• One piece construction – easy to install with no
mechanical linkage adjustment required.
• Exhaust air damper – built in with positive closed
position. Provides exhaust air capability to prevent
pressurization of tight buildings.
• Actuator motor – 24 volt, power open, spring
return with built in torque limiting switch.
Manual 2100-691
Page 2 of 15
GENERAL INFORMATION
Commercial Room Ventilator Model Nomenclature
CRV – F 2
COMMERCIAL ROOM VENTILATOR
FIXED (24V ON/OFF)
CHASSIS SIZE
2 – 1.5 & 2 Ton Models
3 – 2.5 & 3 Ton Models
Unpacking
Upon receipt of the equipment be sure to compare the
model number found on the shipping label with the
accessory identification information on the ordering and
shipping document to verify that the correct accessory
has been shipped.
Inspect the carton housing of each ventilator as it is
received, and before signing the freight bill, verify that
all items have been received and that there is no visible
damage. Note any shortages or damage on all copies
of the freight bill. The receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent. Concealed
damage not discovered until after loading must be
reported to the carrier within 15 days of its receipt.
General
The ventilator should only be installed by a trained
heating and air conditioning technician. These
instructions serve as a guide to the technician installing
the ventilator package. They are not intended as a stepby-step procedure with which the mechanically inclined
owner can install the package.
The ventilator housing is shipped in one carton which
contains the electrical harness, miscellaneous hardware
and installation instructions.
Description
Commercial room ventilators CRV-F2 and CRV-F3 are
designed to be used with the specific models with
"letter" revision codes as designated on the front page
of this installation instructions manual.
The CRV-F ventilator is an electromechanical vent
system designed to provide fresh air to meet indoor air
quality standards.
Commercial room ventilators CRV-F2 and CRV-F3 are
internally mounted dampers with exhaust designed
to provide up to 50% fresh air. The damper blade
is powered by a 24 VAC motor with spring return on
power loss. The damper is powered open anytime A
is energized. Blade stop screws are located under the
fresh air blade and will provide 10 different airflow
settings.
When installed in the models listed on the front page,
the CRV-F provides built-in exhaust provisions. When
the damper blade opens to bring fresh air in, the
damper also opens an exhaust relief. The exhaust air
will flow into the condenser section of the unit. The
condenser fan will help draw exhaust air out when it
is operating with compressor in cooling or heat pump
mode.
Application
The amount of outside fresh air brought into the
structure is dependent on the supply and return duct
static pressure present in the duct system. Refer to
Graphs 1-4 on pages 12-13 for ventilation air that
will be supplied at different blade settings and duct
static pressures. For duct-free applications with return
air filter grilles and supply grilles, use 0.00 supply air
static pressure.
Manual 2100-691
Page 3 of 15
INSTALLATION OF FIELD-INSTALLED CRV-F*
Basic Installation
!
WARNING
Electrical shock hazard.
Disconnect remote electrical power supply
or supplies before servicing.
Failure to do so could result in electric
shock or death.
Preparing Unit for CRV-F Installation
1. Disconnect power to unit.
2. Unpack the CRV-F assembly, which includes the
integral controls and electrical harness, body
panels, miscellaneous hardware and installation
instructions.
Wall Mount Unit Access Panels
3. From existing wall mount unit, remove and save (or
discard) as directed (see Figure 1):
• Blower access panel (save)
• Vent option panel (save)
• Filter access panel (save)
• Filter (save)
• Outer and inner control panel doors (save)
• Filter tray (discard, if applicable)
• Exhaust cover plate (discard)
4. Install new condenser exhaust plate with screen
over opening into condenser section (see Figure 2).
5. Remove filter brackets, if necessary. Two types
of filter brackets have been used with these wall
mount units. If the filter brackets are mounted
flat, they can be used with the commercial room
ventilator (CRV). If the brackets are set at a 30°
angle, they must be removed and discarded. The
circuit breaker offset plate must be loosened and
moved slightly to gain access to several of the
screws holding the filter brackets in place. Tighten
the screws holding control panel after the filter
brackets have been removed.
FIGURE 1
BLOWER ACCESS PANEL
FILTER ACCESS PANEL
VENT OPTION PANEL
FILTER TRAY
EXHAUST COVER PLATE
(THIS PLATE IS DISCARDED)
FILTER
SCREW
CIRCUIT BREAKER
ACCESS DOOR
CONTROL
PANEL DOOR
MIS-3987
Manual 2100-691
Page 4 of 15
FIGURE 2
CondenserExhaustPlatewithScreen
Condenser Exhaust Plate with Screen
PARTITION COVER
INSTALL COVER PLATE
SCREEN MEDIA FACING
PARTITION
CONDENSER PARTITION
4 SCREWS
PLATE
PARTITION SUPPORT ANGLE
SHOWN FACING DOWN
(HIDDEN)
MIS-3633
If filter brackets were removed in Step 5, proceed
to Step 6. If the brackets were not removed,
proceed to Commercial Room Ventilator (CRV) No Hood Installation on page 7.
6. Install filter bracket fill plate (if applicable) as
shown in Figure 3 on page 6.
7. Install provided filter brackets on CRV-F assembly
(see Figure 3).
Manual 2100-691
Page 5 of 15
Loading...
+ 10 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.