Beckhoff EL5112 Users guide

Documentation | EN
EL5112
2-Channel-Incremental Encoder Interface, 5 V (2xAB or 1xABC RS422, TTL)
2021-03-11 | Version: 1.1

Table of content

Table of content
1 Foreword ....................................................................................................................................................7
1.4 Version identification of EtherCAT devices .....................................................................................10
1.4.1 Beckhoff Identification Code (BIC)................................................................................... 12
2 Product overview.....................................................................................................................................14
2.1 EL5112 - Introduction ......................................................................................................................14
2.2 EL5112 - Technical data..................................................................................................................15
2.3 Overview of functions in single-channel and two-channel mode.....................................................16
2.4 Start .................................................................................................................................................16
2.5 EL51xx series overview...................................................................................................................17
2.6 Technology ......................................................................................................................................18
2.7 Technical properties ........................................................................................................................19
2.7.1 Signal types ..................................................................................................................... 19
2.7.2 Latch and Gate/Latch inputs............................................................................................ 23
2.7.3 Status Input...................................................................................................................... 24
2.7.4 EL5112 - Encoder operating voltage (supply voltage)..................................................... 24
3 Basics communication ...........................................................................................................................25
3.1 EtherCAT basics..............................................................................................................................25
3.2 EtherCAT cabling – wire-bound.......................................................................................................25
3.3 General notes for setting the watchdog...........................................................................................26
3.4 EtherCAT State Machine.................................................................................................................28
3.5 CoE Interface...................................................................................................................................29
3.6 Distributed Clock .............................................................................................................................34
4 Mounting and wiring................................................................................................................................35
4.1 Instructions for ESD protection........................................................................................................35
4.2 Installation on mounting rails ...........................................................................................................35
4.3 Installation instructions for enhanced mechanical load capacity .....................................................39
4.4 Connection ......................................................................................................................................39
4.4.1 Connection system .......................................................................................................... 39
4.4.2 Wiring............................................................................................................................... 42
4.4.3 Shielding .......................................................................................................................... 43
4.5 Installation positions ........................................................................................................................43
4.6 Positioning of passive Terminals .....................................................................................................46
4.7 EL5112 - Connection.......................................................................................................................47
4.7.1 Single-channel mode (1 x A, B, C) .................................................................................. 49
4.7.2 Two-channel mode (2 x A, B) .......................................................................................... 55
4.8 EL5112 - LEDs ................................................................................................................................61
5 Commissioning........................................................................................................................................63
5.1 TwinCAT Quick Start .......................................................................................................................63
5.1.1 TwinCAT 2 ....................................................................................................................... 66
5.1.2 TwinCAT 3 ....................................................................................................................... 76
EL5112 3Version: 1.1
Table of content
5.2 TwinCAT Development Environment ..............................................................................................89
5.2.1 Installation of the TwinCAT real-time driver..................................................................... 90
5.2.2 Notes regarding ESI device description........................................................................... 95
5.2.3 TwinCAT ESI Updater ..................................................................................................... 99
5.2.4 Distinction between Online and Offline............................................................................ 99
5.2.5 OFFLINE configuration creation .................................................................................... 100
5.2.6 ONLINE configuration creation ...................................................................................... 105
5.2.7 EtherCAT subscriber configuration................................................................................ 113
5.2.8 NC configuration (motion).............................................................................................. 122
5.3 General Notes - EtherCAT Slave Application................................................................................126
6 EL5112 - Commissioning in single-channel mode.............................................................................134
6.1 Overview of functions ....................................................................................................................134
6.2 Process data for single-channel mode ..........................................................................................136
6.2.1 Sync Manager (SM)....................................................................................................... 136
6.2.2 PDO assignment for single-channel mode .................................................................... 137
6.2.3 Predefined PDO Assignment for single-channel mode ................................................. 143
6.2.4 Synchronicity mode ....................................................................................................... 145
6.2.5 EtherCAT cycle time ...................................................................................................... 145
6.2.6 "Legacy EL5101" mode ................................................................................................. 146
6.3 Basic functions in single-channel mode 1xABC ............................................................................147
6.3.1 Counter value ................................................................................................................ 147
6.3.2 Counter value reset ....................................................................................................... 153
6.3.3 Set counter value........................................................................................................... 154
6.3.4 Detect counting direction ............................................................................................... 156
6.3.5 Save counter value ........................................................................................................ 159
6.3.6 Lock counter value......................................................................................................... 163
6.4 Extended functionalities single-channel mode 1xABC ..................................................................164
6.4.1 Frequency measurement............................................................................................... 164
6.4.2 Period value measurement............................................................................................ 166
6.4.3 Velocity, speed calculation ............................................................................................ 167
6.4.4 Duty cycle evaluation..................................................................................................... 168
6.4.5 Micro-increments ........................................................................................................... 169
6.4.6 Timestamp function ....................................................................................................... 171
6.4.7 Adjustable interference pulse filters............................................................................... 172
6.4.8 Plausibility check ........................................................................................................... 173
6.5 Inputs in single-channel mode.......................................................................................................175
6.5.1 Zero pulse C input ......................................................................................................... 175
6.5.2 Latch input (Latch extern) .............................................................................................. 177
6.5.3 Gate/Latch input ............................................................................................................ 178
6.5.4 Input Status Input........................................................................................................... 180
7 EL5112 - Commissioning in two-channel mode .................................................................................181
7.1 Overview of functions ....................................................................................................................181
7.2 Process data for two-channel mode ..............................................................................................182
7.2.1 Sync Manager (SM)....................................................................................................... 182
7.2.2 PDO assignment in two-channel mode ......................................................................... 183
EL51124 Version: 1.1
Table of content
7.2.3 Predefined PDO Assignment for two-channel mode ..................................................... 189
7.2.4 Synchronicity mode ....................................................................................................... 191
7.2.5 EtherCAT cycle time ...................................................................................................... 191
7.2.6 "Legacy EL5101" mode ................................................................................................. 192
7.3 Basic functions in single-channel mode 2xAB...............................................................................193
7.3.1 Counter value ................................................................................................................ 193
7.3.2 Reset counter value via gate/latch combination input ................................................... 199
7.3.3 Set counter value via gate/latch combination input ....................................................... 199
7.3.4 Save counter value ........................................................................................................ 200
7.3.5 Lock counter value......................................................................................................... 202
7.4 Extended functionalities two-channel mode 2xAB.........................................................................203
7.4.1 Frequency measurement............................................................................................... 203
7.4.2 Period value measurement............................................................................................ 204
7.4.3 Velocity, speed calculation ............................................................................................ 206
7.4.4 Adjustable interference pulse filters............................................................................... 207
7.4.5 Plausibility check ........................................................................................................... 209
7.5 Inputs in two-channel mode...........................................................................................................210
7.5.1 Gate/Latch combination input ........................................................................................ 210
8 Diagnostics ............................................................................................................................................213
8.1 Diagnostics – basic principles of diag messages ..........................................................................213
8.2 EL5112 diagnostics .......................................................................................................................223
9 EL5112 - Object description and parameterization ............................................................................226
9.1 Restore object ...............................................................................................................................226
9.2 Configuration data .........................................................................................................................227
9.3 Command object ...........................................................................................................................229
9.4 Input data.......................................................................................................................................230
9.5 Output data....................................................................................................................................231
9.6 Information / diagnostic data (channel specific) ............................................................................232
9.7 Information / diagnostic data (device specific)...............................................................................232
9.8 Standard objects............................................................................................................................232
10 Appendix ................................................................................................................................................257
10.1 EtherCAT AL Status Codes...........................................................................................................257
10.2 Firmware compatibility...................................................................................................................257
10.3 Firmware Update EL/ES/EM/ELM/EPxxxx ....................................................................................257
10.3.1 Device description ESI file/XML..................................................................................... 258
10.3.2 Firmware explanation .................................................................................................... 261
10.3.3 Updating controller firmware *.efw................................................................................. 262
10.3.4 FPGA firmware *.rbf....................................................................................................... 264
10.3.5 Simultaneous updating of several EtherCAT devices.................................................... 268
10.4 Restoring the delivery state ...........................................................................................................269
10.5 Support and Service ......................................................................................................................270
EL5112 5Version: 1.1
Table of content
EL51126 Version: 1.1
Foreword

1 Foreword

1.1 Notes on the documentation

Intended audience
This description is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards. It is essential that the documentation and the following notes and explanations are followed when installing and commissioning these components. It is the duty of the technical personnel to use the documentation published at the respective time of each installation and commissioning.
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under development.
We reserve the right to revise and change the documentation at any time and without prior announcement.
No claims for the modification of products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, EtherCATG®, EtherCATG10®, EtherCATP®, SafetyoverEtherCAT®, TwinSAFE®, XFC®, XTS® and XPlanar® are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and patents: EP1590927, EP1789857, EP1456722, EP2137893, DE102015105702 with corresponding applications or registrations in various other countries.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
Copyright
© Beckhoff Automation GmbH & Co. KG, Germany. The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization are prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
EL5112 7Version: 1.1
Foreword

1.2 Safety instructions

Safety regulations
Please note the following safety instructions and explanations! Product-specific safety instructions can be found on following pages or in the areas mounting, wiring, commissioning etc.
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
Description of instructions
In this documentation the following instructions are used. These instructions must be read carefully and followed without fail!
DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.
WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.
CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.
NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.
Tip or pointer
This symbol indicates information that contributes to better understanding.
EL51128 Version: 1.1

1.3 Documentation issue status

Version Comment
1.1 • Update chapter “EL51xx series overview”
• Update chapter “EL5112 - Object description and parameterization”
1.0 • First release
0.1 • First preliminary documentation for EL5112
Foreword
EL5112 9Version: 1.1
Foreword

1.4 Version identification of EtherCAT devices

Designation
A Beckhoff EtherCAT device has a 14-digit designation, made up of
• family key
• type
• version
• revision
Example Family Type Version Revision
EL3314-0000-0016 EL terminal
(12 mm, non­pluggable connection level)
ES3602-0010-0017 ES terminal
(12 mm, pluggable connection level)
CU2008-0000-0000 CU device 2008 (8-port fast ethernet switch) 0000 (basic type) 0000
3314 (4-channel thermocouple terminal)
3602 (2-channel voltage measurement)
0000 (basic type) 0016
0010 (high­precision version)
0017
Notes
• The elements mentioned above result in the technical designation. EL3314-0000-0016 is used in the
example below.
• EL3314-0000 is the order identifier, in the case of “-0000” usually abbreviated to EL3314. “-0016” is the EtherCAT revision.
• The order identifier is made up of
- family key (EL, EP, CU, ES, KL, CX, etc.)
- type (3314)
- version (-0000)
• The revision -0016 shows the technical progress, such as the extension of features with regard to the EtherCAT communication, and is managed by Beckhoff. In principle, a device with a higher revision can replace a device with a lower revision, unless specified otherwise, e.g. in the documentation. Associated and synonymous with each revision there is usually a description (ESI, EtherCAT Slave Information) in the form of an XML file, which is available for download from the Beckhoff web site. From 2014/01 the revision is shown on the outside of the IP20 terminals, see Fig. “EL5021 EL terminal, standard IP20 IO device with batch number and revision ID (since 2014/01)”.
• The type, version and revision are read as decimal numbers, even if they are technically saved in hexadecimal.
Identification number
Beckhoff EtherCAT devices from the different lines have different kinds of identification numbers:
Production lot/batch number/serial number/date code/D number
The serial number for Beckhoff IO devices is usually the 8-digit number printed on the device or on a sticker. The serial number indicates the configuration in delivery state and therefore refers to a whole production batch, without distinguishing the individual modules of a batch.
Structure of the serial number: KKYYFFHH
KK - week of production (CW, calendar week) YY - year of production FF - firmware version HH - hardware version
EL511210 Version: 1.1
Foreword
Example with Ser. no.: 12063A02: 12 - production week 12 06 - production year 2006 3A - firmware version 3A 02 ­hardware version 02
Unique serial number/ID, ID number
In addition, in some series each individual module has its own unique serial number.
See also the further documentation in the area
• IP67: EtherCAT Box
• Safety: TwinSafe
• Terminals with factory calibration certificate and other measuring terminals
Examples of markings
Fig.1: EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since 2014/01)
Fig.2: EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number
Fig.3: EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418
EL5112 11Version: 1.1
Foreword

1.4.1 Beckhoff Identification Code (BIC)

The Beckhoff Identification Code (BIC) is increasingly being applied to Beckhoff products to uniquely identify the product. The BIC is represented as a Data Matrix Code (DMC, code scheme ECC200), the content is based on the ANSI standard MH10.8.2-2016.
Fig.4: BIC as data matrix code (DMC, code scheme ECC200)
The BIC will be introduced step by step across all product groups.
Depending on the product, it can be found in the following places:
• on the packaging unit
• directly on the product (if space suffices)
• on the packaging unit and the product
The BIC is machine-readable and contains information that can also be used by the customer for handling and product management.
Each piece of information can be uniquely identified using the so-called data identifier (ANSIMH10.8.2-2016). The data identifier is followed by a character string. Both together have a maximum length according to the table below. If the information is shorter, spaces are added to it. The data under positions 1 to 4 are always available.
The following information is contained:
EL511212 Version: 1.1
Item
Type of
no.
information
1 Beckhoff order
number
2 Beckhoff Traceability
Number (BTN)
3 Article description Beckhoff article
4 Quantity Quantity in packaging
5 Batch number Optional: Year and week
6 ID/serial number Optional: Present-day
7 Variant number Optional: Product variant
...
Explanation Data
Beckhoff order number 1P 8 1P072222
Unique serial number, see note below
description, e.g. EL1008
unit, e.g. 1, 10, etc.
of production
serial number system, e.g. with safety products or calibrated terminals
number on the basis of standard products
Foreword
Number of digits
identifier
S 12 SBTNk4p562d7
1K 32 1KEL1809
Q 6 Q1
2P 14 2P401503180016
51S 12 51S678294104
30P 32 30PF971, 2*K183
incl. data identifier
Example
Further types of information and data identifiers are used by Beckhoff and serve internal processes.
Structure of the BIC
Example of composite information from item 1 to 4 and 6. The data identifiers are marked in red for better display:
BTN
An important component of the BIC is the Beckhoff Traceability Number (BTN, item no.2). The BTN is a unique serial number consisting of eight characters that will replace all other serial number systems at Beckhoff in the long term (e.g. batch designations on IO components, previous serial number range for safety products, etc.). The BTN will also be introduced step by step, so it may happen that the BTN is not yet coded in the BIC.
NOTE
This information has been carefully prepared. However, the procedure described is constantly being further developed. We reserve the right to revise and change procedures and documentation at any time and with­out prior notice. No claims for changes can be made from the information, illustrations and descriptions in this information.
EL5112 13Version: 1.1
Product overview

2 Product overview

2.1 EL5112 - Introduction

Two-channel incremental encoder interface terminal 5V (2xAB or 1xABC RS422, TTL)
Fig.5: EL5112
The EL5112 EtherCAT Terminal is an interface for the direct connection of two incremental encoders with A and B tracks or one encoder with A, B and C tracks. Encoders with differential signals (RS422) or single­ended signals (TTL and Open Collector) can be connected and supplied with power directly from the terminal.
In 2-channel mode, both channels of the gate can be used for locking the counter and optionally as a latch for the separate storage of the counter value. Up to two latch inputs are available in single-channel mode.
The EL5112 enables the measurement of period, frequency and speed with a resolution of 10ns. In addition, duty cycle measurement of the incoming signal is implemented.
Due to the optional interpolating micro-increment function, the EL5112 can supply even more precise axis positions for dynamic axes. In addition to that it supports the synchronous reading of the encoder value together with other input data in the EtherCAT system via high-precision EtherCAT Distributed Clocks (DC). In addition, timestamps can be output for the last registered incremental edge, the edge at the latch input and the zero pulse track C.
Quick links
Basics communication [}25]
Creation of the TwinCAT configuration [}105]
EL5112 - Process data (single-channel mode [}136], two-channel mode [}182])
Configuration data [}227]
EL5112 - Object description [}226]
LEDs [}61] and connection [}47]
EL511214 Version: 1.1
Product overview

2.2 EL5112 - Technical data

Technical data EL5112
Single-channel mode Two-channel mode
Encoder type Incremental, differential (RS422), single-ended (TTL, open collector), counter, pulse gen-
Encoder connection Differential inputs (RS422): A, A, B, B, C, C
Number of channels 1 x A, B, C 2 x A, B Additional inputs Latch, Gate/Latch (24VDC, t
Encoder operating voltage 5V
Counter 32bit (default) or 16bit switchable Cut-off frequency RS422 mode: 20million increments with 4-fold evaluation, corresponds to 5MHz
Quadrature decoder 4-fold evaluation (preset), 2-fold, 1-fold evaluation switchable Micro-increments resolution 1/256bit micro-increments no Broken wire detection to encoder yes for RS422 encoder Distributed Clocks yes Timestamp Resolution 1ns no Special functions Period duration, frequency and speed mea-
Cycle time min. 100µs Current consumption via E-bus typ. 190mA Current consumption from power contacts typ.10mA+load Electrical isolation 500V (E-bus/field voltage) Configuration
Weight approx.50g Permissible ambient temperature range
during operation Permissible ambient temperature range
during storage Permissible relative air humidity 95%, no condensation Dimensions (W x H x D) approx. 15mm x100mm x 70mm (width aligned: 12mm)
Assembly [}35]
Vibration/shock resistance conforms to EN60068-2-6 / EN60068-2-27,
EMC immunity/emission conforms to EN61000-6-2/ EN61000-6-4 Protection class IP20 Installation position variable Approval CE
erator
Differential inputs (RS422): A, A, B, B
Single-ended connection (TTL, Open Collec­tor): A, B, C
Single-ended connection (TTL, Open Collec­tor): A, B
Counters, pulse generators: A, B
>1µs),
ON
Gate/Latch (24VDC, t
>1µs) per channel
ON
Status Input input (max. 5VDC, negative switching, t
DC
power contacts)
>10µs)
ON
(preset), 12VDC, 24V
switchable, 0.3A sum current (generated from the 24VDC-
DC
TTL mode: 4million increments with 4-fold evaluation, corresponds to 1MHz
Open Collector: 400,000 increments with 4-fold evaluation, corresponds to 100kHz
Period duration, frequency and speed mea-
surement,
surement Duty Cycle measurement, micro-increments, filters,
Timestamp on: last incremental edge, zero pulse C, Latch input and Gate/Latch input
via TwinCAT System Manager [}113]
0°C ... +55°C
-25°C ... +85 °C
on 35mm support rail according to EN60715
see also Installation instructions [}39] for enhanced mechanical load capacity
EL5112 15Version: 1.1
Product overview
2.3 Overview of functions in single-channel and two­channel mode
Function
Set counter value via PLC variable X X
zero pulse C X / Latch input X / Gate/Latch
combination input
Reset counter value via zero pulse C X /
Latch input X / Gate/Latch
combination input
Save counter value via zero pulse C X /
Latch input X / Gate/Latch input X / Gate/Latch
combination input
Lock counter value via PLC variable X X
Gate/Latch input X / Gate/Latch
combination input Detect counting direction X / Detect reversion of rotation X / Frequency calculation X X Period duration calculation X X Duty cycle evaluation X / Micro-increments X / Timestamp function X / Filter function X X Plausibility check X X
Single-channel mode 1 x ABC [}134]
/ X
/ X
/ X
/ X
Two-channel mode 2 x AB [}181]

2.4 Start

For commissioning:
• mount the EL5112 as described in the chapter Mounting and wiring [}35]
• configure the EL5112 in TwinCAT as described in the chapter Commissioning [}63].
• Parameterize the EL5112 as described in chapters EL5112 - Commissioning in single-channel mode [}134] and EL5112 - Commissioning in two-channel mode [}181].
EL511216 Version: 1.1

2.5 EL51xx series overview

Product overview
Technical data EL5102
2 x A, B, C
Number of channels 2 1 2 2 1 Encoder
type, incremental
Number of digital inputs per channel
Number of digital outputs per channel
Encoder operating voltage switchable between 5VDC, 12VDC, 24V
Encoder output current per channel
Cut-off frequency 20 million in-
Differential RS422 X X X / X Single-ended TTL X X X X X OpenCollector X X X X X Counter / pulse
generator
DC
X X X X X
2 2 1 1 2
/ / / / 2
X X X X X
0.3 A 0.3 A Sum current
crements,
correspond-
ing to 5 MHz
1 x A, B, C 2 x A, B
20 million in-
crements,
correspond-
ing to 5 MHz
EL5112 EL5122
2 x A, B
Sum current
0.3 A
20 million in-
crements,
correspond-
ing to 5 MHz
0.3 A
4 million in-
crements,
correspond-
ing to 1 MHz
EL5131
1 x A, B, C
0.3 A
20 million in-
crements,
correspond-
ing to 5 MHz
Functions EL5102
2 x A, B, C
Reset counter value via
Set counter value via
Save counter value via
Lock counter value via
Switching at comparison values (Counter / Frequency / Period
value) Detect counting direction X X / / X Detect reversion of rotation X X / / X Frequency measurement X X X X X Period value measurement X X X X X Velocity, speed calculation X X X X X Duty cycle evaluation X X / / X Micro-increments X X / / X Timestamp function X X / / X Adjustable interference pulse
filters Plausibility check X X X X X
zero pulse C X X / / X Latch input X X X X X
PLC variable X X X X X zero pulse C X X / / X Latch input X X X / X Gate/Latch input / / X X / zero pulse C X X / / X Latch input X X X / X Gate/Latch input X X / X X PLC variable X X X X X Gate/Latch input X X X X X
/ / / / X
X X X X X
1 x A, B, C 2 x A, B
EL5112 EL5122
2 x A, B
EL5131
1 x A, B, C
EL5112 17Version: 1.1
Product overview

2.6 Technology

The incremental encoder interface terminals of the EL51xx series enable the connection of incremental encoders to Bus Couplers or the PLC.
Incremental encoder basics
Incremental encoders divide a 360° rotation of the encoder axis into individual steps (increments) and mark a full revolution by means of a special mark (zero pulse). An RS422 encoder transmits the signal symmetrically as a differential line pair. TTL and Open Collector encoders use single signal lines (single-ended).
The terminal evaluates the 90° phase-shifted square wave signals of an incremental encoder on tracks A and B. The zero pulse is captured on track C. With a differential connection, the inverted signals (A, B, C) are also recorded.
These signals are converted by means of the quadrature decoder and the 32-bit counter into a position value with optional quadruple, double or single evaluation. The digital inputs enable latch, reset and set functionalities and thus exact and speed-independent referencing and storage of the counter value.
Encoder type Incremental signals
RS422 encoder with zero pulse A, A, B, B, C, C RS422 encoder without zero pulse A, A, B, B RS422 counter or pulse generator with zero pulse A, A, C, C;
Counting direction specification via track B (B, B)
RS422 counter or pulse generator without zero pulse A, A;
Counting direction specification via track B (B, B) TTL, Open Collector encoder with zero pulse A, B, C TTL, Open Collector encoder without zero pulse A, B TTL, Open Collector counter or pulse generator with zero pulse A, C;
Counting direction specification via B TTL, Open Collector counter or pulse generator without zero pulse A,
Counting direction specification via B
The phase position between the signals on track A and track B determines the counting direction. Forward (cw): Signal on track A leads track B by 90° Reverse (ccw): Signal on track A lags track B by 90°.
With single evaluation the rising edges on track A are counted. With double evaluation the rising and falling edges on track A are counted. With quadruple evaluation the rising and falling edges on track A and track B are counted.
Fig.6: Incremental signals
Absolute value encoders provide an absolute position value directly after switch-on, which is unambiguous over the entire travel path. With incremental encoders, homing must be performed after switch-on in order to be able to determine an unambiguous position. Referencing can be carried out, for example, with the aid of referencing cams or using the zero pulse of the encoder.
EL511218 Version: 1.1
Product overview
NOTE
Differential and single-ended connection
• The RS422 signal transmits a differential voltage, which makes the signal less sensitive to interference compared to a single-ended signal.
ð If the encoder signal is to be transmitted over longer distances or at higher frequencies, an encoder
with RS422 signals is recommended.
ð Shielded and twisted pair cables should be used.

2.7 Technical properties

The EL51xx series incremental encoder interface terminals enable connection of incremental encoders. In addition to the encoder inputs A, B and optional zero pulse C, up to two additional 24VDC inputs are available (latch and gate/latch), which can be used for resetting, setting, blocking and storing the counter value. If the incremental encoder has a fault signal output, this can be connected to the Status Input input (5VDC).
The following inputs are available with the respective technical characteristics:
• Encoder connection: differential signals according to RS422 and single-ended signals from TTL
encoders and Open Collector encoders are supported.
• Latch input and Gate/Latch input
• Status Input
The terminal also provides a parameterizable encoder supply.
• Encoder operating voltage
NOTE
Fast digital inputs – interference from interfering devices
Please note that the input wiring has very little filtering. It has been optimized for fast signal transmission from the input to the evaluation unit. In other words, rapid level changes/pulses in the µs range and/or high­frequency interference signals from devices (e.g. proportional valves, stepper motor or DC motor output stages) arrive at the evaluation unit almost unfiltered/unattenuated. These interferences can be incorrectly detected as a signal.
To suppress interference, an additional input filter can be parameterized. Furthermore, EMC-compliant ca­bling and the use of separate power supply units for the terminal and the devices causing interference are recommended.

2.7.1 Signal types

Supported encoders / signal types
Differential signals according to RS422 are provided as encoder connection. Single-ended signals from TTL encoders and also signals from Open Collector encoders are possible through internal pull-up resistors.
The following signal types are supported:
EL5112 19Version: 1.1
Product overview
Encoder Signal type Setting in
Encoder with or without zero pulse track C
Counter/pulse generator with or without zero pulse track C
Encoder with or without zero pulse track C
Counter/pulse generator with or without zero pulse track C
Encoder with or without zero pulse track C
Counter/pulse generator with or without zero pulse track C
RS422 (diff. input)
TTL (single ended)
open collector 4 400,000 increments
index 0x80n1:1D "Counter mode"
0 20 million increments
1
2 4 million increments
3
5
Cut-off frequency Comments
with 4-fold evaluation, corresponds to 5MHz per track
with 4-fold evaluation, corresponds to 1MHz per track
with 4-fold evaluation, corresponds to 100kHz per track
Signal levels according to RS422 are expected
Detection of broken wire and short circuit
A voltage level of nominally
2.0V to 6.0V with a current of 2.1mA or higher is ex­pected.
No broken wire detection No broken wire detection
The correct wiring for the respective encoder can be found in chapter Connection.
Signal type RS422 (diff. input)
The terminal expects the differential signal levels according to RS422 with the following settings in "Counter mode" (0x80n1:1D):
• 0: Encoder RS422 (diff. input)
• 1: Counter RS422 (diff. input)
A cut-off frequency of up to 20million increments per second is permissible with 4-fold evaluation. This corresponds to 5MHz.
Fig.7: RS422 signal level
Key:
V
CM
V
ID
V
IDLow
A, B, C Signals A, B, C A, B, C
Common mode voltage range Differential voltage Differential voltage too low
Inverted signals A, B, C
NOTE
Exceeding of Common Mode range
Exceeding the Common Mode voltage range can lead to destruction of the device.
EL511220 Version: 1.1
Product overview
RS422 - broken wire and short-circuit detection (open circuit)
In the RS422 (differential input) modes it is possible to detect a broken wire or short circuit at the individual encoder inputs.
• In case of a broken wire, e.g. between input A and input A,
◦ the differential voltage VID is almost 0V, ◦ which leads to an error with low differential voltage.
• In case of a short circuit, e.g. between input A and input A, the error behavior is similar to a broken wire
and also leads to error detection.
Activation of error detection for each channel Index (hex) Name Description
80n0:0B Error detection A TRUE Broken wire and short circuit detection for encoder input A enabled
FALSE Broken wire and short circuit detection for encoder input A disabled
80n0:0C Error detection B TRUE Broken wire and short circuit detection for encoder input B enabled
FALSE Broken wire and short circuit detection for encoder input B disabled
80n0:0D Error detection C TRUE Broken wire and short circuit detection for encoder input C enabled
FALSE Broken wire and short circuit detection for encoder input C disabled
Error detection using the example of a broken wire or short circuit between inputs A and A. Error diagnosis Display Description
LED A1 Green A TRUE level is present
Red An error (open circuit) was detected
0x60n07 "Open circuit" TRUE Group error message for "Open circuit"
FALSE There is no "open circuit" error.
0xA0n0:01 "Error A" TRUE An "open circuit" error (broken wire or short circuit) has occurred at encoder input A.
FALSE There is no "open circuit" error.
A broken wire or short circuit has occurred at one of the encoder inputs
NOTE
Differential and single-ended connection
• The RS422 signal transmits a differential voltage, which makes the signal less sensitive to interference compared to a single-ended signal.
ð If the encoder signal is to be transmitted over longer distances or at higher frequencies, an encoder
with RS422 signals is recommended.
ð Shielded and twisted pair cables should be used.
EL5112 21Version: 1.1
Product overview
Signal type TTL (single-ended) and Open Collector
With the following settings in "Counter mode" (0x80n1:1D), a voltage level of nominally 2.0V to 6.0V with a current of 2.1mA or higher is expected:
• 2: Encoder TTL (single-ended)
• 3: Counter TTL (single-ended)
• 4: Encoder open collector
• 5: Counter open collector
For TTL encoders a cut-off frequency of up to 4 million increments per second is permissible with 4-fold evaluation. This corresponds to 1MHz.
For Open Collector encoders, a cut-off frequency of up to 400,000 increments per second is permissible with 4-fold evaluation. This corresponds to 100kHz.
Fig.8: TTL, Open Collector signal level (single-ended signal)
Key:
V
IN
A, B, C Encoder signals A, B, C
Single-ended input voltage
NOTE
Open circuit detection
Open circuit detection inherently does not work with single-ended lines: TTL and Open Collector encoders and counters/pulse generators.
NOTE
Open Collector wiring
When selecting an Open Collector encoder under "Counter mode" (0x80n1:1D), the inputs A, B, C are con­nected to 5V via pull-up resistors (1kΩ).
EL511222 Version: 1.1
Product overview

2.7.2 Latch and Gate/Latch inputs

The terminal provides two digital 24VDC inputs. The function of these inputs is described in the respective chapter.
Latch input [}177] (Latch extern)
Gate/latch input [}178] (Latch extern 2)
Both inputs are type 3 inputs according to EN61131-2, with a minimum pulse duration of tON>1µs.
Digital input type 3, according to EN61131-2
Signal voltage "0 - LOW" -3V ... +5V typ. 0mA ... 2.6mA typ. Signal voltage "1 - HIGH" 11V ... 30V typ. typ. 2.5mA
Fig.9: Characteristic 24VDC Input type 3
Voltage [V] Input current [mA]
NOTE
Be aware of bouncing when using electromechanical switches and push buttons
When using electromechanical switches and push buttons, repeated closing and opening of the switch or push button can occur when the switch or push button is actuated, which is referred to as bouncing.
• If the function 0x80n0:22 "Enable continuous latch extern" or 0x80n0:23 "Enable continuous latch extern 2" is active, the stored value is overwritten several times due to the bouncing. As a result, parameter 0x60n0: 12 "Latch value" or 0x60n0: 22 "Latch value 2" contains the value that was saved last, not the value that was saved first.
• If the function is deactivated, only the first opening or closing of the switch or push button is detected and saved as a value in the corresponding parameter. No other transactions are taken into account.
EL5112 23Version: 1.1
Product overview

2.7.3 Status Input

The terminal provides a Status Input. The function is described in chapter Status Input. [}180]
The input is 5V compatible.
Digital input, 5V TTL input characteristic
Signal voltage "0 - LOW" -6V … + 0.8V typ. 5mA Signal voltage "1 - HIGH" +2V … +6V typ. 0mA
Voltage [V] Input current [mA]
NOTE
Wiring of the Status Input
In the terminal the Status Input is internally connected to 5V via a pull-up resistor (1kΩ). The encoder out­put must actively pull the signal against GND. The resistance must be dimensioned so that it is less than 120Ω.
External power supply is not recommended. If an external supply is used, the maximum permitted voltage is 5V against GND.

2.7.4 EL5112 - Encoder operating voltage (supply voltage)

The encoder supply is generated internally from the 24V of the power contacts. The encoder supply can be set in index 0x8001 [}228]:17 "Supply voltage". An operating voltage of 5VDC is preset. Voltage values of
5VDC, 12VDC and 24VDC can be selected. The setting applies to both channels. Before switching to higher voltages, ensure that both encoders support the voltage range.
The following tolerances apply
Voltage range Tolerance
5V 12V 24V
DC
DC
DC
+/- 5% (4.75V … 5.25V) +/- 10% (10.8V … 13.2V)
-15% to +20% (20.4V … 28.8V)
Setting the encoder supply via index 0x8001:17 [}228]
The encoder supply is set centrally for both terminal channels via the index 0x8001:17 [}228] (chan­nel 1). The corresponding index 0x8011:17 of the second channel has no parameterization function.
NOTE
Setting the encoder supply voltage
• Before switching to a higher voltage, make sure that the connected encoders support the selected volt­age range!
• To write to 0x80n1:17 "Supply voltage" you have to set the value 0x72657375 (ASCII: "user") in index 0xF008 [}256] "Code word".
EL511224 Version: 1.1
Basics communication

3 Basics communication

3.1 EtherCAT basics

Please refer to the EtherCAT System Documentation for the EtherCAT fieldbus basics.

3.2 EtherCAT cabling – wire-bound

The cable length between two EtherCAT devices must not exceed 100 m. This results from the FastEthernet technology, which, above all for reasons of signal attenuation over the length of the cable, allows a maximum
link length of 5 + 90 + 5 m if cables with appropriate properties are used. See also the Design recommendations for the infrastructure for EtherCAT/Ethernet.
Cables and connectors
For connecting EtherCAT devices only Ethernet connections (cables + plugs) that meet the requirements of at least category 5 (CAt5) according to EN 50173 or ISO/IEC 11801 should be used. EtherCAT uses 4 wires for signal transfer.
EtherCAT uses RJ45 plug connectors, for example. The pin assignment is compatible with the Ethernet standard (ISO/IEC 8802-3).
Pin Color of conductor Signal Description
1 yellow TD + Transmission Data + 2 orange TD - Transmission Data ­3 white RD + Receiver Data + 6 blue RD - Receiver Data -
Due to automatic cable detection (auto-crossing) symmetric (1:1) or cross-over cables can be used between EtherCAT devices from Beckhoff.
Recommended cables
It is recommended to use the appropriate Beckhoff components e.g.
- cable sets ZK1090-9191-xxxx respectively
- RJ45 connector, field assembly ZS1090-0005
- EtherCAT cable, field assembly ZB9010, ZB9020
Suitable cables for the connection of EtherCAT devices can be found on the Beckhoff website!
E-Bus supply
A bus coupler can supply the EL terminals added to it with the E-bus system voltage of 5V; a coupler is thereby loadable up to 2A as a rule (see details in respective device documentation). Information on how much current each EL terminal requires from the E-bus supply is available online and in the catalogue. If the added terminals require more current than the coupler can supply, then power feed
terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.
The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager. A shortfall is marked by a negative total amount and an exclamation mark; a power feed terminal is to be placed before such a position.
EL5112 25Version: 1.1
Basics communication
Fig.10: System manager current calculation
NOTE
Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!

3.3 General notes for setting the watchdog

ELxxxx terminals are equipped with a safety feature (watchdog) that switches off the outputs after a specifiable time e.g. in the event of an interruption of the process data traffic, depending on the device and settings, e.g. in OFF state.
The EtherCAT slave controller (ESC) in the EL2xxx terminals features two watchdogs:
• SM watchdog (default: 100 ms)
• PDI watchdog (default: 100 ms)
SM watchdog (SyncManager Watchdog)
The SyncManager watchdog is reset after each successful EtherCAT process data communication with the terminal. If no EtherCAT process data communication takes place with the terminal for longer than the set and activated SM watchdog time, e.g. in the event of a line interruption, the watchdog is triggered and the outputs are set to FALSE. The OP state of the terminal is unaffected. The watchdog is only reset after a successful EtherCAT process data access. Set the monitoring time as described below.
The SyncManager watchdog monitors correct and timely process data communication with the ESC from the EtherCAT side.
PDI watchdog (Process Data Watchdog)
If no PDI communication with the EtherCAT slave controller (ESC) takes place for longer than the set and activated PDI watchdog time, this watchdog is triggered. PDI (Process Data Interface) is the internal interface between the ESC and local processors in the EtherCAT slave, for example. The PDI watchdog can be used to monitor this communication for failure.
The PDI watchdog monitors correct and timely process data communication with the ESC from the application side.
The settings of the SM- and PDI-watchdog must be done for each slave separately in the TwinCAT System Manager.
EL511226 Version: 1.1
Basics communication
Fig.11: EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog
Notes:
• the multiplier is valid for both watchdogs.
• each watchdog has its own timer setting, the outcome of this in summary with the multiplier is a
resulting time.
• Important: the multiplier/timer setting is only loaded into the slave at the start up, if the checkbox is
activated. If the checkbox is not activated, nothing is downloaded and the ESC settings remain unchanged.
Multiplier
Both watchdogs receive their pulses from the local terminal cycle, divided by the watchdog multiplier:
1/25 MHz * (watchdog multiplier + 2) = 100µs (for default setting of 2498 for the multiplier)
The standard setting of 1000 for the SM watchdog corresponds to a release time of 100ms.
The value in multiplier + 2 corresponds to the number of basic 40 ns ticks representing a watchdog tick. The multiplier can be modified in order to adjust the watchdog time over a larger range.
Example “Set SM watchdog”
This checkbox enables manual setting of the watchdog times. If the outputs are set and the EtherCAT communication is interrupted, the SM watchdog is triggered after the set time and the outputs are erased. This setting can be used for adapting a terminal to a slower EtherCAT master or long cycle times. The default SM watchdog setting is 100ms. The setting range is 0...65535. Together with a multiplier with a range of 1...65535 this covers a watchdog period between 0...~170 seconds.
EL5112 27Version: 1.1
Basics communication
Calculation
Multiplier = 2498 → watchdog base time = 1 / 25MHz * (2498 + 2) = 0.0001seconds = 100µs SM watchdog = 10000 → 10000 * 100µs = 1second watchdog monitoring time
CAUTION
Undefined state possible!
The function for switching off of the SM watchdog via SM watchdog = 0 is only implemented in terminals from version -0016. In previous versions this operating mode should not be used.
CAUTION
Damage of devices and undefined state possible!
If the SM watchdog is activated and a value of 0 is entered the watchdog switches off completely. This is the deactivation of the watchdog! Set outputs are NOT set in a safe state, if the communication is inter­rupted.

3.4 EtherCAT State Machine

The state of the EtherCAT slave is controlled via the EtherCAT State Machine (ESM). Depending upon the state, different functions are accessible or executable in the EtherCAT slave. Specific commands must be sent by the EtherCAT master to the device in each state, particularly during the bootup of the slave.
A distinction is made between the following states:
• Init
• Pre-Operational
• Safe-Operational and
• Operational
• Boot
The regular state of each EtherCAT slave after bootup is the OP state.
Fig.12: States of the EtherCAT State Machine
EL511228 Version: 1.1
Basics communication
Init
After switch-on the EtherCAT slave in the Init state. No mailbox or process data communication is possible. The EtherCAT master initializes sync manager channels 0 and 1 for mailbox communication.
Pre-Operational (Pre-Op)
During the transition between Init and Pre-Op the EtherCAT slave checks whether the mailbox was initialized correctly.
In Pre-Op state mailbox communication is possible, but not process data communication. The EtherCAT master initializes the sync manager channels for process data (from sync manager channel 2), the FMMU channels and, if the slave supports configurable mapping, PDO mapping or the sync manager PDO assignment. In this state the settings for the process data transfer and perhaps terminal-specific parameters that may differ from the default settings are also transferred.
Safe-Operational (Safe-Op)
During transition between Pre-Op and Safe-Op the EtherCAT slave checks whether the sync manager channels for process data communication and, if required, the distributed clocks settings are correct. Before it acknowledges the change of state, the EtherCAT slave copies current input data into the associated DP­RAM areas of the EtherCAT slave controller (ECSC).
In Safe-Op state mailbox and process data communication is possible, although the slave keeps its outputs in a safe state, while the input data are updated cyclically.
Outputs in SAFEOP state
The default set watchdog [}26] monitoring sets the outputs of the module in a safe state - depend­ing on the settings in SAFEOP and OP - e.g. in OFF state. If this is prevented by deactivation of the watchdog monitoring in the module, the outputs can be switched or set also in the SAFEOP state.
Operational (Op)
Before the EtherCAT master switches the EtherCAT slave from Safe-Op to Op it must transfer valid output data.
In the Op state the slave copies the output data of the masters to its outputs. Process data and mailbox communication is possible.
Boot
In the Boot state the slave firmware can be updated. The Boot state can only be reached via the Init state.
In the Boot state mailbox communication via the file access over EtherCAT (FoE) protocol is possible, but no other mailbox communication and no process data communication.

3.5 CoE Interface

General description
The CoE interface (CAN application protocol over EtherCAT)) is used for parameter management of EtherCAT devices. EtherCAT slaves or the EtherCAT master manage fixed (read only) or variable parameters which they require for operation, diagnostics or commissioning.
CoE parameters are arranged in a table hierarchy. In principle, the user has read access via the fieldbus. The EtherCAT master (TwinCAT System Manager) can access the local CoE lists of the slaves via EtherCAT in read or write mode, depending on the attributes.
EL5112 29Version: 1.1
Basics communication
Different CoE parameter types are possible, including string (text), integer numbers, Boolean values or larger byte fields. They can be used to describe a wide range of features. Examples of such parameters include manufacturer ID, serial number, process data settings, device name, calibration values for analog measurement or passwords.
The order is specified in two levels via hexadecimal numbering: (main)index, followed by subindex. The value ranges are
• Index: 0x0000 …0xFFFF (0...65535
• SubIndex: 0x00…0xFF (0...255
dez
)
dez
)
A parameter localized in this way is normally written as 0x8010:07, with preceding “0x” to identify the hexadecimal numerical range and a colon between index and subindex.
The relevant ranges for EtherCAT fieldbus users are:
• 0x1000: This is where fixed identity information for the device is stored, including name, manufacturer,
serial number etc., plus information about the current and available process data configurations.
• 0x8000: This is where the operational and functional parameters for all channels are stored, such as
filter settings or output frequency.
Other important ranges are:
• 0x4000: here are the channel parameters for some EtherCAT devices. Historically, this was the first
parameter area before the 0x8000 area was introduced. EtherCAT devices that were previously equipped with parameters in 0x4000 and changed to 0x8000 support both ranges for compatibility reasons and mirror internally.
• 0x6000: Input PDOs (“input” from the perspective of the EtherCAT master)
• 0x7000: Output PDOs (“output” from the perspective of the EtherCAT master)
Availability
Not every EtherCAT device must have a CoE list. Simple I/O modules without dedicated processor usually have no variable parameters and therefore no CoE list.
If a device has a CoE list, it is shown in the TwinCAT System Manager as a separate tab with a listing of the elements:
Fig.13: “CoE Online” tab
EL511230 Version: 1.1
Basics communication
The figure above shows the CoE objects available in device “EL2502”, ranging from 0x1000 to 0x1600. The subindices for 0x1018 are expanded.
Data management and function “NoCoeStorage”
Some parameters, particularly the setting parameters of the slave, are configurable and writeable. This can be done in write or read mode
• via the System Manager (Fig. “CoE Online” tab) by clicking
This is useful for commissioning of the system/slaves. Click on the row of the index to be parameterized and enter a value in the “SetValue” dialog.
• from the control system/PLC via ADS, e.g. through blocks from the TcEtherCAT.lib library
This is recommended for modifications while the system is running or if no System Manager or operating staff are available.
Data management
If slave CoE parameters are modified online, Beckhoff devices store any changes in a fail-safe manner in the EEPROM, i.e. the modified CoE parameters are still available after a restart. The situation may be different with other manufacturers.
An EEPROM is subject to a limited lifetime with respect to write operations. From typically 100,000 write operations onwards it can no longer be guaranteed that new (changed) data are reliably saved or are still readable. This is irrelevant for normal commissioning. However, if CoE parameters are continuously changed via ADS at machine runtime, it is quite possible for the lifetime limit to be reached. Support for the NoCoeStorage function, which suppresses the saving of changed CoE val­ues, depends on the firmware version. Please refer to the technical data in this documentation as to whether this applies to the respective device.
• If the function is supported: the function is activated by entering the code word 0x12345678 once in CoE 0xF008 and remains active as long as the code word is not changed. After switching the device on it is then inactive. Changed CoE values are not saved in the EEPROM and can thus be changed any number of times.
• Function is not supported: continuous changing of CoE values is not permissible in view of the lifetime limit.
Startup list
Changes in the local CoE list of the terminal are lost if the terminal is replaced. If a terminal is re­placed with a new Beckhoff terminal, it will have the default settings. It is therefore advisable to link all changes in the CoE list of an EtherCAT slave with the Startup list of the slave, which is pro­cessed whenever the EtherCAT fieldbus is started. In this way a replacement EtherCAT slave can automatically be parameterized with the specifications of the user.
If EtherCAT slaves are used which are unable to store local CoE values permanently, the Startup list must be used.
Recommended approach for manual modification of CoE parameters
• Make the required change in the System Manager The values are stored locally in the EtherCAT slave
• If the value is to be stored permanently, enter it in the Startup list. The order of the Startup entries is usually irrelevant.
EL5112 31Version: 1.1
Basics communication
Fig.14: Startup list in the TwinCAT System Manager
The Startup list may already contain values that were configured by the System Manager based on the ESI specifications. Additional application-specific entries can be created.
Online/offline list
While working with the TwinCAT System Manager, a distinction has to be made whether the EtherCAT device is “available”, i.e. switched on and linked via EtherCAT and therefore online, or whether a configuration is created offline without connected slaves.
In both cases a CoE list as shown in Fig. “CoE online tab” is displayed. The connectivity is shown as offline/ online.
• If the slave is offline
◦ The offline list from the ESI file is displayed. In this case modifications are not meaningful or
possible. ◦ The configured status is shown under Identity. ◦ No firmware or hardware version is displayed, since these are features of the physical device. ◦ Offline is shown in red.
Fig.15: Offline list
EL511232 Version: 1.1
Basics communication
• If the slave is online ◦ The actual current slave list is read. This may take several seconds, depending on the size and
cycle time. ◦ The actual identity is displayed ◦ The firmware and hardware version of the equipment according to the electronic information is
displayed ◦ Online is shown in green.
Fig.16: Online list
Channel-based order
The CoE list is available in EtherCAT devices that usually feature several functionally equivalent channels. For example, a 4-channel analog 0...10V input terminal also has four logical channels and therefore four identical sets of parameter data for the channels. In order to avoid having to list each channel in the documentation, the placeholder “n” tends to be used for the individual channel numbers.
In the CoE system 16 indices, each with 255 subindices, are generally sufficient for representing all channel parameters. The channel-based order is therefore arranged in 16
dec
/10
steps. The parameter range
hex
0x8000 exemplifies this:
• Channel 0: parameter range 0x8000:00 ... 0x800F:255
• Channel 1: parameter range 0x8010:00 ... 0x801F:255
• Channel 2: parameter range 0x8020:00 ... 0x802F:255
• ...
This is generally written as 0x80n0.
Detailed information on the CoE interface can be found in the EtherCAT system documentation on the Beckhoff website.
EL5112 33Version: 1.1
Basics communication

3.6 Distributed Clock

The distributed clock represents a local clock in the EtherCAT slave controller (ESC) with the following characteristics:
• Unit 1 ns
• Zero point 1.1.2000 00:00
• Size 64 bit (sufficient for the next 584 years; however, some EtherCAT slaves only offer 32-bit support, i.e. the variable overflows after approx. 4.2 seconds)
• The EtherCAT master automatically synchronizes the local clock with the master clock in the EtherCAT bus with a precision of < 100 ns.
For detailed information please refer to the EtherCAT system description.
EL511234 Version: 1.1
Mounting and wiring

4 Mounting and wiring

4.1 Instructions for ESD protection

NOTE
Destruction of the devices by electrostatic discharge possible!
The devices contain components at risk from electrostatic discharge caused by improper handling.
• Please ensure you are electrostatically discharged and avoid touching the contacts of the device directly.
• Avoid contact with highly insulating materials (synthetic fibers, plastic film etc.).
• Surroundings (working place, packaging and personnel) should by grounded probably, when handling with the devices.
• Each assembly must be terminated at the right hand end with an EL9011 or EL9012 bus end cap, to en­sure the protection class and ESD protection.
Fig.17: Spring contacts of the Beckhoff I/O components

4.2 Installation on mounting rails

WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the bus terminals!
EL5112 35Version: 1.1
Mounting and wiring
Assembly
Fig.18: Attaching on mounting rail
The bus coupler and bus terminals are attached to commercially available 35mm mounting rails (DIN rails according to EN60715) by applying slight pressure:
1. First attach the fieldbus coupler to the mounting rail.
2. The bus terminals are now attached on the right-hand side of the fieldbus coupler. Join the compo­nents with tongue and groove and push the terminals against the mounting rail, until the lock clicks onto the mounting rail. If the terminals are clipped onto the mounting rail first and then pushed together without tongue and groove, the connection will not be operational! When correctly assembled, no significant gap should be visible between the housings.
Fixing of mounting rails
The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At the installation, the locking mechanism of the components must not come into conflict with the fixing bolts of the mounting rail. To mount the mounting rails with a height of 7.5mm under the terminals and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).
EL511236 Version: 1.1
Mounting and wiring
Disassembly
Fig.19: Disassembling of terminal
Each terminal is secured by a lock on the mounting rail, which must be released for disassembly:
1. Pull the terminal by its orange-colored lugs approximately 1cm away from the mounting rail. In doing so for this terminal the mounting rail lock is released automatically and you can pull the terminal out of the bus terminal block easily without excessive force.
2. Grasp the released terminal with thumb and index finger simultaneous at the upper and lower grooved housing surfaces and pull the terminal out of the bus terminal block.
Connections within a bus terminal block
The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by joining the components:
• The six spring contacts of the K-Bus/E-Bus deal with the transfer of the data and the supply of the Bus Terminal electronics.
• The power contacts deal with the supply for the field electronics and thus represent a supply rail within the bus terminal block. The power contacts are supplied via terminals on the Bus Coupler (up to 24V) or for higher voltages via power feed terminals.
Power Contacts
During the design of a bus terminal block, the pin assignment of the individual Bus Terminals must be taken account of, since some types (e.g. analog Bus Terminals or digital 4-channel Bus Termi­nals) do not or not fully loop through the power contacts. Power Feed Terminals (KL91xx, KL92xx or EL91xx, EL92xx) interrupt the power contacts and thus represent the start of a new supply rail.
PE power contact
The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first when plugging together, and can ground short-circuit currents of up to 125A.
EL5112 37Version: 1.1
Mounting and wiring
Fig.20: Power contact on left side
NOTE
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g. disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230V). For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In or­der to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at least 10mm from the group of terminals.
WARNING
Risk of electric shock!
The PE power contact must not be used for other potentials!
EL511238 Version: 1.1
Mounting and wiring

4.3 Installation instructions for enhanced mechanical load capacity

WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, de-energized state before starting mounting, disassembly or wiring of the Bus Terminals!
Additional checks
The terminals have undergone the following additional tests:
Verification Explanation
Vibration 10 frequency runs in 3 axes
6 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude
60.1Hz<f<500Hz acceleration 5g, constant amplitude
Shocks 1000 shocks in each direction, in 3 axes
25 g, 6 ms
Additional installation instructions
For terminals with enhanced mechanical load capacity, the following additional installation instructions apply:
• The enhanced mechanical load capacity is valid for all permissible installation positions
• Use a mounting rail according to EN 60715 TH35-15
• Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth terminal or reinforced end clamp
• The maximum total extension of the terminal segment (without coupler) is: 64 terminals (12mm mounting with) or 32 terminals (24mm mounting with)
• Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of the rail
• The mounting points of the mounting rail must be set at 5 cm intervals
• Use countersunk head screws to fasten the mounting rail
• The free length between the strain relief and the wire connection should be kept as short as possible. A distance of approx. 10cm should be maintained to the cable duct.

4.4 Connection

4.4.1 Connection system

WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the bus terminals!
Overview
The bus terminal system offers different connection options for optimum adaptation to the respective application:
• The terminals of ELxxxx and KLxxxx series with standard wiring include electronics and connection level in a single enclosure.
EL5112 39Version: 1.1
Mounting and wiring
• The terminals of ESxxxx and KSxxxx series feature a pluggable connection level and enable steady wiring while replacing.
• The High Density Terminals (HD Terminals) include electronics and connection level in a single enclosure and have advanced packaging density.
Standard wiring (ELxxxx / KLxxxx)
Fig.21: Standard wiring
The terminals of ELxxxx and KLxxxx series have been tried and tested for years. They feature integrated screwless spring force technology for fast and simple assembly.
Pluggable wiring (ESxxxx / KSxxxx)
Fig.22: Pluggable wiring
The terminals of ESxxxx and KSxxxx series feature a pluggable connection level. The assembly and wiring procedure is the same as for the ELxxxx and KLxxxx series. The pluggable connection level enables the complete wiring to be removed as a plug connector from the top of the housing for servicing. The lower section can be removed from the terminal block by pulling the unlocking tab. Insert the new component and plug in the connector with the wiring. This reduces the installation time and eliminates the risk of wires being mixed up.
The familiar dimensions of the terminal only had to be changed slightly. The new connector adds about 3 mm. The maximum height of the terminal remains unchanged.
A tab for strain relief of the cable simplifies assembly in many applications and prevents tangling of individual connection wires when the connector is removed.
Conductor cross sections between 0.08mm2 and 2.5mm2 can continue to be used with the proven spring force technology.
The overview and nomenclature of the product names for ESxxxx and KSxxxx series has been retained as known from ELxxxx and KLxxxx series.
EL511240 Version: 1.1
Mounting and wiring
High Density Terminals (HD Terminals)
Fig.23: High Density Terminals
The terminals from these series with 16 terminal points are distinguished by a particularly compact design, as the packaging density is twice as large as that of the standard 12mm bus terminals. Massive conductors and conductors with a wire end sleeve can be inserted directly into the spring loaded terminal point without tools.
Wiring HD Terminals
The High Density Terminals of the ELx8xx and KLx8xx series doesn't support pluggable wiring.
Ultrasonically “bonded” (ultrasonically welded) conductors
Ultrasonically “bonded” conductors
It is also possible to connect the Standard and High Density Terminals with ultrasonically “bonded” (ultrasonically welded) conductors. In this case, please note the tables concerning the wire-size width!
EL5112 41Version: 1.1
Mounting and wiring

4.4.2 Wiring

WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or wiring of the bus terminals!
Terminals for standard wiring ELxxxx/KLxxxx and for pluggable wiring ESxxxx/KSxxxx
Fig.24: Connecting a cable on a terminal point
Up to eight terminal points enable the connection of solid or finely stranded cables to the bus terminal. The terminal points are implemented in spring force technology. Connect the cables as follows:
1. Open a terminal point by pushing a screwdriver straight against the stop into the square opening above the terminal point. Do not turn the screwdriver or move it alternately (don't toggle).
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal point closes automatically when the pressure is released, holding the wire securely and permanently.
See the following table for the suitable wire size width.
Terminal housing ELxxxx, KLxxxx ESxxxx, KSxxxx Wire size width (single core wires) 0.08 ... 2.5mm Wire size width (fine-wire conductors) 0.08 ... 2.5mm Wire size width (conductors with a wire end sleeve) 0.14 ... 1.5mm
2
2
2
0.08 ... 2.5mm 0,08 ... 2.5mm
0.14 ... 1.5mm
2
2
2
Wire stripping length 8 ... 9mm 9 ... 10mm
High Density Terminals (HD Terminals [}41]) with 16 terminal points
The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct plug-in technique, i.e. after stripping the wire is simply plugged into the terminal point. The cables are released, as usual, using the contact release with the aid of a screwdriver. See the following table for the suitable wire size width.
EL511242 Version: 1.1
Mounting and wiring
Terminal housing High Density Housing Wire size width (single core wires) 0.08 ... 1.5mm Wire size width (fine-wire conductors) 0.25 ... 1.5mm Wire size width (conductors with a wire end sleeve) 0.14 ... 0.75mm Wire size width (ultrasonically “bonded" conductors) only 1.5mm
2
2
2
2
Wire stripping length 8 ... 9mm

4.4.3 Shielding

Shielding
Encoder, analog sensors and actors should always be connected with shielded, twisted paired wires.

4.5 Installation positions

NOTE
Constraints regarding installation position and operating temperature range
Please refer to the technical data for a terminal to ascertain whether any restrictions regarding the installa­tion position and/or the operating temperature range have been specified. When installing high power dissi­pation terminals ensure that an adequate spacing is maintained between other components above and be­low the terminal in order to guarantee adequate ventilation!
Optimum installation position (standard)
The optimum installation position requires the mounting rail to be installed horizontally and the connection surfaces of the EL/KL terminals to face forward (see Fig. Recommended distances for standard installation position). The terminals are ventilated from below, which enables optimum cooling of the electronics through convection. “From below” is relative to the acceleration of gravity.
EL5112 43Version: 1.1
Mounting and wiring
Fig.25: Recommended distances for standard installation position
Compliance with the distances shown in Fig. Recommended distances for standard installation position is recommended.
Other installation positions
All other installation positions are characterized by different spatial arrangement of the mounting rail - see Fig Other installation positions.
The minimum distances to ambient specified above also apply to these installation positions.
EL511244 Version: 1.1
Fig.26: Other installation positions
Mounting and wiring
EL5112 45Version: 1.1
Mounting and wiring

4.6 Positioning of passive Terminals

Hint for positioning of passive terminals in the bus terminal block
EtherCAT Terminals (ELxxxx / ESxxxx), which do not take an active part in data transfer within the bus terminal block are so called passive terminals. The passive terminals have no current consump­tion out of the E-Bus. To ensure an optimal data transfer, you must not directly string together more than two passive ter­minals!
Examples for positioning of passive terminals (highlighted)
Fig.27: Correct positioning
Fig.28: Incorrect positioning
EL511246 Version: 1.1

4.7 EL5112 - Connection

Mounting and wiring
Fig.29: EL5112 - Connection
Terminal point No. Comment
Single-channel mode 1xABC Two-channel mode 2xAB
A1 1 Encoder input A1 Encoder input A1 B1 2 Encoder input B1 Encoder input B1 C1 / A2 3 Encoder input C1 Encoder input A2 Status input / B2 4 Status input
The Status Input input is internally connected to 5V via a pull-up resistor. The encoder fault signal output must actively pull the signal against GND. External power supply is not recommended. If an ex­ternal supply is used, the maximum permitted voltage is 5V against GND.
+ Ue 5 Encoder supply (5V default, parameterizable 12V,
24V)
-Uo 6 0Vencoder supply 0Vencoder supply Latch 7 Latch extern input Gate/Latch combination input for encoder 1 n.c. 8 Do not connect the terminal point Do not connect the terminal point A1 9 Encoder input A1 (Encoder 1) Encoder input A1 (Encoder 1) B1 10 Encoder input B1 (Encoder 1) Encoder input B1 (Encoder 1) C1 / A2 11 Encoder input C1 (Encoder 1) Encoder input A2 (Encoder 2) B2 12 Do not connect the terminal point Encoder input B2 (Encoder 2) + Ue 13 Encoder supply (5V default, parameterizable 12V,
24V)
-Uo 14 0Vencoder supply 0Vencoder supply Gate 15 Input gate, can also be used as external latch 2 input
for encoder 1
n.c. 16 Do not connect the terminal point Do not connect the terminal point
Encoder input B2
Encoder supply (5V default, parameterizable 12V, 24V)
Encoder supply (5V default, parameterizable 12V, 24V)
Gate/Latch combination input for encoder 2
Setting the encoder supply via index 0x8001:17 [}228]
The encoder supply is set centrally for both terminal channels via the index 0x8001:17 [}228] (chan­nel 1). The corresponding index 0x8011:17 of the second channel has no parameterization function.
EL5112 47Version: 1.1
Mounting and wiring
NOTE
Setting the encoder supply voltage
• Before switching to a higher voltage, make sure that the connected encoders support the selected volt­age range!
• To write to 0x80n1:17 "Supply voltage" you have to set the value 0x72657375 (ASCII: "user") in index 0xF008 [}256] "Code word".
EL511248 Version: 1.1
Mounting and wiring

4.7.1 Single-channel mode (1 x A, B, C)

4.7.1.1 RS422 mode
NOTE
Differential and single-ended connection
The RS422 signal transmits a differential voltage, which makes the signal less sensitive to interference compared to a single-ended signal.
If the encoder signal is to be transmitted over longer distances or at higher frequencies, an encoder with RS422 signals is recommended.
Shielded and twisted pair cables should be used.
Connection of RS422 encoders with or without zero pulse
Fig.30: Connection of RS422 encoders with zero pulse in single-channel mode
Connection instructions
• When using an encoder without zero pulse C, the terminal points for the C track are not con­nected.
EL5112 49Version: 1.1
Mounting and wiring
Connection of RS422 counters / pulse generators with or without zero pulse
Fig.31: Connection of RS422 counter / pulse generators with zero pulse in single-channel mode
Connection instructions
• If a counter / pulse generator is connected, the B track determines the counting direction. In RS422 mode a differential signal is expected on the B track.
• When using a counter / pulse generator without zero pulse C, the terminal points for the C track are not connected.
EL511250 Version: 1.1
4.7.1.2 TTL mode
Connection of TTL encoders with or without zero pulse
Mounting and wiring
Fig.32: Connection of encoders in TTL mode with zero pulse in single-channel mode
Connection instructions
• In TTL mode the inverse inputs are not connected.
• When using an encoder without zero pulse C, the terminal points for the C track are not con­nected.
EL5112 51Version: 1.1
Mounting and wiring
Connection of TTL counters / pulse generators with or without zero pulse
Fig.33: Connection of counters / pulse generators in TTL mode with zero pulse in single-channel mode
Connection instructions
• In TTL mode the inverse inputs are not connected.
• If a counter / pulse generator is connected, the B track determines the counting direction. Input B is not connected.
• When using a counter / pulse generator without zero pulse C, the terminal points for the C track are not connected.
EL511252 Version: 1.1
4.7.1.3 Open Collector mode
Connection of Open Collector encoders with or without zero pulse
Mounting and wiring
Fig.34: Connection of encoders in Open Collector mode with zero pulse in single-channel mode
Connection instructions
• In Open Collector mode the inverse inputs are not connected.
• When using an encoder without zero pulse C, the terminal points for the C track are not con­nected.
EL5112 53Version: 1.1
Mounting and wiring
Connection of Open Collector counters / pulse generators with or without zero pulse
Fig.35: Connection of counters / pulse generators in Open Collector mode with zero pulse in single-channel mode
Connection instructions
• In Open Collector mode the inverse inputs are not connected.
• If a counter / pulse generator is connected, the B track determines the counting direction. Input B is not connected.
• When using a counter / pulse generator without zero pulse C, the terminal points for the C track are not connected.
EL511254 Version: 1.1
Mounting and wiring

4.7.2 Two-channel mode (2 x A, B)

4.7.2.1 RS422 mode
NOTE
Differential and single-ended connection
The RS422 signal transmits a differential voltage, which makes the signal less sensitive to interference compared to a single-ended signal.
If the encoder signal is to be transmitted over longer distances or at higher frequencies, an encoder with RS422 signals is recommended.
Shielded and twisted pair cables should be used.
Connection of RS422 encoders without zero pulse in two-channel mode
Fig.36: Connection of encoders in RS422 mode without zero pulse in two-channel mode
Connection instructions
• In two-channel mode only encoders without zero pulse C can be used. The terminal points for the C track are assigned the signals of the second A track.
EL5112 55Version: 1.1
Mounting and wiring
Connection of RS422 counters / pulse generators without zero pulse in two-channel mode
Fig.37: Connection of counters / pulse generators in RS422 mode without zero pulse in two-channel mode
Connection instructions
• If a counter / pulse generator is connected, the B track determines the counting direction. In RS422 mode a differential signal is expected on the B track.
• Only counters / pulse generators without zero pulse are suitable for use in two-channel mode. The terminal points of the C track are assigned the signals of the second A track.
EL511256 Version: 1.1
4.7.2.2 TTL mode
Connection of TTL encoders without zero pulse in two-channel mode
Mounting and wiring
Fig.38: Connection of encoders in TTL mode without zero pulse in two-channel mode
Connection instructions
• In TTL mode the inverse inputs are not connected.
• Only encoders without zero pulse are suitable for use in two-channel mode. The terminal points for the C track are assigned the signals of the second A track.
EL5112 57Version: 1.1
Mounting and wiring
Connection of TTL counters / pulse generators without zero pulse in two-channel mode
Fig.39: Connection of counters / pulse generators in TTL mode without zero pulse in two-channel mode
Connection instructions
• In TTL mode the inverse inputs are not connected.
• If a counter / pulse generator is connected, the B track determines the counting direction. Input B is not connected.
• Only counters / pulse generators without zero pulse are suitable for use in two-channel mode. The terminal points for the C track are assigned the signals of the second A track.
EL511258 Version: 1.1
4.7.2.3 Open Collector mode
Connection of Open Collector encoders without zero pulse in two-channel mode
Mounting and wiring
Fig.40: Connection of encoders in Open Collector mode without zero pulse in two-channel mode
Connection instructions
• In Open Collector mode the inverse inputs are not connected.
• Only encoders without zero pulse are suitable for use in two-channel mode. The terminal points for the C track are assigned the signals of the second A track.
EL5112 59Version: 1.1
Mounting and wiring
Connection of Open Collector counters / pulse generators without zero pulse in two-channel mode
Fig.41: Connection of counters / pulse generators in Open Collector mode without zero pulse in two-channel mode
Connection instructions
• In Open Collector mode the inverse inputs are not connected.
• If a counter / pulse generator is connected, the B track determines the counting direction. Input B is not connected.
• Only counters / pulse generators without zero pulse are suitable for use in two-channel mode. The terminal points for the C track are assigned the signals of the second A track.
EL511260 Version: 1.1

4.8 EL5112 - LEDs

Single-channel mode (1xABC)
Fig.42: EL5112 - LEDs in single-channel mode
Mounting and wiring
No. Name Color Description
1 A1 green, red Green: indicates TRUE level 2 B1 3 C1
4 Status Input red Fault signal input from encoder. Input is internally connected to 5V via a pull-up resistor. The en-
5 PowerEnc. green Operating voltage display for incremental encoder power supply 7 Latch green is lit, if a signal (+24V) is connected to the latch input 9 Run green This LED indicates the terminal's operating state:
10 Diag red Initialization process active or state of the EtherCAT State Machine: BOOT 15 Gate/Latch green is lit if a signal (+24V) is present at the gate/latch input
Red: There is a broken wire at the respective input. Diagnosis is only possible if the following three conditions are met.
• The corresponding input is differentially wired, i.e.: „Counter mode“ 0x8001:1D =0 (Encoder RS422 (diff. Input)) or „Counter mode“ 0x8001:1D =1 (Counter RS422 (diff. Input))
• "Error Detection" for the respective input is enabled: „Error Detection A“ 0x8000:0B = TRUE „Error Detection B“ 0x8000:0C = TRUE „Error Detection C“ 0x8000:0D = TRUE
• The differential voltage V
coder output must actively pull the signal against GND. on Output active at the encoder, a fault message is present at the encoder off Output not active at the encoder; no fault message is present
off
flashing State of the EtherCAT State Machine: PREOP = function for mailbox communication
Single flash
on State of the EtherCAT State Machine: OP = normal operating state; mailbox and
State of the EtherCAT State Machine [}28]: INIT = initialization of the terminal or BOOTSTRAP = function for firmware updates [}257] of the terminal
and different default settings set State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager
[}113] channels and the distributed clocks.
Outputs remain in safe state
process data communication is possible
is typically less than 0.67V (subject to change).
ID Low
EL5112 61Version: 1.1
Mounting and wiring
Two-channel mode (2xAB)
Fig.43: EL5112 - LEDs in two-channel mode
No. Name Color Description
1 A1 green, red Green: indicates TRUE level 2 B1 3 A2 4 B2
5 PowerEnc. green Operating voltage display for incremental encoder power supply 7 Latch green is lit, if a signal (+24V) is connected to the latch input 9 Run green This LED indicates the terminal's operating state:
10 Diag red Initialization process active or state of the EtherCAT State Machine: BOOT 15 Gate/Latch green is lit if a signal (+24V) is present at the gate/latch input
Red: There is a broken wire at the respective input. Diagnosis is only possible if the following three conditions are met.
• The corresponding input is differentially wired, i.e.: „Counter mode“ 0x8001:1D =0 (Encoder RS422 (diff. Input)) or „Counter mode“ 0x8001:1D =1 (Counter RS422 (diff. Input))
• "Error Detection" for the respective input is enabled: „Error Detection A“ 0x8000:0B = TRUE „Error Detection B“ 0x8000:0C = TRUE
• The differential voltage V
off
flashing State of the EtherCAT State Machine: PREOP = function for mailbox communication
Single flash
on State of the EtherCAT State Machine: OP = normal operating state; mailbox and
State of the EtherCAT State Machine [}28]: INIT = initialization of the terminal or BOOTSTRAP = function for firmware updates [}257] of the terminal
and different default settings set State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager
[}113] channels and the distributed clocks.
Outputs remain in safe state
process data communication is possible
is typically less than 0.67V (subject to change).
ID Low
EL511262 Version: 1.1
Commissioning

5 Commissioning

5.1 TwinCAT Quick Start

TwinCAT is a development environment for real-time control including multi-PLC system, NC axis control, programming and operation. The whole system is mapped through this environment and enables access to a programming environment (including compilation) for the controller. Individual digital or analog inputs or outputs can also be read or written directly, in order to verify their functionality, for example.
For further information please refer to http://infosys.beckhoff.com:
EtherCAT Systemmanual:
Fieldbus Components → EtherCAT Terminals → EtherCAT System Documentation → Setup in the TwinCAT System Manager
TwinCAT2 → TwinCAT System Manager → I/O - Configuration
• In particular, TwinCAT driver installation:
Fieldbus components → Fieldbus Cards and Switches → FC900x – PCI Cards for Ethernet → Installation
Devices contain the terminals for the actual configuration. All configuration data can be entered directly via editor functions (offline) or via the “Scan” function (online):
“offline”: The configuration can be customized by adding and positioning individual components.
These can be selected from a directory and configured.
◦ The procedure for offline mode can be found under http://infosys.beckhoff.com:
TwinCAT2 → TwinCAT System Manager → IO - Configuration → Adding an I/O Device
“online”: The existing hardware configuration is read
◦ See also http://infosys.beckhoff.com:
Fieldbus components → Fieldbus cards and switches → FC900x – PCI Cards for Ethernet → Installation → Searching for devices
The following relationship is envisaged from user PC to the individual control elements:
EL5112 63Version: 1.1
Commissioning
Fig.44: Relationship between user side (commissioning) and installation
The user inserting of certain components (I/O device, terminal, box...) is the same in TwinCAT2 and TwinCAT3. The descriptions below relate to the online procedure.
Sample configuration (actual configuration)
Based on the following sample configuration, the subsequent subsections describe the procedure for TwinCAT2 and TwinCAT3:
• Control system (PLC) CX2040 including CX2100-0004 power supply unit
• Connected to the CX2040 on the right (E-bus):
EL1004 (4-channel digital input terminal 24VDC)
• Linked via the X001 port (RJ-45): EK1100 EtherCAT Coupler
• Connected to the EK1100 EtherCAT coupler on the right (E-bus):
EL2008 (8-channel digital output terminal 24VDC;0.5A)
• (Optional via X000: a link to an external PC for the user interface)
EL511264 Version: 1.1
Commissioning
Fig.45: Control configuration with Embedded PC, input (EL1004) and output (EL2008)
Note that all combinations of a configuration are possible; for example, the EL1004 terminal could also be connected after the coupler, or the EL2008 terminal could additionally be connected to the CX2040 on the right, in which case the EK1100 coupler wouldn’t be necessary.
EL5112 65Version: 1.1
Commissioning

5.1.1 TwinCAT 2

Startup
TwinCAT basically uses two user interfaces: the TwinCAT System Manager for communication with the electromechanical components and TwinCAT PLC Control for the development and compilation of a controller. The starting point is the TwinCAT System Manager.
After successful installation of the TwinCAT system on the PC to be used for development, the TwinCAT2 System Manager displays the following user interface after startup:
Fig.46: Initial TwinCAT2 user interface
Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is “Insert Device [}68]”.
If the intention is to address the TwinCAT runtime environment installed on a PLC as development environment remotely from another system, the target system must be made known first. In the menu under
“Actions” → “Choose Target System...”, via the symbol “ ” or the “F8” key, open the following window:
EL511266 Version: 1.1
Fig.47: Selection of the target system
Use “Search (Ethernet)...” to enter the target system. Thus a next dialog opens to either:
Commissioning
• enter the known computer name after “Enter Host Name / IP:” (as shown in red)
• perform a “Broadcast Search” (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.
Fig.48: Specify the PLC for access by the TwinCAT System Manager: selection of the target system
Once the target system has been entered, it is available for selection as follows (a password may have to be entered):
After confirmation with “OK” the target system can be accessed via the System Manager.
EL5112 67Version: 1.1
Commissioning
Adding devices
In the configuration tree of the TwinCAT2 System Manager user interface on the left, select “I/ODevices” and then right-click to open a context menu and select “ScanDevices…”, or start the action in the menu bar
via . The TwinCAT System Manager may first have to be set to “Configmode” via or via menu “Actions” → “Set/Reset TwinCAT to Config Mode…” (Shift + F4).
Fig.49: Select “Scan Devices...”
Confirm the warning message, which follows, and select “EtherCAT” in the dialog:
Fig.50: Automatic detection of I/O devices: selection the devices to be integrated
Confirm the message “Find new boxes”, in order to determine the terminals connected to the devices. “Free Run” enables manipulation of input and output values in “Config mode” and should also be acknowledged.
Based on the sample configuration [}64] described at the beginning of this section, the result is as follows:
EL511268 Version: 1.1
Commissioning
Fig.51: Mapping of the configuration in the TwinCAT2 System Manager
The whole process consists of two stages, which may be performed separately (first determine the devices, then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by selecting “Device ...” from the context menu, which then reads the elements present in the configuration below:
Fig.52: Reading of individual terminals connected to a device
This functionality is useful if the actual configuration is modified at short notice.
Programming and integrating the PLC
TwinCAT PLC Control is the development environment for the creation of the controller in different program environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two text­based languages and three graphical languages.
Text-based languages
◦ Instruction List (IL)
EL5112 69Version: 1.1
Commissioning
◦ Structured Text (ST)
Graphical languages
◦ Function Block Diagram (FBD) ◦ Ladder Diagram (LD) ◦ The Continuous Function Chart Editor (CFC) ◦ Sequential Function Chart (SFC)
The following section refers to Structured Text (ST).
After starting TwinCAT PLC Control, the following user interface is shown for an initial project:
Fig.53: TwinCAT PLC Control after startup
Sample variables and a sample program have been created and stored under the name “PLC_example.pro”:
EL511270 Version: 1.1
Commissioning
Fig.54: Sample program with variables after a compile process (without variable integration)
Warning 1990 (missing “VAR_CONFIG”) after a compile process indicates that the variables defined as external (with the ID “AT%I*” or “AT%Q*”) have not been assigned. After successful compilation, TwinCAT PLC Control creates a “*.tpy” file in the directory in which the project was stored. This file (“*.tpy”) contains variable assignments and is not known to the System Manager, hence the warning. Once the System Manager has been notified, the warning no longer appears.
First, integrate the TwinCAT PLC Control project in the System Manager via the context menu of the PLC configuration; right-click and select “Append PLC Project…”:
Fig.55: Appending the TwinCAT PLC Control project
EL5112 71Version: 1.1
Commissioning
Select the PLC configuration “PLC_example.tpy” in the browser window that opens. The project including the two variables identified with “AT” are then integrated in the configuration tree of the System Manager:
Fig.56: PLC project integrated in the PLC configuration of the System Manager
The two variables “bEL1004_Ch4” and “nEL2008_value” can now be assigned to certain process objects of the I/O configuration.
Assigning variables
Open a window for selecting a suitable process object (PDO) via the context menu of a variable of the integrated project “PLC_example” and via “Modify Link...” “Standard”:
Fig.57: Creating the links between PLC variables and process objects
In the window that opens, the process object for the variable “bEL1004_Ch4” of type BOOL can be selected from the PLC configuration tree:
EL511272 Version: 1.1
Commissioning
Fig.58: Selecting PDO of type BOOL
According to the default setting, certain PDO objects are now available for selection. In this sample the input of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox “All types” must be ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a byte variable. The following diagram shows the whole process:
Fig.59: Selecting several PDOs simultaneously: activate “Continuous” and “All types”
Note that the “Continuous” checkbox was also activated. This is designed to allocate the bits contained in the byte of the variable “nEL2008_value” sequentially to all eight selected output bits of the EL2008 terminal. In this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol ( ) at the yellow or red object of the variable indicates that a link exists. The links can also be checked by selecting a “Goto Link Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically selected:
EL5112 73Version: 1.1
Commissioning
Fig.60: Application of a “Goto Link” variable, using “MAIN.bEL1004_Ch4” as a sample
The process of assigning variables to the PDO is completed via the menu selection “Actions” → “Generate
Mappings”, key Ctrl+M or by clicking on the symbol in the menu.
This can be visualized in the configuration:
The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs to variable. However, in this example it would then not be possible to select all output bits for the EL2008, since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or similar PDO, it is possible to allocate this a set of bit-standardized variables (type “BOOL”). Here, too, a “Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the respective PLC instance can then be selected.
Activation of the configuration
The allocation of PDO to PLC variables has now established the connection from the controller to the inputs and outputs of the terminals. The configuration can now be activated. First, the configuration can be verified
via (or via “Actions” → “Check Configuration”). If no error is present, the configuration can be
activated via (or via “Actions” → “Activate Configuration…”) to transfer the System Manager settings to the runtime system. Confirm the messages “Old configurations are overwritten!” and “Restart TwinCAT system in Run mode” with “OK”.
A few seconds later the real-time status is displayed at the bottom right in the System Manager. The PLC system can then be started as described below.
Starting the controller
Starting from a remote system, the PLC control has to be linked with the Embedded PC over Ethernet via “Online” → “Choose Run-Time System…”:
EL511274 Version: 1.1
Commissioning
Fig.61: Choose target system (remote)
In this sample “Runtime system 1 (port 801)” is selected and confirmed. Link the PLC with the real-time
system via menu option “Online” → “Login”, the F11 key or by clicking on the symbol .The control program can then be loaded for execution. This results in the message “No program on the controller! Should the new program be loaded?”, which should be acknowledged with “Yes”. The runtime environment is ready for the program start:
EL5112 75Version: 1.1
Commissioning
Fig.62: PLC Control logged in, ready for program startup
The PLC can now be started via “Online” → “Run”, F5 key or .

5.1.2 TwinCAT 3

Startup
TwinCAT makes the development environment areas available together with Microsoft Visual Studio: after startup, the project folder explorer appears on the left in the general window area (cf. “TwinCAT System Manager” of TwinCAT2) for communication with the electromechanical components.
After successful installation of the TwinCAT system on the PC to be used for development, TwinCAT3 (shell) displays the following user interface after startup:
EL511276 Version: 1.1
Commissioning
Fig.63: Initial TwinCAT3 user interface
First create a new project via (or under “File”→“New”→ “Project…”). In the following dialog make the corresponding entries as required (as shown in the diagram):
Fig.64: Create new TwinCAT project
The new project is then available in the project folder explorer:
EL5112 77Version: 1.1
Commissioning
Fig.65: New TwinCAT3 project in the project folder explorer
Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is “Insert Device [}79]”.
If the intention is to address the TwinCAT runtime environment installed on a PLC as development environment remotely from another system, the target system must be made known first. Via the symbol in the menu bar:
expand the pull-down menu:
and open the following window:
Fig.66: Selection dialog: Choose the target system
EL511278 Version: 1.1
Use “Search (Ethernet)...” to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after “Enter Host Name / IP:” (as shown in red)
• perform a “Broadcast Search” (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.
Commissioning
Fig.67: Specify the PLC for access by the TwinCAT System Manager: selection of the target system
Once the target system has been entered, it is available for selection as follows (a password may have to be entered):
After confirmation with “OK” the target system can be accessed via the Visual Studio shell.
Adding devices
In the project folder explorer of the Visual Studio shell user interface on the left, select “Devices” within
element “I/O”, then right-click to open a context menu and select “Scan” or start the action via in the
menu bar. The TwinCAT System Manager may first have to be set to “Config mode” via or via the menu “TwinCAT” → “Restart TwinCAT (Config mode)”.
Fig.68: Select “Scan”
Confirm the warning message, which follows, and select “EtherCAT” in the dialog:
EL5112 79Version: 1.1
Commissioning
Fig.69: Automatic detection of I/O devices: selection the devices to be integrated
Confirm the message “Find new boxes”, in order to determine the terminals connected to the devices. “Free Run” enables manipulation of input and output values in “Config mode” and should also be acknowledged.
Based on the sample configuration [}64] described at the beginning of this section, the result is as follows:
Fig.70: Mapping of the configuration in VS shell of the TwinCAT3 environment
The whole process consists of two stages, which may be performed separately (first determine the devices, then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by selecting “Device ...” from the context menu, which then reads the elements present in the configuration below:
EL511280 Version: 1.1
Commissioning
Fig.71: Reading of individual terminals connected to a device
This functionality is useful if the actual configuration is modified at short notice.
Programming the PLC
TwinCAT PLC Control is the development environment for the creation of the controller in different program environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two text­based languages and three graphical languages.
Text-based languages
◦ Instruction List (IL) ◦ Structured Text (ST)
Graphical languages
◦ Function Block Diagram (FBD) ◦ Ladder Diagram (LD) ◦ The Continuous Function Chart Editor (CFC) ◦ Sequential Function Chart (SFC)
The following section refers to Structured Text (ST).
In order to create a programming environment, a PLC subproject is added to the project sample via the context menu of “PLC” in the project folder explorer by selecting “Add New Item….”:
EL5112 81Version: 1.1
Commissioning
Fig.72: Adding the programming environment in “PLC”
In the dialog that opens select “Standard PLC project” and enter “PLC_example” as project name, for example, and select a corresponding directory:
Fig.73: Specifying the name and directory for the PLC programming environment
The “Main” program, which already exists by selecting “Standard PLC project”, can be opened by double­clicking on “PLC_example_project” in “POUs”. The following user interface is shown for an initial project:
EL511282 Version: 1.1
Commissioning
Fig.74: Initial “Main” program of the standard PLC project
To continue, sample variables and a sample program have now been created:
EL5112 83Version: 1.1
Commissioning
Fig.75: Sample program with variables after a compile process (without variable integration)
The control program is now created as a project folder, followed by the compile process:
Fig.76: Start program compilation
The following variables, identified in the ST/ PLC program with “AT%”, are then available in under “Assignments” in the project folder explorer:
Assigning variables
Via the menu of an instance - variables in the “PLC” context, use the “Modify Link…” option to open a window for selecting a suitable process object (PDO) for linking:
EL511284 Version: 1.1
Commissioning
Fig.77: Creating the links between PLC variables and process objects
In the window that opens, the process object for the variable “bEL1004_Ch4” of type BOOL can be selected from the PLC configuration tree:
Fig.78: Selecting PDO of type BOOL
According to the default setting, certain PDO objects are now available for selection. In this sample the input of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox “All types” must be ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a byte variable. The following diagram shows the whole process:
EL5112 85Version: 1.1
Commissioning
Fig.79: Selecting several PDOs simultaneously: activate “Continuous” and “All types”
Note that the “Continuous” checkbox was also activated. This is designed to allocate the bits contained in the byte of the variable “nEL2008_value” sequentially to all eight selected output bits of the EL2008 terminal. In this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol ( ) at the yellow or red object of the variable indicates that a link exists. The links can also be checked by selecting a “Goto Link Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically selected:
Fig.80: Application of a “Goto Link” variable, using “MAIN.bEL1004_Ch4” as a sample
The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs to variable. However, in this example it would then not be possible to select all output bits for the EL2008, since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or
EL511286 Version: 1.1
Commissioning
similar PDO, it is possible to allocate this a set of bit-standardized variables (type “BOOL”). Here, too, a “Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the respective PLC instance can then be selected.
Note on the type of variable assignment
The following type of variable assignment can only be used from TwinCAT version V3.1.4024.4 on­wards and is only available for terminals with a microcontroller.
In TwinCAT it is possible to create a structure from the mapped process data of a terminal. An instance of this structure can then be created in the PLC, so it is possible to access the process data directly from the PLC without having to declare own variables.
The procedure for the EL3001 1-channel analog input terminal -10...+10V is shown as an example.
1. First the required process data must be selected in the “Process data” tab in TwinCAT.
2. After that, the PLC data type must be generated in the tab “PLC” via the check box.
3. The data type in the “Data Type” field can then be copied using the “Copy” button.
Fig.81: Creating a PLC data type
4. An instance of the data structure of the copied data type must then be created in the PLC.
Fig.82: Instance_of_struct
5. Then the project folder must be created. This can be done either via the key combination “CTRL + Shift + B” or via the “Build” tab in TwinCAT.
6. The structure in the “PLC” tab of the terminal must then be linked to the created instance.
EL5112 87Version: 1.1
Commissioning
Fig.83: Linking the structure
7. In the PLC the process data can then be read or written via the structure in the program code.
Fig.84: Reading a variable from the structure of the process data
Activation of the configuration
The allocation of PDO to PLC variables has now established the connection from the controller to the inputs
and outputs of the terminals. The configuration can now be activated with or via the menu under “TwinCAT” in order to transfer settings of the development environment to the runtime system. Confirm the messages “Old configurations are overwritten!” and “Restart TwinCAT system in Run mode” with “OK”. The corresponding assignments can be seen in the project folder explorer:
A few seconds later the corresponding status of the Run mode is displayed in the form of a rotating symbol
at the bottom right of the VS shell development environment. The PLC system can then be started as
described below.
EL511288 Version: 1.1
Commissioning
Starting the controller
Select the menu option “PLC” → “Login” or click on to link the PLC with the real-time system and load the control program for execution. This results in the message No program on the controller! Should the new program be loaded?, which should be acknowledged with “Yes”. The runtime environment is ready for
program start by click on symbol , the “F5” key or via “PLC” in the menu selecting “Start”. The started programming environment shows the runtime values of individual variables:
Fig.85: TwinCAT development environment (VS shell): logged-in, after program startup
The two operator control elements for stopping and logout result in the required action (accordingly also for stop “Shift + F5”, or both actions can be selected via the PLC menu).

5.2 TwinCAT Development Environment

The Software for automation TwinCAT (The Windows Control and Automation Technology) will be distinguished into:
• TwinCAT2: System Manager (Configuration) & PLC Control (Programming)
• TwinCAT3: Enhancement of TwinCAT2 (Programming and Configuration takes place via a common Development Environment)
Details:
TwinCAT2:
◦ Connects I/O devices to tasks in a variable-oriented manner ◦ Connects tasks to tasks in a variable-oriented manner ◦ Supports units at the bit level ◦ Supports synchronous or asynchronous relationships ◦ Exchange of consistent data areas and process images ◦ Datalink on NT - Programs by open Microsoft Standards (OLE, OCX, ActiveX, DCOM+, etc.)
EL5112 89Version: 1.1
Commissioning
◦ Integration of IEC 61131-3-Software-SPS, Software- NC and Software-CNC within Windows
NT/2000/XP/Vista, Windows 7, NT/XP Embedded, CE
◦ Interconnection to all common fieldbusses
More…
Additional features:
TwinCAT3 (eXtended Automation):
◦ Visual-Studio®-Integration ◦ Choice of the programming language ◦ Supports object orientated extension of IEC 61131-3 ◦ Usage of C/C++ as programming language for real time applications ◦ Connection to MATLAB®/Simulink® ◦ Open interface for expandability ◦ Flexible run-time environment ◦ Active support of Multi-Core- und 64-Bit-Operatingsystem ◦ Automatic code generation and project creation with the TwinCAT Automation Interface
More…
Within the following sections commissioning of the TwinCAT Development Environment on a PC System for the control and also the basically functions of unique control elements will be explained.
Please see further information to TwinCAT2 and TwinCAT3 at http://infosys.beckhoff.com.

5.2.1 Installation of the TwinCAT real-time driver

In order to assign real-time capability to a standard Ethernet port of an IPC controller, the Beckhoff real-time driver has to be installed on this port under Windows.
This can be done in several ways. One option is described here.
In the System Manager call up the TwinCAT overview of the local network interfaces via Options → Show Real Time Ethernet Compatible Devices.
Fig.86: System Manager “Options” (TwinCAT2)
This have to be called up by the Menü “TwinCAT” within the TwinCAT3 environment:
Fig.87: Call up under VS Shell (TwinCAT3)
EL511290 Version: 1.1
Commissioning
The following dialog appears:
Fig.88: Overview of network interfaces
Interfaces listed under “Compatible devices” can be assigned a driver via the “Install” button. A driver should only be installed on compatible devices.
A Windows warning regarding the unsigned driver can be ignored.
Alternatively an EtherCAT-device can be inserted first of all as described in chapter Offline configuration creation, section “Creating the EtherCAT device” [}100] in order to view the compatible ethernet ports via its
EtherCAT properties (tab “Adapter”, button “Compatible Devices…”):
Fig.89: EtherCAT device properties(TwinCAT2): click on “Compatible Devices…” of tab “Adapte””
TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)” within the Solution Explorer under “I/O”:
After the installation the driver appears activated in the Windows overview for the network interface (Windows Start → System Properties → Network)
EL5112 91Version: 1.1
Commissioning
Fig.90: Windows properties of the network interface
A correct setting of the driver could be:
Fig.91: Exemplary correct driver setting for the Ethernet port
Other possible settings have to be avoided:
EL511292 Version: 1.1
Commissioning
Fig.92: Incorrect driver settings for the Ethernet port
EL5112 93Version: 1.1
Commissioning
IP address of the port used
IP address/DHCP
In most cases an Ethernet port that is configured as an EtherCAT device will not transport general IP packets. For this reason and in cases where an EL6601 or similar devices are used it is useful to specify a fixed IP address for this port via the “Internet Protocol TCP/IP” driver setting and to disable DHCP. In this way the delay associated with the DHCP client for the Ethernet port assigning itself a default IP address in the absence of a DHCP server is avoided. A suitable address space is
192.168.x.x, for example.
Fig.93: TCP/IP setting for the Ethernet port
EL511294 Version: 1.1
Commissioning

5.2.2 Notes regarding ESI device description

Installation of the latest ESI device description
The TwinCAT EtherCAT master/System Manager needs the device description files for the devices to be used in order to generate the configuration in online or offline mode. The device descriptions are contained in the so-called ESI files (EtherCAT Slave Information) in XML format. These files can be requested from the respective manufacturer and are made available for download. An *.xml file may contain several device descriptions.
The ESI files for Beckhoff EtherCAT devices are available on the Beckhoff website.
The ESI files should be stored in the TwinCAT installation directory.
Default settings:
TwinCAT2: C:\TwinCAT\IO\EtherCAT
TwinCAT3: C:\TwinCAT\3.1\Config\Io\EtherCAT
The files are read (once) when a new System Manager window is opened, if they have changed since the last time the System Manager window was opened.
A TwinCAT installation includes the set of Beckhoff ESI files that was current at the time when the TwinCAT build was created.
For TwinCAT2.11/TwinCAT3 and higher, the ESI directory can be updated from the System Manager, if the programming PC is connected to the Internet; by
TwinCAT2: Option → “Update EtherCAT Device Descriptions”
TwinCAT3: TwinCAT → EtherCAT Devices → “Update Device Descriptions (via ETG Website)…”
The TwinCAT ESI Updater [}99] is available for this purpose.
ESI
The *.xml files are associated with *.xsd files, which describe the structure of the ESI XML files. To update the ESI device descriptions, both file types should therefore be updated.
Device differentiation
EtherCAT devices/slaves are distinguished by four properties, which determine the full device identifier. For example, the device identifier EL2521-0025-1018 consists of:
• family key “EL”
• name “2521”
• type “0025”
• and revision “1018”
Fig.94: Identifier structure
The order identifier consisting of name + type (here: EL2521-0010) describes the device function. The revision indicates the technical progress and is managed by Beckhoff. In principle, a device with a higher revision can replace a device with a lower revision, unless specified otherwise, e.g. in the documentation. Each revision has its own ESI description. See further notes.
EL5112 95Version: 1.1
Commissioning
Online description
If the EtherCAT configuration is created online through scanning of real devices (see section Online setup) and no ESI descriptions are available for a slave (specified by name and revision) that was found, the System Manager asks whether the description stored in the device should be used. In any case, the System Manager needs this information for setting up the cyclic and acyclic communication with the slave correctly.
Fig.95: OnlineDescription information window (TwinCAT2)
In TwinCAT3 a similar window appears, which also offers the Web update:
Fig.96: Information window OnlineDescription (TwinCAT3)
If possible, the Yes is to be rejected and the required ESI is to be requested from the device manufacturer. After installation of the XML/XSD file the configuration process should be repeated.
NOTE
Changing the “usual” configuration through a scan
ü If a scan discovers a device that is not yet known to TwinCAT, distinction has to be made between two
cases. Taking the example here of the EL2521-0000 in the revision 1019
a) no ESI is present for the EL2521-0000 device at all, either for the revision 1019 or for an older revision.
The ESI must then be requested from the manufacturer (in this case Beckhoff).
b) an ESI is present for the EL2521-0000 device, but only in an older revision, e.g. 1018 or 1017.
In this case an in-house check should first be performed to determine whether the spare parts stock al­lows the integration of the increased revision into the configuration at all. A new/higher revision usually also brings along new features. If these are not to be used, work can continue without reservations with the previous revision 1018 in the configuration. This is also stated by the Beckhoff compatibility rule.
Refer in particular to the chapter “General notes on the use of Beckhoff EtherCAT IO components” and for manual configuration to the chapter “Offline configuration creation [}100]”.
If the OnlineDescription is used regardless, the System Manager reads a copy of the device description from the EEPROM in the EtherCAT slave. In complex slaves the size of the EEPROM may not be sufficient for the complete ESI, in which case the ESI would be incomplete in the configurator. Therefore it’s recommended using an offline ESI file with priority in such a case.
The System Manager creates for online recorded device descriptions a new file “OnlineDescription0000...xml” in its ESI directory, which contains all ESI descriptions that were read online.
EL511296 Version: 1.1
Commissioning
Fig.97: File OnlineDescription.xml created by the System Manager
Is a slave desired to be added manually to the configuration at a later stage, online created slaves are indicated by a prepended symbol “>” in the selection list (see Figure Indication of an online recorded ESI of EL2521 as an example).
Fig.98: Indication of an online recorded ESI of EL2521 as an example
If such ESI files are used and the manufacturer's files become available later, the file OnlineDescription.xml should be deleted as follows:
• close all System Manager windows
• restart TwinCAT in Config mode
• delete “OnlineDescription0000...xml”
• restart TwinCAT System Manager
This file should not be visible after this procedure, if necessary press <F5> to update
OnlineDescription for TwinCAT3.x
In addition to the file described above “OnlineDescription0000...xml”, a so called EtherCAT cache with new discovered devices is created by TwinCAT3.x, e.g. under Windows 7:
(Please note the language settings of the OS!) You have to delete this file, too.
Faulty ESI file
If an ESI file is faulty and the System Manager is unable to read it, the System Manager brings up an information window.
Fig.99: Information window for faulty ESI file (left: TwinCAT2; right: TwinCAT3)
EL5112 97Version: 1.1
Commissioning
Reasons may include:
• Structure of the *.xml does not correspond to the associated *.xsd file → check your schematics
• Contents cannot be translated into a device description → contact the file manufacturer
EL511298 Version: 1.1
Commissioning

5.2.3 TwinCAT ESI Updater

For TwinCAT2.11 and higher, the System Manager can search for current Beckhoff ESI files automatically, if an online connection is available:
Fig.100: Using the ESI Updater (>= TwinCAT2.11)
The call up takes place under: “Options” → “Update EtherCAT Device Descriptions”
Selection under TwinCAT3:
Fig.101: Using the ESI Updater (TwinCAT3)
The ESI Updater (TwinCAT3) is a convenient option for automatic downloading of ESI data provided by EtherCAT manufacturers via the Internet into the TwinCAT directory (ESI = EtherCAT slave information). TwinCAT accesses the central ESI ULR directory list stored at ETG; the entries can then be viewed in the Updater dialog, although they cannot be changed there.
The call up takes place under: “TwinCAT” → “EtherCAT Devices” → “Update Device Description (via ETG Website)…”.

5.2.4 Distinction between Online and Offline

The distinction between online and offline refers to the presence of the actual I/O environment (drives, terminals, EJ-modules). If the configuration is to be prepared in advance of the system configuration as a programming system, e.g. on a laptop, this is only possible in “Offline configuration” mode. In this case all components have to be entered manually in the configuration, e.g. based on the electrical design.
If the designed control system is already connected to the EtherCAT system and all components are energised and the infrastructure is ready for operation, the TwinCAT configuration can simply be generated through “scanning” from the runtime system. This is referred to as online configuration.
In any case, during each startup the EtherCAT master checks whether the slaves it finds match the configuration. This test can be parameterised in the extended slave settings. Refer to note “Installation of the latest ESI-XML device description” [}95].
For preparation of a configuration:
• the real EtherCAT hardware (devices, couplers, drives) must be present and installed
• the devices/modules must be connected via EtherCAT cables or in the terminal/ module strand in the same way as they are intended to be used later
EL5112 99Version: 1.1
Commissioning
• the devices/modules be connected to the power supply and ready for communication
• TwinCAT must be in CONFIG mode on the target system.
The online scan process consists of:
detecting the EtherCAT device [}105] (Ethernet port at the IPC)
detecting the connected EtherCAT devices [}106]. This step can be carried out independent of the preceding step
troubleshooting [}109]
The scan with existing configuration [}110] can also be carried out for comparison.

5.2.5 OFFLINE configuration creation

Creating the EtherCAT device
Create an EtherCAT device in an empty System Manager window.
Fig.102: Append EtherCAT device (left: TwinCAT2; right: TwinCAT3)
Select type “EtherCAT” for an EtherCAT I/O application with EtherCAT slaves. For the present publisher/ subscriber service in combination with an EL6601/EL6614 terminal select “EtherCAT Automation Protocol via EL6601”.
Fig.103: Selecting the EtherCAT connection (TwinCAT2.11, TwinCAT3)
Then assign a real Ethernet port to this virtual device in the runtime system.
Fig.104: Selecting the Ethernet port
EL5112100 Version: 1.1
Loading...