BEA IXIO-DO1 I User Manual

Page 1
2
1
5
6
7
8
4
9
3
IXIO-DO1 I
1. LCD
2. radar antenna (narrow field)
3. radar antenna (wide field)
4. IR-curtain width adjustment
5. IR-lenses
6. cover
7. main connector
8. main adjustment knob
9. IR-curtain angle adjustment knob
Opening & safety sensor for automatic industrial doors
User’s Guide for product version 0403 and higher See product label for serial number
ACCESSORIES
BA: Bracket accessory CA: Ceiling accessory
CDA: Curved door accessory
RA: Rain accessory
Download the BEA DECODER app for a quick overview of settings
9 V battery
ENGLISH
Page 2
2
Pressing a parameter symbol on your remote control, displays the saved value directly on the LCD-screen. Do not unlock first.
HOW TO USE THE LCD?
To adjust contrast, push and turn the grey button simultaneously.
During normal function only.
Push to
select
parameter
Scroll
menu
up-down
Select Back to return to previous menu or display.
Select More to go to next level:
- basic settings
- advanced settings
- diagnostics
Negative display = active output
Select your language before entering the first LCD-menu.
During the first 30 seconds after power-on of the sensor or later in the diagnostics menu.
CHANGING A VALUE
Scroll
values
up-down
Push
to save
new value
VALUE CHECK WITH REMOTE CONTROL
DISPLAY DURING NORMAL FUNCTIONING
FACTORY VALUE VS. SAVED VALUE
NAVIGATING IN MENUS
Scroll menu items
Push to enter the LCD-menu
new value is displayed
more values are displayed
current value is displayed
displayed value = saved value
displayed value = factory value
Opening impulse
Safety
6
6
Enter password if necessary
Not during the first minute after power-on of the sensor.
CHANGING A ZIP CODE
Password
X
X X X
ZIP code
ZIP code
ZIP code
ZIP code
ZIP code
ZIP code
ZIP code
ZIP code
ID #
H24 1 56-KG4 01 0 800/02D
E24 1 56 KG4 01 0 800 02F
E24 1 56-KG4 01 0 800/02F
E24 1 56-KG4
01 0 800/02F
H24 1 56-KG4
01 0 800/02F
H24 1 56-KG4 01 0 800/02F
V
...
See application note on ZIP CODE
Validate the last digit in order to activate the new ZIP code:
- v = valid ZIP code, values will be changed accordingly
- x = invalid ZIP code, no values will be changed
- v/x = valid ZIP code, but from a different product. Only available values will be changed.
Page 3
1
max. 5 cm
2
12-24 V
AC-DC
*
*
3
2.2 m
2.2 m
2.2 m
2.2 m
MOUNTING & WIRING
Fixation is compatible with the ACTIV8.
RADAR OPENING IMPULSE FIELD
ANGLE
WIDTH
4 m x 2 m (wide)
2 m x 2.5 m (narrow)
field size: 9 immunity: 2
field size: 9 immunity: 2
field size: 9 immunity: 2
field size: 9 immunity: 2
The size of the detection field varies according to the mounting height of the sensor.
GREEN
BROWN
YELLOW
WHITE
PINK
GREY
RED
BLUE
POWER SUPPLY
OPENING INPUT
SAFETY INPUT
NOT USED
* Output status when sensor is operational
from 15° to 45°, default 30 °
from -15° to 15°, default 0°
SENSOR
ENGLISH
IXIO-DO1 I: INSTALLATION GUIDE
Page 4
3
5
4
4
max. 9 cm
+
+
+
OR
WIDTH
Additional adjustments are possible by LCD or remote control (see p. 5)
Part of the detection field can be masked to reduce it. The arrow position determines the width of the detection field.
INFRARED SAFETY FIELD
CLOSER
AWAY
If necessary, adjust the IR-curtain angle (from -7° to 4°, default 0°).
Activate the visible* spots to verify the position of the IR-curtain.
ANGLE
SETUP
TEST THE GOOD FUNCTIONING OF THE INSTALLATION BEFORE LEAVING THE PREMISES!
SETTINGS
* Visibility depends on external conditions. When spots are not visible, use the Spotfinder to locate the curtains.
The size of the detection field varies according to the mounting height and the settings of the sensor.
The full door width must be covered.
OR
STANDARD: standard in- and outdoor installations
CRITICAL ENVIRONMENT: critical installations due to surroundings or weather
SHOPPING STREET: installations in narrow streets with pedestrian traffic
Choose one of the following presettings or adjust the sensor manually (see p.5):
Always verify the actual detection field width with a piece of paper and not the Spotfinder, which detects the whole emitted field.
DOOR
SETUP 1 (QUICK)
SETUP 2 (ASSISTED)
OR
2 s
4 s
STEP OUT OF THE INFRARED FIELD!
reference picture
test of full door cycle + reference picture
Page 5
> > > > >
> > > >
>
1
2
A
B
> > >
+
0 1 2 3 4 5 6 7 8 9
5
OVERVIEW OF SETTINGS
Back More
RAD: IMMUNITY
RAD: DIRECTION
RAD: HOLDTIME
RAD: OUTPUT
IR: WIDTH
IR: NUMBER
IR: PRESENCE TIME
IR: OUTPUT
REDIRECTION
FACTORY RESET
More Back
Back More
PRESETTINGS
RAD: FIELDSIZE
IR: IMMUNITY
IR: FREQUENCY
More Back
ZIP CODE all parameter settings in zipped format
(see application note on ZIP CODE)
ID # unique ID-number ERROR LOG last 10 errors + day indication IR: SPOTVIEW view of spot(s) that trigger detection IR: C1 ENERG signal amplitude received on curtain 1 IR: C2 ENERG signal amplitude received on curtain 2
POW ERSUP PLY supply voltage at power connector OPERATINGTIME power duration since first startup RESET LOG delete all saved errors PASSWORD LCD and remotre control password
(0000= no password)
LANGUAGE language of LCD-menu ADMIN enter code to access admin mode
standard
critical
env.
shopping
street
Sensors mounted close to each other should have a different frequency.
increased immunities, 1 curtain increased immunities, redirection = motion and presence
factory values for radar immunity, IR immunity, IR number and redirection
small large
bi uni
uni
AWAY
low
0.5 s 1 s 2 s 3 s 4 s 5 s 6 s 7 s 8 s 9 s
uni
PRM
bi
auto
uni
auto
PRM
auto
PRM: for persons with reduced mobility AWAY: unidirectional motion away from sensor auto: automatic adaptation of field size (small shops)
service
mode
motion 15 s 30 s 1
min 2 min 5 min 10 min
motion
motion
or
presence
motion
and
presence
opening output is active in case of: 0 motion detection 1 motion or presence detection 2 motion and presence detection
20 min 60 min infinite
service mode = no IR detection during 15 minutes (maintenance).
high
BASICADVANCED
DIAGNOSTICS
NO: normally open NC: normally closed
Always additionally adjust the arrow position on the sensor with a screwdriver.
NO
NC
NC
NC
NC
NO
NO
NO
NO
NC
NC
NC
NC
NO
NO
NO
NO: normally open NC: normally closed
low
normal
high
normal
high
higher
highest
< 2.8 m > 2.8 m
full
reset
partial
reset
partial: outputs are not reset
factory value
Page 6
2
1
4
5
1 2
1 2
1 2
1
1
1 2
1 2
1 2
1
1
1 2
1 2
1 2
1 2
1
2
6
8
1
E1
E2
E4
E5
E8
1
3
1
3
TROUBLESHOOTING
ORANGE LED flashes 1 x.
ORANGE LED flashes 2 x.
ORANGE LED flashes 4 x.
ORANGE LED is on.
RED LED flashes quickly after an assisted setup.
RED LED lights up sporadically.
GREEN LED lights up sporadically.
The LED and the LCD­display are off.
The reaction of the door does not correspond to the LED-signal.
The sensor signals an internal fault.
The power supply is too low or too high.
The sensor receives not enough IR-energy.
The sensor encounters a memory problem.
The sensor vibrates.
The sensor sees the door during the assisted setup.
The sensor sees the door.
The sensor is disturbed by external conditions.
The sensor is disturbed by rain and/or leaves.
The sensor vibrates.
Ghosting created by door movement.
The sensor sees the door or other moving objects.
Check power supply
(in the diagnostics menu of the LCD).
Check wiring.
Cut and restore power supply. If orange LED lights up again, replace sensor.
Check output configuration setting. Check wiring.
Check if the sensor is fastened firmly. Check position of cable and cover.
Increase the IR-immunity filter to value 3. Select presetting 2 or 3.
Select presetting 2 or 3. Increase radar-immunity filter.
Change radar field angle.
Check if the sensor and door cover is fastened firmly. Check position of cable and cover.
Change radar field size or angle.
Remove the objects if possible.
Launch an assisted setup and adjust the IR angle.
Replace sensor.
Check wiring.
ORANGE LED flashes 5 x.
The sensor receives too much IR-energy.
ORANGE LED flashes 8 x.
IR power emitter is faulty.
Replace sensor.
The LCD or remote control does not react.
Enter the right password. If you forgot the code, cut and restore the power supply to access the sensor
without entering a password during 1 minute.
The sensor is protected by a password.
The sensor is disturbed by external elements.
Eliminate the cause of disturbance (lamps, rain cover, door controller housing properly grounded).
Move the IR-curtains away from the door. Install the sensor as close to the door as possible. If needed, use a bracket accessory. Launch a new assisted setup.
Decrease the angle of the IR-curtains. Increase the IR-immunity filter (values >2.8 m). Deactivate 1 curtain.
Slightly increase the angle of the IR-curtains. Decrease the IR-immunity filter (values 1-3 <2.8 m).
Page 7
7
x
INSTALLATION
The sensor should be fixed firmly to avoid extreme vibrations.
Do not cover the sensor.
Avoid moving objects and light sources in the detection field.
Avoid highly reflective objects in the infrared field.
It is recommended to clean the optical parts at least once a year or more if required due to environmental conditions.
Do not use aggressive products to clean the optical parts.
The device cannot be used for purposes other than its intended use. All other uses cannot be guaranteed by the manufacturer of the sensor.
The manufacturer of the door system is responsible for carrying out a risk assessment and installing the sensor and the door system in compliance with applicable national and international regulations and standards on door safety.
The manufacturer of the sensor cannot be held responsible for incorrect installations or inappropriate adjustments of the sensor.
Only trained and qualified personnel may install and setup the sensor.
The warranty is invalid if unauthorized repairs are made or attempted by unauthorized personnel.
Always test the good functioning of the installation before leaving the premises.
The door control unit and the door cover profile must be correctly earthed.
MAINTENANCE
SAFETY
LED-SIGNAL
Motion detection
Presence detection
LED flashes
LED flashes quickly
LED is off
LED flashes x times
LED flashes red-green
Page 8
BEA SA | LIEGE Science Park | ALLÉE DES NOISETIERS 5 - 4031 ANGLEUR [BELGIUM] | T +32 4 361 65 65 | F +32 4 361 28 58 | INFO@BEA.BE | WWW.BEA-SENSORS.COM
©BEA | Original instructions | 42.8356 / V4 - 05 .18
BEA hereby declares that the IXIO-DO1 I is in conformity with the basic requirements and the other relevant provisions of the directives 2014/53/EU and 2011/65/EU.
The complete declaration of conformity is available on our website.
Only for EC countries: According to the European Guideline 2012/19/EU for Waste Electrical and Elec
tronic Equipment (WEEE)
TECHNICAL SPECIFICATIONS
Supply voltage: Power consumption: Mounting height: Temperature range: Degree of protection: Noise: Expected lifetime: Norms conformity:
Presence Typical response time: < 200 ms (max. 500 ms)
Active infrared with background analysis Spot: 5 cm x 5 cm (typ) Number of spots: max. 24 per curtain Number of curtains: 2
Solid-state-relay (potential and polarity free) Max. contact current: 100 mA Max. contact voltage: 42 V AC/DC Holdtime: 0.3 to 1 s
Motion Min. detection speed: 5 cm/s
Microwave doppler radar Transmitter frequency: 24.150 GHz Transmitter radiated power: < 20 dBm EIRP Transmitter power density: < 5 mW/cm
2
Solid-state-relay (potential and polarity free) Max. contact current: 100 mA Max. contact voltage: 42 V AC/DC
Detection mode:
Technology:
Output:
Specifications are subject to changes without prior notice. All values are measured in specific conditions and with a temperature of 25°C.
12 V - 24 V AC +/-10% ; 12 V - 30 V DC +/-10% (to be operated from SELV compatible power supplies only) < 2.5 W 2 m to 4 m
(according to the applicable laws and regulations)
-25°C to +55°C; 0-95% relative humidity, non condensing IP54 < 70 dB 20 years EN 300 440-2 V1.4.1; EN 301 489-1 V1.9.2; EN 301 489-3 V1.6.1; EN 62311; EN 62479; EN 50581
PLEASE KEEP FOR FURTHER USE - DESIGNED FOR COLOUR PRINTING