BECKHOFF DK9222-1009-0006 User Manual

I/O
M
1~
L1N
M
1~
L1N
M
1~
L1N
Capacitor motor Universal motor Shaded-pole motor
Application Note DK9222-1009-0006
Bus Terminal
Speed control of single-phase AC motors
Keywords
Speed control Bus Terminals Energy efficiency Square characteristic AC motors KL2791
In order to reduce the power consumption of single-phase AC motors, their speed can be regulated as
required. Depending on the process data, the speed can be reduced in the case of low load requirements in
order to reduce noise emissions, increase energy efficiency and prolong the service life of the units.
Effects of the change in speed
Single-phase AC motors with square load characteristic curves are often used as additional units for fans or pumps, for
example. As opposed to three-phase motors, no start-up optimisation is necessary as in the case of star-delta and adjustment
to different load cases by means of a frequency converter is often not provided for. The additional units are usually switched in
an interval orientated manner or simply activated during a certain phase of the control program. The following AC motors are
in use, depending on the application: capacitor, universal and shaded-pole motors.
Fig. 1: Controllable AC motors on the KL2791
For application notes see disclaimer on the last page
Beckhoff
New Automation Technology
1
I/O
5421 3
Scenario 1
Volume rate of flow
Pump
Start-up
phase
1
st
cut
Constant
cut
Exit Move-out
phase
Tool drive active
Cooling lubricant consumption
Energy consumption
Application Note DK9222-1009-0006
Bus Terminal
When driving working machines whose production or conveying output can be influenced via the drive speed of the motor,
energy can be saved by means of variable speed. This particularly applies if the change in the motor speed is also linked with
large changes in the emitted mechanical output. Increase the speed – higher load, decrease – lower load. This procedure is
particularly suitable for uncontrolled units with a square load characteristic, because regulating the speed just a little brings
about a large change in energy consumption due to its square influence.
Practical example Cooling lubricant pump in a milling machine
Two frequently occurring control scenarios are illustrated here, after which the optimisation is demonstrated. The pump is
coupled in both cases to the tool drive in order to guarantee that sufficient cooling lubrication takes place when the blades cut
into the workpiece.
Scenario 1
Fig. 2 Need for optimised control
Cooling lubrication is fundamentally required during the runtime of the miller (tool drive) in order to achieve appropriate
surface qualities and to keep the thermal loading of the workpiece low. For this reason, the cooling lubricant circulation pump
is linked to the tool drive in order to securely guarantee pumping. There are two operating cases for the pump: Pump on | pump
off; therefore, no changes in the load take place. The pump always runs at full speed and with full power consumption, even
during the phases where the tool is moving in and moving out (1 and 5), at which time the tool drive is active, but the tool
itself is not cutting.
For application notes see disclaimer on the last page
Beckhoff
New Automation Technology
2
Loading...
+ 2 hidden pages