Beckett 100, AFII 85, 150 User Manual

Page 1
MODEL
A
Instruction Manual
AFII 85, AFII 100, AFII 150 Types “HLX” & “FBX” air tube combinations
Voltage: 120 Vac / 60 Hz
AFII burner with type “HLX” air tube
Type “FBX” air tube combinations
A
Oil Burner
FII
Beckett
Page 2
Instruction Manual – Model AFII Oil Burner
Beckett
Contents
Prepare before installing
Prepare burner & site
Adjust, pipe, & wire burner
Startup & adjust burner
Service & maintain burner
Verify specifications ……………………………….…………………..…….………….. 3 Be aware of hazard definitions …………….…………….…..………..……………….. 3 Check certifications/approvals ……………………………………..…………………... 3 Notice special requirements ………………….…………...…………..……………….. 3
Inspect/prepare installation site ……………………...…………..………………….… 4 Prepare burner ……………………………...…..…………………..…………………… 5 HLX arrangement……………….…………….………………………..………………... 6 FBX arrangement …………………………………….….…………..………………….. 7
Mount burner on appliance ………………………………..…………..……………….. 8 Connect fuel lines ………………………………………………………..……………… 8 Wire burner ………………………………………………………………..……………... 8, 9
Startup burner/set combustion ………..……………..….…………..…………………. 10 Set combustion with instruments …………..………….…………..…………………... 10
Perform regular maintenance …………………..……….……………..……….……… 10 To replace the blower wheel ………………………..……………….…………………. 10 Replacement parts ………………………………………………………………………. 11 Owner’s information and warranty ………………………………….………….……… 12
– Air Tube Combination (ATC) codes
Table 1
HLX30 HLX50 HLX70 HLX90 HB AF2-6 0.40-0.85 gph 0.65-1.00 gph 0.75-1.35 gph
USABLE AIR TUBE LENGTH DIM. “A” (see Fig. 5) FIRING RATE RANGE
3” 5” 7” 9” ATC Code Head AFII 85 AFII 100 AFII 150
Head Design – Adjustable w/ stop screw – typical applications: Wet base boilers
HLX30 HLX50 HLX70 HLX90 HC AF2-9 N/A 0.65-1.00 gph 0.75-1.50 gph
AFII AIR TUBE COMBINATION AND FIRING RATE CHART
HLX30 HLX50 HLX70 HLX90 HD AF2-6 0.40-0.85 gph 0.65-1.00 gph 0.75-1.10 gph
HLX30 HLX50 HLX70 HLX90 HE AF2-9 N/A 0.65-1.00 gph 0.75-1.35 gph
FBX30
FBX30 FBX50 FBX70 FBX90 HHXS FB4 N/A 0.75-1.10 gph 1.10-1.25 gph
2
FBX30 FBX50 FBX70 FBX90 HGXS FB3 0.55-0.85 gph 0.55-1.10 gph 0.85-1.20 gph
FBX30 FBX50 FBX70 FBX90 HIXS FB6 N/A 0.85-1.15 gph 1.15-1.35 gph
Head Design – Fixed – typical applications: Furnaces, Dry base boilers, Water heaters
FBX50 FBX70
FBX90
HFXS FB0
0.40-0.65 gph 0.55-0.75 gph 0.75-1.00 gph
Page 3
Beckett
r
Capacity
“HLX” heads
Firing rate ..……..……………....…... 0.40 – 1.50 GPH
Input ..………..….…………… 56,000 – 210,000 Btu/h
“FBX” heads
Firing rate ..…..……………………… 0.40 - 1.35 GPH
Input ..………….…..………….56,000 – 189,000 Btu/h
Fuels U. S.
Electrical
…. No. 1 or No. 2 heating oil only (ASTM D396)
Canada
….... No. 1 stove oil or No. 2 furnace oil only
Power supply ....…….... 120 VAC/60 Hz/single phase
Operating load ……….… 5.8 Amps maximum; Note 1
Motor …..……… ……………………..1/7 hp, 3450 rpm
……….……...…… rotation CW when facing shaft end
Ignition .……... Continuous duty iron-core transformer
………..... Continuous duty solid state igniter
Fuel unit
Air tube
Dimensions
OR
Outlet pressure ………..…..……………………. Note 2
ATC code ……………………….. See Table 1, page 2
Height (maximum) ……….…….….…………13 inches
Width (maximum) ………….………..….. …..14 inches
Depth (chassis only) ………….……….6-11/16 inches
Air tube diameter ………………………….3 ½ inches
Note 1. A burner with an electronic igniter will have a lower operating current. The actual load should be determined by a current meter.
Note 2. See appliance manufacturer’s burner specifications for recommended outlet pressure. Pressure is 140 psig unless otherwise noted.
SK9642
Instruction Manual – Model AFII Oil Burne
Prepare before installing
Be aware of hazard definitions Verify specifications
DANGER
Denotes presence of a hazard which, if ignored, will result in
severe personal injury, death, or substantial property damage.
WARNING
severe personal injury, death, or substantial property damage.
CAUTION
minor personal injury or property damage.
related to personal injury or property damage.
Check certifications/approvals
Underwriters Laboratories has certified this burner to comply with
State and local approvals are shown on burner rating label (see below).
All oil burners should be installed in accordance with regulations of
For recommended installation practice in Canada, refer to the latest
Notice special requirements
This equipment must be installed, adjusted and started only by a experienced with all codes and ordinances, who is responsible for the installation and adjustment of the equipment. The installation must comply with all local codes and ordinances and with the latest revision of the National Fire Protection Standard for Oil-Burning Equipment, NFPA 31 (or CSA B139).
WARNING
Read all instructions before proceeding. Follow all instructions completely. Failure to follow these instructions could result in equipment malfunction, causing severe personal injury, death or substantial property damage.
or controls during unpacking, notify the carrier at once and file the appropriate claim.
When contacting Beckett for service information — Please record the burner serial number (and have available when calling or writing). You will find the serial number on the silver label located on the top right of the burner, to the left of the air dial. See illustration below.
Denotes presence of a hazard which, if ignored, could result in
Denotes presence of a hazard which, if ignored, could result in
NOTICE
Intended to bring special attention to information, but not
ANSI/UL 296 and has listed it for use with #1 or #2 fuel oil as specified in ASTM D396. Low sulfur #1 and #2 fuel oils reduce heat exchanger
deposits with all burners compared to the standard fuels. Reduced deposits extend the service interval for cleaning and improve the efficiency of the appliance over time. Low sulfur fuels reduce particulate and oxides of nitrogen emissions as well. The Oilheat Manufacturers' Association recommends these fuels as the preferred fuels for this burner.
the latest revision of the National Fire Protection Association Standard NFPA 31 and in complete accordance with all local codes and authorities having jurisdiction. Regulation of these authorities take precedence over the general instructions provided in this installation manual.
version of CSA Standard B139.
DANGER
qualified service agency
NOTICE
Concealed damage
– an individual or agency, licensed and
— If you discover damage to the burner
3
Page 4
Instruction Manual – Model AFII Oil Burner
Prepare burner & site
Beckett
Inspect/prepare installation site Inspect/prepare installation site
Chimney or vent
Inspect the chimney or vent, making sure it is properly sized and in good condition for use.
For those installations not requiring a chimney, such as through-the-wall
vented appliances, follow the instructions given by the appliance and power venter (if used) manufacturers.
Direct air supply and sidewall venting
When sidewall venting appliances, carefully follow appliance and power venter instructions for installation and wiring.
AFII burners are equipped with a removable air inlet to allow use of a 4” duct to supply outside air for combustion. Do not exceed 70 equivalent feet. Allow 6 feet for each elbow.
1. Remove the inlet cover.
2. Insert 4" duct into the inlet ring.
3. Fasten duct into place using at least 3 sheet metal screws evenly spaced around the inlet ring. Refer to Figure 1.
4. Remove the barometric draft control unless it is in the same atmospheric pressure zone as the inlet.
On the outside of the home use a 90° elbow pointed downward with a 1/4" mesh screen over its opening. The air inlet elbow must be located above the snow line and in such a way as to prevent leaves and/or other debris from blocking the air flow. Such debris will prevent proper operation of the burner. Refer to local codes for proper location of inlet.
Figure 1
– Outside air connection
4 IN. DUCT
AIR INLET ELBOW
Exhaust fans and other air-using devices
Size air openings large enough to allow for all air-using devices in addition to the minimum area required for combustion air. If there is any possibility of the equipment room developing negative pressure (because of exhaust fans or clothes dryers, for example), pipe combustion air directly to the burner.
Clearances to burner and appliance
Provide space around burner and appliance for easy service and maintenance.
Check minimum clearances against those shown by the appliance manufacturer and by applicable building codes.
Combustion chamber — Burner retrofitting
Verify that the appliance combustion chamber provides at least the minimum dimensions given in Table 2.
CAUTION
When retrofitting an appliance that has an unlined stainless steel combustion chamber, chamber burnout could result from the use of a high performance burner. Protect the chamber from high temperatures through the use of "wet-pac" or a similar ceramic liner. Some equipment may utilize a stainless steel combustion chamber that has been designed and tested by the manufacturer for use with a flame retention burner, therefore ceramic protection would not be necessary. Refer to appliance manufacturer’s instructions. Failure to comply could result in damage to heating equipment.
– Minimum combustion chamber dimensions
Table 2
(continued)
¼” MESH SCREEN
INLET RING
Combustion air supply
See NFPA Standard 31 for complete details.
WARNING
If the burner is not supplied with a reliable combustion air source, the burner cannot properly burn the fuel. This would result in incomplete combustion, causing sooting and possible emission of carbon monoxide. Severe personal injury, death or substantial property damage could occur.
Appliance located in confined space
The confined space should have two (2) permanent openings: one near the top of the enclosure and one near the bottom of the enclosure. Each opening shall have a free area of not less than (1) one square inch per 1,000 BTU’s per hour of the total input rating of all appliances within the enclosure. The openings shall have free access to the building interior, which should have adequate infiltration from the outside.
Firing
rate
(gph)
0.50
0.75
1.00
1.25
1.50
Chamber dimension (inches)
Round
I.D.
Rectangular
Width Length
Height
Floor to
nozzle
8 7 8 12 5-6
9 8 9 12 5-6
10 9 10 12 ½ 5-6
11 10 11 12 ½ 5-6
12 11 12 13 6-7
4
Page 5
Beckett
r
Instruction Manual – Model AFII Oil Burne
Prepare burner & site
Prepare burner
Burner fuel unit
Verify that the burner fuel unit is compatible with the oil supply system. For more details, refer to “Connect fuel lines” on page 8.
Attach air tube (if not already installed)
If using a flange and gasket, slide them onto the air tube. Then attach the air tube to the burner chassis using the sheet metal screws provided. See Figures 3 & 4 on pages 6 & 7 for details.
Install burner nozzle (if not already installed)
WARNING
Make certain the nozzle is selected for the fuel unit pressure used. For applications with fuel unit pressure above 100 psig, the nozzle rated capacity will be less than the appliance firing rate. Use only the specified spray pattern unless combustion test results indicate the need for a change. Failure to use the correct nozzle size and type can result in unacceptable combustion, possibly causing severe personal injury, death or substantial property damage.
1. Remove the plastic plug protecting the nozzle adapter threads
2. Place a ¾” open-end wrench on the nozzle adapter. Insert the nozzle into
the adapter and finger tighten. Finish tightening with a wrench. Use care to avoid bending the burner head support legs or electrodes. See
3. If you remove the head to replace the nozzle (type “HLX” heads), carefully
reconnect the head to the nozzle adapter, making sure to butt the head support to the nozzle adapter shoulder (see Figure 3, page 6).
If the nozzle is already installed, remove the nozzle line assembly to verify that the nozzle size and spray pattern are correct for the application (per appliance manufacturer’s information or Beckett OEM Specification Guide, part number
6711). Verify that the electrode tip settings comply with Figure 2a or 2b.
If the nozzle is not installed, obtain a nozzle of the manufacturer, capacity and spray angle specified in appliance manufacturer’s information or Beckett OEM
Specification Guide
information is not available for the application:
4. Refer to table below to select the mid-range nozzle spray angle for the
head type being used.
5. Fire the burner and make sure the combustion is acceptable and the
flame is not impinging on chamber surfaces.
6. If a shorter flame is needed, select a wider spray angle. If a longer flame
is needed, select a narrower spray angle.
7. Either hollow or solid spray patterns may be used. If combustion results
are not satisfactory with the selected spray pattern, try the other pattern.
CAUTION
, part number 6711. For conversions or upgrades, when
Recommended nozzle spray angles “HLX” heads “FBX” heads
, below.
45°, 60°, or 70° nozzle 60°, 70°, or 80° nozzle
Use care when removing and installing oil nozzles:
CAUTION
Inspect the nozzle adapter before installing nozzle. If it is grooved or scratched on the sealing surface, replace the nozzle line assembly. Otherwise, oil could leak at the nozzle-adapter joint, causing serious combustion problems.
Protect the nozzle orifice and strainer when installing. If the orifice gets
dirt in it or is scratched, the nozzle will not function properly. Do not over-torque the nozzle when installing. This will cause deep
grooves in the nozzle adapter, preventing a seal when a new nozzle is installed.
open-end
Use a wrench or vise to hold the nozzle adapter. DO NOT attempt to remove or replace nozzle without holding adapter. The nozzle alignment could be seriously damaged. Use a nozzle wrench that secures the adapter or use
Do not squeeze the electrodes too tightly when handling the nozzle line assembly. This could change the electrode tip settings or damage the ceramic electrode insulators.
Carefully check and realign electrode tips after replacing nozzle, ensuring the electrode settings comply with Figure 2a or 2b.
3
/4" and 5/8" open-end wrenches.
Check/adjust electrodes
Check the electrode tip settings. Adjust if necessary to comply with the dimensions shown in Figure 2a or Figure 2b. To adjust, loosen the electrode clamp screw and slide/rotate electrodes as necessary. Securely tighten the clamp screw when finished.
Figure 2a
– Electrode settings – HLX Air Tube Combinations
Figure 2b
– Electrode settings – FBX Air Tube Combinations
Servicing nozzle line assembly
1. Turn off power to burner before proceeding.
2. Disconnect copper oil connector tube from nozzle line.
3. Loosen the screw that fastens the rear access door.
4. Remove splined nut.
5. Remove the nozzle line assembly from the burner, being careful not to
damage the electrodes or insulators while handling. Stop halfway to remove igniter/transformer wires.
6. To replace the nozzle assembly, reverse the above steps.
HLX” head air tubes – Be sure stop screw is fastened securely. Seat stop screw on back of choke ring to set the position of the head.
” head air tubes – Use T gauge to set the “Z” dimension to 1-1/8” +/-
FBX
1/32”.
5
Page 6
Instruction Manual – Model AFII Oil Burner
Prepare burner & site
Figure 3 - HLX Arrangement
Beckett
FIRING
RATE
Stop Screw AFII 85 AFII 100 AFII 150
0 0.40-0.65 0.50-0.65 0.75-1.00
1 - 0.60-0.75 0.85-1.10
2 - 0.65-0.80 0.95-1.15
3 0.60-0.75 0.65-0.90 0.95-1.20
4 - 0.75-0.95 1.10-1.25
5 0.70-0.85 0.85-1.00 1.15-1.35
6 - 0.95-1.10 1.15-1.40
7 - - 1.25-1.50
8 - - 1.30-1.50
Firing Rate at
140 psig
0.40 to 0.65 3 - -
0.60 to 0.75 4 3 -
0.70 to 0.85 5 4 -
0.75 to 1.00 - 5 2
0.95 to 1.20 - - 3
1.15 to 1.35 - - 4
1.25 to 1.50 - - 5
AFII 85 AFII 100 AFII 150
AIR
DIAL
SETTING
6
SK9644A
Page 7
Beckett
r
Instruction Manual – Model AFII Oil Burne
Prepare burner & site
Figure 4 - FBX Arrangement
FIRING
RATE
Head AFII 85 AFII 100 AFII 150
FB0 0.40-0.65 0.55-0.75 0.75-1.00
FB3 0.55-0.85 0.55-1.10 0.85-1.20
FB4 - 0.75-1.10 1.10-1.25
FB6 - 0.85-1.15 1.15-1.35
AIR
Firing Rate at
140 psig
0.40 to 0.65 3 - -
0.60 to 0.75 4 3 -
0.70 to 0.85 5 4 -
0.75 to 1.00 - 5 2
0.95 to 1.20 - - 3
1.15 to 1.35 - - 4
1.25 to 1.50 - - 5
AFII 85 AFII 100 AFII 150
DIAL
SETTING
SK9641
7
Page 8
Instruction Manual – Model AFII Oil Burner
Adjust, pipe, & wire burner
Beckett
Mount burner on appliance
Mounting options
Bolt the burner to the appliance using the factory-mounted flange or an adjustable flange.
Mounting dimensions
When using the Beckett universal adjustable flange, mount the air tube at a 2° downward pitch unless otherwise specified by the appliance manufacturer.
Verify that the air tube installed on the burner provides the correct insertion depth. See Figure 5.
The end of the air tube should normally be ¼" back from the inside wall of
the combustion chamber. Never allow the leading edge of the head assembly to extend into the chamber, unless otherwise specified by the heating appliance manufacturer. Carefully measure the insertion depth when using an adjustable flange. Verify the insertion depth when using a welded flange.
Figure 5
– Mounting burner in appliance
Connect fuel lines
(continued)
WARNING
The oil supply inlet pressure to the fuel unit cannot exceed 3
psi. Install a pressure-limiting device in accordance with NFPA 31.
Fuel supply below the level of the burner
When the fuel supply is below the level of the burner, a two-pipe fuel supply system is required. Depending on the fuel line diameter and horizontal and vertical length, the installation may also require a two-stage pump. Consult the fuel unit manufacturer's literature for lift and vacuum capability.
Fuel line installation
Continuous lengths of heavy wall copper tubing are recommended.
Always use flare fittings. Never use compression fittings.
Always install fittings in accessible locations. Fuel lines should not run
against the appliance or the ceiling joists (to avoid vibration noise).
WARNING
Never use Teflon tape on any fuel fitting. Tape fragments can lodge in fuel line components and fuel unit, damaging the equipment and preventing proper operation.
Fuel line valve and filter
Install two high quality shutoff valves in accessible locations on the oil
supply line. Locate one close to the tank and the other close to the burner, upstream of the filter.
NOTICE
Some states require these valves to be fusible-handle design for protection in the event of fire. We recommend this as good industry practice for all installations.
Install a generous capacity filter inside the building between the fuel tank shutoff valve and the burner, locating both the filter and the valve close to the burner for ease of servicing. Filter should be rated for 50 microns or less.
t
cket
Be
T
E
INL
H T I
W
Y L N
SE O U
Y A L
E D
N O VE
VAL
0
2
5
6
-
EA
A2
M P
50 R
34 I S
150 P
100-
H
P G 4
L E U
F R E
T H G
LI
2 &
.
O
N
M P
50 R
34 I S
200 P
150­H P
G
3
L E U
F
O. 2
N
S
AS
P
-
BY
T E
INL
c
e unt
S
by
ade
M
t t
e k c
Be
r o f
y l
e v i s u
l c
Ex
Connect fuel lines
Carefully follow the fuel unit manufacturer’s literature and the latest edition of NFPA 31 for oil supply system specifications. If this information is unavailable, use the following basic guidelines..
Fuel units with automatic bypass do not require a bypass plug.
NOTICE
WARNING
You must install this plug on two-pipe oil systems.
The burner fuel unit is shipped without the bypass plug installed.
install the plug in
DO NOT
the fuel unit if connected to a one-pipe oil system. Failure to comply could cause fuel unit seal failure, oil leakage and potential fire and injury hazard.
Fuel supply level with or above burner
The burner may be equipped with a single-stage fuel unit for these installations. Connect the fuel supply to the burner with a single supply line if you want a one-pipe system (making sure the bypass plug is NOT installed in the fuel unit.) Manual venting of the fuel unit is required on initial start-up. If connecting a two-pipe fuel supply, install the fuel unit bypass plug.
Wire Burner
Burner packaged with appliance
Refer to appliance manufacturer’s wiring diagram for electrical connections.
Burner applied at jobsite
Refer to Figures 6 and 7, page 9, for typical burner wiring, showing cad
cell primary controls. Burner wiring may vary, depending on primary control actually used. The oil valve shown in Figures 6 and 7 may be an optional feature.
NOTICE
All wiring must be in accordance with the latest revision of National Electric Code NFPA 70 and local codes and regulations.
WARNING
The wiring diagrams in this manual are for general reference only, and apply only to burners equipped with R8184G or R7184 primary
controls. For other controls, refer to the control manufacturer’s literature or the diagrams supplied with the appliance. Failure to apply correct wiring could result in severe personal injury, death or substantial property damage.
NOTICE
The R7184 primary control with valve-on delay (prepurge) and burner motor-off delay (postpurge), shown in Figure 7, page 9, requires a constant 120 VAC power source supplied to the The
wire goes to the appliance limit circuit. Please note that other control
RED
wire on the control.
BLACK
manufacturers may use different wire colors for power and limit connections.
8
Page 9
Beckett
r
r
Instruction Manual – Model AFII Oil Burne
Adjust, pipe, & wire burne
Figure 6
Figure 7
– Typical wiring, R8184G or equivalent primary control
SK9437
– Typical wiring, R7184 or equivalent primary control
SK9359
power before servicing.
Electrical shock hazard. Disconnect
power before servicing.
– R7184 primary control features
Table 5
Feature R7184A R7184B R7184P
Interrupted ignition YES YES YES
Limited reset, limited recycle YES YES YES
Diagnostic LED, cad cell indicator YES YES YES
Valve-on delay YES YES
Burner motor-off delay YES
Alarm contacts Optional
DANGER
DANGER
Electrical shock hazard. Disconnect
9
Page 10
Instruction Manual – Model AFII Oil Burner
Startup & adjust burner Service & maintain burner
Startup burner/set combustion Perform regular maintenance
WARNING
Do not attempt to start the burner when excess fuel or vapor has accumulated in the appliance. Starting the burner under these conditions could result in a puffback of hot combustion gases, high smoke levels, or otherwise hazardous operation.
1. Open the shutoff valves in the oil supply line to the burner.
2. Open the air dial. This is an initial air setting for the pump bleeding procedure only. Additional adjustments must be made with instruments.
3. Set the thermostat substantially above room temperature.
4. Close the line voltage switch to start the burner. If the burner does not start immediately you may have to reset the safety switch of the burner primary control.
5. Bleed air from the fuel unit as soon as burner motor starts rotating. To bleed the fuel unit, attach a clear plastic hose over the vent fitting. Loosen the fitting and catch the oil in an empty container. Tighten the fitting when all air has been purged from the oil supply system.
If the burner locks out on safety during bleeding, reset the safety
switch and complete the bleeding procedure. Note — Electronic safety switches can be reset immediately; others may require a three­to five-minute wait.
If burner stops after flame is established, additional bleeding is
probably required. Repeat the bleeding procedure until the pump is primed and a flame is established when the vent fitting is closed.
For R7184 primary controls, see Technician’s Quick Reference Guide,
part number 61351 or 61465, for special pump priming sequence.
Prepare for combustion tests by drilling a ¼" sampling hole in the flue
pipe between the appliance and the barometric draft regulator.
6.
Initial air adjustment
change firing pin on HLX ATC’s, if necessary) to obtain a clean flame. Now the additional combustion tests with instruments can be made.
— Using a smoke tester, adjust the air dial (and
Set combustion with instruments
WARNING
The combustion must be adjusted using test instruments.
Failure to do so could result in burner or appliance failure, causing potential severe personal injury, death or substantial property damage.
1. Let burner run for approximately 5 to 10 minutes.
2. Set the over-fire or stack draft to level specified by appliance manufacturer (usually –0.01 to –0.02 inches w.c. over-fire for natural draft applications).
3. Follow these four steps to properly adjust the burner:
Step 1: Step 2:
Step 3:
Step 4:
4. Once combustion is set, tighten all fasteners on air dial, rear access door and escutcheon plate.
5. Start and stop the burner several times to ensure satisfactory operation. Test the primary control and all other appliance safety controls to verify that they function according to the manufacturer’s specifications.
10
Adjust air until a trace smoke level is achieved At the trace of smoke level, measure the CO
the vital reference point for further adjustments.
Example: 13.5% CO
Increase the air to reduce CO
will be increased by approximately 1.4 to 2.7 percentage points.)
Example: Reduce CO
Recheck smoke level. It should be zero.
This procedure provides a margin of reserve air to accommodate
variable conditions.
If the draft level has to be changed, recheck the smoke and CO levels. Adjust the burner air if necessary.
(2.6% O2)
2
by 1 to 2 percentage points. (O2
2
from 13.5% to 11.5%. (O2 – 2.6% to 5.3%)
2
(or O2). This is
2
WARNING
This equipment must be serviced only by a qualified service agency. The appropriate test instruments must be used. Failure to do so could result in burner or appliance failure, causing potential severe personal injury, death or substantial property damage.
Replace the oil supply line filter. The line filter cartridge must be replaced
to avoid contamination of the fuel unit and nozzle.
Inspect the oil supply system. All fittings should be leak-tight. The supply
lines should be free of water, sludge and other restrictions.
Remove and clean the pump strainer if applicable.
Replace the nozzle with an equivalent nozzle.
Clean and inspect the electrodes for damage, replacing any that are
cracked or chipped.
Check electrode tip settings. Replace electrodes if tips are rounded.
Inspect the igniter cables and connections.
Clean the cad cell grid surface, if necessary.
Make sure the burner housing baffle is in place if required for the burner
application (AFII 85 & AFII 100). Omitting the baffle can result in unacceptable burner combustion.
Inspect all gaskets. Replace any that are damaged or would fail to seal
adequately.
Clean the blower wheel, air inlet, air guide, and retention head of any lint
or foreign material.
If motor is not permanently lubricated, oil motor with a few drops of SAE
20 nondetergent oil at each oil hole. DO NOT over oil motor. Excessive oiling can cause motor failure.
Check motor current. The amp draw should not exceed the nameplate
rating by more than 10%.
Check all wiring for secure connections or insulation breaks.
Check the pump pressure and cutoff function.
Check primary control safety lockout timing.
Check ignition system for proper operation.
Inspect the vent system and chimney for soot accumulation or other
restriction.
Clean the appliance thoroughly according to the manufacturer's
recommendations.
Check the burner performance. Refer to the section “Set combustion
with instruments
It is good practice to make a record of the service performed and the combustion test results.
”.
To replace the blower wheel:
1. Turn off all power to the burner before servicing.
2. Disconnect the burner motor wires.
3. Remove the bolts securing the blower motor to the housing.
4. Remove the blower motor and wheel.
5. Remove the existing wheel.
6. As shown at right, slide the new blower wheel onto the shaft.
Place a .062" (1/16" ± 1/64") feeler gauge on
2
the motor as shown.
Slide blower wheel toward motor until it
contacts feeler gauge.
Rotate the wheel until the setscrew is
centered on the flat of the motor shaft. Tighten the setscrew to secure the wheel.
7. DO NOT use any motor other than the original equipment type motor.
Install the motor on the burner housing. Tighten screws. Reconnect wires.
8.
9. Restore power, start the burner and perform combustion tests. Refer to
the section “
Set combustion with instruments”.
Beckett
SK9190A
Page 11
Beckett
r
r
Instruction Manual – Model AFII Oil Burne
Replacement parts
PART DESCRIPTION PART NO. Air tube combination (ATC) – see Table 1 Specify Blower wheel: AFII 85 (4¼” x 2” strip)
AFII 100 (4½” x 2” tablock) AFII 150 (4½” x 2” tablock)
Box, 4x4 wiring 31613BK Connector tube, 8” long, copper 5394U Coupling, motor to pump 21437U Electrodes: replacement kit (HLX heads)
replacement kit (FBX heads) Escutcheon plate: AFII (blank)
AFII (140 PSI) Flange kit, adjustable 3½” I.D. with gasket 51480 Fuel pump: A2VA7116 (Suntec)
A2EA6520N621L (CleanCut) cordset BFPH071N1161 (Danfoss)
Gasket, flange 31658 Head (FBX): FB0, FB3, FB4, or FB6 Specify Head (HLX) assembly: AFII 6 slot head
AFII 9 slot head
Service & main burn
21439U 21438U 21438U
51484U 51670U
31623 3162302
2460U 2184404U 21808 21391U
51671U 51672U
tain e
PART DESCRIPTION PART NO. Head insulator kit (FB0, 3, 4, 6 heads only) 51685 Igniter, AFII electronic 51805U Inlet air scoop, plastic, sound insulated 51485 Main housing assy, with hole plug: AFII 85
AFII 100 AFII 150
Motor: 1/7 hp, 3450 rpm, 115V / 60Hz 21444U Nozzle adapter 213 Nozzle line electrode head assembly Specify ATC Pedestal kit, AFII mounting 51481 Primary R7184A - interrupted ignition
Control R7184B - valve-on delay R7184P - valve-on/motor off delay R7184P - with alarm contacts
Rear access door 51424U Stop screw: replacement kit 51483 Splined nut 3666
SK8265B
51584U 51584U 51476U
7455U 7456U 7457U 7458U
11
Page 12
Instruction Manual – Model AFII Oil Burner
_
_
Service & maintain burner
Beckett
Owner’s information
WARNING
qualified service agency
experienced with all codes and ordinances, who is responsible for the installation and adjustment of the equipment.
Have your equipment inspected at regular intervals by a qualified
Incorrect operation of the burner could result in severe personal
The following could result in fire hazard, severe personal injury, death or substantial property damage. Read carefully.
Never attempt to use gasoline in your heating appliance.
Never store gasoline or combustible materials near the burner or
Never
Never attempt to light the burner/appliance by throwing burning material
Never attempt to use crankcase or waste oil or material other than the
Never
The Oilheat Manufacturers' Association supports the use of low sulfur fuels as defined by ASTM D396, Grades No. 1 Low Sulfur and No. 2 Low Sulfur, as the preferred heating fuel for the following reasons:
Low sulfur fuels reduce deposits on heat exchanger surfaces, extending the service interval between cleanings.
Low sulfur fuels reduce particulate emissions.
_________________________________________________________________
Form Number 6104BAFII R0803
Printed in U.S.A. © 2003 R.W. Beckett Corporation
This burner must be installed, adjusted and started only by a
— an individual or agency, licensed and
service agency to assure continued proper operation.
Installation and adjustment of the burner requires technical knowledge
and the use of combustion test instruments. or controls. Call your qualified service agency.
injury, death or substantial property damage.
appliance.
attempt to burn
into the appliance.
approved fuel oils in this burner.
restrict the air inlet openings to the burner or the combustion air
ventilation openings in the room.
The reduced deposits increase the efficiency of the appliance.
Low sulfur fuels reduce oxides of nitrogen emissions.
garbage or refuse
R.W.
Do not tamper
in your appliance.
BECKETT
with the unit
U.S.A.: P.O. Box 1289 Elyria, Ohio 44036
Canada: R.W. Beckett Canada, Ltd. Unit #3, 430 Laird Road Guelph, Ontario N1G 3X7
Owner service and maintenance
Properly installed and maintained, your efficient, trouble-free operation. Please take care of your equipment by following the warnings provided and by doing the following (notify your qualified service agency if you find anything wrong):
Regular Service
Have your burner/heating appliance serviced annually by your qualified
service agency, unless an extended service interval has been determined as follows.
With properly configured burners, there are special Clearburn® practices
(such as low sulfur fuels, fuel additive programs, outside combustion air, high effectiveness filtration, etc.) that can extend service intervals. Discuss this with your qualified service agency to determine the proper regular service interval for your heating system.
Daily
Check the room in which your burner/appliance is installed. Make sure:
air ventilation openings are clean and unobstructed nothing is blocking the burner inlet air openings no combustible materials are stored near the heating appliance there are no signs of oil or water leakage around the burner or
appliance
Weekly
Check your oil tank level. Always keep your oil tank full, especially
during the summer, in order to prevent condensation of moisture on the inside surface of the tank.
burner will provide years of
AFII
Warranty
Beckett warrants its equipment specifically to those who have purchased it for resale, including your qualified service agency (dealer). In the event of any problems with your equipment or its installation, you should contact your dealer for assistance.
CORPORATION
12
Bar code
Loading...