Installers' Information Manual, Users' Information Manual, Wiring Diagram, Parts List and
Warranty are inside or attached and should be read before the Installation is started or before
service is attempted.
After factory final assembly, this furnace has been dielectrically tested. Operation tests have
been performed on the burners, fan control and blower motor.
- TO THE INSTALLER -
AFFIX THIS PACKET ADJACENT TO
THE FURNACE.
- TO THE OWNER -
RETAIN THIS PACKET AND ITS CONTENTS FOR
FURTHER REFERENCE.
in
TABLE OF CONTENTS:
INSTALLERS' MANUAL
INSTALLERS' INFORMATION MANUAL
GAMA VENTING TABLES ADDENDUM
SIDEWALL VENTING ADDENDUM
USER'S MANUAL
(PRINTED IN RED AND BLACK AND INSERTED IN THE CENTER OF THIS PACKET.)
F\ (0 hi
408320 A
f
f'
r’i r\
>, C ;
t f
/■ /
i
ï: 7/- -i-
RAGE
1-35
36-62
63-66
MANUAL PACKET 403293 A
INSTRUCTION ASSEMBLY 408310 B
COVER ASSEMBLY 406303 A
PARTS
FUNCTIONAL PARTS LIST
The format of this parts list allows you to get the part
number quickly. It allows you to easily identify the part and
the part number. Propane Conversion Kit and Filter Frames
are also listed in the parts list.
If you do not know the part number, find the part illustra
tion to the left and note the illustration number. Locate the
illustration number in the Parts List on the back foldout of
this packet Read across the list to locate the part number
for the appropriate size furnace.
EXAMPLE: You need an inducer motor relay for a
60,000 BTUH input 1/3 H.P. furnace:
1. Find the inducer motor relay in the
illustration and get the illustration
number (In this case 13).
2. Go to the table and read down to
illustration number 13.
3. Read across the row to find the part
number for the 60,000 BTUH input
1/3 H.P.furnace.
A.
Read part number 9043-316.
408360 A
INSTALLERS' MANUAL
To assure both sate and proper operation, please caretully toliow the instructions in this manual to
correctly install this new turnace.
ATTENTION, INSTALLER! After installing turnace, give the user:
—Users’ Information Manual —Parts List
—Installers’ Information Manual —Warranty Information
ATTENTION, USER! Your furnace installer should give you the above four important documents relating
to your furnace. Keep these as long as you keep your furnace. Pass these documents on to later furnace
purchasers or Users'. If any of the four documents is missing or damaged, contact your installer or furnace
manufacturer for replacement. For efficient service, please give your furnace model and serial number,
listed in Section 1 of your Users’ Information Manual or from your furnace rating plate. Throughout this
Installers' Information Manual, we frequently use the word "you" when referring to the person responsible
for application, installation and service of your furnace. Please remember to have only qualified service
technicians perform these services.
WARNING', Individuals who install this furnace, must have the training and experience necessary
to Install gas furnaces. They must also have training and experience necessary to Install related
comfort air conditioning appliances. Improper installation could create a hazard, resulting In damage,
injury or death.
While we have written these instructions as accurately and thoroughly as possible, they may not
cover every system variation or contingency. Also, questions of interpretation may arise. For more
information, solutions to particular problems or clarification, contact your focal distributor or the
manufacturer. See the furnace rating plate for who to contact.
Furnace installation must follow all applicable NATIONAL, STATE and LOCAL CODES.
UPFLOW
ELECTRONIC IGNITION INDUCED DRAFT FURNACE
WARNING: FOR YOUR SAFETY, WHAT TO DO IF YOU SMELL GAS:
— DO NOT TRY TO LIGHT ANY APPLIANCE;
— DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN THE BUILDING;
— IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR'S PHONE; FOLLOW GAS
SUPPLIER'S INSTRUCTIONS;
— IF YOU CANNOT REACH GAS SUPPLIER, CALL FIRE DEPARTMENT.
HORIZONTAL
DOWNFLOW
IMPORTANT SAFETY NOTE: After installing the furnace, show the user how to turn off gas and
electricity to furnace. Point out control and switch locations for turning off gas and electricity. Go over
Sections 4 and 6 of Users' Information Manual and Section 29 in this manual with user. Make sure user
understands the importance of following all safety precautions.
PREPARING TO INSTALL FURNACE..............................................................................................................................2
IMPORTANT SAFETY RULES..........................................................................................................................................3
DETERMINING BEST FURNACE LOCATION..................................................................................................................3
IDENTIFYING FURNACE DIMENSIONS. SPECIFICATIONS, AND POSITION..............................................................4
ALLOWING FOR CLEARANCES.......................................................................................................................................7
TOOLS NEEDED FOR INSTALLATION..........................................................................................................................17
INSTALLING GAS PIPING.............................................................................................................................................. 18
FOLLOWING FIELD WIRING DIAGRAMS......................................................................................................................19
SEQUENCE OF OPERATION.........................................................................................................................................20
CHECKING GAS INPUT..................................................................................................................................................27
DERATING FOR HIGH ALTITUDES...............................................................................................................................29
MEASURING DUCT WORK STATIC PRESSURE.........................................................................................................31
MEASURING AIR TEMPERATURE RISE.......................................................................................................................32
MAINTAINING FURNACE IN GOOD WORKING ORDER............................................................................................. 34
GETTING OTHER INFORMATION AND PUBLICATIONS.............................................................................................34
SICTION1 -
PREPARING TO INSTALL TURNACB.
A. Literature.
Review this manual. Users’ Information Manual and Parts
List. In particular, see User's Information Manual and
Parts List for location and identification of furnace com
ponents.
After installing furnace, give this Installers' Information
Manual, Users' Information Manual, Warranty and Parts
List to user. You may have questions as you install the
furnace. If you need help on any of the installation in
structions or other matters relating to the furnace, contact
the office where you bought the furnace. You may also
refer to the furnace rating plate for a contact name.
B, Installation Positions.
1. You may install furnace as-shipped in an upflow or
horizontal configuration in one of three positions
shown in Figure 1.
VENT
OUTLET
VENT
OUTLET
HORiZONTAL
LEFT SIDE DOWN
TVPE 1
UPftOW
TVPE 2
HORIZONTAL
RIGHT SIDE OOWN
TVPE 3
FIGURE 1
2. You may convert furnace quickly and easily from its
as-shipped configuration. After conversion, you can
install it as a downflow or horizontal furnace In one
of three positions shown in Figure 2.
VENT
OUTLET
VENT
OUTLET
G. Provide adequate combustion and ventilation air to space
where furnace is being installed. See Section 8 for more
information. Connect this furnace to an approved vent
system, venting combustion products outdoors. See Sec
tion 9 for more information.
H. Never test for gas leaks with an open flame. Use a com
mercial soap made specifically for leak detection to check
all connections. See Section 11 for more information.
VENT
OUTLET
TYPE 4
TYPE 5
TYPE 6
FIGURE 2
SECTION 2 — IMPORTANT SAFETY RULES*
WARNING: Read and exactly follow these rules. Fail
ure to do so could cause Improper furnace operation,
resulting In damage, injury or death.
A. Signal words.
To alert you to potential hazards, we use the signal words
"WARNING" and "CAUTION" throughout this
manual. "WARNING" alerts you to situations that could
cause serious injury or death. "CAUTION” alerts you to
situations that could cause minor or moderate injury or
property damage. To help you, we use the words "must"
and "should" in this manual. "Must" is mandatory, "Should"
is advisory.
6. Use only the type of gas approved for this furnace; refer
to furnace rating plate.
WARNING: Only use natural gas In furnaces de
signed for natural gas. Only use Propane (LP) gas
for furnaces designed for Propane (L.P) gas. Make
sure furnace will operate properly on gas type avail
able to user. Do not use this furnace with butane.
Using wrong gas could create a hazard, resulting In
damage, injury, or death.
C. DO NOT install this furnace outdoors or in a mobile home,
trailer or recreational vehicle. It is not A.G.A. designcertified for these installations. This furnace is suitable
for a home built on site or manufactured home completed
at final site.
D. Carefully choose furnace installation site. DO NOT di
rectly expose furnace to drafts, wind or other outdoor
conditions. See Section 8 for more information.
E. DO NOT install furnace in a corrosive or contaminated
atmosphere. Make sure all combustion and ventilation
air requirements are adhered to in addition to local codes
and ordinances. See Section 8 for more information.
F. DO NOT use this furnace during construction when ad
hesives, sealers, and/or new carpets are being installed.
If the furnace must be used during construction, provide
clean outdoor air for combustion and ventilation to ^rnace
space. See Section 8 for more information.
I. Always install duct system with furnace. Be sure duct
system has external static pressure within allowable fur
nace range. See Sections 16 and 25 for more information.
J. Completely seal supply and return air ducts to furnace
casing. Duct work must run to an area outside furnace
air space. Seal duct work wherever it runs through walls,
ceilings or floors. See Section 16 for more information.
SECTION 3 — MEETING CODES.
Before installing furnace, make sure you know all applicable
codes, National, state and local codes may take precedence
over any instructions in this manual. Be sure to consult:
— Authorities having jurisdiction over furnaces;
— Local code authorities for information on electrical
wiring, gas piping and vent pipe;
— Current National Fuel Gas Code ANSI Z223.1/NFPA
54:
— Current National Electrical Code ANSI/NFPA 70.
See Section 30 for information on getting copies of these
codes.
SECTION 4 — DETERMINING BEST
FURNACE LOCATION.
You may install this furnace as an upflow or downflow fur
nace in an alcove, attic, basement, closet, garage, or utility
room. Install furnace so all electrical components are pro
tected from water.
You may install it as a horizontal furnace in an alcove, garage,
attic, basement or crawl space.
Select furnace location to meet all requirements in this manual,
making sure to refer to;
— Section 2 for safety rules;
— Section 6 for minimum clearances;
— Section 7 for furnace suspension;
— Section 8 for combustion and ventilation air;
— Section 9 for venting:
— Section 11 for gas piping;
— Section 12 for electrical wiring;
— Section 16 and 25 for duct work;
— Section 17 for filters.
Consult local code authorities for additional location require
ments.
Locate the furnace close to the chimney/vent and as near the
center of the air distribution system as possible. Install furnace
as level as possible.
Provide ample space for servicing and cleaning. Location
must allow 30 inches minimum front clearance for service.
Always comply with minimum clearances shown on inside of
front door. Do not install furnace directly on carpeting, tile or
any combustible material other than wood flooring.
NOTE: A combustible floor base, available from manu
facturer, is required for downflow furnace installation on
wood flooring.
HAZARDOUS LOCATIONS.
When furnace is in a residential garage, it must be installed
so that burners and ignition source are located no less than
fS'inches above the floor. Also, furnace should be protected
from physical damage by vehicles.
When furnace is in public garages, airplane hangers, or other
buildings having hazardous atmospheres, install unit in ac
cordance with recommended good practice requirements of
the National Fire Protection Association, Inc. See Section 30.
SECTION 5 — IDENTIFYING FURNACE DI
MENSIONS, SPECIFICATIONS, AND POSITION.
2, Furnace as-shipped position may be converted to a
downflow furnace by following instructions in B. be
low. Once conversion is complete, furnace may be
installed as a downflow furnace. Furnace may also
then be installed as a horizontal on its right or left
side. See Figure 2.
WARNING: Do not install furnace on its back. Doing so
could cause a fire, resulting In damage, injury or death.
See Figure 3 for dimensional drawings and specification table.
B. Converting furnace from as-shipped configuration.
READ ALL INSTRUCTIONS THOROUGHLY BEFORE
STARTING CONVERSION.
NOTE: Start conversion with furnace on its back.
A. A unique feature of this furnace is that it may be installed
as an upflow furnace, horizontal furnace, or downflow
furnace (minor conversion required).
1. Furnace as-shipped is an upflow furnace. Furnace
may be installed in this position or may be installed
as a horizontal on its right or left side without any
conversion. See Figure 1.
WARNING: When servicing controls, all wires must
be labeled prior to disconnection. Mlswlring can cause
improper operation resulting In damage, Injury, or
death.
1. Remove front door. Study components described in
conversion. See Figure 4.
2. Remove two junction box mounting screws from top
plate. Remove four top plate mounting screws. Save
all screws. Remove top plate and front duct flange.
3. Disconnect pressure switch wires and inducer motor
connector wires.
4. Remove ten screws from the inducer pan; save
screws. DO NOT drop screws into heat exchanger
openings.
5. Lift inducer pan (with inducer motor and pressure
switch stilt in place) about 1/4 inch and tilt left side
up to clear casing flanges. Use care not to damage
inducer gasket.
NOTE: If possible, decide on direction of gas entry
now. Screws to inlet gas valve fitting are accessible.
See Section 11.
6. Rotate inducer pan 180 degrees, line up mounting
holes and place inducer pan in furnace. Use care
not to damage gasket. Replace ten screws in in
ducer pan. See Figure 5.
7. Pressure switch wires will no longer reach pressure
switch. Remove cable tie around excess length of
red/yellow piggyback, blue and purple pressure switch
wires.
8. Connect pressure switch wires as follows. Wires are
numbered on insulation near terminals.
a. #1 Purple wire to pressure switch, terminal 'C
(Common).
b. #2 Blue wire to pressure switch, terminal 'NC
(Normally Closed).
c. #7 and #8 Red/Yellow piggyback wire to pres
sure switch, terminal 'NO' (Normally Open).
d. Route all pressure switch wires over inducer
motor.
e. Reconnect inducer motor connector.
f. Replace wire tie in area that prevents wires from
touching hot surfaces.
9. Rgmove four screws that secure bottom plate to cas
ing sides. Remove bottom plate; save screws,
10. Install top plate, removed in step 2, where bottom
plate was. Secure with four screws. Inducer outlet is
now lined up with vent outlet in top plate.
11. Stand up furnace with top plate down. Line front duct
flange up with holes. Place bottom plate on top of
duct flange and secure both to casing with four
screws.
12. Install junction box on bottom plate using two #6B
screws removed in Step 2. Junction box cover and
screw of junction box must face front of furnace.
13. Gasket around flue collar must be in place. If gasket
is loose, glue It. If gasket is damaged, replace it.
14. Install a single wall vent pipe section (minimum length
30 inches) (Field-Supplied) to inducer outlet with three
equally spaced screws. This pipe serves as an in
ducer outlet extension to which an appropriate vent
can be attached. Due to minor variations in vent pipe,
available from different manufacturers in the field,
and to assure the tightest seal possible, inducer out
let extension is not supplied with furnace. Additional
vent pipe sections or Type B1 adapter may then be
added when installing the furnace.
WARNINGS If Inducer outlet extension Is shorter than
30 Inches and chimney or vent becomes blocked, com
bustion products may be drawn Into furnace. This could
cause nausea or asphyxiation, resulting In Injury or death.
15. Conversion from as-shipped configuration is now
complete.
SECTION 6 — ALLOWING FOR CLEARANCES.
WARNING: Do not Install furnace on Its back, doing so
could cause a fire, resulting In damage. Injury or death.
Establishing clearances from combustible material.
Locate clearance label on inside of front door. See Figure 6.
WARNINGS Furnace Installation must meet all minimum
clearances from combustible material specified In this
manual and all applicable codes. Failure to provide re
quired clearance between furnace and combustible mate
rials could cause a fire, resulting In damage, injury, or
death.
WARNINGS This furnace Is A.G.A. design certified for
direct Installation on wood flooring for upflow and hori
zontal positions.
• Do not install furnace on carpeting, tile or other
combustible material.
• Do not Install furnace In a closet In horizontal
position.
• Do not Install furnace on wood flooring without
special base In downflow position.
MINIMUM INCHES CLEARANCE
CLOSET.
UPFLOW POSITION
• FOR CASING WIDTHS 17 INCHES OR LARGER 0 CLEARANCE MAY
BE USED. 18 INCH FRONT CLEARANCE REQUIRED FOR ALCOVE. FOR
INSTALLATION ON COMBUSTIBLE FLOORING.
MINIMUM INCHES CLEARANCE
CLOSET.
DOWNFLOW POSITJON
• FOR CASING WIDTHS 17 INCHES OR LARGER 0 CLEARANCE MAY
BE USED. 18 INCH FRONT CLEARANCE REOUIRED FOR ALCOVE. FOR
INSTALLATION ON COMBUSTIBLE FLOORING ONLY WHEN INSTALLED ON
SPECIAL BASE PART N0. 4-024400.
MINIMUM INCHES CLEARANCE
• CLEARANCE SHOWN IS FOR AIR INLET AND AIR OUTLET ENDS.
VENT MUST MAINTAIN CLEARANCE LISTED ABOVE.
FOR INSTALLATION ON COMBUSTIBLE FLOORING.
FOR HORIZONTAL POSITION LINE CONTACT IS ONLY PERMISSIBLE
BETWEEN LINES FORMED BY INTERSECTIONS OF TOP AND TWO SIDES OF
FURNACE JACKET AND BUILDING JOISTS. STUDS OR FRAMING.
ALL POSITIONS RLOUIRE 30 INCHES FRONT CLEARANCE FOR SERVICE*
TOP SIDES BACK
11*0
1002
TOP SIDES BACK
11*06
10
HORiZONTAL POSmON
TOP SIDES* BACK
12*
1
2*
0 COMBUSTIBLE MATERIAL IN ALCOVE OR
FRONT VENT
0 COMBUSTIBLE MATERIAL IN ALCOVE OR
FRONT VENT
02
rO COMBUSTIBLE MATERIAL IN ALCOVE.
FRONT VENT
018
018
6 WHEN USING SINGLE WALL
6
1 WHEN USING B1
6 WHEN USING SINGLE WALL
1 WHEN USING B1
6 WHEN USING SINGLE WALL
1 WHEN USING B1
40ZB№
MINIMUM CLEARANCES
FROM COMBUSTIBLE MATERIALS
FIGURE 6
1. Upflow Installation.
Upflow position is approved for installation on
wood flooring. Typical upflow furnace installa
tions are an alcove, attic, basement, closet, ga
rage, or utility room. See Figure 6 or furnace
clearance plate for minimum clearances to com
bustible materials.
2. Horizontal Installation
a. Horizontal position is approved for installa
tion on wood flooring. Typical horizontal fur
nace installations are an alcove, garage, at
tic, or crawl space. See Figure 6 or furnace
clearance plate for minimum clearances to
combustible materials.
b. Attic Installation.
Line contact is permissible for furnaces
installed in horizontal positions. The in
tersection of furnace top and sides forms
a line. This line may be in contact with
combustible material. However, maintain
a 6" clearance to vent connection unless
Type B1 vent is used. See Figure 7.
Doing any of the above could cause a fire resulting in
damage, injury, or death.
TYPICAL ATTIC INSTALLATION
FIGURE 7
When using single wall vent pipe in horizon
tal installations, horizontal furnaces with
14.50" high casings must be raised 1" to
have 6” clearance to combustible material.
See Figure 7.
Furnace installation on combustible flooring is
permitted with combustible floor base available
from manufacturer. Read installation instructions
packaged with combustible floor base to correctly
install. See Figure 8.
c. Install a platform under furnace that extends
a minimum 30" in front of furnace. This pro
vides a work area and keeps insulating ma
terials away from combustion air openings.
Secure platform to ioists.
WARNINOs When a furnace Is installed
In an attic or other Insulated space, keep
all insulating materials at least 12" away
from furnace and all burner combustion
air openings. Failure to do so could cause
nausea, asphyxiation or fire, resulting In
damage. Injury, or death.
d. Crawl Space Installation.
Furnace can be hung from floor joists or in
stalled on suitable blocks or pad. Pad or
blocks should provide enough height to re
duce potential for water damage. See Sec
tion 7.
3. Downflow Installation.
You must convert furnace from as-shipped con
figuration for downflow furnace installation. See
Section 5.
DOWNFLOW FLOOR OPENING
FIGURE 8
See Figure 9 for installation diagram on com
bustible floor.
4. Service Clearance.
Allow minimum front clearance of 30 inches for service.
See Figure 6 or inside of front door for minimum service
clearance.
SECTION 7 — SUSPENDING FURNACE.
Some installations will require that furnace be suspended
from rafters or floor joists.
A common way to do this using threaded rods is shown in
Figure 10. Consider this means when people may walk un
derneath furnace. Figure 11 shows another common suspen
sion means using pipe strap. Other means that provide ad
equate support may be used.
When furnace is not suspended in a crawl space, elevate
furnace off ground to avoid water damage and allow for air
conditioning coil drain.
Downflow position is approved for installation on
non-combustible flooring. Typical downflow fur
nace installations are an alcove, attic, closet,
basement, garage, or utility room. See Figure 6
or furnace clearance plate for minimum clear
ances to combustible materials.
NOTE: Level furnace from front to back and from left to right
within 1M" per four feet.
FURNACE, PLENUM, AND BASE INSTALLED ON A
COMBUSTIBLE FLOOR
FIGURE 9
SICTION S PROVIDING FOR COMBUSTION
AND ViNTILATION AIR.
Before you begin installing furnace, pian to provide enough
combustion and ventiiation air following:
— Current National Fuel Gas Code ANSI Z223.1/NFPA
54, Section 5;
— Local Code authorities. Refer to Section 31 of this
manual for these codes.
Ventilation is the process of replacing air which is required
for furnace operation. The total amount of ventilation air pro
vided within structure must equal all requirements of gas ap
pliances in the building, plus any air quantities removed by
range hoods, exhaust fans, etc.
Another reason to supply fresh outdoor air for combustion
and ventilation is that it dilutes contaminants found in indoor
air. These contaminants include bleaches, adhesives, clean
ing solutions, detergents, solvents, cat litter, spray can pro
pellants and most refrigerants.
WARNINDi Furnace and any other fuel-burning appli
ances must have enough fresh air for propsr combus
tion and ventilation. Lack of adequate combustion and
ventilation air could cause nausea or asphyxiation, re
sulting in injury or death.
WARNINOi During construction, do not use air from
inside structure for combustion and ventilation. Vapors
from soma construction adhesives and materials can be
come corrosive in the presence of a flame. This could
cause failure of heat exchanger or vent system, result
ing in damage. Injury or death.
WARNINO: Combustion and vsntllatlon air that contains
chlorine, fluorine, bromine and Iodine could cause heat
exchanger or vent system failure, resulting In damage,
Injury or death,
WARNINO: When installing a furnace In an attic or other
insulated space, keep furnace free and clear of all lnsu>
lating materials. Make surs all Insulation Is at least 12"
away from burner combustion air openings and well away
from openings into furnace space that supply air for
combustion and ventilation. Failure to do this could causa
nausea, asphyxiation or fire, resulting In damage, injury
or death.
WARNINGS When Installing furnace in an alcove, attic,
basement, closet, garage, or utility room do not store
items in front of furnace or In front of closet or utility
door which would block combustion air openings to fur*
nace. Failure to do this could cause nausea, asphyxia
tion or fire, resulting In damags, Injury or death.
DO NOT install furnace where any combustion or ventilation
air openings will allow outside air to blow directly against
furnace.
WARNINGS Drafts blowing directly against furnace could
cause improper combustion which could cause heat ex
changer failure or fire, resulting In damage, Injury or
death.
Sufficient air MUST be provided to insure there wilt not be a
negative pressure in furnace room or space. In addition, there
MUST be a positive seal between furnace and return air duct
to avoid pulling air from burner area.
Provide adequate combustion and ventilation air by consider'
ing volume of furnace installation space. Use these instruc
tions and current National Fuel Gas Code ANSI Z223.1/NFPA
54 to determine whether furnace is in an unoonfined or con
fined space.
If ratio is less than 50, installation space is a con
fined space. If ratio is 50 or greater, installation space
is an unconfined space.
B. Installing furnace In confined space.
WARNING: You must provide permanent air open
ings to a conflned furnace installation space from
another area as described below. Failure to do ao
could result In Inadéquat# combustion and vsntllatlon
air. Thsae could cause nausea, asphyxiation or fire,
resulting In damage, injury or death.
1. Combustion and ventilation air openings.
a. All combustion and ventilation air from inside the
structure.
1. The furnace space must be provided with
two permanent openings to an additional
room(s) of sufficient volume so that the
combined volume of all spaces meet the cri
teria above for an unconfined space.
The total input of all gas appliances within
the combined space must be considered in
making this determination. See Figure 12.
2. a. Each opening must have minimum free
area of one square Inch per 1,000 Btuh
per hour of the total combined input rat
ing of all gas appliances within the con
fined furnace space, but not less than
100 square inches. One opening must
be within 12 inches of the top and an
other opening within 12 inches of the
bottom of the furnace space. See Fig
ure 12.
A. Determining If your space Is confined or unconflned.
Two factors determine whether a furnace installation
space is confined or unconfined:
— Volume of installation space;
— Total gas input of appliances to be installed in that
space.
To determine which your space is:
1. First calculate furnace installation space volume in
cubic feet.
2. Determine combined input rating (BTUH) of all gas
appliances in furnace installation space, including
furnace input. This is the total combined input rating.
3. Divide total combined input rating by 1,000. Then
divide this number into installation space volume.
Here's the formula:
Space Volume
Ratio
Total lnput/1,000
10
For example:
Total Input
Btuh(square Inches)
40,000-100,000100
120,000120
140,000
b. If building is of unusually tight construc
tion, provide a permanent opening di
rectly communicating with the outdoors.
Opening shall have a minimum free area
of one square inch per 4000 Btuh of
total input rating for all equipment in the
enclosure.
If return air is taken directly from hall
way or space next to furnace that com
municates with furnace spaces, all air
for combustion must come from out
doors.
b. All combustion and ventilation air from outdoors.
1. The furnace space must be provided with
two permanent air openings directly to the
outdoors, or by ducts to the outdoors or
spaces (attic or crawl spaces) that freely ac
cess the outdoors. These combustion and
ventilation openings will give fresh air free
access to furnace space for combustion and
ventilation. You must also provide air suffi
cient for all other gas appliances within fur
nace space.
Free Area Per Opening
140
Ducts must freely access outdoors or spaces
(attic or crawl spaces) which freely access
the outdoors. Well ventilated attics or crawl
spaces usually satisfy this requirement.
2. Locate one combustion and ventilation air
operîing within 12" of top of furnace space.
Locate another within 12" of bottom of fur
nace space.
3. When directly accessing the outdoors, each
opening must have a minimum free area of
one square inch per 4,000 Btuh of total
combined input rating of all gas appliances
within furnace space. See Figure 13A.
4. If combustion air ducts will run vertically,
ducts and each opening must have a mini
mum free area of one square inch per 4,000
Btuh total combined input rating. You must
allow for all gas appliances within the fur
nace space. See Figure 13B.
For example:
Required
Total Input
Btuh
40,00010.04
60,00015.05
80,000
100,000
120,00030.07
140,00035.0
Free Area per Opening
(square inches)
20.06
25.06
Suggested
Round Pipe
(inches dia.)
7
11
5. if combustion air ducts will run horizontally, ducts
and each opening must have a minimum free
area of one square inch per 2,000 Btuh total
combined input rating. You must allow for all
gas appliances within the furnace space. See
Figure 14.
CHIMNEY OR CAS vent
NOTE: EACH AIR DUCT
OPENINO SHALL HAVE A
FREE AREA OF NOT LESS
THAN ONE SQUARE INCH
PER 2.000 BTU PER HOUR
OF THE TOTAL INPUT RATInC
OF ALL EQUIPMENT IN THE
ENCLOSURE
to 25% free area. Assume metal louvers and grilles
have 60 to 75% free area. Refer to current National
Fuel Gas Code ANSI Z223.1/NFPA 54.
Example: Furnace is 100,000 Btuh input and is to be
installed in a confined space that contains no other
gas appliances. Rectangular combustion and ventilation air ducts will run horizontally from outdoors to
furnace space.
a. Calculate free area required.
Because combustion and ventilation air ducts run
horizontally, allow 2,000 Btuh. See 2b. above.
Furnace Input
Btuh
Free Area Required
2,Q0Q Btuh
per square inch
IF THE EQUIPMENT ROOM IS LOCATED AGAINST AND OUTSIDE WALL ANO THE AIR OPENINGS
COMMUNICATE OIRECTLY WITH THE OUTDOORS. EACH OPENING SHALL HAVE A FREE AfffiA
OF NOT lessthanone SQUARE INCH PER 4,000 BTU PER HOUR OF THE TOTAL INPUT
RATING OF ALL EQUIPMENT IN THE ENCLOSURE.
EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS.
FIGURE 14
For example:
Total input
Btuh
Free Area per Opening
(square Inches)
Round Pipe
(Inches dia.)
40,000206
60,00030
80,00040
100,000
508
120,000609
140,00070
6. Ducts which introduce combustion and ventila
tion air from outside structure into furnace space,
must have the same cross sectional area as the
free area of openings to which they connect.
The minimum dimension of rectangular air ducts
shall not be less than 3 inches.
2. Louvers, grilles, and screens.
Sometimes, louvers, grilles, or screens cover com
bustion and ventilation air openings. If so, you must
provide larger openings than those calculated above.
This is necessary because louvers, grilles and
screens block and reduce an opening's free area.
Louver, grille and screen manufacturers supply tech
nical data on their products, which usually includes
the Tree area." Sizing the openings with louvers,
grille or screen in place will provide minimum free
area to furnace space as calculated above. Do not
use screen smaller than 1/4" mesh. If you do not
know free area, assume that wood louvers have 20
7
8
10
100,000
50 square inches
2,000
Each opening must have a free area of 50 square
inches.
Calculate overall area of openings to give needed
b.
free area once you cover them to keep out rain
and other outside elements.
Example: If you will use wood louvers to cover
combustion and ventilation air openings and you
do not know free area of wood louvers, use 20%,
as suggested in ANSI Z223.1/NFPA 54.
100 x Free area
from a) above)
Louver free area
openings expressed
overall area of
openings with wood
louvers installed
as a percentage
100 x 50
250 square inches
20
Each of the two combustion and ventilation air
openings must have a total area of 250 square
inches. This is when wood louvers cover openings
for a 100,000 Btuh input furnace and combustion
and ventilation air ducts run horizontally.
c. Calculate minimum rectangular duct size needed.
If you choose a rectangular duct with the mini
mum allowed dimension of 3", the other duct
dimension must be at least 16-2/3". This is cal
culated by dividing the 50 square inches of free
area from a) by 3", with equals 16-2/3".
WARNINGi You must fix combustion and ventila
tion air louvers and grilles In open position or Inter
lock them with furnace operation. Furnace operation
12
with louvvrs or grilles closed could cause Inadequate
combustion or ventilation air, resulting In Injury or
death.
C. Installing furnace in unconfIned space.
Refer to current National Fuel Gas Code ANSI 2223.1/
NFPA 54 for more information. This code does not re
quire that you make special provisions for combustion
and ventilation when furnace is in an unconfined space.
However, it is always prudent to arrange for combustion
and ventilation air as if installation space is confined
space.
In the past, infiltration through loose construction pro
vided enough air for combustion and ventilation when
furnace was in an unconfined space. Current construction
methods may now prevent infiltration of air into unconfined
space. These current methods include increased insula
tion, vapor barriers, tight fitting doors and windows, and
weather-stripping.
D. Allowing for exhauet fan operation.
1, When furnace is in a ventilated attic, crawl space,
residertce garage, or outside the heated space, ex
haust fan drafts can adversely affect its operation.
These drafts can come from kitchens, bathrooms,
clothes dryers or anywhere within the heated space.
WARNING: Exhaust fans that blow against fur
nace could cause heat exchanger failure or fire,
resulting In damage, Injury, or death.
2. When furnace is in a repair garage or inside the
heated space, exhaust fans can adversely affect its
operation. Exhaust fans in kitchens, bathrooms,
clothes dryers or anywhere within heated space in
crease combustion and ventilation air requirements.
This is because exhaust fans reduce the amount of
combustion and ventilation air available to the fur
nace. A fireplace also reduces amount of combus
tion and ventilation air. You must allow for these
reductions.
WARNING: You must allow for reduction of air
available for combustion and ventilation by ex
haust fans and fireplaces. Failure to do so could
result In Inadequate combustion and ventilation
sir. This could cause nausea, asphyxiation, or
firs, resulting In damage, Injury, or death.
3. Exhaust fan air may contain compounds of chlorine,
fluorine, bromine, and iodine. If used for combus
tion, this contaminated air will adversely affect fur
nace operation.
WARNING: If used for combustion and ventila
tion, contaminated exhaust fan air could cause
heat exchanger or vent system failure resulting
In damage, Injury, or death.
SICTION 9 —
PROVIDING P
Vent furnace using these instructions and Venting Adden
dum. Also, meet requirements of local utilities and other local
code authorities. You must connect furnace to a vent or fac
tory-built chimney or a suitably sized, constructed and lined
masonry chimney. Vent or factory-built chimney must meet a
recognized standard. Chimney lining method and material
must comply with local requirements. Use corrosion-resistant
material meeting nationally recognized standards for vent
construction.
INTING.
WARNING: Inadequate vent or chimney could allow
combustion products to collect In structure, resulting In
Injury or death.
WARNING: Vent this furnace separately from any appli
ance designed to burn solid fuel, particularly wood-burn-
Ing or coal burning appliances. Improper venting could
allow combustion products to collect In structure, result
ing In injury or death.
A. Venting category.
The furnaces covered by this manual are design-certified
as CATEGORY 1 for venting, CATEGORY 1 furnaces
have non-positive vent static pressure and rely on the
beat content of combustion products to vent. You may
common vent CATEGORY 1 furnaces.
The furnaces covered in this manual are also designcertified as CATEGORY 3 for venting, only when they
are installed with manufacturer specified vent system
components and installation practices.
Category 3 gas appliances rely on the heat content of
combustion products and mechanical or other means to
vent. You may not common vent CATEGORY 3 gas ap
pliances.
B. Types of vent systems.
These definitions will help you understand the terms we
use.
1. "Vent" and "chimney" refer to open passageways.
These passageways convey vent gases from vent
connectors to the outside. Gases begin their final
ascent at the vent or chimney. Vents and chimneys
usually run vertically or nearly vertical. When they
serve only one gas appliance, they are called "dedi
cated" vents or chimneys. Whan they serve multiple
gas appliances, they are called "common" vents or
chimneys.
2. A "vent connector" connects a gas appliance to a
vent or chimney. Vent connectors usually run directly
from the furnace draft inducer collar to vent or chim
ney. Vent connectors may have vertical and horizon
tal runs.
3. A "venting system" is a continuous open passage
way from the draft inducer collar to the outside.
Venting systems usually have vent connector(s) and
a vent or chimney. Venting systems commonly serve
a single furnace or a single furnace and a water
heater. Other multiple-appliance venting systems are
13
less common.
C. Design considerations.
1. General considerations.
Avoid oversizing furnace for your application. Se
lect a furnace model with a rated heating output
close to the calculated heating toad. This extends
the firing period, decreasing the potential for con
densate formation in the vent.
a. Too small a vent cannot carry all combustion
products outdoors. Too large a vent will not vent
combustion products rapidly enough to avoid
potential for condensation. Refer to Venting Ad
dendum for correct size vent.
b. Vent height must be a minimum of five feet.
Minimize vent connector horizontal runs to the
extent possible for best performance.
c. The designer must consider the building's ori
entation, answering these questions. Will the
vent terminate outside the building where its op
eration could be adversely affected by winds?
Could any adjacent buildings adversely affect
vent operation? Allowing for these factors can
reduce the possibility of downdraft conditions.
b. Use Type B1 vent connectors in or through at
tics, crawl spaces, or other cold areas. Install
thimbles that meet local codes when vent con
nectors pass through walls or partitions of com
bustible material.
c. Keep vent connectors as short as possible by
locating furnace as dose as practical to vent or
chimney. Avoid unnecessary turns or bends
which create resistance to
Adding an elbow adds resistance. For example,
adding a 6" 90-degree elbow would be the
equivalent of adding 20 feet of horizontal 6" pipe.
45-degree elbows have lower resistance than 90degree elbows, and can work for most vent runs.
d. You may increase vent connector diameter to
overcome installation limitations and obtain con
nector capacity equal to furnace input. Make this
increase as close as possible to draft inducer
collar, allowing for necessary adapters and fit
tings.
e. If you join two or more vent connectors before
they enter the vertical vent or chimney, use cau
tion. See Venting Addendum.
flow of vent gases.
d. If your local experience indicates possible con
densation problems, provide for draining and
disposal of venting system condensate.
2. Vent sizing.
a. Sometimes the horizontal distance from the fur
nace to the vent or chimney is already given;
this is known as the horizontal vent connector
run. The vent or chimney height is also usually
given as is the Btuh input of the gas appliances
served by the vent.
Check these parameters to be sure the venting
system will work. Use approved engineering
practices, Venting Addendum, these instructions,
and Part 7 of current National Fuel Gas Code
ANSI Z223.1/NFPA 54. Use vent capacity tables
in Venting Addendum to check existing or new
vent sizes for CATEGORY 1 furnaces.
b. See Venting Addendum for single appliance
venting and multiple appliance (common) vent
ing. For multi-story installations, refer to current
National Fuel Gas Code ANSI Z223.1/NFPA 54.
c. Minimum vent connector diameter from furnace
to vent or chimney is same as draft inducer col
lar.
3. Vent connector.
a. Vent connectors must be made of noncombus
tible, corrosion resistant material capable of
withstanding vent gas temperatures. They must
be thick enough to withstand physical damage
and be accessible for inspection, cleaning and
replacement.
f. Do not connect this furnace to any portion of a
vent system which operates under positive pres
sure. Positive pressure would result with CAT
EGORY 3 and 4 appliances connected to the
vent.
g. Do not connect vent connector to a chimney flue
serving a fireplace unless you permanently seal
fireplace flue opening.
4. Vertical vent or chimney.
a. Vents and chimneys usually extend vertically with
offsets not exceeding 45-degrees. Consider vent
pipe runs more than 45'degrees as horizontal
runs. Include their length in the total horizontal
run.
b. Designer and installer must provide an appropri
ately sized common vent for all appliances con
nected to it. See Venting Addendum.
c. Connect this CATEGORY 1 furnace only to vent
systems with other CATEGORY 1 appliances.
WARNING: Do not connect this Category 1
furnace to a vent system used by Category 3
and 4 appliances. Do not connect It to vents
with mechanical draft systems operating at
positive pressure. Improper venting could al
low combustion products to collect in struc
ture during use, resulting In damage, Injury
or death.
5. Chimney.
Furnace is suitable for venting into a properly sized
and lined masonry chimney. Consult National Fuel
Gas Code ANSI Z223.1/NFPA 54 for construction
details. If chimney is oversized, liner is inadequate
14
OT evidence of condensate exists, consider using
chimney as a pathway for suitably sized Type B1
vent liner. See Figure 15.
FIGURE 15
WARNIN9I Support Type B1 vent liner in ma
sonry chimney. Maintain at least a 1" clearance
on all sides to reduce possibility of condensate
in vent. Condensate may cause vent to deterio
rate allowing combustion products to collect In
structure, which could result In injury or death.
See Figure 16.
NOTE; For more information on proper chimney in
spection and relining procedures, Gas Research In
stitute (GRI) has a topical report entitled "Masonry
Chimney Inspection and Reiintng". Obtain copies
through American Gas Association (A.G.A.) at
1-800-841-8400.
6. Vent termination.
a. Terminate ail verticai vents with a iisted vent
cap or roof assembly unless local codes require
otherwise. See vent cap or roof assembly
manufacturer's instructions. Locate vent termi
nation (vent cap or roof assembly) in an area
without positive wind pressures or eddy currents.
Eddy currents occur when air swirls over roof
peaks. They can cause down-drafts and ad
versely affect vent operation. See Figure 17.
FIGURE 16
WAKNINOi Vent liner muet not block opening
where other epplicncee' vent connector* enter
chimney. Blocked opening* could cau»* com
bustion products to collact In atructur*, r*sutt-
Ing In damag*, Injury or dssth.
WARNINOt Do not uaa unllnad masonry chlm-
naya. Thasa Incraasa risk of condansats forma
tion, which may causa chlmnay to datariorata,
allowing combustion products to collact In
structura, raaulting In damaga. Injury or death.
Some vent terminations or caps protect against
eddy currents and down-drafts, Consult their
manufacturer's instructions. Vent terminations or
caps should usually be at least the same size as
the vent. They may be larger if the installation
warrants.
b. Vent systems must end at least five feet above
the highest gas appliance connection. Vent pipe
must extend at least three feet above the point
where it passes through the roof. Vent termina
tion must be at least two feet higher than any
portion of building within ten feet horizontal and
vent termination must be at least two feet higher
than roof peaks within ten feet horizontal. See
Figures 18 and 19. Some vent cap manufactur
ers offer vent caps that allow reduced clearances.
Consult their Instructions.
15
D. Installation.
1. Vent connectors.
Attach vent connector at draft inducer collar. Make
sure flue gasket is in place providing a seat. Use a
minimum of three equally spaced screws around
connection. Connect all other vent pipes using three
equally spaced screws at each joint. Exception is
only when you use Type B1 vent pipe with self
locking connections or high temperature plastic pipe.
WARNINGS Unsecured vent pips connections
may loosen. This can allow combustion products
to collact In structura, resulting In Injury or death.
Install vent connectors without any dips or sags.
Slope them upward from furnace at least f/4” per
foot. To prevent sagging, at each joint support vent
connectors and horizontal portions using hinges,
straps or equivalent. Seal all connections where vent
connectors enter chimney. See Figure 15.
TERMINATION MORE THAN 10 FEET FROM RIDGE
FIGURE 18
TERMINATION 10 FEET OR LESS FROM RIDGE
FIGURE 19
WAftNINGt Failure to properly terminate
vent chimney systems could allow combus
tion products to collect In structure, result
ing In Injury or death.
c. Terminate venting system at least three feet
above any forced-air building inlet within ten feet.
Consider doors, windows and gravity air building
inlets. Locate vent termination at least four feet
below, four horizontal feet from or one foot above
any of these openings.
To avoid blockage, attach vent connector to a ma
sonry chimney above the extreme bottom. For in
spection ease, use thimble or slip joint to make vent
connector removal easy. Firmly attach connector.
Insert all vent connectors into, but not beyond, inside
chimney wall.
2. Vertical vent or chimney systems.
Install vent materials following their listing terms,
manufacturer's instructions, these instructions and
local codes.
A gas vent passing through a roof must extend
through roof flashing, jack or thimble. It must termi
nate above roof surface.
E. Existing vent considerations.
Masonry chimneys previously used for venting solid fuel
or oil burning equipment should be lined with suitable
metal liner. Also provide an accessible clean out per cur
rent National Fuel Gas Code ANSI Z223.1/NFPA 54.1.
1. Inspection of vents (chimneys).
a. Make sure existing vent or chimney is proper
size and construction for appliances that will use
it. The best way to do this is to size as if it were
a new installation. Compare the existing vent to
your calculations and make necessary correc
tions.
b. Examine vent or chimney cleanouts to make sure
they remain tightly closed when not in use. Make
sure vent or chimney passageway is clear and
free of obstructions. Look for evidence of con
densate or deterioration in vent or chimney. Ei
ther of these means an inadequate vent.
c. If you find an inadequate vent or chimney, do
not leave it as is. Repair or replace it. A new
vent must meet these instructions and current
16
National Fuel Gas Code ANSI Z223.1/NFPA 54.
Rabuild a chimney to meet national standards.
MCriON 10 —
TOOLS NIIDID rOR INSTALLATION.
WARNINOi An Inadequate vent or chimney
could allow combuatlon products to collect
In structure, resulting In Injury or death.
d. Sometimes you wiii repiace a common vented
appliance. Make sure common vent size is cor
rect for aJl appliances connected to it. If you re
move a furnace from a common vent without
replacing it, the vent will likely be too large for
remaining appliances. See Venting Addendum.
e. The following steps shall be followed with each
appliance remaining connected to common vent
ing system placed in operation, while other ap
pliances remaining connected to common venting
system are not in operation.
1. Seal any unused openings in common vent
ing system.
2. Visually inspect venting system for proper
size and horizontal pitch and determine there
is no blockage or restriction, leakage, corro
sion and other deficiencies which could
cause an unsafe condition.
3. Insofar as is practical, close all building doors
and windows and all doors between space
in which appliances remaining connected to
common venting systems are located and
other spaces of building. Turn on clothes
dryers and any appliances not connected to
common venting system. Turn on any ex
haust fans, such as range hoods and bath
room exhausts so they will operate at maxi
mum speed. Do not operate a summer ex
haust fan. Close fireplace dampers.
4. Follow Operating Instructions. Place appli
ance being inspected in operation. Adjust
thermostat so appliance will operate con
tinuously.
5. After it has been determined that each ap
pliance remaining connected to common
venting system properly vents when tested
as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any
other gas-burning appliance to their previous
conditions of use.
6. If improper venting is observed during any
of the above tests, common venting systems
must be corrected.
NOTE: Follow current National Fuel Gas
Code ANSI 2223.1/NFPA 54 to correct im
proper common vent operation. Any common
vent resizing must approach minimum size
determined by using Venting Addendum.
ITEM
TOOL DESCRIPTION
HAND TOOLS
A.
1.Carton KnHe
1/4" nut driver
2.
5/16" nut driver
3.
4.3/8” nut driver
1/4" X 8" straight-
5.
blade screwdriver
#2 X 8" Phillips
6.
screwdriver
7/16" open end or
7.
tubing wrench
2-8" to 14" pipe
8.
wrenches
4" adjustable
9.
wrench
10.8” Channel-lock
ptiei^
3/16" Allen
11.
wrench
12.
9/64" Allen
wrench
B.
SUPPLIES
13.Pipe thread sealant
suitable for use with
propane (LP) gas
14.
Bottle of soap
solutbn
15.
2-1/8” pipe, manual
shutoff valves
C.
TEST INSTRUMENTS
16.
Volt meter with 50
and 150 volt ranges
17.Clamp around
ammeter with 10 amp
and higher ranges
USED FOR
Furnace removal from
carton
Control box cover
Casing and blower
Blower and motor
mounts
Wire terminals and manifold
pressure adjustment
Components in control box
Main burner orifices
Gas pipe installatbn
Blower wheel set screw
tightening
Strain reliefs
Inlet and outlet pressure tap
plug removal from gas control
Honeywell gas inlet fitting
Gas pipe and controls
Gas leak checking
Gas control inlet and
pressure checking
Electrbal chedt of controls
and power supply
Amp draw of motors and
control check
17
18. 10-turn coil of wire
to fit on ammeter
19. "U" Tube Water
Manometer with O.V
resolution 0“to 15"
W.C. range
20. Slope gauge with
0.01” pressure
measurement taps
and tubing, Oto 1"
W.C. range
Room thermostat heat
anticipator setting
Gas pressure
measurement
Duct work static pressure
furnace. A convenient way to do this when you have
reduced bottom clearance, is to make drip leg by
using a 1/2" to Г NPT Tee, Then install a 1-1/2"
long.l” NPT nipple in Tee with a Г NPT pipe cap to
complete drip leg.
3. When using black iron gas pipe, install an A.G.A.
listed ground joint union between drip leg (sediment
trap) and furnace gas control. Locate ground joint
union to allow easy servicing of burner assembly
and gas control.
4. Install gas pipe to inlet side of furnace gas control.
21. 2 thermometers
with 1 -degree
Fahrenheit
resolution, 50
degrees F to 175
degrees F range
22. Stop watch
23. Torque wrench
(100 inch-pounds)
Temperature rise measured
through lurnace
Gas input meter timing
Proper screw installation
SICTION 11 — INSTALLING GAS PIPING.
Equipment needed: Save time by getting these tools before
you start: Item number(s) 8,12.13 and 14 listed in Section
10.
A. Preparation.
Gas piping must meet requirements of current National
Fuel Gas Code ANSI Z223.1/NFPA 54 and local codes.
Size of pipe running to furnace depends on:
• Length of pipe;
• Number of fittings;
• Specific gravity of gas;
• Input requirements fBtuh) of all gas-fired appli
ances attached to same main supply line.
Refer to current National Fuel Gas Code ANSI Z223.1/
NFPA 54 for correct gas pipe sizing information.
Plan furnace gas supply piping so it will not interfere with
removal of burner assembly, front door or blower door
for servicing.
Always use a pipe thread sealant which is resistant to
propane (LP) gas solvent action. Sparingly apply sealant
to all joints on male threads only, starting two threads
back from end.
B. Installation.
1. Install A.G.A. listed manual shut-off valve in gas
supply line immediately upstream of furnace. Install
1/8" NPT plugged tapping accessible for test gauge
connection. Omit separate, plugged tapping if local
area accepts plugged tapping in gas control inlet.
2. After in-line manual shut-off valve, install a drip leg
(sediment trap) at gas supply line inlet connection to
WARNINGS Do not thread gas pipe too far. Do
ing so may cause gas control to split or crack
which could cause a gas leak or distortion or
malfunction of gas control. Thasa could causa a
firs or explosion resulting in damage, Injury or
death.
5. Isolate gas control from gas supply line pressure
during leak check. Gas supply line test pressure de
termines how you isolate gas control.
WARNINGS At gas supply line, test pressure
equal to or less than 14 Inches W.C. (1/2 PSI).
Isolate gas control from gas supply line by turning
furnace gas control knob clockwise > to off posi
tion. Unexpected surges could damage gas con
trol causing gas to leak, resulting In firs or ex
plosion.
WARNINGS When test pressure la above 14
Inches W.C. (1/2 PSI), completely disconnect gas
control from gas supply line. Failure to Isolate
gas control from test pressure could damage H,
causing gas to leak, resulting in firs or explosion.
6. Use a commercial soap solution made to detect leaks
and check all gas piping connections. Bubbles indi
cate gas leakage. Seat all leaks before proceeding.
WARNINGi Never use an open flams to check
for gas leaks. If a leak doss exist, a firs or explo
sion could occur, resulting In damage. Injury or
death.
Furnace Gas Entry Piping.
1. See below for gas entry holes and knockouts.
a. A 1-1/4* X 2-3/4" knockout in top plate.
b. A 1-1/2" diameter hole and a 1-1/4" x 1-15/16"
knockout in right side of casing.
c. Two 1-5/8" diameter knockouts in left side of
casing.
2. Changing Gas Control Inlet.
You may want to change direction of gas inlet elbow
on gas control. Gas control is shipped for right side
gas entry. If you need top entry, remove the fitting. If
you need left side gas entry, rotate the fitting 180
degrees.
18
a. Use 9/64" Hex Allen wrench to remove tour
screws. Check that O-ring is in bottom of gas
inlet elbow. Rotate elbow to desired position.
WARNINGi Provide furnace with ita own separate elec
trical circuit, means of circuit protection and electrical
disconnect switch. Follow current National Electrical Code
ANSI/NFPA 70 and state and local codes. Failure to pro
vide these shut-off means could cause electrical shock
or fire, resulting In damage, Injury or death.
install proper electrical grounding by attaching grounding
source to green wire conductor in furnace junction box. Fol
low current National Electrical Code ANSI/NFPA 70 and local
codes.
WARNINGS Furnace must have proper electrical ground.
Failure to provide a proper electrical ground could cause
electrical shock or fire, resulting In damage. Injury or
death.
fICTION 13 —
FOLLOWING FIELD WIRING DIAGRAM
HEATING COOUNG
THERMOSTAT MODEL
b. Alternately tighten tour screws to 45 inch pounds
to form a gas tight seal.
c. Use a commercial soap solution made to detect
leaks and check all gas piping connections.
Bubbles indicate gas leakage. Seal all leaks be
fore proceeding.
WARNINOi Never use an open flame to
check for gas leaks. If a leak does exist, a
fire or explosion could occur, resulting In
damage, Injury or death.
3. Allowing tor Electronic Air Cleaners.
Some large electronic air cleaners will interfere with
incoming gas line. Install air cleaner on opposite fur
nace side from gas entry or route gas pipe over top
of air cleaner through one of alternate knockouts.
SICTION 12 —
INSTALLING ILICTRICAL WIRING.
Equipment Needed: Save time by getting these tools before
you start: Item number(s) 2 listed in Section 10.
Select a location for room thermostat that is away from sup
ply and return air registers, on draft-free interior wall, and not
near lights, television, direct sunlight, or other heat sources.
Install thermostat following field wiring diagram in Section
13. Use electrical wiring that meets current National Electrical
Code ANSI/NFPA 70 and local codes. Use Type T (63 de
grees C rise) wire or equivalent. See Section 30 for code
information.
TO 115V 1 PH 60 H2
POWR SUPPLY PER
LOCAL CODES
FIELD WIRING DIAGRAM
FIGURE 21
NOTE: When replacing original wire, use same type, color,
or equivalent wire. Remember to renumber wire ends.