set/Reset TwinCATtoConfig Mode…”
• TwinCAT3: by selection of in the Menubar or by „TwinCAT“ → “RestartTwinCAT(ConfigMode)“
Online scanning in Config mode
The online search is not available in RUN mode (production operation). Note the differenti-
Note
ation between TwinCAT programming system and TwinCAT target system.
The TwinCAT2 icon ( ) or TwinCAT3 icon ( ) within the Windows-Taskbar always shows the TwinCAT mode of the local IPC. Compared to that, the System Manager window of TwinCAT2 or the user interface of TwinCAT3 indicates the state of the target system.
Fig.87: Differentiation local/target system (left: TwinCAT2; right: TwinCAT3)
Right-clicking on “I/O Devices” in the configuration tree opens the search dialog.
Fig.88: Scan Devices (left: TwinCAT2; right: TwinCAT3)
This scan mode attempts to find not only EtherCAT devices (or Ethernet ports that are usable as such), but also NOVRAM, fieldbus cards, SMB etc. However, not all devices can be found automatically.
EM700470 Version: 2.0
Commissioning
Fig.89: Note for automatic device scan (left: TwinCAT2; right: TwinCAT3)
Ethernet ports with installed TwinCAT real-time driver are shown as “RT Ethernet” devices. An EtherCAT frame is sent to these ports for testing purposes. If the scan agent detects from the response that an EtherCAT slave is connected, the port is immediately shown as an “EtherCAT Device” .
Fig.90: Detected Ethernet devices
Via respective checkboxes devices can be selected (as illustrated in Fig. “Detected Ethernet devices” e.g. Device 3 and Device 4 were chosen). After confirmation with “OK” a device scan is suggested for all selected devices, see Fig.: “Scan query after automatic creation of an EtherCAT device”.
Selecting the Ethernet port
Ethernet ports can only be selected for EtherCAT devices for which the TwinCAT real-time
Note
driver is installed. This has to be done separately for each port. Please refer to the respec­tive installation page [}54].
Detecting/Scanning the EtherCAT devices
Online scan functionality
During a scan the master queries the identity information of the EtherCAT slaves from the
Note
Fig.91: Example default state
slave EEPROM. The name and revision are used for determining the type. The respective devices are located in the stored ESI data and integrated in the configuration tree in the de­fault state defined there.
Slave scanning in practice in series machine production
The scanning function should be used with care. It is a practical and fast tool for creating an
Attention
EM7004 71Version: 2.0
initial configuration as a basis for commissioning. In series machine production or reproduc­tion of the plant, however, the function should no longer be used for the creation of the con-
figuration, but if necessary for comparison [}75] with the defined initial configura­tion.Background: since Beckhoff occasionally increases the revision version of the deliv­ered products for product maintenance reasons, a configuration can be created by such a scan which (with an identical machine construction) is identical according to the device list; however, the respective device revision may differ from the initial configuration.
Commissioning
Example:
Company A builds the prototype of a machine B, which is to be produced in series later on. To do this the prototype is built, a scan of the IO devices is performed in TwinCAT and the initial configuration ‘B.tsm’ is created. The EL2521-0025 EtherCAT terminal with the revision 1018 is located somewhere. It is thus built into the TwinCAT configuration in this way:
Fig.92: Installing EthetCAT terminal with revision -1018
Likewise, during the prototype test phase, the functions and properties of this terminal are tested by the programmers/commissioning engineers and used if necessary, i.e. addressed from the PLC ‘B.pro’ or the NC. (the same applies correspondingly to the TwinCAT3 solution files).
The prototype development is now completed and series production of machine B starts, for which Beckhoff continues to supply the EL2521-0025-0018. If the commissioning engineers of the series machine production department always carry out a scan, a B configuration with the identical contents results again for each machine. Likewise, A might create spare parts stores worldwide for the coming series-produced machines with EL2521-0025-1018 terminals.
After some time Beckhoff extends the EL2521-0025 by a new feature C. Therefore the FW is changed, outwardly recognizable by a higher FW version and a new revision -1019. Nevertheless the new device naturally supports functions and interfaces of the predecessor version(s); an adaptation of ‘B.tsm’ or even ‘B.pro’ is therefore unnecessary. The series-produced machines can continue to be built with ‘B.tsm’ and
‘B.pro’; it makes sense to perform a comparative scan [}75] against the initial configuration ‘B.tsm’ in order to check the built machine.
However, if the series machine production department now doesn’t use ‘B.tsm’, but instead carries out a scan to create the productive configuration, the revision -1019 is automatically detected and built into the configuration:
Fig.93: Detection of EtherCAT terminal with revision -1019
This is usually not noticed by the commissioning engineers. TwinCAT cannot signal anything either, since virtually a new configuration is created. According to the compatibility rule, however, this means that no EL2521-0025-1018 should be built into this machine as a spare part (even if this nevertheless works in the vast majority of cases).
In addition, it could be the case that, due to the development accompanying production in company A, the new feature C of the EL2521-0025-1019 (for example, an improved analog filter or an additional process data for the diagnosis) is discovered and used without in-house consultation. The previous stock of spare part devices are then no longer to be used for the new configuration ‘B2.tsm’ created in this way.Þ if series machine production is established, the scan should only be performed for informative purposes for comparison with a defined initial configuration. Changes are to be made with care!
If an EtherCAT device was created in the configuration (manually or through a scan), the I/O field can be scanned for devices/slaves.
EM700472 Version: 2.0
Commissioning
Fig.94: Scan query after automatic creation of an EtherCAT device (left: TwinCAT2; right: TwinCAT3)
Fig.95: Manual triggering of a device scan on a specified EtherCAT device (left: TwinCAT2; right:
TwinCAT3)
In the System Manager (TwinCAT2) or the User Interface (TwinCAT3) the scan process can be monitored via the progress bar at the bottom in the status bar.
Fig.96: Scan progressexemplary by TwinCAT2
The configuration is established and can then be switched to online state (OPERATIONAL).
Fig.97: Config/FreeRun query (left: TwinCAT2; right: TwinCAT3)
In Config/FreeRun mode the System Manager display alternates between blue and red, and the EtherCAT device continues to operate with the idling cycle time of 4 ms (default setting), even without active task (NC, PLC).
Fig.98: Displaying of “Free Run” and “Config Mode” toggling right below in the status bar
Fig.99: TwinCAT can also be switched to this state by using a button (left: TwinCAT2; right: TwinCAT3)
The EtherCAT system should then be in a functional cyclic state, as shown in Fig. “Online display example”.
EM7004 73Version: 2.0
Commissioning
Fig.100: Online display example
Please note:
• all slaves should be in OP state
• the EtherCAT master should be in “Actual State” OP
• “frames/sec” should match the cycle time taking into account the sent number of frames
• no excessive “LostFrames” or CRC errors should occur
The configuration is now complete. It can be modified as described under manual procedure [}65].
Troubleshooting
Various effects may occur during scanning.
• An unknown device is detected, i.e. an EtherCAT slave for which no ESI XML description is available. In this case the System Manager offers to read any ESI that may be stored in the device. This case is described in the chapter "Notes regarding ESI device description".
Device are not detected properly Possible reasons include:
- faulty data links, resulting in data loss during the scan
- slave has invalid device description The connections and devices should be checked in a targeted manner, e.g. via the emergency scan. Then re-run the scan.
Fig.101: Faulty identification
In the System Manager such devices may be set up as EK0000 or unknown devices. Operation is not possible or meaningful.
EM700474 Version: 2.0
Commissioning
Scan over existing Configuration
Change of the configuration after comparison
With this scan (TwinCAT2.11 or 3.1) only the device properties vendor (manufacturer), de-
Attention
If a scan is initiated for an existing configuration, the actual I/O environment may match the configuration exactly or it may differ. This enables the configuration to be compared.
Fig.102: Identical configuration (left: TwinCAT2; right: TwinCAT3)
If differences are detected, they are shown in the correction dialog, so that the user can modify the configuration as required.
vice name and revision are compared at present! A ‘ChangeTo’ or ‘Copy’ should only be carried out with care, taking into consideration the Beckhoff IO compatibility rule (see above). The device configuration is then replaced by the revision found; this can affect the supported process data and functions.
Fig.103: Correction dialog
It is advisable to tick the “Extended Information” check box to reveal differences in the revision.
EM7004 75Version: 2.0
Commissioning
Colour Explanation
green This EtherCAT slave matches the entry on the other side. Both type and revision match. blue This EtherCAT slave is present on the other side, but in a different revision. This other
revision can have other default values for the process data as well as other/additional functions. If the found revision is higher than the configured revision, the slave may be used provided compatibility issues are taken into account.
If the found revision is lower than the configured revision, it is likely that the slave cannot be used. The found device may not support all functions that the master expects based on the
higher revision number. light blue This EtherCAT slave is ignored (“Ignore” button) red • This EtherCAT slave is not present on the other side.
• It is present, but in a different revision, which also differs in its properties from the one specified. The compatibility principle then also applies here: if the found revision is higher than the configured revision, use is possible provided compatibility issues are taken into account, since the successor devices should support the functions of the predecessor devices. If the found revision is lower than the configured revision, it is likely that the slave cannot be used. The found device may not support all functions that the master expects based on the higher revision number.
Device selection based on revision, compatibility
The ESI description also defines the process image, the communication type between mas-
Note
Example:
If an EL2521-0025-1018 is specified in the configuration, an EL2521-0025-1018 or higher (-1019, -1020) can be used in practice.
Fig.104: Name/revision of the terminal
If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection dialog matches the Beckhoff state of production. It is recommended to use the last device revision when creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions should only be used if older devices from stock are to be used in the application.
ter and slave/device and the device functions, if applicable. The physical device (firmware, if available) has to support the communication queries/settings of the master. This is back­ward compatible, i.e. newer devices (higher revision) should be supported if the EtherCAT master addresses them as an older revision. The following compatibility rule of thumb is to be assumed for Beckhoff EtherCAT Terminals/ Boxes/ EJ-modules:
device revision in the system >= device revision in the configuration
This also enables subsequent replacement of devices without changing the configuration (different specifications are possible for drives).
In this case the process image of the device is shown in the configuration tree and can be parameterised as follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...
EM700476 Version: 2.0
Fig.105: Correction dialog with modifications
Commissioning
Once all modifications have been saved or accepted, click “OK” to transfer them to the real *.tsm configuration.
Change to compatible device
TwinCAT offers a function “Change to Compatible Type…” for the exchange of a device whilst retaining the links in the task.
Fig.106: DialogChange to Compatible Type…” (left: TwinCAT2; right: TwinCAT3)
This function is preferably to be used on AX5000 devices. If called, the System Manager suggests the devices that it finds in the associated sub-folder; in the case of the AX5000, for example, in \TwinCAT\IO
\EtherCAT\Beckhoff AX5xxx.
Change to Alternative Type
The TwinCAT System Manager offers a function for the exchange of a device: Change to Alternative Type
Fig.107: TwinCAT2 Dialog Change to Alternative Type
EM7004 77Version: 2.0
Commissioning
If called, the System Manager searches in the procured device ESI (in this example: EL1202-0000) for details of compatible devices contained there. The configuration is changed and the ESI-EEPROM is overwritten at the same time – therefore this process is possible only in the online state (ConfigMode).

4.2.7 EtherCAT subscriber configuration

In the left-hand window of the TwinCAT2 System Manager or the Solution Explorer of the TwinCAT3 Development Environment respectively, click on the element of the terminal within the tree you wish to configure (in the example: EL3751 Terminal 3).
Fig.108: Branch element as terminal EL3751
In the right-hand window of the TwinCAT System manager (TwinCAT2) or the Development Environment (TwinCAT3), various tabs are now available for configuring the terminal. And yet the dimension of complexity of a subscriber determines which tabs are provided. Thus as illustrated in the example above the terminal EL3751 provides many setup options and also a respective number of tabs are available. On the contrary by the terminal EL1004 for example the tabs "General", "EtherCAT", "Process Data" and “Online“ are available only. Several terminals, as for instance the EL6695 provide special functions by a tab with its own terminal name, so “EL6695” in this case. A specific tab “Settings” by terminals with a wide range of setup options will be provided also (e.g. EL3751).
„General“ tab
Fig.109: “General” tab
Name Name of the EtherCAT device Id Number of the EtherCAT device Type EtherCAT device type Comment Here you can add a comment (e.g. regarding the
system).
Disabled Here you can deactivate the EtherCAT device. Create symbols Access to this EtherCAT slave via ADS is only
available if this control box is activated.
EM700478 Version: 2.0
Commissioning
„EtherCAT“ tab
Fig.110: „EtherCAT“ tab
Type EtherCAT device type Product/Revision Product and revision number of the EtherCAT device Auto Inc Addr. Auto increment address of the EtherCAT device. The
auto increment address can be used for addressing each EtherCAT device in the communication ring through its physical position. Auto increment addressing is used during the start-up phase when the EtherCAT master allocates addresses to the EtherCAT devices. With auto increment addressing the first EtherCAT slave in the ring has the address 0000 decremented by 1 (FFFF
EtherCAT Addr. Fixed address of an EtherCAT slave. This address is
allocated by the EtherCAT master during the start-up phase. Tick the control box to the left of the input field in order to modify the default value.
Previous Port Name and port of the EtherCAT device to which this
device is connected. If it is possible to connect this device with another one without changing the order of the EtherCAT devices in the communication ring, then this combination field is activated and the EtherCAT device to which this device is to be connected can be selected.
Advanced Settings This button opens the dialogs for advanced settings.
. For each further slave the address is
hex
, FFFE
hex
hex
etc.).
The link at the bottom of the tab points to the product page for this EtherCAT device on the web.
“Process Data” tab
Indicates the configuration of the process data. The input and output data of the EtherCAT slave are represented as CANopen process data objects (Process Data Objects, PDOs). The user can select a PDO via PDO assignment and modify the content of the individual PDO via this dialog, if the EtherCAT slave supports this function.
EM7004 79Version: 2.0
Commissioning
Fig.111: “Process Data” tab
The process data (PDOs) transferred by an EtherCAT slave during each cycle are user data which the application expects to be updated cyclically or which are sent to the slave. To this end the EtherCAT master (Beckhoff TwinCAT) parameterizes each EtherCAT slave during the start-up phase to define which process data (size in bits/bytes, source location, transmission type) it wants to transfer to or from this slave. Incorrect configuration can prevent successful start-up of the slave.
For Beckhoff EtherCAT EL, ES, EM, EJ and EP slaves the following applies in general:
• The input/output process data supported by the device are defined by the manufacturer in the ESI/XML description. The TwinCAT EtherCAT Master uses the ESI description to configure the slave correctly.
• The process data can be modified in the system manager. See the device documentation. Examples of modifications include: mask out a channel, displaying additional cyclic information, 16-bit display instead of 8-bit data size, etc.
• In so-called “intelligent” EtherCAT devices the process data information is also stored in the CoE directory. Any changes in the CoE directory that lead to different PDO settings prevent successful startup of the slave. It is not advisable to deviate from the designated process data, because the device firmware (if available) is adapted to these PDO combinations.
If the device documentation allows modification of process data, proceed as follows (see Figure “Configuring the process data”).
• A: select the device to configure
• B: in the “Process Data” tab select Input or Output under SyncManager (C)
• D: the PDOs can be selected or deselected
• H: the new process data are visible as linkable variables in the system manager The new process data are active once the configuration has been activated and TwinCAT has been restarted (or the EtherCAT master has been restarted)
• E: if a slave supports this, Input and Output PDO can be modified simultaneously by selecting a so­called PDO record (“predefined PDO settings”).
EM700480 Version: 2.0
Commissioning
Fig.112: Configuring the process data
Manual modification of the process data
According to the ESI description, a PDO can be identified as “fixed” with the flag “F” in the
Note
A detailed description [}86] can be found at the end of this section.
PDO overview (Fig. “Configuring the process data”, J). The configuration of such PDOs cannot be changed, even if TwinCAT offers the associated dialog (“Edit”). In particular, CoE content cannot be displayed as cyclic process data. This generally also applies in cases where a device supports download of the PDO configuration, “G”. In case of incorrect con­figuration the EtherCAT slave usually refuses to start and change to OP state. The System Manager displays an “invalid SM cfg” logger message: This error message (“invalid SM IN cfg” or “invalid SM OUT cfg”) also indicates the reason for the failed start.
„Startup“ tab
The Startup tab is displayed if the EtherCAT slave has a mailbox and supports the CANopen over EtherCAT (CoE) or Servo drive over EtherCAT protocol. This tab indicates which download requests are sent to the mailbox during startup. It is also possible to add new mailbox requests to the list display. The download requests are sent to the slave in the same order as they are shown in the list.
EM7004 81Version: 2.0
Commissioning
Fig.113: „Startup“ tab
Column Description
Transition Transition to which the request is sent. This can either be
• the transition from pre-operational to safe-operational (PS), or
• the transition from safe-operational to operational (SO).
If the transition is enclosed in "<>" (e.g. <PS>), the mailbox request is fixed and cannot be
modified or deleted by the user. Protocol Type of mailbox protocol Index Index of the object Data Date on which this object is to be downloaded. Comment Description of the request to be sent to the mailbox
Move Up This button moves the selected request up by one
position in the list.
Move Down This button moves the selected request down by one
position in the list.
New This button adds a new mailbox download request to
be sent during startup.
Delete This button deletes the selected entry. Edit This button edits an existing request.
“CoE – Online” tab
The additional CoE - Online tab is displayed if the EtherCAT slave supports the CANopen over EtherCAT (CoE) protocol. This dialog lists the content of the object list of the slave (SDO upload) and enables the user to modify the content of an object from this list. Details for the objects of the individual EtherCAT devices can be found in the device-specific object descriptions.
EM700482 Version: 2.0
Commissioning
Fig.114: “CoE – Online” tab
Object list display
Column Description
Index Index and sub-index of the object Name Name of the object Flags RW The object can be read, and data can be written to the object (read/write)
RO The object can be read, but no data can be written to the object (read only) P An additional P identifies the object as a process data object.
Value Value of the object
EM7004 83Version: 2.0
Commissioning
Update List The Update list button updates all objects in the
displayed list
Auto Update If this check box is selected, the content of the
objects is updated automatically.
Advanced The Advanced button opens the Advanced Settings
dialog. Here you can specify which objects are displayed in the list.
Fig.115: Dialog “Advanced settings”
Online - via SDO Information If this option button is selected, the list of the objects
included in the object list of the slave is uploaded from the slave via SDO information. The list below can be used to specify which object types are to be uploaded.
Offline - via EDS File If this option button is selected, the list of the objects
included in the object list is read from an EDS file provided by the user.
EM700484 Version: 2.0
„Online“ tab
Commissioning
Fig.116: „Online“ tab
State Machine
Init This button attempts to set the EtherCAT device to
the Init state.
Pre-Op This button attempts to set the EtherCAT device to
the pre-operational state.
Op This button attempts to set the EtherCAT device to
the operational state.
Bootstrap This button attempts to set the EtherCAT device to
the Bootstrap state.
Safe-Op This button attempts to set the EtherCAT device to
the safe-operational state.
Clear Error This button attempts to delete the fault display. If an
EtherCAT slave fails during change of state it sets an error flag.
Example: An EtherCAT slave is in PREOP state (pre­operational). The master now requests the SAFEOP state (safe-operational). If the slave fails during change of state it sets the error flag. The current state is now displayed as ERR PREOP. When the Clear Error button is pressed the error flag is cleared, and the current state is displayed as PREOP again.
Current State Indicates the current state of the EtherCAT device. Requested State Indicates the state requested for the EtherCAT
device.
DLL Status
Indicates the DLL status (data link layer status) of the individual ports of the EtherCAT slave. The DLL status can have four different states:
EM7004 85Version: 2.0
Commissioning
Status Description
No Carrier / Open No carrier signal is available at the port, but the port
is open.
No Carrier / Closed No carrier signal is available at the port, and the port
is closed.
Carrier / Open A carrier signal is available at the port, and the port is
open.
Carrier / Closed A carrier signal is available at the port, but the port is
closed.
File Access over EtherCAT
Download With this button a file can be written to the EtherCAT
device.
Upload With this button a file can be read from the EtherCAT
device.
"DC" tab (Distributed Clocks)
Fig.117: "DC" tab (Distributed Clocks)
Operation Mode Options (optional):
• FreeRun
• SM-Synchron
• DC-Synchron (Input based)
• DC-Synchron
Advanced Settings… Advanced settings for readjustment of the real time determinant TwinCAT-
clock
Detailed information to Distributed Clocks are specified on http://infosys.beckhoff.com:
Fieldbus Components → EtherCAT Terminals → EtherCAT System documentation → EtherCAT basics → Distributed Clocks
4.2.7.1 Detailed description of Process Data tab
Sync Manager
Lists the configuration of the Sync Manager (SM). If the EtherCAT device has a mailbox, SM0 is used for the mailbox output (MbxOut) and SM1 for the mailbox input (MbxIn). SM2 is used for the output process data (outputs) and SM3 (inputs) for the input process data.
If an input is selected, the corresponding PDO assignment is displayed in the PDO Assignment list below.
EM700486 Version: 2.0
Commissioning
PDO Assignment
PDO assignment of the selected Sync Manager. All PDOs defined for this Sync Manager type are listed here:
• If the output Sync Manager (outputs) is selected in the Sync Manager list, all RxPDOs are displayed.
• If the input Sync Manager (inputs) is selected in the Sync Manager list, all TxPDOs are displayed.
The selected entries are the PDOs involved in the process data transfer. In the tree diagram of the System Manager these PDOs are displayed as variables of the EtherCAT device. The name of the variable is identical to the Name parameter of the PDO, as displayed in the PDO list. If an entry in the PDO assignment list is deactivated (not selected and greyed out), this indicates that the input is excluded from the PDO assignment. In order to be able to select a greyed out PDO, the currently selected PDO has to be deselected first.
Activation of PDO assignment
ü If you have changed the PDO assignment, in order to activate the new PDO assign-
Note
ment,
a) the EtherCAT slave has to run through the PS status transition cycle (from pre-opera-
tional to safe-operational) once (see Online tab [}85]),
b) and the System Manager has to reload the EtherCAT slaves
( button for TwinCAT2 or button for TwinCAT3)
PDO list
List of all PDOs supported by this EtherCAT device. The content of the selected PDOs is displayed in the PDO Content list. The PDO configuration can be modified by double-clicking on an entry.
Column Description
Index PDO index. Size Size of the PDO in bytes. Name Name of the PDO.
If this PDO is assigned to a Sync Manager, it appears as a variable of the slave with this parameter as the name.
Flags F Fixed content: The content of this PDO is fixed and cannot be changed by the
System Manager.
M Mandatory PDO. This PDO is mandatory and must therefore be assigned to a
Sync Manager! Consequently, this PDO cannot be deleted from the PDO Assignment list
SM Sync Manager to which this PDO is assigned. If this entry is empty, this PDO does not take
part in the process data traffic.
SU Sync unit to which this PDO is assigned.
PDO Content
Indicates the content of the PDO. If flag F (fixed content) of the PDO is not set the content can be modified.
Download
If the device is intelligent and has a mailbox, the configuration of the PDO and the PDO assignments can be downloaded to the device. This is an optional feature that is not supported by all EtherCAT slaves.
PDO Assignment
If this check box is selected, the PDO assignment that is configured in the PDO Assignment list is downloaded to the device on startup. The required commands to be sent to the device can be viewed in the
Startup [}81] tab.
EM7004 87Version: 2.0
Commissioning
PDO Configuration
If this check box is selected, the configuration of the respective PDOs (as shown in the PDO list and the PDO Content display) is downloaded to the EtherCAT slave.

4.3 General Notes - EtherCAT Slave Application

This summary briefly deals with a number of aspects of EtherCAT Slave operation under TwinCAT. More detailed information on this may be found in the corresponding sections of, for instance, the EtherCAT System Documentation.
Diagnosis in real time: WorkingCounter, EtherCAT State and Status
Generally speaking an EtherCAT Slave provides a variety of diagnostic information that can be used by the controlling task.
This diagnostic information relates to differing levels of communication. It therefore has a variety of sources, and is also updated at various times.
Any application that relies on I/O data from a fieldbus being correct and up to date must make diagnostic access to the corresponding underlying layers. EtherCAT and the TwinCAT System Manager offer comprehensive diagnostic elements of this kind. Those diagnostic elements that are helpful to the controlling task for diagnosis that is accurate for the current cycle when in operation (not during commissioning) are discussed below.
Fig.118: Selection of the diagnostic information of an EtherCAT Slave
In general, an EtherCAT Slave offers
• communication diagnosis typical for a slave (diagnosis of successful participation in the exchange of process data, and correct operating mode) This diagnosis is the same for all slaves.
as well as
• function diagnosis typical for a channel (device-dependent) See the corresponding device documentation
The colors in Fig. “Selection of the diagnostic information of an EtherCAT Slave” also correspond to the variable colors in the System Manager, see Fig. “Basic EtherCAT Slave Diagnosis in the PLC”.
EM700488 Version: 2.0
Commissioning
Colour Meaning
yellow Input variables from the Slave to the EtherCAT Master, updated in every cycle red Output variables from the Slave to the EtherCAT Master, updated in every cycle green Information variables for the EtherCAT Master that are updated acyclically. This means that
it is possible that in any particular cycle they do not represent the latest possible status. It is therefore useful to read such variables through ADS.
Fig. “Basic EtherCAT Slave Diagnosis in the PLC” shows an example of an implementation of basic EtherCAT Slave Diagnosis. A Beckhoff EL3102 (2-channel analogue input terminal) is used here, as it offers both the communication diagnosis typical of a slave and the functional diagnosis that is specific to a channel. Structures are created as input variables in the PLC, each corresponding to the process image.
Fig.119: Basic EtherCAT Slave Diagnosis in the PLC
The following aspects are covered here:
EM7004 89Version: 2.0
Commissioning
Code Function Implementation Application/evaluation
A The EtherCAT Master's diagnostic infor-
mation updated acyclically (yellow) or provided
acyclically (green).
B In the example chosen (EL3102) the
EL3102 comprises two analogue input channels that transmit a single function status for the most recent cycle.
C For every EtherCAT Slave that has cyclic
process data, the Master displays, using what is known as a WorkingCounter, whether the slave is participating success­fully and without error in the cyclic ex­change of process data. This important, el­ementary information is therefore provided for the most recent cycle in the System Manager
1. at the EtherCAT Slave, and, with identical contents
2. as a collective variable at the EtherCAT Master (see Point A)
for linking.
D Diagnostic information of the EtherCAT
Master which, while it is represented at the slave for linking, is actually determined by the Master for the Slave concerned and represented there. This information cannot be characterized as real-time, because it
• is only rarely/never changed, except when the system starts up
• is itself determined acyclically (e.g. EtherCAT Status)
Status
• the bit significations may be found in the device documentation
• other devices may supply more information, or none that is typical of a slave
WcState (Working Counter) 0: valid real-time communication in
the last cycle 1: invalid real-time communication This may possibly have effects on
the process data of other Slaves that are located in the same Syn­cUnit
State current Status (INIT..OP) of the
Slave. The Slave must be in OP (=8) when operating normally.
AdsAddr
The ADS address is useful for communicating from the PLC/task via ADS with the EtherCAT Slave, e.g. for reading/writing to the CoE. The AMS-NetID of a slave corre­sponds to the AMS-NetID of the EtherCAT Master; communication with the individual Slave is possible via the port (= EtherCAT address).
At least the DevState is to be evaluated for the most recent cycle in the PLC.
The EtherCAT Master's diagnostic informa­tion offers many more possibilities than are treated in the EtherCAT System Documenta­tion. A few keywords:
• CoE in the Master for communication with/through the Slaves
• Functions from TcEtherCAT.lib
• Perform an OnlineScan
In order for the higher-level PLC task (or cor­responding control applications) to be able to rely on correct data, the function status must be evaluated there. Such information is therefore provided with the process data for the most recent cycle.
In order for the higher-level PLC task (or cor­responding control applications) to be able to rely on correct data, the communication sta­tus of the EtherCAT Slave must be evaluated there. Such information is therefore provided with the process data for the most recent cy­cle.
Information variables for the EtherCAT Mas­ter that are updated acyclically. This means that it is possible that in any particular cycle they do not represent the latest possible sta­tus. It is therefore possible to read such vari­ables through ADS.
Diagnostic information
It is strongly recommended that the diagnostic information made available is evaluated so that the application can react accordingly.
Attention
CoE Parameter Directory
The CoE parameter directory (CanOpen-over-EtherCAT) is used to manage the set values for the slave concerned. Changes may, in some circumstances, have to be made here when commissioning a relatively complex EtherCAT Slave. It can be accessed through the TwinCAT System Manager, see Fig. “EL3102, CoE directory”:
EM700490 Version: 2.0
Commissioning
Fig.120: EL3102, CoE directory
EtherCAT System Documentation
The comprehensive description in the EtherCAT System Documentation (EtherCAT Basics
Note
A few brief extracts:
• Whether changes in the online directory are saved locally in the slave depends on the device. EL terminals (except the EL66xx) are able to save in this way.
• The user must manage the changes to the StartUp list.
--> CoE Interface) must be observed!
Commissioning aid in the TwinCAT System Manager
Commissioning interfaces are being introduced as part of an ongoing process for EL/EP EtherCAT devices. These are available in TwinCAT System Managers from TwinCAT 2.11R2 and above. They are integrated into the System Manager through appropriately extended ESI configuration files.
EM7004 91Version: 2.0
Commissioning
Fig.121: Example of commissioning aid for a EL3204
This commissioning process simultaneously manages
• CoE Parameter Directory
• DC/FreeRun mode
• the available process data records (PDO)
Although the "Process Data", "DC", "Startup" and "CoE-Online" that used to be necessary for this are still displayed, it is recommended that, if the commissioning aid is used, the automatically generated settings are not changed by it.
The commissioning tool does not cover every possible application of an EL/EP device. If the available setting options are not adequate, the user can make the DC, PDO and CoE settings manually, as in the past.
EtherCAT State: automatic default behaviour of the TwinCAT System Manager and manual operation
After the operating power is switched on, an EtherCAT Slave must go through the following statuses
• INIT
• PREOP
• SAFEOP
• OP
to ensure sound operation. The EtherCAT Master directs these statuses in accordance with the initialization routines that are defined for commissioning the device by the ES/XML and user settings (Distributed Clocks (DC), PDO, CoE). See also the section on "Principles of Communication, EtherCAT State Machine" in this connection. Depending how much configuration has to be done, and on the overall communication, booting can take up to a few seconds.
The EtherCAT Master itself must go through these routines when starting, until it has reached at least the OP target state.
The target state wanted by the user, and which is brought about automatically at start-up by TwinCAT, can be set in the System Manager. As soon as TwinCAT reaches the status RUN, the TwinCAT EtherCAT Master will approach the target states.
EM700492 Version: 2.0
Standard setting
The advanced settings of the EtherCAT Master are set as standard:
• EtherCAT Master: OP
• Slaves: OP This setting applies equally to all Slaves.
Commissioning
Fig.122: Default behaviour of the System Manager
In addition, the target state of any particular Slave can be set in the "Advanced Settings" dialogue; the standard setting is again OP.
Fig.123: Default target state in the Slave
EM7004 93Version: 2.0
Commissioning
Manual Control
There are particular reasons why it may be appropriate to control the states from the application/task/PLC. For instance:
• for diagnostic reasons
• to induce a controlled restart of axes
• because a change in the times involved in starting is desirable
In that case it is appropriate in the PLC application to use the PLC function blocks from the TcEtherCAT.lib, which is available as standard, and to work through the states in a controlled manner using, for instance, FB_EcSetMasterState.
It is then useful to put the settings in the EtherCAT Master to INIT for master and slave.
Fig.124: PLC function blocks
Note regarding E-Bus current
EL/ES terminals are placed on the DIN rail at a coupler on the terminal strand. A Bus Coupler can supply the EL terminals added to it with the E-bus system voltage of 5 V; a coupler is thereby loadable up to 2 A as a rule. Information on how much current each EL terminal requires from the E-bus supply is available online and in the catalogue. If the added terminals require more current than the coupler can supply, then power feed terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.
The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager as a column value. A shortfall is marked by a negative total amount and an exclamation mark; a power feed terminal is to be placed before such a position.
EM700494 Version: 2.0
Commissioning
Fig.125: Illegally exceeding the E-Bus current
From TwinCAT 2.11 and above, a warning message "E-Bus Power of Terminal..." is output in the logger window when such a configuration is activated:
Fig.126: Warning message for exceeding E-Bus current
Caution! Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in
Attention
a terminal block!
EM7004 95Version: 2.0
Object description and parameterization

5 Object description and parameterization

EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT XML Device Description.
Note
Note
Introduction
The CoE overview contains objects for different intended applications:
Objects required for parameterization [}97] during commissioning
We recommend downloading the latest XML file from the download area of the Beckhoff website and installing it according to installation instructions.
Parameterization via the CoE list (CAN over EtherCAT)
The EtherCAT device is parameterized via the CoE - Online tab [}82] (double-click on the respective object) or via the Process Data tab [}79](allocation of PDOs). Please note the
following general CoE notes when using/manipulating the CoE parameters:
- Keep a startup list if components have to be replaced
- Differentiation between online/offline dictionary, existence of current XML description
- use “CoE reload” for resetting changes
Objects intended for regular operation [}98], e.g. through ADS access.
Objects for indicating internal settings [}98] (may be fixed)
The following section first describes the objects required for normal operation, followed by a complete overview of missing objects.
EM700496 Version: 2.0
Object description and parameterization

5.1 Objects for commissioning

Index 80n0 AO Settings Ch.1 - 4 (for 2 ≤ n ≤ 5)
Index (hex) Name Meaning Data type Flags Default
80n0:0 AO Settings Ch.1 - 4 Maximum subindex UINT8 RO 0x13 (19 80n0:01 Enable user scale FALSE
The user scaling is deactivated
TRUE The user scaling (object 0x80n0:11, 0x80n0:12) is active; the output value is then calculated as described in the
Calculation example [}14].
80n0:02 Presentation 0:
Signed Presentation: The output value is output as signed integer in the two's complement 0x7FFF = +10Volt 0x8001 = -10Volt
1: Unsigned Presentation: In the negative range, the value is output as an absolute value 0x7FFF = 10Volt 0x8001 = 10Volt
BOOLEAN RW 0x00 (0
BIT3 RW 0x00 (0
)
dec
)
dec
)
dec
2: Enable absolute value with MSB as sign: The output value is displayed in magnitude-sign format 0x7FFF = +10Volt 0xFFFF = -10Volt
80n0:05 Disable watchdog FALSE
BOOLEAN RW 0x00 (0
dec
The watchdog is active. In the event of a failure of com­munication, the analog output value will be set to either the manufacturer's or the user's default value.
TRUE The watchdog timer is deactivated. In the event of a fail-
ure of communication, the analog output value will not be set to either the manufacturer's or the user's default value.
80n0:06 Enable user default
output
FALSE The manufacturer's value (0V) will be output if the
BOOLEAN RW 0x00 (0
dec
watchdog timer triggers
TRUE
If the watchdog timer triggers, the user-specific output
value [}14] (object 0x80n0:13) will be output. 80n0:11 Offset User scaling offset compensation INT16 RW 0x0000 (0 80n0:12 Gain User scaling gain compensation:
The gain is represented in fixed-point format, with the
-16
factor 2
.
INT32 RW 0x00010000
(65536
dec
A value of 1 for the gain factor therefore corresponds to
65536
(0x00010000).
dec
80n0:13 Default output
Definition of the user-specific output value [}14] that is
INT16 RW 0x0000 (0
presented to the output if the watchdog timer for the
cyclic communication triggers.
)
)
)
dec
)
)
dec
Index 80nE AO Internal data Ch.1 - 4 (for 2 ≤ n ≤ 5)
Index (hex) Name Meaning Data type Flags Default
80nE:0 AO Internal data Ch.1
- 4
80nE:01 DAC raw value DAC raw value INT16 RO 0x0000 (0
EM7004 97Version: 2.0
Maximum subindex UINT8 RO 0x01 (1
)
dec
)
dec
Object description and parameterization
Index 80nF AO Vendor data Ch.1 - 4 (for 2 ≤ n ≤ 5)
Index (hex) Name Meaning Data type Flags Default
80nF:0 AO Vendor data Ch.1
Maximum subindex UINT8 RO 0x02 (2
- 4
80nF:01 Calibration offset Calibration offset INT16 RW 0x0800
(2048
80nF:02 Calibration gain Calibration gain INT16 RW 0x7D00
(32000
Index 8060 ENC Settings Ch.1 - 4 (for 6 ≤ n ≤ 9)
Index (hex) Name Meaning Data type Flags Default
80n0:0 ENC Settings Ch.1 - 4 Maximum subindex UINT8 RO 0x06 (6 80n0:02 Enable reset The counter is set to zero whenever a latch event occurs BOOLEAN RW 0x00 (0 80n0:03 Enable up/down
counter
80n0:04 Gate polarity 0: Gate disabled
80n0:06 Evaluation mode 0: 1-fold (single evaluation)
Enable up/down counter instead of the encoder BOOLEAN RW 0x00 (0
BIT2 RW 0x01 (1
1: Gate input responds to positive edge and locks the
counter
2: Gate input responds to negative edge and locks the
counter
BIT2 RW 0x03 (3
1: 2-fold (two-fold evaluation)
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
3: 4-fold (four-fold evaluation)
Index 80A0 PLS Settings
Index (hex) Name Meaning Data type Flags Default
80A0:0 PLS Settings Maximum subindex UINT8 RO 0x12 (18 80A0:01 Encoder as PLS
0: Channel 1 is the source for PLS functions
BIT2 RW 0x00 (0
source
1: Channel 2 is the source for PLS functions
2: Channel 3 is the source for PLS functions
3: Channel 4 is the source for PLS functions 80A0:11 Output mask Determines which of the digital outputs are assigned to
UINT16 RW 0x0000 (0 the PLS. Sample: 0x00FF, outputs 0-7 are assigned to the PLS, outputs 8-15 can be controlled freely by the PLC.
80A0:12 Default output If no valid table entry is available (counter value is >=0
UINT16 RW 0x0000 (0 but less than the first entry in the table), this value is out­put

5.2 Objects for regular operation

The EM7004 has no such objects.
)
dec
)
dec
)
dec
)
dec

5.3 Standard objects (0x1000-0x1FFF)

The standard objects have the same meaning for all EtherCAT slaves.
Index 1000 Device type
Index (hex) Name Meaning Data type Flags Default
1000:0 Device type Device type of the EtherCAT slave: The Lo-Word con-
tains the CoE profile used (5001). The Hi-Word contains the module profile according to the modular device pro­file.
UINT32 RO 0x00001389
(5001
)
dec
EM700498 Version: 2.0
Object description and parameterization
Index 1008 Device name
Index (hex) Name Meaning Data type Flags Default
1008:0 Device name Device name of the EtherCAT slave STRING RO EM7004
Index 1009 Hardware version
Index (hex) Name Meaning Data type Flags Default
1009:0 Hardware version Hardware version of the EtherCAT slave STRING RO 02
Index 100A Software version
Index (hex) Name Meaning Data type Flags Default
100A:0 Software version Firmware version of the EtherCAT slave STRING RO 01
Index 1011 Restore default parameters
Index (hex) Name Meaning Data type Flags Default
1011:0 Restore default pa-
rameters
1011:01 SubIndex 001 If this object is set to "0x64616F6C" in the set value dia-
Restore default parameters UINT8 RO 0x01 (1
UINT32 RW 0x00000000 log, all backup objects are reset to their delivery state.
(0
)
dec
)
dec
Index 1018 Identity
Index (hex) Name Meaning Data type Flags Default
1018:0 Identity Information for identifying the slave UINT8 RO 0x04 (4
)
dec
1018:01 Vendor ID Vendor ID of the EtherCAT slave UINT32 RO 0x00000002
(2
)
dec
1018:02 Product code Product code of the EtherCAT slave UINT32 RO 0x1B5C3452
(459027538 )
1018:03 Revision Revision numberof the EtherCAT slave; the low word (bit
0-15) indicates the special terminal number, the high word (bit 16-31) refers to the device description
1018:04 Serial number Serial number of the EtherCAT slave; the low byte (bit
0-7) of the low word contains the year of production, the high byte (bit 8-15) of the low word contains the week of
UINT32 RO 0x00100000
(1048576
dec
UINT32 RO 0x00000000
(0
)
dec
production, the high word (bit 16-31) is 0
Index 10F0 Backup parameter handling
Index (hex) Name Meaning Data type Flags Default
10F0:0 Backup parameter
handling
10F0:01 Checksum Checksum across all backup entries of the EtherCAT
Information for standardized loading and saving of backup entries
slave
UINT8 RO 0x01 (1
)
dec
UINT32 RO 0x00000000
(0
)
dec
dec
)
EM7004 99Version: 2.0
Object description and parameterization
Index 1601 DO RxPDO-Map
Index (hex) Name Meaning Data type Flags Default
1601:0 DO RxPDO-Map PDO Mapping RxPDO 2 UINT8 RO 0x10 (16 1601:01 SubIndex 001 1. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x01 (Output 0))
1601:02 SubIndex 002 2. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x02 (Output 1))
1601:03 SubIndex 003 3. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x03 (Output 2))
1601:04 SubIndex 004 4. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x04 (Output 3))
1601:05 SubIndex 005 5. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x05 (Output 4))
1601:06 SubIndex 006 6. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x06 (Output 5))
1601:07 SubIndex 007 7. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x07 (Output 6))
1601:08 SubIndex 008 8. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x08 (Output 7))
1601:09 SubIndex 009 9. PDO Mapping entry (object 0x7010 (DO Outputs), en-
try 0x09 (Output 8))
1601:0A SubIndex 010 10. PDO Mapping entry (object 0x7010 (DO Outputs),
entry 0x0A (Output 9))
1601:0B SubIndex 011 11. PDO Mapping entry (object 0x7010 (DO Outputs),
entry 0x0B (Output 10))
1601:0C SubIndex 012 12. PDO Mapping entry (object 0x7010 (DO Outputs),
entry 0x0C (Output 11))
1601:0D SubIndex 013 13. PDO Mapping entry (object 0x7010 (DO Outputs),
entry 0x0D (Output 12))
1601:0E SubIndex 014 14. PDO Mapping entry (1bits align) UINT32 RO 0x0000:00, 1 1601:0F SubIndex 015 15. PDO Mapping entry (object 0x7010 (DO Outputs),
entry 0x0F (Output 14))
1601:10 SubIndex 016 16. PDO Mapping entry (object 0x7010 (DO Outputs),
entry 0x10 (Output 15))
UINT32 RO 0x7010:01, 1
UINT32 RO 0x7010:02, 1
UINT32 RO 0x7010:03, 1
UINT32 RO 0x7010:04, 1
UINT32 RO 0x7010:05, 1
UINT32 RO 0x7010:06, 1
UINT32 RO 0x7010:07, 1
UINT32 RO 0x7010:08, 1
UINT32 RO 0x7010:09, 1
UINT32 RO 0x7010:0A, 1
UINT32 RO 0x7010:0B, 1
UINT32 RO 0x7010:0C, 1
UINT32 RO 0x7010:0D, 1
UINT32 RO 0x7010:0F, 1
UINT32 RO 0x7010:10, 1
dec
)
Index 1602 AO RxPDO-Map Ch.1
Index (hex) Name Meaning Data type Flags Default
1602:0 AO RxPDO-Map Ch.1 PDO Mapping RxPDO 3 UINT8 RO 0x01 (1 1602:01 SubIndex 001 1. PDO Mapping entry (object 0x7020 (AO Outputs
Ch.1), entry 0x11 (Analog output))
UINT32 RO 0x7020:11, 16
Index 1603 AO RxPDO-Map Ch.2
Index (hex) Name Meaning Data type Flags Default
1603:0 AO RxPDO-Map Ch.2 PDO Mapping RxPDO 4 UINT8 RO 0x01 (1 1603:01 SubIndex 001 1. PDO Mapping entry (object 0x7030 (AO Outputs
Ch.2), entry 0x11 (Analog output))
UINT32 RO 0x7030:11, 16
Index 1604 AO RxPDO-Map Ch.3
Index (hex) Name Meaning Data type Flags Default
1604:0 AO RxPDO-Map Ch.3 PDO Mapping RxPDO 5 UINT8 RO 0x01 (1 1604:01 SubIndex 001 1. PDO Mapping entry (object 0x7040 (AO Outputs
Ch.3), entry 0x11 (Analog output))
UINT32 RO 0x7040:11, 16
Index 1605 AO RxPDO-Map Ch.4
Index (hex) Name Meaning Data type Flags Default
1605:0 AO RxPDO-Map Ch.4 PDO Mapping RxPDO 6 UINT8 RO 0x01 (1 1605:01 SubIndex 001 1. PDO Mapping entry (object 0x7050 (AO Outputs
Ch.4), entry 0x11 (Analog output))
UINT32 RO 0x7050:11, 16
)
dec
)
dec
)
dec
)
dec
EM7004100 Version: 2.0
Loading...