Mount burner on appliance ………………………………..…………..……………….. 8
Connect fuel lines ………………………………………………………..……………… 8
Wire burner ………………………………………………………………..……………... 8, 9
Startup burner/set combustion ………..……………..….…………..…………………. 10
Set combustion with instruments …………..………….…………..…………………... 10
Perform regular maintenance …………………..……….……………..……….……… 10
To replace the blower wheel ………………………..……………….…………………. 10
Replacement parts ………………………………………………………………………. 11
Owner’s information and warranty ………………………………….………….……… 12
Note 1. A burner with an electronic igniter will have a lower operating current.
The actual load should be determined by a current meter.
Note 2. See appliance manufacturer’s burner specifications for
recommended outlet pressure. Pressure is 140 psig unless otherwise noted.
SK9642
Instruction Manual – Model AFII Oil Burne
Prepare before installing
Be aware of hazard definitions Verify specifications
DANGER
Denotes presence of a hazard which, if ignored, will result in
severe personal injury, death, or substantial property damage.
WARNING
severe personal injury, death, or substantial property damage.
CAUTION
minor personal injury or property damage.
related to personal injury or property damage.
Check certifications/approvals
• Underwriters Laboratorieshas certified this burner to comply with
• State and local approvals are shown on burner rating label (see below).
• All oil burners should be installed in accordance with regulations of
• For recommended installation practice in Canada, refer to the latest
Notice special requirements
This equipment must be installed, adjusted and started only
by a
experienced with all codes and ordinances, who is responsible for the
installation and adjustment of the equipment. The installation must comply
with all local codes and ordinances and with the latest revision of the National
Fire Protection Standard for Oil-Burning Equipment, NFPA 31 (or CSA B139).
WARNING
Read all instructions before proceeding. Follow all
instructions completely. Failure to follow these instructions could result in
equipment malfunction, causing severe personal injury, death or substantial
property damage.
or controls during unpacking, notify the carrier at once and file the appropriate
claim.
When contacting Beckett for service information — Please
record the burner serial number (and have available when calling or writing).
You will find the serial number on the silver label located on the top right of the
burner, to the left of the air dial. See illustration below.
Denotes presence of a hazard which, if ignored, could result in
Denotes presence of a hazard which, if ignored, could result in
NOTICE
Intended to bring special attention to information, but not
ANSI/UL 296 and has listed it for use with #1 or #2 fuel oil as specified in
ASTM D396. Low sulfur #1 and #2 fuel oils reduce heat exchanger
deposits with all burners compared to the standard fuels. Reduced
deposits extend the service interval for cleaning and improve the
efficiency of the appliance over time. Low sulfur fuels reduce
particulate and oxides of nitrogen emissions as well. The Oilheat
Manufacturers' Association recommends these fuels as the
preferred fuels for this burner.
the latest revision of the National Fire Protection Association
Standard NFPA 31 and in complete accordance with all local codes
and authorities having jurisdiction. Regulation of these authorities
take precedence over the general instructions provided in this
installation manual.
version of CSA Standard B139.
DANGER
qualified service agency
NOTICE
Concealed damage
– an individual or agency, licensed and
— If you discover damage to the burner
3
Page 4
Instruction Manual – Model AFII Oil Burner
Prepare burner & site
Beckett
Inspect/prepare installation site Inspect/prepare installation site
Chimney or vent
• Inspect the chimney or vent, making sure it is properly sized and in good
condition for use.
For those installations not requiring a chimney, such as through-the-wall
•
vented appliances, follow the instructions given by the appliance and
power venter (if used) manufacturers.
Direct air supply and sidewall venting
• When sidewall venting appliances, carefully follow appliance and power
venter instructions for installation and wiring.
• AFII burners are equipped with a removable air inlet to allow use of a 4”
duct to supply outside air for combustion. Do not exceed 70 equivalent
feet. Allow 6 feet for each elbow.
1. Remove the inlet cover.
2. Insert 4" duct into the inlet ring.
3. Fasten duct into place using at least 3 sheet metal screws evenly
spaced around the inlet ring. Refer to Figure 1.
4. Remove the barometric draft control unless it is in the same
atmospheric pressure zone as the inlet.
On the outside of the home use a 90° elbow pointed downward with a 1/4"
mesh screen over its opening. The air inlet elbow must be located above
the snow line and in such a way as to prevent leaves and/or other debris
from blocking the air flow. Such debris will prevent proper operation of the
burner. Refer to local codes for proper location of inlet.
Figure 1
– Outside air connection
4 IN. DUCT
AIR
INLET
ELBOW
Exhaust fans and other air-using devices
Size air openings large enough to allow for all air-using devices in addition
to the minimum area required for combustion air. If there is any possibility
of the equipment room developing negative pressure (because of exhaust
fans or clothes dryers, for example), pipe combustion air directly to the
burner.
Clearances to burner and appliance
• Provide space around burner and appliance for easy service and
maintenance.
• Check minimum clearances against those shown by the appliance
manufacturer and by applicable building codes.
Combustion chamber — Burner retrofitting
Verify that the appliance combustion chamber provides at least the minimum
dimensions given in Table 2.
CAUTION
When retrofitting an appliance that has an unlined stainless
steel combustion chamber, chamber burnout could result from the use of a
high performance burner. Protect the chamber from high temperatures
through the use of "wet-pac" or a similar ceramic liner. Some equipment may
utilize a stainless steel combustion chamber that has been designed and
tested by the manufacturer for use with a flame retention burner, therefore
ceramic protection would not be necessary. Refer to appliance manufacturer’s
instructions. Failure to comply could result in damage to heating equipment.
– Minimum combustion chamber dimensions
Table 2
(continued)
¼” MESH
SCREEN
INLET
RING
Combustion air supply
See NFPA Standard 31 for complete details.
WARNING
If the burner is not supplied with a reliable combustion air
source, the burner cannot properly burn the fuel. This would result in
incomplete combustion, causing sooting and possible emission of carbon
monoxide. Severe personal injury, death or substantial property damage could
occur.
Appliance located in confined space
The confined space should have two (2) permanent openings: one near
the top of the enclosure and one near the bottom of the enclosure. Each
opening shall have a free area of not less than (1) one square inch per
1,000 BTU’s per hour of the total input rating of all appliances within the
enclosure. The openings shall have free access to the building interior,
which should have adequate infiltration from the outside.
Firing
rate
(gph)
0.50
0.75
1.00
1.25
1.50
Chamber dimension (inches)
Round
I.D.
Rectangular
Width Length
Height
Floor to
nozzle
8 7 8 12 5-6
9 8 9 12 5-6
10 9 10 12 ½ 5-6
11 10 11 12 ½ 5-6
12 11 12 13 6-7
4
Page 5
Beckett
r
Instruction Manual – Model AFII Oil Burne
Prepare burner & site
Prepare burner
Burner fuel unit
• Verify that the burner fuel unit is compatible with the oil supply system. For
more details, refer to “Connect fuel lines” on page 8.
Attach air tube (if not already installed)
If using a flange and gasket, slide them onto the air tube. Then attach the air
tube to the burner chassis using the sheet metal screws provided. See Figures
3 & 4 on pages 6 & 7 for details.
Install burner nozzle (if not already installed)
WARNING
Make certain the nozzle is selected for the fuel unit pressure
used. For applications with fuel unit pressure above 100 psig, the nozzle rated
capacity will be less than the appliance firing rate. Use only the specified spray
pattern unless combustion test results indicate the need for a change. Failure
to use the correct nozzle size and type can result in unacceptable combustion,
possibly causing severe personal injury, death or substantial property
damage.
1. Remove the plastic plug protecting the nozzle adapter threads
2. Place a ¾” open-end wrench on the nozzle adapter. Insert the nozzle into
the adapter and finger tighten. Finish tightening with a
wrench. Use care to avoid bending the burner head support legs or
electrodes. See
3. If you remove the head to replace the nozzle (type “HLX” heads), carefully
reconnect the head to the nozzle adapter, making sure to butt the head
support to the nozzle adapter shoulder (see Figure 3, page 6).
If the nozzle is already installed, remove the nozzle line assembly to verify that
the nozzle size and spray pattern are correct for the application (per appliance
manufacturer’s information or Beckett OEM Specification Guide, part number
6711). Verify that the electrode tip settings comply with Figure 2a or 2b.
If the nozzle is not installed, obtain a nozzle of the manufacturer, capacity and
spray angle specified in appliance manufacturer’s information or Beckett OEM
Specification Guide
information is not available for the application:
4. Refer to table below to select the mid-range nozzle spray angle for the
head type being used.
5. Fire the burner and make sure the combustion is acceptable and the
flame is not impinging on chamber surfaces.
6. If a shorter flame is needed, select a wider spray angle. If a longer flame
is needed, select a narrower spray angle.
7. Either hollow or solid spray patterns may be used. If combustion results
are not satisfactory with the selected spray pattern, try the other pattern.
CAUTION
, part number 6711. For conversions or upgrades, when
Use care when removing and installing oil nozzles:
CAUTION
• Inspect the nozzle adapter before installing nozzle. If it is grooved or
scratched on the sealing surface, replace the nozzle line assembly.
Otherwise, oil could leak at the nozzle-adapter joint, causing serious
combustion problems.
Protect the nozzle orifice and strainer when installing. If the orifice gets
•
dirt in it or is scratched, the nozzle will not function properly.
Do not over-torque the nozzle when installing. This will cause deep
•
grooves in the nozzle adapter, preventing a seal when a new nozzle is
installed.
⅝”
open-end
• Use a wrench or vise to hold the nozzle adapter. DO NOT attempt to
remove or replace nozzle without holding adapter. The nozzle alignment
could be seriously damaged. Use a nozzle wrench that secures the
adapter or use
• Do not squeeze the electrodes too tightly when handling the nozzle line
assembly. This could change the electrode tip settings or damage the
ceramic electrode insulators.
• Carefully check and realign electrode tips after replacing nozzle,
ensuring the electrode settings comply with Figure 2a or 2b.
3
/4" and 5/8" open-end wrenches.
Check/adjust electrodes
Check the electrode tip settings. Adjust if necessary to comply with the
dimensions shown in Figure 2a or Figure 2b. To adjust, loosen the electrode
clamp screw and slide/rotate electrodes as necessary. Securely tighten the
clamp screw when finished.
Figure 2a
– Electrode settings – HLX Air Tube Combinations
Figure 2b
– Electrode settings – FBX Air Tube Combinations
Servicing nozzle line assembly
1. Turn off power to burner before proceeding.
2. Disconnect copper oil connector tube from nozzle line.
3. Loosen the screw that fastens the rear access door.
4. Remove splined nut.
5. Remove the nozzle line assembly from the burner, being careful not to
damage the electrodes or insulators while handling. Stop halfway to
remove igniter/transformer wires.
6. To replace the nozzle assembly, reverse the above steps.
“HLX” head air tubes – Be sure stop screw is fastened securely. Seat
stop screw on back of choke ring to set the position of the head.
“
” head air tubes – Use T gauge to set the “Z” dimension to 1-1/8” +/-
FBX
1/32”.
5
Page 6
Instruction Manual – Model AFII Oil Burner
Prepare burner & site
Figure 3 - HLX Arrangement
Beckett
FIRING
RATE
Stop Screw AFII 85 AFII 100 AFII 150
0 0.40-0.65 0.50-0.65 0.75-1.00
1 - 0.60-0.75 0.85-1.10
2 - 0.65-0.80 0.95-1.15
3 0.60-0.75 0.65-0.90 0.95-1.20
4 - 0.75-0.95 1.10-1.25
5 0.70-0.85 0.85-1.00 1.15-1.35
6 - 0.95-1.10 1.15-1.40
7 - - 1.25-1.50
8 - - 1.30-1.50
Firing Rate at
140 psig
0.40 to 0.65 3 - -
0.60 to 0.75 4 3 -
0.70 to 0.85 5 4 -
0.75 to 1.00 - 5 2
0.95 to 1.20 - - 3
1.15 to 1.35 - - 4
1.25 to 1.50 - - 5
AFII 85 AFII 100 AFII 150
AIR
DIAL
SETTING
6
SK9644A
Page 7
Beckett
r
Instruction Manual – Model AFII Oil Burne
Prepare burner & site
Figure 4 - FBX Arrangement
FIRING
RATE
Head AFII 85 AFII 100 AFII 150
FB0 0.40-0.65 0.55-0.75 0.75-1.00
FB3 0.55-0.85 0.55-1.10 0.85-1.20
FB4 - 0.75-1.10 1.10-1.25
FB6 - 0.85-1.15 1.15-1.35
AIR
Firing Rate at
140 psig
0.40 to 0.65 3 - -
0.60 to 0.75 4 3 -
0.70 to 0.85 5 4 -
0.75 to 1.00 - 5 2
0.95 to 1.20 - - 3
1.15 to 1.35 - - 4
1.25 to 1.50 - - 5
AFII 85 AFII 100 AFII 150
DIAL
SETTING
SK9641
7
Page 8
Instruction Manual – Model AFII Oil Burner
Adjust, pipe, & wire burner
Beckett
Mount burner on appliance
Mounting options
• Bolt the burner to the appliance using the factory-mounted flange or an
adjustable flange.
Mounting dimensions
• When using the Beckett universal adjustable flange, mount the air tube at
a 2° downward pitch unless otherwise specified by the appliance
manufacturer.
• Verify that the air tube installed on the burner provides the correct
insertion depth. See Figure 5.
The end of the air tube should normally be ¼" back from the inside wall of
•
the combustion chamber. Never allow the leading edge of the head
assembly to extend into the chamber, unless otherwise specified by the
heating appliance manufacturer. Carefully measure the insertion depth
when using an adjustable flange. Verify the insertion depth when using a
welded flange.
Figure 5
– Mounting burner in appliance
Connect fuel lines
(continued)
WARNING
The oil supply inlet pressure to the fuel unit cannot exceed 3
psi. Install a pressure-limiting device in accordance with NFPA 31.
Fuel supply below the level of the burner
When the fuel supply is below the level of the burner, a two-pipe fuel supply
system is required. Depending on the fuel line diameter and horizontal and
vertical length, the installation may also require a two-stage pump. Consult the
fuel unit manufacturer's literature for lift and vacuum capability.
Fuel line installation
• Continuous lengths of heavy wall copper tubing are recommended.
Always use flare fittings. Never use compression fittings.
Always install fittings in accessible locations. Fuel lines should not run
•
against the appliance or the ceiling joists (to avoid vibration noise).
WARNING
Never use Teflon tape on any fuel fitting. Tape fragments can
lodge in fuel line components and fuel unit, damaging the equipment and
preventing proper operation.
Fuel line valve and filter
Install two high quality shutoff valves in accessible locations on the oil
•
supply line. Locate one close to the tank and the other close to the burner,
upstream of the filter.
NOTICE
Some states require these valves to be fusible-handle design
for protection in the event of fire. We recommend this as good industry
practice for all installations.
• Install a generous capacity filter inside the building between the fuel tank
shutoff valve and the burner, locating both the filter and the valve close to
the burner for ease of servicing. Filter should be rated for 50 microns or
less.
t
cket
Be
T
E
INL
H
T
I
W
Y
L
N
SE O
U
Y
A
L
E
D
N
O
VE
VAL
0
2
5
6
-
EA
A2
M
P
50 R
34
I
S
150 P
100-
H
P
G
4
L
E
U
F
R
E
T
H
G
LI
2 &
.
O
N
M
P
50 R
34
I
S
200 P
150H
P
G
3
L
E
U
F
O. 2
N
S
AS
P
-
BY
T
E
INL
c
e
unt
S
by
ade
M
t
t
e
k
c
Be
r
o
f
y
l
e
v
i
s
u
l
c
Ex
Connect fuel lines
Carefully follow the fuel unit manufacturer’s literature and the latest edition of
NFPA 31 for oil supply system specifications. If this information is unavailable,
use the following basic guidelines..
Fuel units with automatic bypass do not require a bypass plug.
NOTICE
WARNING
You must install this plug on two-pipe oil systems.
The burner fuel unit is shipped without the bypass plug installed.
install the plug in
DO NOT
the fuel unit if connected to a one-pipe oil system. Failure to comply could
cause fuel unit seal failure, oil leakage and potential fire and injury hazard.
Fuel supply level with or above burner
The burner may be equipped with a single-stage fuel unit for these
installations. Connect the fuel supply to the burner with a single supply line if
you want a one-pipe system (making sure the bypass plug is NOT installed in
the fuel unit.) Manual venting of the fuel unit is required on initial start-up. If
connecting a two-pipe fuel supply, install the fuel unit bypass plug.
Wire Burner
Burner packaged with appliance
• Refer to appliance manufacturer’s wiring diagram for electrical connections.
Burner applied at jobsite
Refer to Figures 6 and 7, page 9, for typical burner wiring, showing cad
•
cell primary controls. Burner wiring may vary, depending on primary
control actually used. The oil valve shown in Figures 6 and 7 may be an
optional feature.
NOTICE
All wiring must be in accordance with the latest revision of
National Electric Code NFPA 70 and local codes and regulations.
WARNING
The wiring diagrams in this manual are for general reference
only, and apply only to burners equipped with R8184G or R7184 primary
controls. For other controls, refer to the control manufacturer’s literature or the
diagrams supplied with the appliance. Failure to apply correct wiring could
result in severe personal injury, death or substantial property damage.
NOTICE
The R7184 primary control with valve-on delay (prepurge) and
burner motor-off delay (postpurge), shown in Figure 7, page 9, requires a
constant 120 VAC power source supplied to the
The
wire goes to the appliance limit circuit. Please note that other control
RED
wire on the control.
BLACK
manufacturers may use different wire colors for power and limit connections.
8
Page 9
Beckett
r
r
Instruction Manual – Model AFII Oil Burne
Adjust, pipe, & wire burne
Figure 6
Figure 7
– Typical wiring, R8184G or equivalent primary control
SK9437
– Typical wiring, R7184 or equivalent primary control
Do not attempt to start the burner when excess fuel or vapor
has accumulated in the appliance. Starting the burner under these conditions
could result in a puffback of hot combustion gases, high smoke levels, or
otherwise hazardous operation.
1. Open the shutoff valves in the oil supply line to the burner.
2. Open the air dial. This is an initial air setting for the pump bleeding
procedure only. Additional adjustments must be made with instruments.
3. Set the thermostat substantially above room temperature.
4. Close the line voltage switch to start the burner. If the burner does not
start immediately you may have to reset the safety switch of the burner
primary control.
5. Bleed air from the fuel unit as soon as burner motor starts rotating.
To bleed the fuel unit, attach a clear plastic hose over the vent fitting.
Loosen the fitting and catch the oil in an empty container. Tighten the
fitting when all air has been purged from the oil supply system.
If the burner locks out on safety during bleeding, reset the safety
•
switch and complete the bleeding procedure. Note — Electronic
safety switches can be reset immediately; others may require a threeto five-minute wait.
• If burner stops after flame is established, additional bleeding is
probably required. Repeat the bleeding procedure until the pump is
primed and a flame is established when the vent fitting is closed.
• For R7184 primary controls, see Technician’s Quick Reference Guide,
part number 61351 or 61465, for special pump priming sequence.
• Prepare for combustion tests by drilling a ¼" sampling hole in the flue
pipe between the appliance and the barometric draft regulator.
6.
Initial air adjustment
change firing pin on HLX ATC’s, if necessary) to obtain a clean flame.
Now the additional combustion tests with instruments can be made.
— Using a smoke tester, adjust the air dial (and
Set combustion with instruments
WARNING
The combustion must be adjusted using test instruments.
Failure to do so could result in burner or appliance failure, causing potential
severe personal injury, death or substantial property damage.
1. Let burner run for approximately 5 to 10 minutes.
2. Set the over-fire or stack draft to level specified by appliance manufacturer
(usually –0.01 to –0.02 inches w.c. over-fire for natural draft applications).
3. Follow these four steps to properly adjust the burner:
Step 1:
Step 2:
Step 3:
Step 4:
4. Once combustion is set, tighten all fasteners on air dial, rear access door
and escutcheon plate.
5. Start and stop the burner several times to ensure satisfactory operation.
Test the primary control and all other appliance safety controls to verify
that they function according to the manufacturer’s specifications.
10
Adjust air until a trace smoke level is achieved
At the trace of smoke level, measure the CO
the vital reference point for further adjustments.
Example: 13.5% CO
•
Increase the air to reduce CO
will be increased by approximately 1.4 to 2.7 percentage points.)
Example: Reduce CO
•
Recheck smoke level. It should be zero.
This procedure provides a margin of reserve air to accommodate
•
variable conditions.
• If the draft level has to be changed, recheck the smoke and CO
levels. Adjust the burner air if necessary.
(2.6% O2)
2
by 1 to 2 percentage points. (O2
2
from 13.5% to 11.5%. (O2 – 2.6% to 5.3%)
2
(or O2). This is
2
WARNING
This equipment must be serviced only by a qualified service
agency. The appropriate test instruments must be used. Failure to do so could
result in burner or appliance failure, causing potential severe personal injury,
death or substantial property damage.
Replace the oil supply line filter. The line filter cartridge must be replaced
to avoid contamination of the fuel unit and nozzle.
Inspect the oil supply system. All fittings should be leak-tight. The supply
lines should be free of water, sludge and other restrictions.
Remove and clean the pump strainer if applicable.
Replace the nozzle with an equivalent nozzle.
Clean and inspect the electrodes for damage, replacing any that are
cracked or chipped.
Check electrode tip settings. Replace electrodes if tips are rounded.
Inspect the igniter cables and connections.
Clean the cad cell grid surface, if necessary.
Make sure the burner housing baffle is in place if required for the burner
application (AFII 85 & AFII 100). Omitting the baffle can result in
unacceptable burner combustion.
Inspect all gaskets. Replace any that are damaged or would fail to seal
adequately.
Clean the blower wheel, air inlet, air guide, and retention head of any lint
or foreign material.
If motor is not permanently lubricated, oil motor with a few drops of SAE
20 nondetergent oil at each oil hole. DO NOT over oil motor. Excessive
oiling can cause motor failure.
Check motor current. The amp draw should not exceed the nameplate
rating by more than 10%.
Check all wiring for secure connections or insulation breaks.
Check the pump pressure and cutoff function.
Check primary control safety lockout timing.
Check ignition system for proper operation.
Inspect the vent system and chimney for soot accumulation or other
restriction.
Clean the appliance thoroughly according to the manufacturer's
recommendations.
Check the burner performance. Refer to the section “Set combustion
with instruments
It is good practice to make a record of the service performed and the
combustion test results.
”.
To replace the blower wheel:
1. Turn off all power to the burner before servicing.
2. Disconnect the burner motor wires.
3. Remove the bolts securing the blower motor to
the housing.
4. Remove the blower motor and wheel.
5. Remove the existing wheel.
6. As shown at right, slide the new blower wheel
onto the shaft.
• Place a .062" (1/16" ± 1/64") feeler gauge on
2
the motor as shown.
Slide blower wheel toward motor until it
•
contacts feeler gauge.
Rotate the wheel until the setscrew is
•
centered on the flat of the motor shaft.
Tighten the setscrew to secure the wheel.
7. DO NOT use any motor other than the original equipment type motor.
Install the motor on the burner housing. Tighten screws. Reconnect wires.
8.
9. Restore power, start the burner and perform combustion tests. Refer to
the section “
Set combustion with instruments”.
Beckett
SK9190A
Page 11
Beckett
r
r
Instruction Manual – Model AFII Oil Burne
Replacement parts
PART DESCRIPTION PART NO.
Air tube combination (ATC) – see Table 1 Specify
Blower wheel: AFII 85 (4¼” x 2” strip)
AFII 100 (4½” x 2” tablock)
AFII 150 (4½” x 2” tablock)
Box, 4x4 wiring 31613BK
Connector tube, 8” long, copper 5394U
Coupling, motor to pump 21437U
Electrodes: replacement kit (HLX heads)
experienced with all codes and ordinances, who is responsible for the
installation and adjustment of the equipment.
• Have your equipment inspected at regular intervals by a qualified
•
• Incorrect operation of the burner could result in severe personal
The following could result in fire hazard, severe personal injury, death or
substantial property damage. Read carefully.
• Never attempt to use gasoline in your heating appliance.
• Never store gasoline or combustible materials near the burner or
• Never
• Never attempt to light the burner/appliance by throwing burning material
• Never attempt to use crankcase or waste oil or material other than the
• Never
The Oilheat Manufacturers' Association supports the use of low sulfur fuels as defined by ASTM D396, Grades No. 1 Low Sulfur and No. 2 Low Sulfur, as
the preferred heating fuel for the following reasons:
• Low sulfur fuels reduce deposits on heat exchanger surfaces, extending the service interval between cleanings.
Properly installed and maintained, your
efficient, trouble-free operation. Please take care of your equipment by
following the warnings provided and by doing the following (notify your
qualified service agency if you find anything wrong):
Regular Service
Have your burner/heating appliance serviced annually by your qualified
•
service agency, unless an extended service interval has been
determined as follows.
• With properly configured burners, there are special Clearburn® practices
(such as low sulfur fuels, fuel additive programs, outside combustion air,
high effectiveness filtration, etc.) that can extend service intervals.
Discuss this with your qualified service agency to determine the proper
regular service interval for your heating system.
Daily
• Check the room in which your burner/appliance is installed. Make sure:
air ventilation openings are clean and unobstructed
nothing is blocking the burner inlet air openings
no combustible materials are stored near the heating appliance
there are no signs of oil or water leakage around the burner or
appliance
Weekly
• Check your oil tank level. Always keep your oil tank full, especially
during the summer, in order to prevent condensation of moisture on the
inside surface of the tank.
burner will provide years of
AFII
Warranty
Beckett warrants its equipment specifically to those who have purchased it for
resale, including your qualified service agency (dealer). In the event of any
problems with your equipment or its installation, you should contact your
dealer for assistance.
CORPORATION
12
Bar code
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.