These publications can help you install the air
conditioner or heat pump. You can usually find these at
your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
FOR MORE INFORMATION, CONTACT
THESE PUBLISHERS:
ACCAAir Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSIAmerican National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating,
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code
(latest revision), Article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special
attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.
&stloV
3-064
3-064
3-064
3-064
3-064
3-064
3-064
3-064
3-064
3-064
3-064
3-064
3-064
3-064
.oN
3
dleiF
esahP
rewoP
stiuriC
1-802/032
1
1-802/032
1
1-802/032
1-802/032
3-802/032
1
3-802/032
1
3-802/032
1
3-802/032
1
1
1
1
1
1-802/032
1
1-802/032
1
1-802/032
1-802/032
1-802/032
1-802/032
3-802/032
1
3-802/032
1
3-802/032
1
3-802/032
1
3-802/032
1
1
1
1
1
1
1-802/032
1
1-802/032
1-802/032
1-802/032
1-802/032
1-802/032
3-802/032
1
3-802/032
1
3-802/032
2
3-802/032
2
3-802/032
2
1
1
1
1
1
92
55
2ro1
18
2ro1
58
32
14
05
05
11
02
42
42
73
75
2ro1
36
2ro1
98
2ro1
98
3ro1
311
72
54
45
45
55
41
32
82
82
82
44
2ro1
56
2ro1
07
2ro1
69
2ro1
69
3ro1
411
63
45
36
36
46
91
82
23
23
33
1
muminiM
tiucriC
yticapmA
2
2
mumixaM
dleiF
lanretxE
roesuF
eriW
tiucriC
eziS
rekaerB
54
06
09
09
03
54
05
05
51
02
52
52
05
06
07
09
09
53
05
06
06
06
02
52
03
03
03
06
07
08
05
06
07
07
07
52
53
53
53
53
8
6
4
4
01
8
8
8
41
21
01
01
8
6
6
3
3
021
2
8
8
6
6
6
21
01
01
01
01
6
4
4
001
3
001
3
021
2
8
6
4
4
4
01
8
8
8
8
dnuorG
rewoP
eriW
eziS
01
01
8
8
01
01
01
01
41
21
01
01
01
01
8
8
8
6
01
01
01
01
01
21
01
01
01
01
01
8
8
8
8
6
01
01
6
6
6
01
01
01
01
01
3
tiucriCmuminiM
yticapmA
.tkC
.tkC
.tkC
A
B
C
---
---
---
---
---
---
92
25
---
33
25
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
73
62
---
73
25
---
73
25
---
25
25
62
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
44
12
---
44
62
---
44
25
---
44
25
---
44
25
62
---
---
---
---
---
---
63
82
---
63
82
---
73
82
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
mumixaM
esuFlanretxE
tiucriCro
rekaerB
.tkC
.tkC
.tkC
A
B
C
---
---
---
---
---
---
54
06
---
54
06
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
05
03
---
05
06
---
05
06
---
05
06
03
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
06
52
---
06
03
---
06
06
---
06
06
---
06
06
03
---
---
---
---
---
---
05
03
---
05
03
---
05
03
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
2
rewoPdleiF
eziSeriW
.tkC
.tkC
.tkC
A
B
C
---
---
---
---
---
---
01
6
---
8
6
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
8
01
---
8
6
---
8
6
---
6
6
01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
8
01
---
8
01
---
8
6
---
8
6
---
8
6
01
---
---
---
---
---
---
8
01
---
8
01
---
8
01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
2
.tkC
A
B
---
---
---
---
01
01
01
01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
01
01
01
01
01
01
01
01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
01
01
01
01
01
01
01
01
01
01
---
---
---
---
01
01
01
01
01
01
---
---
---
---
---
---
---
---
---
---
Manual 2100-455A
Page7 of 25
dnuorG
eziSeriW
.tkC
.tkC
C
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
--01
---
---
---
---
---
---
---
---
---
---
---
---
---
---
--01
---
---
---
---
---
---
---
---
---
---
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
These units are suitable for 0 inch clearance to
combustible material. See Wall Mounting Instructions
and Figures 3, 4, 5, 6 & 7 for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.
Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct. The spacing between
louvers on the grille shall not be larger than 5/8 inch.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
Any grille that meets with 5/8 inch louver criteria may
be used. It is recommended that Bard Return Air Grille
Kit RG2 through RG5 or RFG2 through RFG5 be
installed when no return duct is used. Contact
distributor or factory for ordering information. If using
a return air filter grille, filters must be of sufficient size
to allow a maximum velocity of 400 fpm.
FILTERS
A 2-inch pleated filter is supplied with each unit. The
filter slides into position making it easy to service. This
filter can be serviced from the outside by removing the
filter access door.
CONDENSATE DRAIN – EVAPORATOR
A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
DUCT WORK
Any heat pump is more critical of proper operating
charge and an adequate duct system than a straight air
conditioning unit. All duct work, supply and return,
must be properly sized for the design airflow
requirement of the equipment. Air Conditioning
Contractors of America (ACCA) is an excellent guide to
proper sizing. All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.
Manual 2100-455A
Page8 of 25
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the weight
of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket is provided
for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance. If a
combustible wall use a minimum of 30" x 10"
dimensions for sizing. However, it is generally
recommended that a 1-inch clearance is used for
ease of installation. The supply air opening would
then be 32" x 12". See Figures 3 and 4 for details.
3. Locate and mark lag bolt locations and bottom
mounting bracket location. See Figure 3.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top. Top
rain flashing is shipped with unit attached to back of
unit on the right side.
6. Position unit in opening and secure with 5/16 lag
bolts; use 3/4 inch diameter flat washers on the lag
bolts.
7. Secure rain flashing to wall and caulk across entire
length of top. See Figure 3.
8. For additional mounting rigidity, the return air and
supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum
of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
Manual 2100-455A
Page9 of 25
Foam
flanges
Top
0" min.
"
3
8
1
Supply Duct
"6
7
8
0" min.
Opening
Return Air
MIS-2209
Wall Section
Apply a bead of caulk
Rain Flashing (supplied)
along entire length of top
and behind side mounting
FIGURE 3
MOUNTING INSTRUCTIONS
ABCDE
30106 1/216
32125 1/225
43"
C
A
C
Optional
Top Outlet
D
Panel
Heater
Access
B
16"
Supply Opening
16"
16"
30"
Return Opening
16"
Unit Mounting
Holes, 12 places
16"
(Install before unit)
Bottom Wall Bracket
16"
Wall
"
8
5
6
"CH3S1" Wall Mounting Instructions
Manual 2100-455A
Page10 of 25
MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIM. TO MAINTAIN 0"
COMBUSTIBLE MATERIALS
REQUIRED DIM. TO MAINTAIN
OPTIONAL 1" CLEARANCE FROM
16"
D
16"
16"
16"
16"
3E8
"
1
)RDP
PLQ
PLQ
0,6$
IODQJHV
5DLQ)ODVKLQJVXSSOLHG
$SSO\DEHDGRIFDXON
DORQJHQWLUHOHQJWKRIWRS
DQGEHKLQGVLGHPRXQWLQJ
FIGURE 4
MOUNTING INSTRUCTIONS
7RS
&
2SWLRQDO
7RS2XWOHW
'
6XSSO\'XFW
3DQHO
+HDWHU
$FFHVV
(
%
2SHQLQJ
5HWXUQ$LU
8QLW0RXQWLQJ
+ROHVSODFHV
:DOO6HFWLRQ
%RWWRP:DOO%UDFNHW
,QVWDOOEHIRUHXQLW
:DOO
$
6XSSO\2SHQLQJ
&
'
5HWXUQ2SHQLQJ
&+6DQG&+6:DOO0RXQWLQJ,QVWUXFWLRQV
Manual 2100-455A
Page11 of 25
FIGURE 5
ELECTRIC HEAT CLEARANCE
Typical Building
Outside Sheeting
Unit
Supply Air Duct
Flange of Wall
Wall Frame
Inside Sheeting
Supply Air
Duct
1" OPTIONAL CLEARANCE
RECOMMENDED
Side section view of supply air
duct for wall mounted unit showing
0" clearance to combustible surfaces.
MIS-2210
Note: This unit is approved for 0" clearance, but the optional 1" clearance is recommended. See Figures 3 & 4.
Manual 2100-455A
Page12 of 25
FIGURE 6
1" clearance
1" clearance
9 13/16"
6 1/8"
15 7/8"
29 7/8"
51 1/4"
44 7/8"
Supply Opening
Return Opening
These structural
members must be
able to support the
entire weight of the
unit.
Locate stud to match
spacing for rest of wall.
A second member may
be required for some
walls.
!
Follow all local building codes
when framing wall to support unit.
Note: duct maybe in attic or
below rafters as shown.
Rafters
Supply Air
Finished Ceiling
Wall Sleeve
Return Air
Outside Wall
False Wall
Duct
RETURN AIR
Ducted Supply - Return At Unit
Note: duct maybe in attic or
below rafters as shown.
Unit (outside)
Supply Air
Note: direction of return
grille louvers is pointed down
for lowest sound level as shown.
Outside Wall
Rafters
Return Air
Duct
Finished Ceiling
Manual 2100-455A
Page14 of 25
Return Air
Grille
MIS-2027
remrofsnarT
AVALFeguaGeriW
mumixaM
ecnatsiD
teeFnI
553.2
eguag02
eguag81
eguag61
egaug41
egaug21
54
06
001
061
052
FIGURE 9
COMMON WALL MOUNTING INSTALLATIONS
Closet Installation
Note: duct maybe in attic or
below rafters as shown.
Supply Air
Rafters
Finished Ceiling
Wall Sleeve
Duct
Grille
Unit (outside)
WIRING – LOW VOLTAGE WIRING
230 / 208V, 1 phase and 3 phase equipment dual
primary voltage transformers. All equipment leaves the
factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
TAPRANGE
240253 – 216
208220 – 187
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size. Each outdoor unit is marked with a “Minimum
Circuit Ampacity”. This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required. If this is the
case, the unit serial plate will so indicate. All models
are suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”. These instructions must be adhered
to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring must
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C
copper) for all models including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out. This tab
will now line up with the slot in the door. When shut, a
padlock may be placed through the hole in the tab
preventing entry.
See “Start Up” section for important information on
three phase scroll compressor start ups.
Outside Wall
Return Air
Closet Wall
Raised Closet Floor
Return Air
Closet Wall
Grille
MIS-2240
FIGURE 10
UNIT 24V TERMINAL BOARD
T7652H1000 THERMOSTAT
BARD PART #8403-052
G
C
Rc
Rh
Y1
G
C
C
G
Y1
R
R
Y
Factory Jumper
B
Y2
Y2
Y1
W1
1F93-380 THERMOSTAT
B
B
W1
W1
W2
W2 E
W3
L
BARD PART #8403-049
L
E
UNIT LOW VOLTAGE
TERMINAL BLOCK
DH
A1
W3/A1
O1
MIS-2026 A
Nine (9) wires should be run from thermostat subbase to
the 24V terminal board in the unit. A nine conductor,
18 gauge copper color-coded thermostat cable is
recommended. The connection points are shown in
Figure 10.
IMPORTANT
Only the thermostat combinations as shown
above will work with this equipment.
TABLE 3
THERMOSTAT WIRE SIZE
Manual 2100-455A
Page15 of 25
LOW VOLTAGE CONNECTIONS
These units use a grounded 24 volt AC low voltage
circuit and require at least a 2 stage heating and a 2
stage cooling thermostat.
The “R” terminal is the hot terminal and the “C”
terminal is grounded.
“G” terminal is the fan input.
“Y” terminal is the compressor Stage 1 input.
“Y1” terminal is the compressor Stage 2 input.
“B” terminal is the reversing valve input. The reversing
valve must be energized for heating mode.
TABLE 4
WALL THERMOSTAT
tatsomrehTserutaeFtnanimoderP
940-3048
)083-39F1(
250-3048
taeh.gts2;looc.gts2
cinortcelEelbammargorP
revoegnahclaunaMrootuA
taeh.gts3;looc.gts2
cinortcelEelbammargorP
revoegnahclaunaMrootuA
“R” terminal is 24 VAC hot.
“C” terminal is 24 VAC grounded.
“L” terminal is compressor lockout output. This
terminal is activated on a high or low pressure trip by
the electronic heat pump control. This is a 24 VAC
output.
“W2” terminal is second stage heat (if equipped).
“O1” terminal is the ventilation input. This terminal
energizes any factory installed ventilation option.
“E” terminal is the emergency heat input. This terminal
energizes the emergency heat relay if equipped.
NOTE: For total and proper control using DDC, a
total of 7 controlled outputs are required (6 if
no ventilation system is installed). For proper
system operation under Emergency Heat
conditions where the compressor needs to be
deactivated, the B-W2-E outputs need to be
energized. Removing the Y (compressor) signal
alone turns the compressor off, but does not
activate the additional circuitry embedded in
the heat pump for proper and complete
operation.
LOW VOLTAGE CONNECTIONS
FOR DDC CONTROL
Fan OnlyEnergize G
Cooling Mode 1st StageEnergize Y, G
Cooling Mode 2nd StageEnergize Y, Y1, G
Heat Pump Heating 1st StageEnergize Y, G, B
START UP
These units require R-410A refrigerant & Polyol Ester oil.
APPLICATION:
1. Use separate service and manufacturing equipment
to avoid cross contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A
refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250
psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and
R-12. Although nearly azeotropic, charge with
liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot
withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero,
but must be reclaimed due to its global warming
potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly
absorb moisture and strongly hold this moisture in
the oil.
10. A liquid line dryer must be used - even a deep
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes MAXIMUM.
12. If compressor removal is necessary, always plug
compressor immediately after removal. Purge with
small amount of nitrogen when inserting plugs.
Heat Pump Heating 2nd Stage Energize Y, Y1, G, B
3rd Stage Heating
w/Heat Pump (if employed)
VentilationEnergize G, O1
Emergency HeatEnergize B, W2, E, G
Manual 2100-455A
Page16 of 25
Energize G, W2, Y, B, Y1
START UP CONT’D.
SAFETY PRACTICES:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can
be irritating to the skin, and liquid refrigerant will
freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become flammable.
4. Do not inhale R-410A – the vapor attacks the
nervous system, creating dizziness, loss of
coordination and slurred speech. Cardiac
irregularities, unconsciousness and ultimate death
can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces
hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands significantly at
warmer temperatures. Once a cylinder or line is full
of liquid, any further rise in temperature will cause
it to burst.
IMPORTANT INSTALLER NOTE
For improved start-up performance, wash the indoor coil
with a dish washing detergent.
PRESSURE SERVICE PORTS
R-410A requires high pressure hose connections and
gauges. High and Low pressure service ports are
installed on all units so that the system operating
pressures can be observed. Pressure tables can be found
later in the manual covering all models on both cooling
and heating cycles. It is imperative to match the correct
pressure table to the unit by model number.
HIGH & LOW PRESSURE SWITCH
All models are supplied with a remote reset high and low
pressure switch. If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.
High/Low Pressure control provides protection for the
compressor. In the event system pressures go above 540
PSI or below 35 PSI, in either cooling or heating mode,
the compressor will be stopped. This will activate the
“L” terminal of the low voltage terminal strip. This
terminal can be used for remote indication of a pressure
lockout. The lockout circuit will hold compressor off
line. When the system problem is corrected, the unit
operation can be restored by turning the main power
supply off and then back on, or reset the room thermostat.
The low pressure control has a bypass to eliminate
nuisance lockout on cold start up.
The bypass timer should be set to 200 seconds, and this
is to assure there is no nuisance tripping of the lowpressure control during startup in heating mode under
cold weather conditions. See Figure 10:
FIGURE 11
LOW PRESSURE CONTROL BYPASS TIMER
THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION
Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.
However, three phase compressors will rotate in either
direction depending upon phasing of the power. Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made. All three
phase units incorporate a phase monitor to ensure proper
field wiring. See the “Phase Monitor” section later in
this manual.
Verification of proper rotation must be made any time a
compressor is changed or rewired. If improper rotation
is corrected at this time there will be no negative impact
on the durability of the compressor. However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for several minutes, the compressor’s
internal protector will trip.
All three phase ZR3 compressors are wired identically
internally. As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.
Manual 2100-455A
Page17 of 25
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized. Reverse
rotation also results in an elevated sound level over that
with correct rotations, as well as, substantially reduced
current draw compared to tabulate values.
The direction of rotation of the compressor may be
changed by reversing any two line connections to the unit.
PHASE MONITOR
All units with three phase compressors are equipped with
a 3 phase line monitor to prevent compressor damage due
to phase reversal.
The phase monitor in this unit is equipped with two
LEDs. If the Y signal is present at the phase monitor and
phases are correct, the green LED will light. If phases are
reversed, the red fault LED will be lit and compressor
operation is inhibited.
If a fault condition occurs, reverse two of the supply leads
to the unit. Do not reverse any of the unit factory wires
as damage may occur.
HEATING STAGE 1 – A 24V solenoid coil on reversing
valve controls heating cycle operation. Two thermostat
options, one allowing “Auto” changeover from cycle to
cycle and the other constantly energizing solenoid coil
during heating season and thus eliminating pressure
equalization noise except during defrost, are to be used.
On “Auto” option a circuit is completed from R-W1 and
R-Y on each heating “on” cycle, energizing reversing
valve solenoid and pulling in compressor contactor
starting compressor and outdoor motor. R-G also make
starting indoor blower motor. Heat pump heating cycle
now in operation. The second option has no “Auto”
changeover position, but instead energizes the reversing
valve solenoid constantly whenever the system switch on
subbase is placed in “Heat” position, the “B” terminal
being constantly energized from R. A thermostat demand
for Stage 1 heat completes R-Y circuit, pulling in
compressor contactor starting compressor and outdoor
motor. R-G also make starting indoor blower motor.
HEATING STAGE 2 – Circuit R-Y2 makes at the
thermostat energizing the 2nd stage solenoid in the
compressor.
SERVICE HINTS
1. Caution homeowner to maintain clean air filters at all
times. Also, not to needlessly close off supply and
return air registers. This reduces airflow through the
system, which shortens equipment service life as well
as increasing operating costs.
2. Switching to heating cycle at 75° F or higher outside
temperature may cause a nuisance trip of the remote
reset high pressure switch. Turn thermostat off then
on to reset the high pressure switch.
3. The heat pump wall thermostats perform multiple
functions. Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.
4. Check all power fuses or circuit breakers to be sure
they are the correct rating.
5. Periodic cleaning of the outdoor coil to permit full
and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COOLING STAGE 1 – Circuit R-Y makes at thermostat
pulling in compressor contactor, starting the compressor
and outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling operation
or can be energized by manual fan switch on subbase of
constant air circulation.
COOLING STAGE 2 – Circuit R-Y1 makes at the
thermostat energizing the 2nd stage solenoid in the
compressor. Default position is not energized.
Compressor will run at low capacity until this solenoid is
energized.
COMPRESSOR CURRENT & PRESSURE
CONTROL MODULE
The compressor control module monitors compressor
current and pressure and prevents internal overload trips
due to low voltage or extremely high ambient
temperatures by de-energizing the full capacity
compressor solenoid. The control monitors current to the
compressor and discharge pressure. If current is sensed
that is in excess of 93% of the compressor, maximum
continuous current rating or pressure is sensed greater
than 525 PSI, the compressor control module deenergizes for a time as determined by the time
potentiometer on the compressor control module. This
will drop the current draw and pressure and allow the
compressor to run at 75 percent of capacity rather than
not at all. Once the time period has elapsed the full
capacity compressor solenoid will re-energize and try
again to run at full capacity. If the pressure or current is
exceeded again, the coil will again de-energize. This
sequence will repeat until the ambient temperature drops
or the line voltage increases enough that the trip values
are not exceeded.
The relay on the compressor control module is a single
pole double throw relay. The full capacity compressor
solenoid connects to the common terminal of the relay.
Once current is sensed by the compressor control module,
the relay closes and the second stage cooling call (if
present) is sent to the full capacity compressor solenoid.
This sequence prevents damage to the full capacity
compressor solenoid by ensuring that the solenoid is not
energized when the compressor is not running. A brief
time delay in this sequence also prevents locked rotor
amperage during start-up from tripping the device and
engaging the time delay period.
Manual 2100-455A
Page18 of 25
DEFROST CYCLE
The defrost cycle is controlled by temperature and time
on the solid state heat pump control. See Figure 12.
When the outdoor temperature is in the lower 40° F
temperature range or colder, the outdoor coil
temperature is 32° F or below. This coil temperature is
sensed by the coil temperature sensor mounted near the
bottom of the outdoor coil. Once coil temperature
reaches 30° F or below, the coil temperature sensor
sends a signal to the control logic of the heat pump
control and the defrost timer will start.
After 60 minutes at 30° F or below, the heat pump
control will place the system in the defrost mode.
During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57° F, the
coil temperature sensor will send a signal to the heat
pump control which will return the system to heating
operations automatically.
If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.
The heat pump defrost control board has an option of
30, 60 or 90-minute setting. All models are shipped
from the factory on the 60-minute pin. If special
circumstances require a change to another time, remove
the wire from the 60-minute terminal and reconnect to
the desired terminal. The manufacturer's
recommendation is for 60-minute defrost cycles. Refer
to Figure 12.
FIGURE 12
DEFROST CONTROL BOARD
There is a cycle speed up jumper on the control. This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.
Use a small screwdriver or other metallic object, or
another 1/4 inch QC, to short between the SPEEDUP
terminals to accelerate the HPC timer and initiate
defrost.
Be careful not to touch any other terminals with the
instrument used to short the SPEEDUP terminals. It
may take up to 10 seconds with the SPEEDUP terminals
shorted for the speedup to be completed and the defrost
cycle to start.
As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and run
through the 1-minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.
There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a 0° coil temperature. This
can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.
By placing a jumper across the SEN JMP terminals (a
1/4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit. This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.
In order to terminate the defrost test the SEN JMP
jumper must be removed. If left in place too long the
compressor could stop due to the high pressure control
opening because of high pressure condition created by
operating in the cooling mode with
outdoor fan off. Pressure will rise
fairly fast as there is likely no
actual frost on the outdoor coil in
this artificial test condition.
There is also a 5-minute compressor
time delay function built into the
HPC. This is to protect the
compressor from short cycling
conditions. In some instances, it is
helpful to the service technician to
override or speed up this timing
period, and shorting out the
SPEEDUP terminals for a few
seconds can do this.
Manual 2100-455A
Page19 of 25
TROUBLESHOOTING
SOLID STATE HEAT PUMP CONTROL
TROUBLESHOOTING PROCEDURE
1. Turn on AC power supply to indoor and outdoor
units.
2. Turn thermostat blower switch to fan on. The indoor
blower should start. (If it doesn’t, troubleshoot
indoor unit and correct problem.)
A nominal 24-volt direct current coil activates the
internal compressor solenoid. The input control circuit
voltage must be 18 to 28 volt ac. The coil power
requirement is 20 VA. The external electrical
connection is made with a molded plug assembly (PN
029-0311-00). This plug contains a full wave rectifier
to supply direct current to the unloader coil.
Compressor Solenoid Test Procedure – If it is
suspected that the unloader is not working, the
following methods may be used to verify operation.
1. Operate the system and measure compressor
amperage. Cycle the compressor solenoid on and
off at ten-second intervals. The compressor
amperage should go up or down at least 25 percent.
2. If step one does not give the expected results, shut
unit off. Apply 18 to 28 volt ac to the solenoid
molded plug leads and listen for a click as the
solenoid pulls in. Remove power and listen for
another click as the solenoid returns to its original
position.
3. If clicks can’t be heard, shut off power and remove
the control circuit molded plug from the compressor
and measure the solenoid coil resistance. The
resistance should be 32 to 60 ohms depending on
compressor temperature.
4. Next, check the molded plug.
Voltage check: Apply control voltage to the plug wires (18
to 28 volt ac). The measured
connectors in the plug should be around 15 to 27 vdc.
Resistance check: Measure the resistance from the end of
one molded plug lead to either of the two female
connectors in the plug. One of the connectors should read
close to zero ohms, while the other should read infinity.
Repeat with other wire. The same female connector as
before should read zero, while the other connector again
reads infinity. Reverse polarity on the ohmmeter leads and
repeat. The female connector that read infinity previously
should now read close to zero ohms.
Replace plug if either of these test methods does not
show the desired results.
dc voltage at the female
FAN BLADE SETTING DIMENSIONS
Shown in Figure 13 are the correct fan blade setting
dimensions for proper air delivery across the outdoor
coil.
Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.
FIGURE 13
FAN BLADE SETTING
TABLE 6
FAN BLADE DIMENSION
ledoMAnoisnemiD
LLA0.1
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each
side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser and
bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud
assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
R-410A
REFRIGERANT CHARGE
The correct system R-410A charge is shown on the unit
rating plate. Optimum unit performance will occur with
a refrigerant charge shown on the unit serial plate.
If correct charge is in doubt, recover the refrigerant and
recharge per the charge on the unit rating plate. See
Table 7 for proper subcooling levels for evaluation of
proper charge.
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain
1 Maximum ESP (inches WC) shown is with 2" thick disposable filter.
2 Rated CFM for 2nd Stage Operation – required for maximum performance rating.
3 1st Stage – the CFM output on 1st Stage Heating or Cooling.
4 Blower only CFM is the total air being circulated during continuous fan mode.
approximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at both 230/
208 or 460 volts.
4
ylnOrewolB
edoMtneVro
taeHcirtcelE
TABLE 9
MAXIMUM ESP OF OPERATION
deepShgiH
LLA5.
Manual 2100-455A
Page23 of 25
TABLE 10
PRESSURE TABLE
GNILOOCYTICAPACHGIH
LEDOM
1S3HC
1S4HC
1S5HC
RIANRUTER
ERUTAREPMET
BD°57
BW°26
BD°08
BW°76
BD°58
BW°27
BD°57
BW°26
BD°08
BW°76
BD°58
BW°27
BD°57
BW°26
BD°08
BW°76
BD°58
BW°27
ERUSSERP57oF08oF58oF09oF59oF001oF501oF011oF511oF
EDISWOL
431
431
431
531
731
831
041
EDISHGIH
892
813
933
363
883
514
EDISWOL
341
341
341
441
641
EDISHGIH
603
623
843
273
EDISWOL
841
841
841
EDISHGIH
713
733
EDISWOL
131
EDISHGIH
EDISWOL
EDISHGIH
EDISWOL
EDISHGIH
EDISWOL
EDISHGIH
EDISWOL
EDISHGIH
EDISWOL
EDISHGIH
331
803
233
041
241
613
043
541
741
723
253
031
633
543
753
131
953
931
041
863
441
541
183
941
063
583
531
731
653
083
441
641
563
093
941
151
873
404
131
231
183
604
041
141
193
614
541
641
504
134
841
893
624
151
351
214
144
831
931
604
134
841
941
614
244
351
451
134
754
431
531
034
554
341
441
144
764
841
941
654
384
341
544
674
051
351
654
884
551
851
274
505
931
041
654
384
941
051
864
594
451
551
484
215
731
831
284
015
641
841
494
325
151
351
115
145
641
015
651
325
161
145
041
905
051
225
551
045
041
835
051
255
551
175
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
TABLE 11
PRESSURE TABLE
GNILOOCYTICAPACWOL
LEDOM
1S3HC
1S4HC
1S5HC
RIANRUTER
ERUTAREPMET
BD°57
BW°26
BD°08
BW°76
BD°58
BW°27
BD°57
BW°26
BD°08
BW°76
BD°58
BW°27
BD°57
BW°26
BD°08
BW°76
BD°58
BW°27
ERUSSERP57oF08oF58oF09oF59oF001oF501oF011oF511oF
EDISWOL
931
041
141
241
341
541
EDISHGIH
952
482
803
333
953
EDISWOL
941
051
151
251
EDISHGIH
662
192
613
EDISWOL
451
551
EDISHGIH
572
EDISWOL
731
EDISHGIH
182
EDISWOL
641
EDISHGIH
882
EDISWOL
151
EDISHGIH
892
EDISWOL
631
EDISHGIH
392
EDISWOL
541
EDISHGIH
003
EDISWOL
051
EDISHGIH
113
651
103
723
731
931
103
323
741
941
903
133
251
451
023
343
731
931
613
043
741
941
423
943
251
451
533
163
351
243
863
751
851
453
183
041
141
543
073
051
151
453
973
551
651
663
293
141
241
463
983
151
251
373
993
651
751
683
314
741
583
014
551
751
593
124
061
261
904
634
341
441
493
914
351
451
404
034
851
951
814
544
341
441
314
934
351
451
424
054
851
951
934
664
FEERGEDLIOCROODTUOGNIRETNEERUTAREPMETRIA
941
151
834
464
951
161
944
674
561
761
564
394
641
741
744
574
651
751
854
784
161
261
474
405
541
541
464
984
551
551
674
205
061
061
394
025
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
Manual 2100-455A
Page24 of 25
F
931
o
574
921
061
874
364
F
641
214
o
841
071
114
564
F56
o
F06
o
FEERGEDLIOCROODTUOGNIRETNEERUTAREPMETRIA
F55
o
F05
o
F54
o
F04
o
F53
o
F03
o
F52
o
F02
o
TABLE 12
F51
o
PRESSURE TABLE
141
721
611
501
59
68
87
17
46
95
45
134
911
244
321
314
801
783
463
49
643
38
033
47
813
66
903
16
403
75
303
65
254
801
724
204
673
404
99
383
353
09
463
433
28
643
713
57
033
403
86
613
492
36
403
882
75
392
482
35
F56
431
983
o
F06
221
963
o
FEERGEDLIOCROODTUOGNIRETNEERUTAREPMETRIA
F55
111
053
o
F05
101
433
o
F54
023
19
o
F04
803
o
38
F53
892
o
57
F03
192
o
86
F52
682
o
26
F02
382
o
75
331
941
883
434
031
911
763
604
183
601
843
311
133
853
59
99
833
613
58
78
123
303
77
77
603
392
07
07
492
482
46
46
582
872
06
26
972
372
16
85
TABLE 13
003
05
65
482
382
94
PRESSURE TABLE
F51
o
35
172
382
36
572
65
182
592
F01
o
F5
o
ERUSSERP0
ERUTAREPMET
RIANRUTER
55
64
092
45
44
EDISHGIH
EDISWOL
EDISWOL
GNITAEHYTICAPACHGIH
LEDOM
S3HC°07
772
64
272
082
44
EDISHGIH
EDISHGIH
EDISWOL
F01
94
o
F5
64
o
ERUSSERP0
EDISWOL
ERUTAREPMET
RIANRUTER
GNITAEHYTICAPACWOL
S5HC°07
S4HC°07
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
LEDOM
172
082
56
572
06
EDISHGIH
EDISWOL
S3HC°07
472
65
572
072
85
EDISHGIH
EDISHGIH
EDISWOL
S5HC°07
S4HC°07
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
Manual 2100-455A
Page25 of 25
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.