conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ....................... ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ....................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
FOR MORE INFORMATION, CONTACT
THESE PUBLISHERS:
ACCAAir Conditioning Contractors of America1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSIAmerican National Standards Institute11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPANational Fire Protection AssociationBatterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manual 2100-586D
Page 3 of 25
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
C 36 H 1 – A 05 V P X X X X
MODEL
NUMBER
CAPACITY |
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
Note All 230/208V units with or without electric heat have circuit breaker. 0C is for 460V circuit breaker & 0KW. No 460V electric heat options w/circuit
breaker available.
H - Heat Pump
VENTILATION OPTIONS
B - Blank-off Plate
V - Commercial Ventilator - Mod. Spring Return w/Exhaust
S - Economizer (Internal) - Fully Modulating with Exhaust
R - Energy Recovery Ventilator - Motorized with Exhaust
(See Spec. Sheet S3459)
460V -0Z and all 460V KW options are with Rotary Disconnect.
X - Beige
1 - White
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
S - Stainless Steel
FILTER OPTIONS
X - 1-Inch Fiberglass (MERV 2)
M - 2-Inch Pleated (MERV 11)
P - 2-Inch Pleated (MERV 8)
See available heater options by unit model number.
COIL OPTIONS
X - Standard Hydrophilic Fin
Indoor Coil & Uncoated
Aluminum Outdoor Coil
1 - Phenolic Coated Indoor Coil
2 - Phenolic Coated Outdoor Coil
3 - Phenolic Coated ID & OD Coil
SUPPLY AIR OUTLET
X - Front (Standard)
WARNING
Falling or tipping the unit could cause injury or death!
Use two (2) people or a machine to move the unit.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by
trained, experienced service and installation technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss/gain calculation made according to methods
of Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
Manual 2100-586D
Page 4 of 25
DUCT WORK
All duct work, supply and return, must be properly sized
for the design airow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing. All duct work or portions
thereof not in the conditioned space should be properly
insulated in order to both conserve energy and prevent
condensation or moisture damage.
Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA). When
duct runs through unheated spaces, it should be insulated
with a minimum of one inch of insulation. Use insulation
with a vapor barrier on the outside of the insulation.
Flexible joints should be used to connect the duct work to
the equipment in order to keep the noise transmission to a
minimum.
A 1/4 inch clearance to combustible material for the rst
three feet of duct attached to the outlet air frame is required.
See Wall Mounting Instructions and Figures 3A, 3B and 4
for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the wall
cavity.
Some installations may not require any return air duct. A
metallic return air grille is required with installations not
requiring a return air duct. The spacing between louvers on
the grille shall not be larger than 5/8 inch.
FILTERS
A 1-inch throwaway lter is standard with each
unit. The lter slides into position making it easy to
service. This lter can be serviced from the outside by
removing the lter access panel. 2-inch pleated lters
are also available as optional accessories. The internal
lter brackets are adjustable to accommodate the 2-inch
lter by bending two (2) tabs down on each side of the
lter support bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in
the service door.
If the unit is equipped with a fresh air damper assembly,
the assembly is shipped already attached to the unit.
The damper blade is locked in the closed position.
To allow the damper to operate, the maximum and
minimum blade position stops must be installed. See
Figure 1.
All capacity, efciency and cost of operation
information is based upon the fresh air blank-off plate
in place and is recommended for maximum energy
efciency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
Any grille that meets with 5/8 inch louver criteria may be
used. It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used. Contact distributor or factory
for ordering information. If using a return air lter grille,
lters must be of sufcient size to allow a maximum
velocity of 400 fpm.
NOTE: If no return air duct is used, applicable installation
codes may limit this cabinet to installation only in a
single story structure.
FIGURE 1
FRESH AIR DAMPER
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at
the top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
Manual 2100-586D
Page 5 of 25
INSTALLATION INSTRUCTIONS
WARNING
Failure to bolt the unit to the wall could result
in the unit falling, causing injury or death!
Follow all mounting instructions.
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to ensure that they are capable of carrying the
weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket, attached
to skid for shipping, is provided for ease of
installation, but is not required.
2. The unit itself is suitable for 0 inch clearance,
but the supply air duct ange and the rst 3 feet
of supply air duct require a minimum of 1/4 inch
clearance to combustible material. However, it is
generally recommended that a 1-inch clearance is
used for ease of installation and maintaining the
required clearance to combustible material. See
Figure 3 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom
mounting bracket location. See Figures 3A & 3B.
4. Mount bottom mounting bracket.
5. Hook top rain ashing, attached to front - right of
supply ange for shipping, under back bend of top.
6. Position unit in opening and secure with 5/16 lag bolts;
use 7/8 inch diameter at washers on the lag bolts.
7. Secure rain ashing to wall and caulk across entire
length of top. See Figures 3A & 3B.
WARNING
Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the rst 3 feet of duct can result in
re causing damage, injury or death.
8. For additional mounting rigidity, the return air
and supply air frames or collars can be drilled
and screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
PLACEMENT
1. On side-by-side installations, maintain a minimum
of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
2. Care should be taken to ensure that the recirculation
and obstruction of condenser discharge air does
not occur. Recirculation of condenser discharge
air can be from either a single unit or multiple
units. Any object such as shrubbery, a building
or a large object can cause obstructions to the
condenser discharge air. Recirculation or reduced
airow caused by obstructions will result in reduced
capacity, possible unit pressure safety lockouts and
reduced unit service life.
Units with a draw through condenser, such as
the C**H 11 EER, it is recommended there be a
minimum distance of 15 feet between the front of
the unit and any barrier to airow.
REQUIRED STEPS AFTER FINAL
PLACEMENT (C48H & C60H UNITS
ONLY)
The compressor is secured to the unit base for shipping.
Although unit will perform as designed with the
compressor secured in place, there may be noticeable
additional noise and vibration. To obtain the lowest
noise and vibration levels, remove the compressor
Clearances Required for Service Access
and Adequate Condenser Airow
MODELSLEFT SIDERIGHT SIDE
C24H, C30H36"36"
C36H, C42H, C48H, C60H36"36"
Manual 2100-586D
Page 6 of 25
Minimum Clearances Required to
Combustible Materials
MODELS
C24H, C30H1/4"0"
C36H, C42H, C48H, C60H1/4"0"
SUPPLY AIR DUCT
FIRST THREE FEET
CABINET
3"
8620-160 Drain Fitting Supplied with unit,
field installed.
Panel
Air Inlet
Door
Vent Option
Condenser
Filter Access
Ventilation
Air
Front View
F
W
5.75
G
Panel
indoor coil
Electric
Cond.
Access
Heater
4° Pitch
Rain Hood
Side View
Heat
Built In
Air
Disconnect
(Lockable)
Access Panel
Drain for
Outlet
C. Breaker/
ERV and
ECONWMS
only hood
Low Voltage
Electrical
Entrance
High Voltage
Electrical
Entrance
D
2.13
A
C H
K
J
I
Supply Air Opening
Return Air Opening
Top Rain
Flashing
Shipping
Location
Back View
Electrical
Entrances
Optional
Side Wall
Mounting
Brackets
(Built In)
T
S
S
M
.44
L
Q
P
S
N
O
E
R
S
S
B
Bottom Installation
Bracket - optional use
for direct mount, not
used when unit
installed with curb
shipping brackets after the unit is in its nal operating
location.
Remove the side grille to gain access to the compressor
shipping brackets. The brackets are located on the
compressor double isolation base at the front and rear
of the compressor. The brackets are secured to the unit
base with two (2) screws, and secured to the isolation
plate with a 1/4" nut. Remove and dispose of the two
(2) screws and brackets. Re-install the 1/4" nut once
bracket is removed.
FIGURE 2
Dimensions of Basic Unit for Architectural & Installation Requirements (Nominal)