Bard 920-0074 User Manual

OPERATION INSTRUCTIONS
ENERGY RECOVERY VENTILATOR
WITH EXHAUST
Model:
2 Through 5 Ton
920-0074 QWSERV
QW*S Series
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual: 2100-533A Supersedes: 2100-533 File: Volume II, Tab 14 Date: 12-08-10
Manual 2100-533A Page 1 of 12
CONTENTS
Electrical Specifications .......................................... 3
General Description of ERV ................................... 3
Control Requirements ............................................ 3
Recommended Control Sequences ....................... 4
Control Wiring ........................................................ 4
Ventilation Airflow ................................................... 4
Performance & Application Data ............................ 5
Energy Recovery Ventilator Maintenance ........6 & 7
Maintenance Procedures ....................................... 7
Figures
Figure 1 Blower Speed Adjustment ....................... 4
Figure 2 Belt Replacement .................................... 8
Figure 3 Hub Assembly with Ball Bearings ............ 9
Figure 4 Disconnect & Tape Off Wiring ................ 11
Figure 5 Field Set CO
Wiring Diagram
.............................................................. 10
Tables
Table 1 Ventilation Air (CFM)................................ 4
Table 2 Summer Cooling Performance ................ 5
Table 3 Winter Heating Performance ................... 6
Sensor Jumpers .............. 12
2
Manual 2100-533A Page 2 of 12
COPYRIGHT DECEMBER 2009
BARD MANUFACTURING COMPANY, INC.
BRYAN, OHIO USA 43506
ELECTRICAL SPECIFICATIONS
ledoMegatloVspmA
4700-029802/0322.2V42
egatloV
GENERAL DESCRIPTION
The Energy Recovery Ventilator was designed to provide energy efficient, cost effective ventilation to meet I. A. Q. (Indoor Air Quality) requirements while still maintaining good indoor comfort and humidity control for a variety of applications such as schools, classrooms, lounges, conference rooms, beauty salons and others. It provides a constant supply of fresh air for control of airborne pollutants including CO2, smoke, radon, formaldehyde, excess moisture, virus and bacteria.
The ventilator incorporates patented rotary heat exchange state-of-the-art technology to remove both heat & moisture and provides required ventilation to meet the requirements of ASHRAE 62.1 standard.
It is designed as a single package which is factory installed. The package consists of a unique rotary Energy Recovery Cassette that can be easily removed for cleaning or maintenance. It has two 15-inch diameter heat transfer wheels for efficient heat transfer. The heat transfer wheels use a permanently bonded dry desiccant coating for total heat recovery.
Ventilation is accomplished with 2 blower/motor assemblies each consisting of a drive motor and dual blowers for maximum ventilation at low sound levels. Motor speeds can be adjusted so that air is exhausted at the same rate that fresh air is brought into the structure thus not pressuring the building. The rotating energy wheels provide the heat transfer effectively during both summer and winter conditions.
lortnoC
ledoM
4700-029
ehthtiwesUroF
stinUgniwolloF
C-,B-,A-S2WQ C-,B-,A-S3WQ C-,B-,A-S4WQ C-,B-,A-S5WQ
CONTROL REQUIREMENTS
1. Indoor blower motor must be run whenever the ERV is run.
2. Select the correct motor speed on the ERV. Using Table 1 of the ERV Installation Instructions determine the motor speed needed to get the desired amount of ventilation air needed. For instance, do not use the high speed tap on a ERV if only 200 CFM of ventilation air is needed. Use the low speed tap. Using the high speed tap would serve no useful purpose and would effect the overall efficiency of the air conditioning system. System operation costs would also increase.
3. Run the ERV only during periods when the conditioned space is occupied. Running the ERV during unoccupied periods wastes energy, decreases the expected life of the ERV, and can result in a large moisture buildup in the structure. The ERV can remove up to 60 to 70% of the moisture in the incoming air, not 100% of it. Running the ERV when the structure is unoccupied allows moisture to build up in the structure because there is little or no cooling load. Thus, the air conditioner is not running enough to remove the excess moisture being brought in. Use a control system that in some way can control the system based on occupancy.
NOTE: The Energy Recovery Ventilator is NOT a
dehumidifier.
NOTE: Operation is not recommended below 5°F
outdoor temperature because freezing of moisture in the heat transfer wheel can occur.
IMPORTANT
Operating the ERV during unoccupied periods can result in a build up of moisture in the classroom.
Manual 2100-533A Page 3 of 12
RECOMMENDED CONTROL SEQUENCES
Several possible control scenarios are listed below:
1. Use a programmable electronic thermostat with auxiliary terminal to control the ERV based on daily programmed occupancy periods. Bard markets and recommends Bard Part No. 8403-060 programmable electronic thermostat for heat pump applications.
2. Use a motion sensor in conjunction with a mechanical thermostat to determine occupancy in the classroom. Bard markets the CS2000A for this use.
3. Use a DDC control system to control the ERV based on a room occupancy schedule.
4. Tie the operation of the ERV into the light switch. The lights in a room are usually on only when occupied.
5. Use a manual timer that the occupants turn to energize the ERV for a specific number of hours.
VENTILATION AIRFLOW
The ERV is equipped with a 3-speed motor to provide the capability of adjusting the ventilation rates to the requirements of the specific application by simply changing motor speeds.
TABLE 1
VENTILATION AIR (CFM)
deepShgiH
)kcalB(
MFC
The ERV units are wired from the factory on medium intake and low exhaust speeds. The ERV is equipped with independently controlled 3-speed motor to provide the capability of adjusting the ventilation rates to the requirements of the specific application and to be able to provide positive pressure in the structure. This is accomplished by setting the intake blower on a higher speed than the exhaust blower.
054573003
deepSmuideM
)eulB(
)deR(
deepSwoL
6. Use a programmable mechanical timer to energize the ERV and indoor blower during occupied periods of the day.
7. Use Bard Part No. 8403-056 CO2 controller for “on­demand” ventilation.
CONTROL WIRING
The QWSERV comes wired in the low voltage control circuit from the factory.
With the “X” Remote Thermostat Option, it is default wired into the “A” terminal, which drives the vent to operate only during occupied periods when using a Bard 8403-060 thermostat or Bard CS2000 controller. If you prefer for the QWSERV to operate anytime the blower is operational, you will need to install a jumper wire from “G” to “A”. If you prefer to use Bard 8403-056 CO2 controller to make the ventilation “on-demand”, there is a connection adjacent to the thermostat connections in the unit upper right-hand corner, and is marked to match CO2 controller connections. Furthermore, disconnect and tape off the wire as shown in Figure 4 and you will need to field set the CO2 sensor jumpers per Figure 5.
WARNING
Open disconnect to shut all power OFF before doing this. Failure to do so could result in injury or death due to electrical shock.
Moving the speed taps located in the control panel can change the blower speed of the intake and exhaust. See Figure 1.
FIGURE 1
BLOWER SPEED ADJUSTMENT
With the “D” Door Mounted Thermostat Option, the thermostat is already connected and programmed to operate the QWSERV only during occupied periods.
With the “H” Door Mounted Thermostat and CO controller, the unit is ready to go with “on-demand” ventilation as controlled by the CO2 controller.
Manual 2100-533A Page 4 of 12
2
Loading...
+ 8 hidden pages