INSTALLATION INSTRUCTIONS
ELECTRONIC OIL IGNITER
●
240 VAC
APPLICATION INFORMATION:
This igniter is designed for use with 240 VAC.
◦
It is rated for continuous duty and can be used with intermittent, or interrupted ignition primary controls.
◦
The Beckett oil igniter is designed to mount in the same manner as standard ignition transformers and igniters.
◦
This igniter can be adapted to multiple base plates to accommodate Beckett residential and commercial burners. It will also fi t
◦
on many other vendors’ transformer base plates.
CAUTION! Do not use this igniter beyond its design specifi cations. Improper operation and igniter failure may result.
SPECIFICATIONS:
Input Voltage: 168-264 VAC, 50/60 Hz
Output Voltage: 19 kV peak
Output Current: 25 mA RMS
Input Current: 0.3A
Secondary Floating Ground
Ambient Operating Temperature: -40 to +150° F
Storage Temperature: -40 to +150° F
Moisture: 5 to 95% Relative Humidity, Condensing
Electrical Shock Hazard
Failure to disconnect all power sources
could result in severe personal injury or
death.
Disconnect all electrical power to the burner before servicing.
y
There could be more than one disconnect switch in the supply
circuit.
Installation and service must only be performed by a qualifi ed
y
service technician.
Perform all wiring in compliance with the National Electric Code
y
ANSI/NFPA 70 (Canada CSA C22.1).
Connect burner housing and circuit to earth ground.
y
Installation Instructions (If base plate is already
installed, skip to step number 9):
Locate the igniter blue “hot” and white “neutral” input leads.
1.
Install the 32411 igniter gasket, if required, and route the leads
2.
through the appropriate base plate lead exit hole. Make sure
these leads are not being crushed.
Mount the igniter fl ush to base plate with the mounting screws
3.
supplied.
Note: Use #6 x 7/16” screws when using the bottom mounting
4.
holes. Use #10 thread forming paint scraping screws, if using
the two top mounting holes for 5199701 & 5199702. For
5199703, use 1/4” machine screws, placing (1) 1/4” lockwasher
between screw head and baseplate to ensure ground.
Table 1 - Complete Igniter Base Plate Assemblies
Part No. Burner Models
5199701U AF, AFG, NX, and CF375
5199702U SM, SF, CF500, and CF800
5199703U
5199707U Wayne ‘M’ Models.
5199708U Wayne ‘E’ Models.
Tighten all screws securely.
5.
Install the barrier and base plate gaskets for AF, AFG, and
6.
CF375 Beckett burners. Do not use barrier gasket on NX.
Use gaskets for other burner models, as required by the manu-
7.
facturer.
Use of top mounting screws is possible for Beckett AF, AFG,
8.
NX, CF375, SM, SF, CF500 and CF800.
Mount the assembled unit to the burner using the screws sup-
9.
plied.
Use “paint scraping” screws for all burners (2 at the hinge and
10.
2 for non-hinged base plates). Tighten these screws securely
to provide effective grounding to burner housing.
Verify the burner is properly grounded.
11.
Carefully route the igniter input leads to prevent them from be-
12.
ing pinched during closing. Install cad cell, if applicable.
Fasten cad cell leads to control, if applicable. Wire white to
13.
neutral and blue to primary control ignition lead. Refer to control or appliance manufacturer’s wiring diagram.
Verify the igniter secondary output terminals are correctly
14.
arranged to make good electrical contact with the oil burner
electrodes.
Close the igniter. Install and securely tighten the two front
15.
base plate retaining screws (4 screws, if no hinge).
Reconnect electric power to the burner circuit.
16.
Verify with instruments that the burner is adjusted to the
17.
manufacturer’s recommended settings
Cycle the burner several times to verify prompt and smooth
18.
ignition before leaving.
CF1000, CF1400, CF2300, CF2500A, CF3500
Electrical Shock Hazard
Failure to wire the burner correctly could cause
serious injury or death.
Perform all wiring in compliance with ANSI/NFPA 70 (Canada CSA 22.1).
y
Connect the electrical circuit and burner housing to earth ground.
y
Figure 1 - Igniter Assembly Components (5199701U shown. Other models will have different baseplates and terminals.)
Igniter Input Leads
Mounting Screws
Baseplate
Igniter
240 VAC Oil Igniter
Field Installed Cad Cell
(if applicable)
Baseplate Gasket
Barrier Gasket
32411 Igniter Gasket
(between baseplate and igniter)
Table 2 - Igniter Base Plate Bill of Materials
Part No. Burner Models
5199701U AF, AFG, NX, and CF375 31405 51780BK 32411 32301*
5199702U SM, SF, CF500, and CF800 31481 51855BK 32411 n/a
5199703U
5199707U Wayne ‘M’ Models. n/a 51899BK n/a n/a
5199708U Wayne ‘E’ Models. n/a 21847 n/a n/a
* 32301 Barrier Gasket is not used on igniters for the NX burner. It is used only on AF, AFG & CF375.
CF1000, CF1400, CF2300,
CF2500A, CF3500
Baseplate
Gasket
31412 31412 32411 n/a
Baseplate
Igniter
Gasket
R.W. BECKETT CORPORATION
P.O. Box 1289, Elyria, Ohio 44036
Barrier
Gasket
R.W. BECKETT CANADA, LTD
430 Laird, Unit 3, Guelph, Ontario, N1G 3X7
Part No. 61586 R03, Printed in the USA 05/10