Low ambient control is required with economizer for low temperature compressor operation.
Manual 2100-587C
Page 5 of 59
AIR CONDITIONING MODULE OPTIONS
CCM
STDSTDSTDXN/A
STDSTDSTD--HCMA-28
STD = Standard equipment
HPC
LPC
LAC
Factory Installed
Code
Field Installed
Part
CCM Compressor control module has adjustable 30 second to 5 minute delay-on-breaktimer. On
initial power up, or any time the power is interrupted, the delay-on-make will be 2 minutes plus
10% of the delay-on-break setting. There is no delay-on-make during routine operation of the
unit. The module also provides the lockout feature (with 1 retry) for high and/or low pressure
controls, and a 2 minute timed bypass for low pressure control.
HPC High pressure control is auto reset. Always used with compressor control module (CCM)
which is included. See note .
LPC Low pressure control is auto reset. Always used with compressor control module (CCM) which
is included. See note .
LAC Low ambient control permits cooling operation down to 0°F.
circulating air stream as the result of residual oil burning off of the heat exchanger tubes. This oil
is required during the forming process of the stainless steel heat exchanger tubes to facilitate the
bending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In vapor
form this may be irritating to the eyes or could cause headaches. This is a one-time occurrence,
and ventilation of the space may be required depending upon the space being conditioned.
Filter Sizes (Inches)20 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 2
Charge (R-410A)156156156240240240246246246
* 75° C Copper wire size
** Maximum time delay fuse or circuit breaker
Manual 2100-587C
Page 7 of 59
M
G
N
P
D
A
FF
GG
HH
Y
Z
T
C
KJ
BB
DD
R
W
S
S
S
S
CC
F
B
AA
X
U
I
V
S
B
EE
O
E
L
II
Q
H
FILTER
SERVICE
DOOR
GAS
PANEL
VENT OPTION
CIRCUIT BREAKER/
FRONT
RETURN OPENING
CONDENSER
BACK
SUPPLY OPENING
DISCONNECT ACCESS
RIGHT SIDE
LOW VOLTAGE
PANEL (LOCKABLE)
PANEL DOOR
COMBUSTION
AIR EXHAUST
AIR INTAKE
COMBUSTION
ENTRANCES
VESTIBULE
DOOR
AIR INLETS
CONTROL
ENTRANCES
CONDENSER
4 DEG. PITCH IN TOP
AIR OUTLET
HIGH VOLTAGE
ENTRANCES
FRONT DOOR
MIS-3240 A
UNITABCDEFGHIJKLMNOPQR
WG3S231.6387.533.38 28.75
41.63
43.38
UNITSTUVWXYZAABBCCDDEEFFGGHHII
WG3S23.7524.9
13.75
34.9
3.252.75
2.514.883014.12 15.4442.8815.31
2.253.884217.348.44
4.5
12.191040.25
43.81
0.44
3.75
16
9.8829.88 15.88 27.25
1.257.251.13
FIGURE 1
UNIT DIMENSIONS
Manual 2100-587C
Page 8 of 59
1. IMPORTANT
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians. All duct work or portions thereof not in the
conditioned space should be properly insulated in order
to both conserve energy and prevent condensation or
moisture damage.
2. APPLICATION
This is a fan-assisted forced air gas furnace with electric
air conditioning for outdoor installation. A fan-assisted
furnace is equipped with an integral mechanical means
to draw products of combustion through the combustion
chamber and heat exchanger. The furnace installation
must conform with local building codes and ordinances
or, in their absence, with the National Fuel Gas Code
ANSI Z223.1 or CAN/CGA-B149.1, latest edition, and
the National Electrical Code ANSI/NFPA-7 or CSA
C22.1, latest edition. It is the personal responsibility
and obligation of the purchaser to contact a qualied
installer to assure that installation is adequate and is in
conformance with governing codes and ordinances.
3. DUCT WORK
The unit is designed for use with or without duct
work. See Warning on Page 9. Flanges are provided
for attaching the supply and return ducts. These
instructions explain the recommended method to install
the air cooled self-contained electric air conditioning
and gas heating unit and the electrical wiring
connections and gas piping to the unit. The refrigerant
system is completely assembled and charged. All
internal wiring is complete.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
heating/cooling system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
All duct work, supply and return, must be properly
sized for the design airow requirement of the
equipment. Air Conditioning Contractors of America
(ACCA) is an excellent guide to proper sizing.
Refer to Table 9 in this Manual for maximum static
pressure available for duct design.
See Figure 3 and clearance information in Section 9 and
Table 2 for additional information.
WARNING
In all cases, there must be a metal duct
connectionmadetothesupplyairange,and
a one inch clearance to combustibles must be
maintained to this duct connection.
For free blow applications, a metal sleeve
must be used in the wall opening itself,
again maintaining a one inch clearance to
combustibles.
Failuretousethesheetmetalcancausere
resulting in property damage, injury, or death.
A one-inch clearance to combustible material for the
rst three feet of duct attached to the outlet air frame is
required. See Wall Mounting Instructions and Figures
2, 2A, 3 and 3A for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.
Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct. The spacing between
louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with the 5/8 inch louver criteria
may be used. It is recommended that Bard Return Air
Grille or Return Filter Grille be installed when no return
duct is used. Contact distributor or factory for ordering
information. If using a return air lter grille, lters
must be of sufcient size to allow a maximum velocity
of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
4. HIGH ALTITUDE APPLICATIONS
Ratings of gas utilization equipment are based on
sea level operation and need not be changed for
operation at elevations up to 6,000 feet. For operation
at elevations above 6,000 feet and in the absence of
specic recommendations from the local authority
having jurisdiction, equipment ratings shall be reduced
as specied in Section 21.
Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one-inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
Manual 2100-587C
Page 9 of 59
5. TRANSPORTATION DAMAGE
All units are packed securely in shipping container.
All units should be carefully inspected upon arrival for
damage. In the event of damage, the consignee should:
1. Note on delivery receipt of any damage to container.
2. Notify carrier promptly, and request an inspection.
3. In case of concealed damage, the carrier must be
notied as soon as possible within 15 days after
delivery.
4. Claims for any damage, apparent or concealed,
should be led with the carrier, using the following
supporting documents:
A. Original Bill of Lading, certied copy, or
indemnity bond.
8. MOUNTING THE UNIT
1. These units are secured by wall mounting
brackets which secure the unit to the outside
wall surface at both sides. A bottom mounting
bracket is provided for ease of installation but
is not required.
CAUTION
If the bottom bracket is used, be certain the
bracket is secured to the outside wall surface
inawaysufcienttosupporttheentire
weight of the unit during installation until side
mounting brackets are secured.
B. Original paid freight bill of indemnity in lieu
thereof.
C. Original invoice or certied copy thereof
showing trade and other discounts or
deductions.
D. Copy of the inspection report issued by
carrier’s representative at the time damage is
reported to carrier.
6. INSTALLATION
Size of unit for proposed installation should be based
on heat loss/heat gain calculations made according
to methods of Air Conditioning Contractors of
America (ACCA). The air duct should be installed
in accordance with the Standards of the National
Fire Protection Association for the Installation of Air
Conditioning and Ventilating Systems of Other Than
Residence Type, NFPA No. 90A, and Residence Type
Warm Air Heating and Air Conditioning Systems,
NFPA No. 90B. Where local regulations are at a
variance with instructions, installer should adhere to
local codes.
7. WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as
detailed in Figure 4.
2. On wood-frame walls, the wall construction
must be strong and rigid enough to carry the
weight of the unit without transmitting any unit
vibration.
2. The WG3S2, WG4S2 and WG5S2 models are
suitable for 0 inch clearance on the installation
mounting wall and to the top. For all models the
supply air duct ange and the rst 3 feet of
supply air duct require a minimum of 1-inch
clearance to combustible material.
WARNING
Failure to provide the one inch clearance
between the supply duct and a combustible
lag bolts; use 7/8 inch diameter at washers on the lag bolts. Use lag bolts long enough to
support the unit’s weight when mounted to the
structure. This length may be dependant on the
type of construction.
7. Secure rain ashing to wall and caulk across
entire length of top. See Figure 3.
3. Concrete block walls must be thoroughly
inspected to insure that they are capable of
carrying the weight of the installed unit.
Manual 2100-587C
Page 10 of 59
8. On side-by-side installations, maintain a
minimum of 20 inches clearance on right side
to allow access to control panel and burner
compartment, and to allow proper airow to the outdoor coil. Additional clearance may be
required to meet local or national codes.
FIGURE 2A
FOR WG3S2
MOUNTING INSTRUCTIONS
Manual 2100-587C
Page 11 of 59
FIGURE 2B
FOR WG4S2 AND WG5S2
MOUNTING INSTRUCTIONS
Manual 2100-587C
Page 12 of 59
FIGURE 3
COMBUSTIBLE CLEARANCE
WARNING
A minimum of one (1) inch clearance must be maintained between the supply air duct and combustible materials.
adequate re protection, adequate combustion air, and
room for service personnel.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation
around the unit for proper operation in the cooling
mode. Whenever possible, it is desirable to allow
additional clearance, especially around the condenser
inlet and discharge openings. DO NOT install the unit
in a location that will permit discharged air from the
condenser to recirculate to the condenser inlet.
The vent terminal is shipped in the burner
compartment. See Figure 7. Remove the two shipping
screws and separate the two-piece assembly. Install the
vent terminal by using the four screws provided. Make sure gasket is in place. See Figure 8. The combustion
air intake hood is factory installed.
11. OPTIONAL VERTICAL VENTING
With the optional vertical venting kit (VVK-5) this unit
may be vented vertically through a roof or overhang.
The kit includes a stainless steel transition drain tee,
silicone sealant, and drain tubing.
If unit is installed with vertical vent kit, annually
inspect the vent system and drain. Replace any portion
of the vent system that shows signs of deterioration.
Make sure drain is open and free of obstruction.
CAUTION
Vent terminal must be installed as shown in Figure 8 for proper operation of the heating system.
NOTE: The inner vent hood gasket is designed to stretch over and seal around the combustion
air blower outlet. This is a very critical seal to prevent water and ue products from entering the
unit. Care must be taken to insure this gasket is in place and sealing properly.
FIGURE 8
VENT TERMINAL AND COMBUSTION AIR INTAKE
Manual 2100-587C
Page 17 of 59
12. VENT RESIZING INSTRUCTIONS
13. FRESH AIR INTAKE
When an existing furnace is removed from a venting
system servicing other appliances, the venting system
is likely to be too large to properly vent the remaining
attached appliances.
The following steps shall be followed with each of the
appliances remaining connected to the common venting
system, placed in operation one at a time while the
other appliances remaining connected to the common
venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel
Gas code, ANSI Z223.1 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deciencies which could cause
an unsafe condition.
3. In so far as is practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system
are located and other spaces of the building. Turn
on clothes dryers and any appliances not connected
to the venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close replace dampers.
All units are built with fresh air inlet slots punched in
the service panel.
The default unit is built with blank-off plates
installed. All capacity, efciency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh
air blank-off plate in place and is recommended for
maximum energy efciency.
One of several other ventilation options may be
installed. Refer to model number and/or supplemental
installation instructions.
14. CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at
the top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
4. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage
at the draft hood relief opening after 5 minutes of
main burner operation. Use the ame of a match or
candle.
6. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, replace dampers and any other gas-
burning appliances to their previous conditions of
use.
7. If improper venting is observed during any of the
above tests, the venting system must be corrected.
Manual 2100-587C
Page 18 of 59
Loading...
+ 41 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.