Bard CH5S1, CH4S1, CH3S1 User Manual 2

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE HEAT PUMPS
Models:
CH3S1 CH4S1 CH5S1
THIS IS AN R-410A
HIGH PRESSURE
REFRIGERANT SYSTEM
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
NOTE
Manual : 2100-455A Supersedes: 2100-455 File: Volume III Tab 17 Date: 08-18-06
© Copyright 2004
Manual 2100-455A Page 1 of 25
CONTENTS
Getting Other Information and Publications
For More Information ............................................... 3
Wall Mount General
Heat Pump Wall Mount Model Nomenclature ....... 4
Shipping Damage ................................................. 8
General .............................................................. 8
Duct Work ............................................................. 8
Filters .............................................................. 8
Condensate Drain – Evaporator ........................... 8
Installation Instructions
Wall Mounting Information .................................... 9
Mounting the Unit .................................................. 9
Wiring – Main Power ........................................... 15
Wiring – Low Voltage Wiring ............................... 15
Low Voltage Connections ................................... 16
Start Up
Application .......................................................... 16
Safety Practices .................................................. 17
Important Installer Note....................................... 17
Pressure Service Ports ....................................... 17
High & Low Pressure Switch .............................. 17
Three Phase Scroll Compressor Start Up ... 17 & 18
Phase Monitor..................................................... 18
Service Hints ....................................................... 18
Sequence of Operation ....................................... 18
Compressor Current & Pressure
Control Module ................................................... 18
Defrost Cycle ...................................................... 19
Troubleshooting
Solid State Heat Pump Control
Troubleshooting Procedure................................. 20
Checking Temperature Sensor
Outside Unit Circuit ............................................. 21
Temperature vs. Resistance of Temperature ...... 21
Compressor Solenoid ......................................... 22
Fan Blade Setting Dimensions ........................... 22
Removal of Fan Shroud ...................................... 22
Refrigerant Charge R-410A ................................ 22
Pressure Tables ............................................. 24-25
Figures
Figure 1 Unit Dimensions CH3S1 ...................... 5
Figure 2 Unit Dimensions CH4S1 & CH5S1 ...... 6
Figure 3 Mounting Instructions CH3S1 ............ 10
Figure 4
Figure 5 Electric Heat Clearance ..................... 12
Figure 6 Wall Mounting Instructions ................. 13
Figure 7 Wall Mounting Instructions ................. 13
Figure 8 Common Wall Mounting Installations . 14 Figure 9 Common Wall Mounting Installations . 15
Figure 10 Unit 24V Terminal Board .................... 15
Figure 11 Low Pressure Control Bypass Timer . 17
Figure 12 Defrost Control Board ........................ 19
Figure 13 Fan Blade Setting .............................. 22
Manual 2100-455A Page 2 of 25
Mounting Instructions CH4S1/CH5S1 .
11
Tables
Table 1 Electric Heat Table ................................ 4
Table 2 Electrical Specifications ........................ 7
Table 3 Thermostat Wire Size ......................... 15
Table 4 Wall Thermostat .................................. 16
Table 5 Troubleshooting .................................. 20
Table 6 Fan Blade Dimensions........................ 22
Table 7 Refrigerant Charge ............................. 23
Table 8 Indoor Blower Performance ................ 23
Table 9 Maximum ESP of Operation ............... 23
Table 10 Pressure Table - High Cooling ............ 24
Table 11 Pressure Table - Low Cooling ............. 24
Table 12 Pressure Table - High Heating ............ 25
Table 13 Pressure Table - Low Heating ............. 25
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-455A Page 3 of 25
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
CH 4S 1 – A 05 B P X X X X
MODEL NUMBER
KW
CAPACITY
3S - 3 ton 4S - 4 ton 5S - 5 ton
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
VENTILATION OPTIONS
B - Blank-off Plate R - Energy Recovery V - Commercial Ventilator -
Motorized with Exhaust
FILTER OPTIONS
P - 2-Inch Pleated
COLOR OPTIONS
X - Beige (Standard) 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
CONTROL MODULES
COIL OPTIONS
X - Standard
OUTLET OPTIONS
X - Front (Standard) T - Top Outlet
sledoM
1-0421-8023-0423-8023-0641-0421-8023-0423-8023-064
WKA 4 5 6 9
01 51 81
02
UTBAUTBAUTBAUTBAUTBAUTBAUTBAUTBAUTBAUTB
8.02560711.81008218.02560711.8100821
6.14031432.63006526.14031432.6300652
5.26002151.45004832.63002152.13004830.81002155.26002151.45004832.63002152.13004830.8100215
Manual 2100-455A Page 4 of 25
ELECTRIC HEAT TABLE
A-1S3HCB-1S3HCC-1S3HC
4.41005025.21063512.7084024.41005025.21063512.708402
7.12006037.81030328.01007037.12006037.81030328.0100703
TABLE 1
A-1S4HC A-1S5HC
7.61056314.4104201
2.38052861.2700215
B-1S4HC B-1S5HC
3.34004165.73050646.1200416
C-1S4HC C-1S5HC
43"
29 7/8"
9 13/16"
Supply
Opening
6 1/8"
48 1/16"
15 7/8"
Return
Opening
Flashing
Top Rain
2 1/4"
8 9/16"
(12) Wall
Entrances
Opt. High Voltage
Mounting Holes
MIS-2146
FIGURE 1
UNIT DIMENSIONS
6 7/8"
39 7/8"
Optional Top Outlet
7/8"
6 9/16"
"CH3S1" Unit Dimensions
" 31"
43 7/8"
Heater Access
42 3/16"
Top View
16"
Door
16"
84 11/16"
16"
Door
C. Breaker
Control Panel
5 13/16"
Entrance
Access Door
Low Voltage
13 3/8"
16"
32 3/4"
Outlet
Cond.
Entrance
High Voltage
Cond.
Grille
31 5/8"
Inlet
Grille
16"
Access Door
Right Side View Back View
Drain for optional
drain pan
Front View
1 3/8"
Slope Top
Door
Blower Access
Door
Vent Option
Filter Access
Access Door
Grille
Outlet
Cond.
Manual 2100-455A Page 5 of 25
Hose
Evap. Drain
Left Side View
6 1/8"
9 13/16"
48 1/16"
15 7/8"
Top Rain
Flashing
2 1/4"8 9/16"
Opt. High
Voltage
Entrances
MIS-2020 A
"CH4S1 and CH5S1" Unit Dimensions
FIGURE 2
UNIT DIMENSIONS
6 7/8"
43"
29 7/8"
6 9/16"
7/8"
31"
Supply
Opening
16"
Door
Heater Access
Return
Opening
16"
Control Panel
94 11/16"
Door
16"
C. Breaker
5 13/16"
Low Voltage
Access Door
13 3/8"
16"
Entrance
High Voltage
16"
42 3/4"
Cond.
Outlet
Entrance
41 5/8"
Grille
Holes
(12) Wall
Mounting
Access Door
Back View
22 3/16"
Right Side View
39 7/8"
Manual 2100-455A Page 6 of 25
Optional Top Outlet
1 3/8"
43 7/8"
Top View
Slope Top
42 3/16"
Door
Door
Filter Access
Blower Access
Vent Option
Access Door
Inlet Grille
Condenser
Grille
Cond.
Outlet
Drain for optional
drain pan
Front View
Hose
Evap. Drain
Left Side View
TABLE 2
ELECTRICAL SPECIFICATIONS
TIUCRICELGNIS TIUCRICLAUD
detaR
ledoM
Z0A-1S3HC
50A 01A 51A
Z0B-1S3HC
60B 90B 51B
Z0C-1S3HC
60C 90C 51C
Z0A-1S4HC 40A 50A 01A 51A 02A
Z0B-1S4HC 60B 90B 51B 81B
Z0C-1S4HC 60C 90C 51C 81C
Z0A-1S5HC 40A 50A 01A 51A 02A
Z0B-1S5HC 60B 90B 51B 81B
Z0C-1S5HC 60C 90C 51C 81C
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75°C copper wire. All wiring must conform to NEC and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code
(latest revision), Article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special
attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.
&stloV
3-064 3-064 3-064 3-064
3-064 3-064 3-064 3-064 3-064
3-064 3-064 3-064 3-064 3-064
.oN
3
dleiF
esahP
rewoP
stiuriC
1-802/032
1
1-802/032
1 1-802/032 1-802/032
3-802/032
1
3-802/032
1
3-802/032
1
3-802/032
1
1
1
1
1
1-802/032
1
1-802/032
1
1-802/032 1-802/032 1-802/032 1-802/032
3-802/032
1
3-802/032
1
3-802/032
1
3-802/032
1
3-802/032
1
1
1
1
1
1
1-802/032
1
1-802/032 1-802/032 1-802/032 1-802/032 1-802/032
3-802/032
1
3-802/032
1
3-802/032
2
3-802/032
2
3-802/032
2
1
1
1
1
1
92 55
2ro1
18
2ro1
58 32
14 05 05
11 02 42 42
73 75
2ro1
36
2ro1
98
2ro1
98
3ro1
311
72 54 45 45 55
41 32 82 82 82
44
2ro1
56
2ro1
07
2ro1
69
2ro1
69
3ro1
411
63 45 36 36 46
91 82 23 23 33
1
muminiM tiucriC
yticapmA
2
2
mumixaM
dleiF
lanretxE
roesuF
eriW
tiucriC
eziS
rekaerB
54 06 09 09
03 54 05 05
51 02 52 52
05 06 07 09 09
53 05 06 06 06
02 52 03 03 03
06 07 08
05 06 07 07 07
52 53 53 53 53
8 6 4 4
01 8 8 8
41
21
01
01 8
6 6 3 3
021
2 8
8 6 6 6
21
01
01
01
01 6
4 4
001
3
001
3
021
2 8
6 4 4 4
01 8 8 8 8
dnuorG
rewoP
eriW eziS
01
01 8 8
01
01
01
01
41
21
01
01
01
01 8 8 8 6
01
01
01
01
01
21
01
01
01
01
01 8 8 8 8 6
01
01 6 6 6
01
01
01
01
01
3
tiucriCmuminiM
yticapmA
.tkC
.tkC
.tkC
A
B
C
---
---
---
---
---
---
92
25
---
33
25
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
73
62
---
73
25
---
73
25
---
25
25
62
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
44
12
---
44
62
---
44
25
---
44
25
---
44
25
62
---
---
---
---
---
---
63
82
---
63
82
---
73
82
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
mumixaM
esuFlanretxE
tiucriCro
rekaerB
.tkC
.tkC
.tkC
A
B
C
---
---
---
---
---
---
54
06
---
54
06
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
05
03
---
05
06
---
05
06
---
05
06
03
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
06
52
---
06
03
---
06
06
---
06
06
---
06
06
03
---
---
---
---
---
---
05
03
---
05
03
---
05
03
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
2
rewoPdleiF
eziSeriW
.tkC
.tkC
.tkC
A
B
C
---
---
---
---
---
---
01
6
---
8
6
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
8
01
---
8
6
---
8
6
---
6
6
01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
8
01
---
8
01
---
8
6
---
8
6
---
8
6
01
---
---
---
---
---
---
8
01
---
8
01
---
8
01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
2
.tkC
A
B
---
---
---
---
01
01
01
01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
01
01
01
01
01
01
01
01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
01
01
01
01
01
01
01
01
01
01
---
---
---
---
01
01
01
01
01
01
---
---
---
---
---
---
---
---
---
---
Manual 2100-455A Page 7 of 25
dnuorG
eziSeriW
.tkC
.tkC
C
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
--­01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
--­01
---
---
---
---
---
---
---
---
---
---
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment, required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
These units are suitable for 0 inch clearance to combustible material. See Wall Mounting Instructions and Figures 3, 4, 5, 6 & 7 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
FILTERS
A 2-inch pleated filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access door.
CONDENSATE DRAIN – EVAPORATOR
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
DUCT WORK
Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Manual 2100-455A Page 8 of 25
Loading...
+ 17 hidden pages