Bard CRV-F2, CRV-F3 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
Partial Flow
Commercial Room Ventilator
24 Volt On/Off
with Spring Return and Exhaust
Models:
For Use with Bard Single Stage Wall Mount
Air Conditioner and Heat Pump Models:
CRV-F2 CRV-F3
: W18A/LB, W24A/LB, W18HB, W24HB : W30A/LB, W36A/LB, W30HB, W36HB
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-691 Supersedes: NEW Date: 3-1-19
Page 1 of 15
CONTENTS
General Information ...............................................3
Commercial Room Ventilator Model Nomenclature ...
Unpacking .......................................................... 3
General ..............................................................3
Description .........................................................3
Application .........................................................3
Installation of Field-Installed CRV-F* .................4
Basic Installation .................................................4
Preparing Unit for CRV-F Installation ................. 4
Commercial Room Ventilator (CRV) No Hood
Installation .....................................................7
Blade Adjustment for Desired Ventilation Air ........11
3
Figures
Figure 1 Wall Mount Unit Access Panels ............. 4
Figure 2 Condenser Exhaust Plate with Screen..... 5
Figure 3 Filter Bracket and Filter Bracket
Fill Plate Installation ............................ 6
Figure 4 Extension Cable Installation .................. 7
Figure 5 Damper Assembly Installation ............... 8
Figure 6 Vent Door Assembly .............................. 8
Figure 7 Required Control Connections for CRV
with Air Conditioners ............................ 9
Figure 8 Required Control Connections for CRV
with Heat Pumps ............................... 10
Figure 9 Blade Adjustment For Desired
Ventilation Air .................................... 11
Figure 10 Call for Ventilation With or Without
Compressor Operation ........................ 14
Figure 11 Call for Compressor or Fan Only with
Ventilation Off ................................... 15
Graphs
Graph 1 W18 Ventilation Delivery ...................... 12
Graph 2 W24 Ventilation Delivery ...................... 12
Graph 3
Graph 4 W36 Ventilation Delivery ...................... 13
W30 Ventilation Delivery ....................... 13
CRV FEATURES
One piece construction – easy to install with no
mechanical linkage adjustment required.
Exhaust air damper – built in with positive closed
position. Provides exhaust air capability to prevent pressurization of tight buildings.
Actuator motor – 24 volt, power open, spring
return with built in torque limiting switch.
Manual 2100-691 Page 2 of 15
GENERAL INFORMATION
Commercial Room Ventilator Model Nomenclature
CRV – F 2
COMMERCIAL ROOM VENTILATOR
FIXED (24V ON/OFF)
CHASSIS SIZE
2 – 1.5 & 2 Ton Models 3 – 2.5 & 3 Ton Models
Unpacking
Upon receipt of the equipment be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped.
Inspect the carton housing of each ventilator as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt.
General
The ventilator should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the ventilator package. They are not intended as a step­by-step procedure with which the mechanically inclined owner can install the package.
The ventilator housing is shipped in one carton which contains the electrical harness, miscellaneous hardware and installation instructions.
Description
Commercial room ventilators CRV-F2 and CRV-F3 are designed to be used with the specific models with "letter" revision codes as designated on the front page of this installation instructions manual.
The CRV-F ventilator is an electromechanical vent system designed to provide fresh air to meet indoor air quality standards.
Commercial room ventilators CRV-F2 and CRV-F3 are internally mounted dampers with exhaust designed to provide up to 50% fresh air. The damper blade is powered by a 24 VAC motor with spring return on power loss. The damper is powered open anytime A is energized. Blade stop screws are located under the fresh air blade and will provide 10 different airflow settings.
When installed in the models listed on the front page, the CRV-F provides built-in exhaust provisions. When the damper blade opens to bring fresh air in, the damper also opens an exhaust relief. The exhaust air will flow into the condenser section of the unit. The condenser fan will help draw exhaust air out when it is operating with compressor in cooling or heat pump mode.
Application
The amount of outside fresh air brought into the structure is dependent on the supply and return duct static pressure present in the duct system. Refer to Graphs 1-4 on pages 12-13 for ventilation air that will be supplied at different blade settings and duct static pressures. For duct-free applications with return air filter grilles and supply grilles, use 0.00 supply air static pressure.
Manual 2100-691 Page 3 of 15
INSTALLATION OF FIELD-INSTALLED CRV-F*
Basic Installation
!
WARNING
Electrical shock hazard.
Disconnect remote electrical power supply or supplies before servicing.
Failure to do so could result in electric shock or death.
Preparing Unit for CRV-F Installation
1. Disconnect power to unit.
2. Unpack the CRV-F assembly, which includes the
integral controls and electrical harness, body panels, miscellaneous hardware and installation instructions.
Wall Mount Unit Access Panels
3. From existing wall mount unit, remove and save (or discard) as directed (see Figure 1):
Blower access panel (save)
Vent option panel (save)
Filter access panel (save)
Filter (save)
Outer and inner control panel doors (save)
Filter tray (discard, if applicable)
Exhaust cover plate (discard)
4. Install new condenser exhaust plate with screen over opening into condenser section (see Figure 2).
5. Remove filter brackets, if necessary. Two types of filter brackets have been used with these wall mount units. If the filter brackets are mounted flat, they can be used with the commercial room ventilator (CRV). If the brackets are set at a 30° angle, they must be removed and discarded. The circuit breaker offset plate must be loosened and moved slightly to gain access to several of the screws holding the filter brackets in place. Tighten the screws holding control panel after the filter brackets have been removed.
FIGURE 1
BLOWER ACCESS PANEL
FILTER ACCESS PANEL
VENT OPTION PANEL
FILTER TRAY
EXHAUST COVER PLATE
(THIS PLATE IS DISCARDED)
FILTER
SCREW
CIRCUIT BREAKER ACCESS DOOR
CONTROL PANEL DOOR
MIS-3987
Manual 2100-691 Page 4 of 15
FIGURE 2
Condenser Exhaust Plate with Screen
Condenser Exhaust Plate with Screen
PARTITION COVER
INSTALL COVER PLATE
SCREEN MEDIA FACING
PARTITION
CONDENSER PARTITION
4 SCREWS
PLATE
PARTITION SUPPORT ANGLE SHOWN FACING DOWN (HIDDEN)
MIS-3633
If filter brackets were removed in Step 5, proceed
to Step 6. If the brackets were not removed, proceed to Commercial Room Ventilator (CRV) No Hood Installation on page 7.
6. Install filter bracket fill plate (if applicable) as shown in Figure 3 on page 6.
7. Install provided filter brackets on CRV-F assembly (see Figure 3).
Manual 2100-691 Page 5 of 15
Loading...
+ 10 hidden pages