INSTALLATION INSTRUCTIONS

WALL MOUNTED

PACKAGE AIR CONDITIONERS

MODELS

WL4822

WL4823

WL6022

WL6023

WL602N

Bard Manufacturing Company

Manual :

2100-351D

Bryan, Ohio 43506

Supersedes: 2100-351C

Since 1914...Moving ahead just as planned.

File:

Volume III Tab 16

Date:

09-20-01

 

© Copyright 2001

Contents

Getting Other Information and Publications

1

Wall Mount General Information

 

Air Conditioning Wall Mount Model Nomenclature . 2

Shipping Damage ...................................................

6

General ...............................................................

6

Duct Work ...............................................................

6

Condensate Drain ...................................................

6

Filters ...............................................................

6

Installation Instructions

 

Wall Mounting Information ......................................

7

Mounting the Unit ...................................................

7

Wiring – Main Power ............................................

13

Wiring – Low Voltage Wiring ................................

13

Figures

 

 

Figure 1

Unit Dimensions .....................................

3

 

WA602N, WA6023, WA4823

 

Figure 2

Unit Dimensions .....................................

4

 

WA6022, WA4822

 

Figure 3

Mounting Instructions .............................

8

 

WA602N, WA6023, WA4823

 

Figure 4

Mounting Instructions .............................

9

 

WA6022, WA4822

 

Figure 5

Electric Heat Clearance .......................

10

Figure 6

Wall Mounting Instructions ...................

11

Figure 7

Wall Mounting Instructions ...................

11

Figure 8 Common Wall Mounting Installations ...

12

Figure 9

Unit 24V Terminal Board ......................

14

Figure 10

Fan Blade Setting .................................

17

Start Up

 

Important Installer Note ........................................

15

Crankcase Heaters ...............................................

15

High Pressure Switch ...........................................

15

Three Phase Scroll Compressor Start Up ............

15

Service Hints ........................................................

15

Sequence of Operation .........................................

15

Compressor Control Module .................................

15

Adjustments ..........................................................

16

Phase Monitor ......................................................

16

Pressure Service Ports .........................................

16

Troubleshooting

 

Fan Blade Setting Dimensions .............................

17

Removal of Fan Shroud ........................................

17

Refrigerant Charge ...............................................

17

Pressure Table ......................................................

18

Optional Accessories ............................................

19

Tables

 

 

Table 1

Electric Heat Table .................................

2

Table 2

Electrical Specifications .........................

5

Table 3

Thermostat Wire Size ..........................

13

Table 4

Wall Thermostat and Subbase

 

 

Combinations .......................................

13

Table 5

Fan Blade Dimensions .........................

17

Table 6

Indoor Blower Performance .................

17

Table 7

Refrigerant Charge ...............................

17

Table 8

Rated CFM and Rated ESP .................

17

Table 9

Maximum ESP of Operation

 

 

Electric Heat Only ................................

18

Table 10

Pressure Table .....................................

18

Table 11

Optional Accessories ...........................

19

Getting Other Information and Publications

These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

National Electrical Code ........................

ANSI/NFPA 70

Standard for the Installation ...................

ANSI/NFPA

90A

 

of Air Conditioning and

 

Ventilating Systems

 

Standard for Warm Air ..........................

ANSI/NFPA

90B

 

Heating and Air

 

Conditioning Systems

 

Load Calculation for ..............................

ACCA Manual J

Residential Winter and

 

Summer Air Conditioning

 

Duct Design for Residential ...................

ACCA Manual

D Winter and Summer Air Conditioning

 

and Equipment Selection

 

For more information, contact these publishers:

ACCA

Air Conditioning Contractors of America

 

1712 New Hampshire Ave. N.W.

 

Washington, DC 20009

 

Telephone: (202) 483-9370

 

Fax: (202) 234-4721

ANSI

American National Standards Institute

 

11 West Street, 13th Floor

 

New York, NY 10036

 

Telephone: (212) 642-4900

 

Fax: (212) 302-1286

ASHRAE American Society of Heating Refrigerating,

and Air Conditioning Engineers, Inc.

1791 Tullie Circle, N.E.

Atlanta, GA 30329-2305

Telephone: (404) 636-8400

Fax: (404) 321-5478

NFPA

National Fire Protection Association

 

Batterymarch Park

 

P.O. Box 9101

 

Quincy, MA 02269-9901

 

Telephone: (800) 344-3555

 

Fax: (617) 984-7057

Manufactured under the following U.S. patent numbers:

5,485,878; 5,301,777; 5,002,116; 4,924,934; 4,875,520; 4,825,936; 4,432,409

Manual 2100-351

Page 1

WALL MOUNT GENERAL INFORMATION

AIR CONDITIONING WALL MOUNT MODEL NOMENCLATURE

MODEL NUMBER

WL 60

 

 

CAPACITY

 

60 - 5 Ton

 

 

REVISIONS

FEATURE CODE

 

3

- 3 ton air openings

 

 

on 5 ton cabinet

VOLTS & PHASE

2

- 2 ton air openings

A - 230/208/60/1

 

on 5 ton cabinet

B - 230/208/60/3

2 3 A 10 X N X X X A

CONTROL MODULES

 

 

 

 

 

 

KW

VENTILATION OPTIONS

B - Blank-off Plate

 

COIL OPTIONS

 

X -

Standard

COLOR OPTIONS

1

-

Phenolic Coated Evaporator

2

-

Phenolic Coated Condenser

X - Beige (Standard)

3

-

Phenolic Coated Evaporator

1

- White

and Condenser

2

- Mesa Tan

 

4

- Buckeye Gray

OUTLET OPTIONS

 

 

X - Front (Standard)

FILTER OPTIONS

 

N - No Filter

WL4823, WL6023, WL602N models ONLY

X - One Inch Throwaway Filter

WL4822, WL6022 models ONLY

W -

One Inch Washable Filter WL4822, WL6022 models ONLY

P -

Two Inch Pleated Filter WL4822, WL6022 models ONLY

NOTE: All vent options are without exhaust capability. May require separate field supplied barometric relief in building.

Model WL602N is identical to Model WL6023. All references in this manual to WL6023 apply to WL602N also.

TABLE 1

ELECTRIC HEAT TABLE

Models

 

WL6023A ONLY

 

 

WL6023B ONLY

 

 

 

 

 

 

 

 

 

 

 

240V-1

208V-1

240V-1

208V-1

KW

 

 

 

 

 

 

 

 

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

AMPS

BTUH

 

 

 

 

 

 

 

 

 

5.0

20.8

17,050

18.1

12,800

- - -

- - -

- - -

- - -

 

 

 

 

 

 

 

 

 

9.0

- - -

- - -

- - -

- - -

21.7

30,600

18.7

23,030

 

 

 

 

 

 

 

 

 

10.0

41.6

34,130

36.2

25,600

- - -

- - -

- - -

- - -

 

 

 

 

 

 

 

 

 

WL4822A, WL4822B, WL4823A, WL4823B, WL6022A, WL6022B are not approved for use with electric heat.

Manual 2100-351

Page 2

Page

Manual

3

351-2100

 

FIGURE 1

UNIT DIMENSIONS

WL602N, WL6023, WL4823 ONLY

MIS-1451

351-2100 Manual

4 Page

FIGURE 2

UNIT DIMENSIONS

WL6022, WL4822 ONLY

MIS-1452

Page

Manual

5

351-2100

 

TABLE 2

ELECTRICAL SPECIFICATIONS

SINGLE CIRCUIT

DUAL CIRCUIT

 

 

 

3

1

2

2

3

1

2

2

 

 

 

 

 

 

 

Minimum

Maximum

 

 

 

 

 

 

No.

 

Maximum

 

 

External Fuse

 

 

Ground

 

 

 

External

Field

 

Circuit

or

Field Power

 

Rated

Field

Minimum

Fuse or

Power

Ground

Ampacity

Ckt. Breaker

Wire Size

Wire Size

 

Volts &

Power

Circuit

Ckt.

Wire

Wire

 

 

 

 

 

 

 

 

 

CKT A

CKT B

CKT A

CKT B

CKT A

CKT B

CKT A

CKT B

Model

Phase

Circuits

Ampacity

Breaker

Size

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL4822A00, A0Z

230/208-1

1

38

50

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL4822B00, B0Z

230/208-3

1

26

35

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL4823A00, A0Z

230/208-1

1

38

50

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL4823B00, B0Z

230/208-3

1

26

35

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL6022A00, A0Z

 

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A05

230/208-1

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A10

 

1

55

60

6

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WL6022B00, B0Z

230/208-3

1

32

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

B09

1

34

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WL6023A00, A0Z

 

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A05

230/208-1

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A10

 

1

55

60

6

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WL6023B00, B0Z

230/208-3

1

32

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

B09

 

1

34

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WL602NA00, A0Z

 

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A05

230/208-1

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A10

 

1

55

60

6

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WL602NB00, B0Z

230/208-3

1

32

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

B09

1

34

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75° C copper wire. All Wiring must conform to NEC and all local codes.

lThese “minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.