The Energy Recovery Ventilator was designed to
provide energy efficient, cost effective ventilation to
meet I. A. Q. (Indoor Air Quality) requirements while
still maintaining good indoor comfort and humidity
control for a variety of applications such as schools,
classrooms, lounges, conference rooms, beauty salons
and others. It provides a constant supply of fresh air for
control of airborne pollutants including CO2, smoke,
radon, formaldehyde, excess moisture, virus and
bacteria.
The ventilator incorporates patented rotary heat
exchange state-of-the-art technology to remove both
heat & moisture and provides required ventilation to
meet the requirements of ASHRAE 62.1 standard.
It is designed as a single package which is factory
installed. The package consists of a unique rotary
Energy Recovery Cassette that can be easily removed
for cleaning or maintenance. It has two 15-inch
diameter heat transfer wheels for efficient heat transfer.
The heat transfer wheels use a permanently bonded dry
desiccant coating for total heat recovery.
Ventilation is accomplished with 2 blower/motor
assemblies each consisting of a drive motor and dual
blowers for maximum ventilation at low sound levels.
Motor speeds can be adjusted so that air is exhausted at
the same rate that fresh air is brought into the structure
thus not pressuring the building. The rotating energy
wheels provide the heat transfer effectively during both
summer and winter conditions.
1. Indoor blower motor must be run whenever the ERV
is run.
2. Select the correct motor speed on the ERV. Using
Table 1 of the ERV Installation Instructions
determine the motor speed needed to get the desired
amount of ventilation air needed. For instance, do
not use the high speed tap on a ERV if only 200
CFM of ventilation air is needed. Use the low speed
tap. Using the high speed tap would serve no useful
purpose and would effect the overall efficiency of the
air conditioning system. System operation costs
would also increase.
3. Run the ERV only during periods when the
conditioned space is occupied. Running the ERV
during unoccupied periods wastes energy, decreases
the expected life of the ERV, and can result in a large
moisture buildup in the structure. The ERV can
remove up to 60 to 70% of the moisture in the
incoming air, not 100% of it. Running the ERV
when the structure is unoccupied allows moisture to
build up in the structure because there is little or no
cooling load. Thus, the air conditioner is not running
enough to remove the excess moisture being brought
in. Use a control system that in some way can
control the system based on occupancy.
NOTE: The Energy Recovery Ventilator is NOT a
dehumidifier.
NOTE: Operation is not recommended below 5°F
outdoor temperature because freezing of
moisture in the heat transfer wheel can occur.
IMPORTANT
Operating the ERV during unoccupied periods
can result in a build up of moisture in the
classroom.
Manual 2100-533A
Page3 of 12
Page 4
RECOMMENDED CONTROL
SEQUENCES
Several possible control scenarios are listed below:
1. Use a programmable electronic thermostat with
auxiliary terminal to control the ERV based on daily
programmed occupancy periods. Bard markets and
recommends Bard Part No. 8403-060 programmable
electronic thermostat for heat pump applications.
2. Use a motion sensor in conjunction with a
mechanical thermostat to determine occupancy in
the classroom. Bard markets the CS2000A for this
use.
3. Use a DDC control system to control the ERV based
on a room occupancy schedule.
4. Tie the operation of the ERV into the light switch.
The lights in a room are usually on only when
occupied.
5. Use a manual timer that the occupants turn to
energize the ERV for a specific number of hours.
VENTILATION AIRFLOW
The ERV is equipped with a 3-speed motor to provide
the capability of adjusting the ventilation rates to the
requirements of the specific application by simply
changing motor speeds.
TABLE 1
VENTILATION AIR (CFM)
deepShgiH
)kcalB(
MFC
The ERV units are wired from the factory on medium
intake and low exhaust speeds. The ERV is equipped
with independently controlled 3-speed motor to provide
the capability of adjusting the ventilation rates to the
requirements of the specific application and to be able to
provide positive pressure in the structure. This is
accomplished by setting the intake blower on a higher
speed than the exhaust blower.
054573003
deepSmuideM
)eulB(
)deR(
deepSwoL
6. Use a programmable mechanical timer to energize
the ERV and indoor blower during occupied periods
of the day.
7. Use Bard Part No. 8403-056 CO2 controller for “ondemand” ventilation.
CONTROL WIRING
The QWSERV comes wired in the low voltage control
circuit from the factory.
With the “X” Remote Thermostat Option, it is default
wired into the “A” terminal, which drives the vent to
operate only during occupied periods when using a Bard
8403-060 thermostat or Bard CS2000 controller. If you
prefer for the QWSERV to operate anytime the blower
is operational, you will need to install a jumper wire
from “G” to “A”. If you prefer to use Bard 8403-056
CO2 controller to make the ventilation “on-demand”,
there is a connection adjacent to the thermostat
connections in the unit upper right-hand corner, and is
marked to match CO2 controller connections.
Furthermore, disconnect and tape off the wire as shown
in Figure 4 and you will need to field set the CO2 sensor
jumpers per Figure 5.
WARNING
Open disconnect to shut all power OFF before
doing this. Failure to do so could result in injury
or death due to electrical shock.
Moving the speed taps located in the control panel can
change the blower speed of the intake and exhaust. See
Figure 1.
FIGURE 1
BLOWER SPEED ADJUSTMENT
With the “D” Door Mounted Thermostat Option, the
thermostat is already connected and programmed to
operate the QWSERV only during occupied periods.
With the “H” Door Mounted Thermostat and CO
controller, the unit is ready to go with “on-demand”
ventilation as controlled by the CO2 controller.
NOTE: Sensible
performance only
is shown for
winter application.
ENERGY RECOVERY VENTILATOR
MAINTENANCE
GENERAL INFORMATION
The ability to clean exposed surfaces within air moving
systems is an important design consideration for the
maintenance of system performance and air quality.
The need for periodic cleaning will be a function of
operating schedule, climate, and contaminants in the
indoor air being exhausted and in the outdoor air being
supplied to the building. All components exposed to the
airstream, including energy recovery wheels, may
require cleaning in most applications.
Rotary counterflow heat exchangers (heat wheels) with
laminar airflow are “self-cleaning” with respect to dry
particles. Smaller particles pass through; larger
particles land on the surface and are blow clear as the
flow direction is reversed. For this reason the primary
need for cleaning is to remove films of oil based
aerosols that have condensed on energy transfer
surfaces. Buildup of material over time may eventually
reduce airflow. Most importantly, in the case of
desiccant coated (enthalpy) wheels, such films can close
off micron sized pores at the surface of the desiccant
material, reducing the efficiency with which the
desiccant can adsorb and desorb moisture.
FREQUENCY
In a reasonably clean indoor environment such as a
school, office building, or home, experience shows that
reductions of airflow or loss of sensible (temperature)
effectiveness may not occur for ten or more years.
However, experience also shows that measurable
changes in latent energy (water vapor) transfer can occur
in shorter periods of time in commercial, institutional
and residential applications experiencing moderate
occupant smoking or with cooking facilities. In
applications experiencing unusually high levels of
occupant smoking, such as smoking lounges, nightclubs,
bars and restaurants, washing of energy transfer
surfaces, as frequently as every six months, may be
necessary to maintain latent transfer efficiency. Similar
washing cycles may also be appropriate for industrial
applications involving the ventilation of high levels of
smoke or oil based aerosols such as those found in
welding or machining operations, for example. In these
applications, latent efficiency losses of as much as 40%
or more may develop over a period of one to three years.
Manual 2100-533A
Page6 of 12
Page 7
CLEANABILITY AND PERFORMANCE
In order to maintain energy recovery ventilation
systems, energy transfer surfaces must be accessible for
washing to remove oils, grease, tars and dirt that can
impede performance or generate odors. Washing of the
desiccant surfaces is required to remove contaminate
buildups that can reduce adsorption of water molecules.
The continued ability of an enthalpy wheel to transfer
latent energy depends upon the permanence of the bond
between the desiccant and the energy transfer surfaces.
Bard wheels feature silica gel desiccant permanently
bonded to the heat exchange surface without adhesives;
the desiccant will not be lost in the washing process.
Proper cleaning of the Bard energy recovery wheel will
restore latent effectiveness to near original performance.
MAINTENANCE PROCEDURES
NOTE: Local conditions can vary and affect the
required time between routine maintenance
procedures, therefore all sites (or specific units
at a site) may not have the same schedule to
maintain acceptable performance. The
following timetables are recommended and can
be altered based on local experience.
QUARTERLY MAINTENANCE
1. Inspect mist eliminator/prefilter and clean if
necessary. This filter is located in the wall sleeve
and can be accessed by either removing the exterior
louver grille, the vent package from inside the unit,
or by disconnecting the unit from the wall brackets,
and rolling the unit away from the sleeve on its
integral wheel system. The filter is an aluminum
mesh filter and can be cleaned with water and any
detergent not harmful to aluminum.
2. Inspect the comfort air filter and clean or replace as
necessary. This filter is located behind the fronthinged service door.
6. Use a shop vacuum with brush attachment to clean
both sides of the energy recovery wheels.
7. Reverse shop vacuum to use as a blower and blow
out any residual dry debris from the wheel.
NOTE: Discoloration and staining of the wheel
does not affect its performance. Only
excessive buildup of foreign material needs
to be removed.
8. If any belt chirping or squealing noise is present,
apply a small amount of LPS-1 or equivalent dry
film lubricant to the belt.
ANNUAL MAINTENANCE
1. Inspect and conduct the same procedures as outlined
under Quarterly Maintenance.
2. To maintain peak latent (moisture) removal
capacity, it is recommended that the energy
recovery wheels be sprayed with a diluted nonacid
based evaporator coil cleaner or alkaline detergent
solution such as 409.
NOTE: Do not use acid based cleaners, aromatic
solvents, temperatures in excess of 170°F or
steam. Damage to the wheel may result.
Do not disassemble and immerse the entire heat
wheel in a soaking solution, as bearing and
other damage may result.
3. Rinse wheel thoroughly after application of the
cleaning solution, and allow to drain before
reinstalling.
4. No re-lubrication is required to heat wheel bearings
of the drive motor, or to the intake and exhaust
blower motors.
5. If any belt chirping or squealing noise is present,
apply a small amount of LPS-1 or equivalent dry
film lubricant to the belt.
3. Inspect energy recovery ventilator for proper wheel
rotation and dirt buildup. This can be done in
conjunction with Item 2 above. Energize the energy
recovery ventilator after inspecting the filter and
observe for proper rotation and/or dirt buildup.
4. Recommended energy recovery wheel cleaning
procedures follow: Disconnect all power to the unit.
Open the front-hinged service door to the unit.
5. Remove the front cassette retaining panel from the
front of the ERV. Unplug the amp connectors to the
cassette drive motor. Slide energy recovery cassette
out of the ventilator.
Manual 2100-533A
Page7 of 12
Page 8
If belts "squeak" or "chirp"
lubricate lightly with LPS-1
or equivalent "dry film"
lubricant.
FIGURE 2
BELT REPLACEMENT INSTRUCTIONS
Route (1) replacement belt
in top groove of pulley.
Route (1) replacement belt
in bottom groove of pulley.
Belt Replacement
Instructions
Manual 2100-533A
Page8 of 12
MIS-2166
Page 9
FIGURE 3
HUB ASSEMBLY WITH BALL BEARINGS
Manual 2100-533A
Page9 of 12
Page 10
Relay
Control
4
1
2
2
Motor Plug
Motor Plug
Exhaust
Motor
Blower
Capacitor
Exhaust
4
1
3
Exhaust
Motor Plug
Intake
Intake
1
Capacitor
Intake
Motor Plug
Ground
To Unit High Voltage 240/208-60-1
Power Plug
Speed Plug
Exhaust
32
1
2
3
Power Plug
Green
Black
Block
Term.
Black
2323
23
2
2
4114-100
Motor
Blower
4
3
480V
208V
Transformer
120 V
Com
Speed Plug
Intake
Capacitor
Cassette
Motor Plug
4
3
1
Damper
Motor
Control Relay
Motor
Cassette
2
Motor Plug
Cassette
CO2 Disconnect
Red
Red
Relay
24
Control
29
Brown/White
Brown/White
Black/White
2134567891011
for Wiring Energy Recovery to Unit
12
Note: See Control Wiring Section of Installation Inst.
Black/White
Brown/White
CO2 SENSOR IS USED
DISCONNECT WHEN
2
27
Control Plug
213456789101112
Red/White
Brwn/White
Black/White
Orange
Black
1
Black/White
Blk/Red
Red
Transformer
480
240
208
COM
120 V
Exhaust
Speed
Plug
Black
Black
Black
Intake
Speed Plug
Yellow
White
Capacitor
WIRE FOR 208V OPERATION
TERMINAL BLOCK AND CONNECT RED
DISCONNECT ORANGE WIRE FROM
1
26
26
28
28
25
25
Note: See Control Wiring Section of Installation Inst. for Wiring Energy Recovery to Unit
25
25
28
28
26
Brown
Yellow
Green
Orange
26
26
2
3
Cassette
4
Motor Plug
Black
Capacitor
3
Motor
Red (Low Speed)
White
2
28
Motor Plug
Intake
Blue (Med. Speed)
1
Black (High Speed)
Intake
4
Blower
Red (Low Speed)
Blue (Med. Speed)
Black (High Speed)
White
25
2
431
Motor Plug
Exhaust
DANGER
!
*DISCONNECT POWER BEFORE
*ELECTRICAL SHOCK HAZARD
SERVICING.
WARNING
!
USE COPPER CONDUCTORS
75° C.
ONLY SUITABLE FOR AT LEAST
Motor
Blower
Capacitor
Exhaust
1
Black/White
White
Green
Brown
Motor
Cassette
Brown/White
ComponentCapacitor
Bl ower M otor4/3 70
Cassette Motor3/250
Motor
Intake
Damper
Manual 2100-533A
Page10 of 12
Page 11
FIGURE 4
DISCONNECT & TAPE OFF WIRE
MIS-2759
DISCONNECT AND TAPE OFF FOR
CO2 CONTROLLED VENTILATION
Manual 2100-533A
Page11 of 12
Page 12
FIGURE 5
FIELD SET CO
SENSOR JUMPERS
2
QWSERV VENT PACKAGE
2 CONTROLLER SETTING FOR 1000 PPM
CO
OFF
"SW1" SET TO ON
ON
OFF
OUTSW2SW1
ON
0-100%
AN
VOLTAGE
CURRENT
20-100%
"AN" SET TO VOLTAGE"SW2" SET TO ON
"OUT" SET TO 20-100%
MIS-2756
Manual 2100-533A
Page12 of 12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.