Bard C24H1-B, C30H1-C, C30H1-A, C30H1-B, C36H1-A Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGED HEAT PUMP
Models:
C24H1-A C24H1-B C30H1-A C30H1-B C30H1-C
C36H1-A C36H1-B C36H1-C C42H1-A C42H1-B C42H1-C
C48H1-A C48H1-B C48H1-C C60H1-A C60H1-B C60H1-C
www.bardhvac.com
Manual: 2100-586D Supersedes: 2100-5486C Date: 7-28-15
Page 1 of 25
CONTENTS
Getting Other Information and Publications 3
Wall Mount General Information
Wall Mount Model Nomenclature .............................. 4
Shipping Damage ..................................................... 4
General ................................................................. 4
Duct Work .................................................................5
Filters ................................................................. 5
Fresh Air Intake ......................................................... 5
Condensate Drain .................................................... 5
Installation Instructions
Wall Mounting Information ........................................6
Mounting the Unit ...................................................... 6
Placement ................................................................. 6
Clearances Required ................................................ 6
Minimum Clearances ................................................ 6
Wiring – Main Power ............................................... 13
Wiring – Low Voltage Wiring ................................... 13
Optional Outdoor T-Stat Applications ...................... 13
Figures
Figure 1 Fresh Air Damper Assembly ..................... 5
Figure 2 Unit Dimensions ....................................... 7
Figure 3A Mounting Instructions C24H, C30H ..........8
Figure 3B Mounting Instructions C36, 42, 48, 60H ... 9
Figure 4 Electric Heat Clearance ......................... 10
Figure 5 Wall Mounting Instructions ..................... 11
Figure 6 Wall Mounting Instructions ..................... 11
Figure 7 Common Wall Mounting Installations ..... 12
Figure 8 Defrost Control Board ............................ 17
Figure 9 Fan Blade Setting ................................... 20
Figure 10 Control Disassembly .............................. 25
Figure 11 Winding Test ........................................... 25
Figure 12 Drip Loop ................................................ 25
Start Up
General ............................................................... 14
Topping Off System Charge .................................... 14
Safety Practices ...................................................... 14
Important Installer Note ........................................... 15
High & Low Pressure Switch ................................... 15
Three Phase Scroll Compressor ............................. 15
Phase Monitor ......................................................... 15
Service Hints ........................................................... 15
Sequence of Operation ........................................... 16
Pressure Service Ports ........................................... 16
Defrost Cycle .......................................................... 16
Troubleshooting
Solid State Heat Pump Control ............................... 18
Checking Temperature Sensor ............................... 19
Fan Blade Setting Dimensions ................................ 20
Removal of Fan Shroud .......................................... 20
R-410A Refrigerant Charge ....................................20
Troubleshooting GE ECM Motors ........................... 24
Troubleshooting GE ECM Motors ........................... 25
Tables
Table 1 Clearances Required ............................... 6
Table 2 Min. Clearances Required ........................ 6
Table 3 Troubleshooting......................................18
Table Temperature F vs. Resistance ............... 19
Table 4 Fan Blade Dimension ............................. 20
Table 5A Cooling Pressure .................................... 21
Table 5B Heating Pressure ................................... 21
Table 6 Electrical Specications C**H ................ 22
Table 7 Indoor Blower Performance ................... 23
Manual 2100-586D Page 2 of 25
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ....................... ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ....................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-586D Page 3 of 25
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
C 36 H 1 – A 05 V P X X X X
MODEL
NUMBER
CAPACITY |
24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton
Note  All 230/208V units with or without electric heat have circuit breaker. 0C is for 460V circuit breaker & 0KW. No 460V electric heat options w/circuit breaker available.
H - Heat Pump
VENTILATION OPTIONS
B - Blank-off Plate V - Commercial Ventilator - Mod. Spring Return w/Exhaust S - Economizer (Internal) - Fully Modulating with Exhaust R - Energy Recovery Ventilator - Motorized with Exhaust (See Spec. Sheet S3459)
460V -0Z and all 460V KW options are with Rotary Disconnect.
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW 0C - 0KW 0Z - 0KW 04 - 4KW 05 - 5KW 06 - 6KW F8 - 8KW S8 - 8KW 09 - 9KW 10 -10KW 15 -15KW 20 -20KW
CONTROL MODULES
(See Spec. Sheet S3459)
COLOR OPTIONS
X - Beige 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze S - Stainless Steel
FILTER OPTIONS
X - 1-Inch Fiberglass (MERV 2) M - 2-Inch Pleated (MERV 11) P - 2-Inch Pleated (MERV 8)
See available heater options by unit model number.
COIL OPTIONS
X - Standard Hydrophilic Fin Indoor Coil & Uncoated Aluminum Outdoor Coil 1 - Phenolic Coated Indoor Coil 2 - Phenolic Coated Outdoor Coil 3 - Phenolic Coated ID & OD Coil
SUPPLY AIR OUTLET
X - Front (Standard)
WARNING
Falling or tipping the unit could cause injury or death! Use two (2) people or a machine to move the unit.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss/gain calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-586D Page 4 of 25
DUCT WORK
All duct work, supply and return, must be properly sized
for the design airow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the rst
three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3A, 3B and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
FILTERS
A 1-inch throwaway lter is standard with each unit. The lter slides into position making it easy to service. This lter can be serviced from the outside by removing the lter access panel. 2-inch pleated lters
are also available as optional accessories. The internal
lter brackets are adjustable to accommodate the 2-inch lter by bending two (2) tabs down on each side of the lter support bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service door.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 1.
All capacity, efciency and cost of operation
information is based upon the fresh air blank-off plate in place and is recommended for maximum energy
efciency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory
for ordering information. If using a return air lter grille, lters must be of sufcient size to allow a maximum
velocity of 400 fpm.
NOTE: If no return air duct is used, applicable installation codes may limit this cabinet to installation only in a single story structure.
FIGURE 1
FRESH AIR DAMPER
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Manual 2100-586D Page 5 of 25
INSTALLATION INSTRUCTIONS
WARNING
Failure to bolt the unit to the wall could result
in the unit falling, causing injury or death!
Follow all mounting instructions.
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to ensure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance,
but the supply air duct ange and the rst 3 feet
of supply air duct require a minimum of 1/4 inch clearance to combustible material. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 3 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figures 3A & 3B.
4. Mount bottom mounting bracket.
5. Hook top rain ashing, attached to front - right of supply ange for shipping, under back bend of top.
6. Position unit in opening and secure with 5/16 lag bolts;
use 7/8 inch diameter at washers on the lag bolts.
7. Secure rain ashing to wall and caulk across entire
length of top. See Figures 3A & 3B.
WARNING
Failure to provide the 1/4 inch clearance between the supply duct and a combustible
surface for the rst 3 feet of duct can result in re causing damage, injury or death.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
PLACEMENT
1. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper
airow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
2. Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or a large object can cause obstructions to the condenser discharge air. Recirculation or reduced
airow caused by obstructions will result in reduced
capacity, possible unit pressure safety lockouts and reduced unit service life.
Units with a draw through condenser, such as
the C**H 11 EER, it is recommended there be a minimum distance of 15 feet between the front of
the unit and any barrier to airow.
REQUIRED STEPS AFTER FINAL PLACEMENT (C48H & C60H UNITS ONLY)
The compressor is secured to the unit base for shipping. Although unit will perform as designed with the compressor secured in place, there may be noticeable additional noise and vibration. To obtain the lowest noise and vibration levels, remove the compressor
Clearances Required for Service Access
and Adequate Condenser Airow
MODELS LEFT SIDE RIGHT SIDE
C24H, C30H 36" 36"
C36H, C42H, C48H, C60H 36" 36"
Manual 2100-586D Page 6 of 25
Minimum Clearances Required to Combustible Materials
MODELS
C24H, C30H 1/4" 0"
C36H, C42H, C48H, C60H 1/4" 0"
SUPPLY AIR DUCT
FIRST THREE FEET
CABINET
3"
8620-160 Drain Fitting ­Supplied with unit, field installed.
Panel
Air Inlet
Door
Vent Option
Condenser
Filter Access
Ventilation Air
Front View
F
W
5.75
G
Panel
indoor coil
Electric
Cond.
Access
Heater
4° Pitch
Rain Hood
Side View
Heat
Built In
Air
Disconnect
(Lockable)
Access Panel
Drain for
Outlet
C. Breaker/
ERV and
ECONWMS
only hood
Low Voltage
Electrical Entrance
High Voltage
Electrical Entrance
D
2.13
A
C H
K
J
I
Supply Air Opening
Return Air Opening
Top Rain
Flashing
Shipping
Location
Back View
Electrical
Entrances
Optional
Side Wall
Mounting
Brackets
(Built In)
T
S
S
M
.44
L
Q
P
S
N
O
E
R
S
S
B
Bottom Installation Bracket - optional use for direct mount, not used when unit installed with curb
shipping brackets after the unit is in its nal operating
location.
Remove the side grille to gain access to the compressor shipping brackets. The brackets are located on the compressor double isolation base at the front and rear of the compressor. The brackets are secured to the unit base with two (2) screws, and secured to the isolation plate with a 1/4" nut. Remove and dispose of the two (2) screws and brackets. Re-install the 1/4" nut once bracket is removed.
FIGURE 2
Dimensions of Basic Unit for Architectural & Installation Requirements (Nominal)
WIDTH
DEPTH
MODEL
C24H1 C30H1
C36H1 C42H1
C48H1 C60H1
(W)
38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 10.88 25.75 17.93 26.75 28.75 29.25 27.00 2.63 39.13 22.75 9.14 5.00 12.00 5.00
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
HEIGHT
(D)
All dimensions are in inches. Dimensional drawings are not to scale.
SUPPLY RETURN
(H)
A B C B E F G I J K L M N O P Q R S T
C**H
RIGHT UNIT
Manual 2100-586D Page 7 of 25
D
12"
12"
12"
12"
12"
C CA
28"
1"
3"
4"
Typ.
4
1
2
"
B
E
14"
1"
3
1
8
"
4"
Typ.
5"
4
1
2
"
7
8
"
RETURN AIR
SUPPLIED
Return Opening
16 7/84 9/164 1/21030
17 5/83 13/165 1/48 1/228 1/2
EDCBA
COMBUSTIBLE MATERIALS
RECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
THE SIDE MOUNTING FLANGES AND UNDER
1/4" CLEARANCE ON ALL
RAIN FLASHING
COMBUSTIBLE MATERIALS
DUCT
TOP FLASHING AT TIME OF INSTALLATION.
1/4" MIN. CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
OPENING
ENTIRE LENGTH OF TOP.
MATERIALS
NOTES:
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL STRUCTURE
TOP
MIS-311 C
Wall Opening and Hole Location View Right Side View
WALL
HEATER ACCESS
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
SUPPLY AIR
Supply Opening
W*R UNIT SHOWN, W*L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
FIGURE 3A
C24H, C30H
MOUNTING INSTRUCTIONS
Manual 2100-586D Page 8 of 25
Loading...
+ 17 hidden pages