Bard CMA-32 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
CMA-32
Low Ambient Fan Cycling Control
The CMA-32 is a field-installable low ambient fan cycling control kit.
for use on R-410A refrigerant systems.
The
8607-017 Terminal Block
1012-066 Screw (1)
8612-027 230V Head Pressure Control
1804-0520 Extension Tube Assembly
8611-115 Plug Assembly
113-353 Mounting Bracket
1012-065 Screws (2)
The CMA-32 kit is for use with Bard models W42A2D, W48A2D and W60A2D wall-mount air conditioners.
This fan cycling low ambient control is only
CMA-32
kit consists of:
INSTALLATION
Disconnect all power to wall-mount unit. Remove outer and inner control panel covers and right side condenser inlet grille. Circled numbers provided in Figure 1 on page 2 correspond to the following installation steps. Dashed lines indicate where a wire has been disconnected from the terminal.
1. Mount 8607-017 terminal block to unit control panel with 1012-066 screw as shown in Figure 1.
2. Disconnect black high voltage outdoor motor lead from compressor contactor and reconnect to terminal block.
3. Remove the upper service port cap from the liquid line. Install the low ambient control on the liquid line by screwing it onto the service port as shown in Figure 2 on page 3. Use wrenches to make the connection snug and check for leaks.
4.
Route low ambient control wires up through the bushing in the bottom of the control panel. Replace sealing compound after routing wires through the bushing. Route the wires through the wire holders in the control panel as shown in Figure 1.
5. Connect the low ambient control wires between the terminal block and T2 of the compressor contactor (see Figure 1).
6. Recheck wiring by referring to Figure 1. Turn on power to unit. Check for proper operation of the unit by energizing in cooling mode (first or second stage). The compressor should start—except when equipped with economizer and enthalpy control is energizing “free cooling” mode. Energizing “Y2” will override the enthalpy control allowing the mechanical cooling to operate. Run the unit for at least 5 minutes. The condensor fan motor should not run until the liquid pressure has reached 350 PSI. Should the liquid pressure fall below 225 PSI while running, the condensor fan motor will de­energize until the head pressure builds to 350 PSI.
7. Apply “This unit is equipped with CMA-32 control module” label to the inside of the inner control panel cover above the unit wiring diagram.
8. Replace the right side condenser inlet grille and inner and outer control panel covers. This completes the installation.
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 7960-778 Supersedes: NEW Date: 5-24-16
Page 1 of 4
FIGURE 1
Manual 7960-778 Page 2 of 4
Loading...
+ 2 hidden pages