Bard CompleteStat CS9B-THOA, CompleteStat CS9B-THOCA, CompleteStat CS9BE-THOA, CompleteStat CS9BE-THOCA, CS9B-THOA Installation And Operation Manual

...
INSTALLATION, OPERATION &
QUICK START GUIDE
Models:
CS9B-THOA CS9B-THOCA
TM
Controller
CS9BE-THOA CS9BE-THOCA
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-684 Supersedes: NEW Date: 3-20-18
Page 1 of 25
TABLE OF CONTENTS
INSTALLATION ........................................................3
Mounting Controller ............................................ 3
CompleteStat Setup Information .......................... 4
BASIC OPERATION .................................................5
Basic Setup ....................................................... 5
Quick Start Programming .................................... 5
System Selection ............................................. 5
Air Conditioner Applications ............................. 6
Heat Pump Applications................................... 7
System Enable ................................................ 9
Setpoints ........................................................ 9
Sequence of Operation ...................................... 10
WIRING DIAGRAMS .............................................15
FIGURES
Figure 1 CompleteStat Dimensions .................... 3
Figure 2 CompleteStat Buttons and Screens ....... 5
Figure 3 Application Menu ................................ 5
Figure 4 Additional Setup (Air Conditioner) ........ 6
Figure 5 Fan Setup (Air Conditioner) .................. 6
Figure 6 Dehumidification (Air Conditioner) ........ 7
Figure 7 Additional Setup (Heat Pump) .............. 7
Figure 8 Aux Heat Setup ................................. 7
Figure 9 Fan Setup (Heat Pump) ....................... 8
Figure 10 Dehumidification (Heat Pump) ............. 9
Figure 11 Additional Setup (Heat Pump) .............. 9
Figure 12 System Enable .................................... 9
Figure 13 Setpoints ........................................... 9
Figure 14 CompleteStat Terminal Descriptors
and Optional Inputs .......................... 11
TABLES
Table 1 Controller Connections ....................... 11
Table 2 Conventional 1H/1C, 2H/1C, 1H/2C
or 2H/2C without Econ ...................... 12
Table 3 Conventional 1H/1C, 2H/1C, 1H/2C
or 2H/2C with Econ ........................... 12
Table 4
Single Stage Heat Pump without Econ
Table 5 Two Stage Heat Pump without Econ .... 13
Table 6 Single Stage Heat Pump with Econ ..... 14
Table 7 Two Stage Heat Pump with Econ ........ 14
Table 8 Wiring Diagram Index ...................... 115
WIRING DIAGRAMS
WD 1 Conventional 1H/1C, 1H/2C, 2H/1C
or 2H/2C, with or without
Dehumidification and Ventilation,
No Economizer ................................. 16
WD 2 Conventional 1H/1C or 2H/1C with
TM
Honeywell W7220 JADE
Control Economizer, with or without
Dehumidification .............................. 17
WD 3 Conventional 1H/2C or 2H/2C with Honeywell W7220 JADE
TM
Control Economizer, No Dehumidification,
2 Stage Compressor Only ................... 18
... 13
NOTE
Screenshots shown in this manual reflect default settings (when applicable).
WD 4 Heat Pump 2H/1C or 3H/1C, with or without Dehumidification and
Ventilation, No Economizer ................ 18
WD 5 Heat Pump 2 Stage, with or without
Dehumidification and Ventilation ........ 19
WD 6 Heat Pump 1 Stage with Honeywell W7220 JADE
with or without Dehumidification ........ 19
WD 7 Heat Pump 2 Stage with W7220 JADE
TM
without Dehumidification ................... 20
WD 8 Gas/Electric 1H/1C, with or without Dehumidification and Ventilation,
No Economizer ................................. 20
WD 9 Gas/Electric 1H/2C, with or without Dehumidification and Ventilation,
No Economizer ................................. 21
WD 10 I-TEC
®
with No Ventilation ............................ 21
WD 11 I-TEC
®
with CRV Ventilation Package ............. 22
WD 12 I-TEC
®
with ERV Ventilation Package and 8403-067 CO
(Fully Modulating) ............................. 23
WD 13 Q-TEC 1 Stage Air Conditioner, with or without Dehumidification and
Ventilation, No Economizer ............... 24
WD 14 Q-TEC 1 Stage Heat Pump, with or without
Dehumidification and Ventilation ........ 24
WD 15 QW*S Series 2 Stage Heat Pump, with or without Dehumidification and
Ventilation ....................................... 25
WD 16 C**H Heat Pump 2 Stage with W7220 JADE
with or without Dehumidification ........ 25
TM
Control Economizer,
Control Economizer, with or
2 Stage Heat Pump Series
2 Stage Heat Pump Series
2 Stage Heat Pump Series
Detector
2
TM
QA**/Q**A Series
TM
QH**/Q**H Series
TM
Control Economizer,
Manual 2100-684 Page 2 of 25
INSTALLATION
IMPORTANT: For optimum temperature sensor performance, the Bard CompleteStat must be mounted on an interior wall and away from any heat sources, sunlight, windows, air vents, air circulation obstructions and/or any other cause of erratic or false temperature sensing. Thermostat covers are not recommended as
they interfere with motion and temperature sensing.
Mounting Controller
1. It is recommended that18 AWG solid-conductor control wire is used for installation. See the low voltage wiring diagrams beginning on page 15 for exact number of conductors.
NOTE: Shielded wire must be used in applications
where transient signals may accumulate and affect digital signal from control to unit.
2. Turn the hex screws in the bottom and top of the controller clockwise (inward) until they clear the cover. Remove base plate from controller.
FIGURE 1
CompleteStat Dimensions
3. Route control wiring through base plate.
4. With the embossed “UP” arrows of the base plate pointing in the appropriate direction, fasten the base plate to the desired wall location. A vertical/ horizontal 2x4 wall handybox can be used for the CO
-sensing CompleteStat and a vertical-only 2x4
2
wall handybox can be used for non-CO
-sensing
2
CompleteStat.
5. Make appropriate control wire connections to terminal blocks. See low voltage wiring diagrams beginning on page 15.
6. Replace controller over base plate, being careful not to pinch/dislodge connections.
7. Turn hex screws in bottom/top of controller counter­clockwise (outward) to secure cover.
Dimensions in Inches (mm)
Models
CS9B(E)-THOA
CS9B(E)-THOCA 5.192 (132) 1.437 (36.5)
Height
(A)
5.551 (141)
Width
(B)
4.192 (106) 1.125 (29)
Depth
B
A
Manual 2100-684 Page 3 of 25
CompleteStat Setup at Time of Installation
Determine the following information prior to installation.
1. Degrees Scale: °F °C
2. Unit Type: A/C HP
3. Options: A/C – 1H/1C 2H/2C 1H/2C 2H/1C
HP – 1 Stage 2 Stage
4. Economizer: Yes No
5. Fan: Off Delay (seconds) Unoccupied: Auto On Occupied: Auto On
6. Humidity: Dehumidification Yes No
7. Humidity Setpoint:
8. Dehum Span:
9. Electric Strip Heat: Yes No
10. Reversing Valve: Active Htg Active Clg
11. System: Off Cool Heat Auto
12. Cool Setpoint:
13. Heat Setpoint:
14. Cool Setback:
15. Heat Setback:
16. Standby Time: Minutes
17. Motion Sensing: Daily Schedule
18. Date:
19. Time:
20. Occupied Minimum Cooling:
21. Occupied Maximum Cooling:
22. Unoccupied Minimum Cooling:
23. Unoccupied Maximum Cooling:
24. CO
25. CO
Setpoint:
2
Span :
2
NOTES _______________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
Manual 2100-684 Page 4 of 25
BASIC OPERATION
BASIC SETUP
These instructions are intended to provide the basic settings to get the equipment started.
FIGURE 2
CompleteStat Buttons and Home, Overide and Configuration Screens
Navigate the menus and change settings by pressing a combination of the four arrow buttons and the ENTER button.
ENTER button to select and/or exit value editing
UP or DOWN button to move among entries
RIGHT or LEFT button to move among value fields
LEFT button to return to the home screen
NOTE: Although cooling/heating setpoints can be
accessed by simply pressing the UP or DOWN buttons during normal operation, any changes made in this fashion will not be permanent but last only for a specific length of time as an “override” feature. See Setpoints on page 9 for further information.
NOTE: The screen will revert back to the home screen
if inactive for “X” number of seconds (factory default is 120 seconds). See page 14 in the latest version of CompleteStat Controller Advanced Programming & Features 2100-685 for information on adjusting the inactivity setting.
NOTE: If the screen includes up and down arrows in
the upper corners (as shown in Figure 7 on page 7), additional choices can be found by continuing to press the UP or DOWN buttons.
SYSTEM
SETPOINTS DATE/TIME TECHNICIAN ABOUT
MAIN MENU
QUICK START PROGRAMMING
System Selection
To select A/C or HP, stages of heating and cooling, and with/without economizer:
1. Press RIGHT button to access Main Menu screen.
2. Press DOWN button to scroll to TECHNICIAN. Press ENTER button.
3.
Controller will ask for password. Press UP and RIGHT buttons to enter ‘BARD’. Press ENTER button.
4. Press ENTER button again to enter the APPLICATION menu (see Figure 3).
FIGURE 3
Application Menu
APPLICATION
DEGREES: ºF
UNIT_TYPE: HP OPT: 2 STAGES ADDITIONAL SETUP
5. Press ENTER button again to choose DEGREES.
NOTE:
The UNIT_TYPE category must be set to “NOT CONFIGURED” before the controller will allow the scale to be changed (see step 7 on page 6).
Manual 2100-684 Page 5 of 25
6. Press UP or DOWN button to choose °F (Fahrenheit) or °C (Celsius). Press ENTER to save selection of scale.
NOTE: The change from F to C will not take effect
on the home screen until the 24VAC power is cycled off and back on.
7. Press DOWN button to scroll to UNIT_TYPE. Press ENTER button.
8. Press UP or DOWN button to choose from the available system types (A/C, HP or Not Configured). Press ENTER button to select/save appropriate choice.
3. Press ENTER button to select/save appropriate economizer option.
4. Press LEFT button to go back to ADDITIONAL SETUP.
5. The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions. To access or change blower settings, press DOWN button to scroll to FAN. Press ENTER button to enter FAN SETUP (see Figure 5).
FIGURE 5
Fan Setup (Air Conditioner)
10. Press DOWN button to scroll to OPT. Press ENTER button.
11. Press UP or DOWN button to choose from the following available system stages:
A/C – 1H/1C HP – 1 Stage
A/C – 2H/2C HP – 2 Stages
A/C – 1H/2C
A/C – 2H/1C
NOTE: These are stages of compressor operation.
12. Press ENTER button to select/save appropriate model stage.
13. Press DOWN button to scroll to ADDITIONAL SETUP. Press ENTER button.
Air Conditioner Applications (see Figure 4)
NOTE: The following is for A/C applications. Heat
pump application information can be found in the following section.
FIGURE 4
Additional Setup (Air Conditioner)
ADDITIONAL SETUP
VENTILATION
FAN HUMIDITY MOTION SENSOR SENSORS STAGING
Ventilation, Fan and Humidity Setup
1. Press ENTER button to enter VENTILATION menu.
2. Press ENTER button to highlight ECON options. Press UP or DOWN button to choose from the available economizer options:
NONE = No economizer, or standard vent
package (ERV/CRV/MFAD)
EN/DIS = Economizer in system
FAN SETUP
SPEEDS: CONSTANT SPEED
OFF DELAY (SECS): 0 UNOCC: AUTO OCC: AUTO
6. Press DOWN button to scroll through selections; adjust as necessary.
Speeds: Constant speed (nonadjustable)
Off Delay: “0” = System fan will run for
specified time after call ends; 0-600 seconds in 30-second increments.
Unocc: “ON” = System fan will run
continuously during all operational modes; “AUTO” = System fan will operate during call for cooling or heating, but will cycle off when no compressor or no heating is needed (factory default).
Occ: “ON” = System fan will run continuously
during all operational modes; “AUTO” = System fan will operate during call for cooling or heating, but will cycle off when no compressor or no heating is needed (factory default).
7. Press ENTER button to save changes to FAN mode selections.
8. Press LEFT button to go back to ADDITIONAL SETUP.
9. Press DOWN button to scroll to HUMIDITY. Press ENTER button to enter HUMIDITY SETUP.
10. Press DOWN button to scroll to DEHUMIDIFICATION. Press ENTER button (see Figure 6).
11. Press ENTER button again to highlight current dehum choice (default is ENABLE).
Manual 2100-684 Page 6 of 25
FIGURE 6
Dehumidification (Air Conditioner)
DEHUMIDIFICATION
DEHUM: ENABLE
ALLOW HEATING DEHUM: YES DEHUM SETPT: 60%RH DEHUM SPAN: 5%RH
12.
Press UP or DOWN button to toggle ENABLE/ DISABLE. Press ENTER button to select/save choice.
13. Press DOWN button to scroll through additional DEHUMIDIFICATION screen choices:
• ALLOW HTG DEHUM = Allows
dehumidification in heating: YES/NO (default is YES).
• DEHUM SETPT = Relative Humidity (RH)
setpoint: 45% RH to 80% RH, 1% increments (default is 60%RH).
DEHUM SPAN = Amount of RH% removal
allowed past setpoint: 5% to 10%, 1% increments (default is 5%RH).
14. Press ENTER button to save changes.
15. Press LEFT button to return to the home screen. Proceed to System Enable on page 9 to continue the setup process.
Heat Pump Applications (see Figure 7)
NOTE: The following is for heat pump applications.
A/C application information can be found in the previous section.
FIGURE 7
Additional Setup (Heat Pump)
1. Press RIGHT button to access Main Menu screen.
2. Press DOWN button to scroll to TECHNICIAN. Press ENTER button.
3.
Controller will ask for password. Press UP and RIGHT buttons to enter ‘BARD’. Press ENTER button.
4. In the TECHNICIAN menu screen, press ENTER button to enter the APPLICATION menu.
5. Press DOWN button to scroll to ADDITIONAL SETUP. Press ENTER button.
6. Press ENTER button again to choose AUX ELECTRIC HEAT.
7. Press ENTER button again to highlight current AUX HEAT choices (see Figure 8).
8. Press UP or DOWN button to scroll through AUX HEAT screen choices:
• W/O LOCKOUT = Auxiliary heat will activate
regardless of compressor operation or outdoor air temperature (factory default). If W/O LOCKOUT is chosen, proceed to set delay-on time (Step 9).
COMP LOCKOUT = Compressor locks out
below the selected outdoor air temperature.
Requires optional Bard 8403-061 Outdoor Air Temperature Sensor.
NONE = No auxiliary strip heat; controller will
not energize W2. If NONE is chosen, press LEFT button to return to the home screen.
9. Press DOWN button to highlight DELAY (MINS).
10. Press ENTER button to highlight default DELAY minutes.
11. Press UP or DOWN button to select amount of minutes desired to delay the electric heat before activation: 10-120 minutes, in 10 minute increments (factory default 15 minutes). Press ENTER button to save choice.
ADDITIONAL SETUP
AUX ELECTRIC HEAT
VENTILATION FAN HUMIDITY MOTION SENSOR SENSORS STAGING
Auxiliary Electric Heat Setup
If the heat pump selection is chosen, electric heat must be configured. These steps do not apply to air conditioners or other types of conventional heating. To configure the auxiliary heat from the home screen:
12. Press LEFT button to return to ADDITIONAL SETUP.
FIGURE 8
Aux Heat Setup
DEHUMIDIFICATION
AUX HEAT: W/O LOCKOUT
DELAY (MINS): 15
Manual 2100-684 Page 7 of 25
If COMP LOCKOUT was chosen during the heat strip configuration process, an optional outdoor air temperature sensor will have to be installed/ configured to specifically set the temperature at which the compressor will no longer be allowed to operate. Refer to the latest version of CompleteStat Controller Advanced Programming & Features 2100-685 to configure the outdoor air temperature sensor.
To install Bard 8403-061 Outdoor Air Temperature Sensor, attach the leads to terminals “OAT” and “GND”. To set the compressor outdoor air temperature limits from the home screen:
1. Press RIGHT button to access Main Menu screen.
2. Press DOWN button to scroll to TECHNICIAN. Press ENTER button.
3. In the TECHNICIAN menu screen, press UP or DOWN button to scroll to LIMITS. Press ENTER button.
4. Press DOWN button to scroll to COMP OAT CLG LOW. Press ENTER button.
5. Press UP or DOWN button to select outdoor air temperature for compressor lockout (factory default 0ºF). Press ENTER to save choice.
6. Press LEFT button to return to TECHNICIAN menu.
Off Delay: “0” = System fan will run for specified time after call ends; 0-600 seconds in 30-second increments.
Occ: “ON” = System fan will run continuously
9. Press ENTER button to save changes to FAN
Unocc: “ON” = System fan will run continuously during all operational modes; “AUTO” = System fan will operate during call for cooling or heating, but will cycle off when no compressor or no heating is needed (factory default).
during all operational modes; “AUTO” = System fan will operate during call for cooling or heating, but will cycle off when no compressor or no heating is needed (factory default).
SETUP selections.
FIGURE 9
Fan Setup (Heat Pump)
FAN SETUP
SPEEDS: CONSTANT SPEED
OFF DELAY (SECS): 0 UNOCC: AUTO OCC: AUTO
Ventilation, Fan and Humidity Setup
1. In the TECHNICIAN menu screen, press ENTER button to enter the APPLICATION menu.
2. Press DOWN button to scroll to ADDITIONAL SETUP. Press ENTER button.
3. Press DOWN button to scroll to VENTILATION. Press ENTER button.
4. Press UP or DOWN button to choose from the available economizer options:
NONE = No economizer, or standard vent
package (ERV/CRV/MFAD). This is the factory default.
EN/DIS = Economizer in system
5. Press ENTER button to select/save appropriate economizer option.
6. Press LEFT button to go back to ADDITIONAL SETUP.
7. The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions. To access or change blower settings, press DOWN button to scroll to FAN. Press ENTER button to enter FAN SETUP (see Figure 9).
8. Press DOWN button to scroll through selections; adjust as necessary.
Speeds: Constant speed (nonadjustable)
10. Press LEFT button to go back to ADDITIONAL SETUP.
11. Press DOWN button to scroll to HUMIDITY. Press ENTER button to enter HUMIDITY SETUP.
12. Press ENTER button again to choose DEHUMIDIFICATION (see Figure 10).
13. Press ENTER button again to highlight current dehum choice (default is ENABLE).
14. Press UP or DOWN button to toggle ENABLE/ DISABLE. Press ENTER button to select/save choice.
15. Press DOWN button to scroll through additional DEHUMIDIFICATION screen choices:
• ALLOW HTG DEHUM = Allows
dehumidification in heating as well as cooling: YES/NO (default is YES).
• DEHUM SETPT = Relative Humidity (RH)
setpoint: 45% RH to 80% RH, 1% increments (default is 60%RH).
DEHUM SPAN = Amount of RH% removal
allowed past setpoint: 5% to 10%, 1% increments (default is 5%RH).
16. Press ENTER button to save changes.
Manual 2100-684 Page 8 of 25