Bard 403293A User Manual

IMPORTANT
Installers' Information Manual, Users' Information Manual, Wiring Diagram, Parts List and Warranty are inside or attached and should be read before the Installation is started or before service is attempted.
After factory final assembly, this furnace has been dielectrically tested. Operation tests have
been performed on the burners, fan control and blower motor.
- TO THE INSTALLER -
THE FURNACE.
- TO THE OWNER -
RETAIN THIS PACKET AND ITS CONTENTS FOR
FURTHER REFERENCE.
in
TABLE OF CONTENTS:
INSTALLERS' MANUAL
INSTALLERS' INFORMATION MANUAL GAMA VENTING TABLES ADDENDUM SIDEWALL VENTING ADDENDUM
USER'S MANUAL
(PRINTED IN RED AND BLACK AND INSERTED IN THE CENTER OF THIS PACKET.)
F\ (0 hi
408320 A
f
f'
r’i r\
>, C ;
t f
/■ /
i
ï: 7/- -i-
RAGE
1-35 36-62 63-66
MANUAL PACKET 403293 A
INSTRUCTION ASSEMBLY 408310 B
COVER ASSEMBLY 406303 A
PARTS
FUNCTIONAL PARTS LIST
The format of this parts list allows you to get the part number quickly. It allows you to easily identify the part and the part number. Propane Conversion Kit and Filter Frames are also listed in the parts list.
If you do not know the part number, find the part illustra
tion to the left and note the illustration number. Locate the
illustration number in the Parts List on the back foldout of this packet Read across the list to locate the part number for the appropriate size furnace.
EXAMPLE: You need an inducer motor relay for a
60,000 BTUH input 1/3 H.P. furnace:
1. Find the inducer motor relay in the illustration and get the illustration number (In this case 13).
2. Go to the table and read down to illustration number 13.
3. Read across the row to find the part number for the 60,000 BTUH input
1/3 H.P.furnace.
A.
Read part number 9043-316.
408360 A
INSTALLERS' MANUAL
To assure both sate and proper operation, please caretully toliow the instructions in this manual to correctly install this new turnace.
ATTENTION, INSTALLER! After installing turnace, give the user:
—Users’ Information Manual —Parts List —Installers’ Information Manual —Warranty Information
ATTENTION, USER! Your furnace installer should give you the above four important documents relating
to your furnace. Keep these as long as you keep your furnace. Pass these documents on to later furnace purchasers or Users'. If any of the four documents is missing or damaged, contact your installer or furnace manufacturer for replacement. For efficient service, please give your furnace model and serial number, listed in Section 1 of your Users’ Information Manual or from your furnace rating plate. Throughout this Installers' Information Manual, we frequently use the word "you" when referring to the person responsible for application, installation and service of your furnace. Please remember to have only qualified service technicians perform these services.
WARNING', Individuals who install this furnace, must have the training and experience necessary to Install gas furnaces. They must also have training and experience necessary to Install related comfort air conditioning appliances. Improper installation could create a hazard, resulting In damage, injury or death.
While we have written these instructions as accurately and thoroughly as possible, they may not cover every system variation or contingency. Also, questions of interpretation may arise. For more information, solutions to particular problems or clarification, contact your focal distributor or the manufacturer. See the furnace rating plate for who to contact.
Furnace installation must follow all applicable NATIONAL, STATE and LOCAL CODES.
UPFLOW
ELECTRONIC IGNITION INDUCED DRAFT FURNACE
WARNING: FOR YOUR SAFETY, WHAT TO DO IF YOU SMELL GAS: — DO NOT TRY TO LIGHT ANY APPLIANCE; — DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN THE BUILDING; — IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR'S PHONE; FOLLOW GAS
SUPPLIER'S INSTRUCTIONS;
— IF YOU CANNOT REACH GAS SUPPLIER, CALL FIRE DEPARTMENT.
HORIZONTAL
DOWNFLOW
IMPORTANT SAFETY NOTE: After installing the furnace, show the user how to turn off gas and
electricity to furnace. Point out control and switch locations for turning off gas and electricity. Go over Sections 4 and 6 of Users' Information Manual and Section 29 in this manual with user. Make sure user understands the importance of following all safety precautions.
920101
404200 A
SECTION
_________________________
TABiE Of CONTENTS
____________________________________
PAPE
SECTION 1 SECTION SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION
SECTION 8 SECTION 9 SECTION
10 SECTION 11 SECTION 12 SECTION SECTION
13
14 SECTION 15 SECTION SECTION
SECTION
16
17
18 SECTION 19
SECTION 20
SECTION 21
SECTION 22 SECTION
23
SECTION 24 SECTION 25 SECTION 26 SECTION 27 SECTION
28
SECTION 29 SECTION 30
PREPARING TO INSTALL FURNACE..............................................................................................................................2
IMPORTANT SAFETY RULES..........................................................................................................................................3
2
MEETING CODES.............................................................................................................................................................3
DETERMINING BEST FURNACE LOCATION..................................................................................................................3
IDENTIFYING FURNACE DIMENSIONS. SPECIFICATIONS, AND POSITION..............................................................4
ALLOWING FOR CLEARANCES.......................................................................................................................................7
SUSPENDING FURNACE.................................................................................................................................................8
7
PROVIDING FOR COMBUSTION AND VENTILATION AIR........................................................................................... 9
PROVIDING FOR PROPER VENTING
......
...........................................................................
-........................................13
TOOLS NEEDED FOR INSTALLATION..........................................................................................................................17
INSTALLING GAS PIPING.............................................................................................................................................. 18
INSTALLING ELECTRICAL WIRING.............................................................................................................................. 19
FOLLOWING FIELD WIRING DIAGRAMS......................................................................................................................19
ADJUSTING ROOM THERMOSTAT HEAT ANTICIPATOR...........................................................................................19
SEQUENCE OF OPERATION.........................................................................................................................................20
INSTALLING DUCTWORK..............................................................................................................................................20
SELECTING AND INSTALLING FILTER FRAMES.........................................................................................................23
CHECKING BEFORE STARTING FURNACE.................................................................................................................25
ADJUSTING PILOT..........................................................................................................................................................25
ADJUSTING MANIFOLD PRESSURE.............................................................................................................................26
CHECKING GAS INPUT..................................................................................................................................................27
ORIFICE SIZE..................................................................................................................................................................29
DERATING FOR HIGH ALTITUDES...............................................................................................................................29
ADJUSTING BLOWER SPEED.......................................................................................................................................30
MEASURING DUCT WORK STATIC PRESSURE.........................................................................................................31
MEASURING AIR TEMPERATURE RISE.......................................................................................................................32
CHECKING CONTROLS.................................................................................................................................................33
BLOWER TIMINGS..........................................................................................................................................................33
MAINTAINING FURNACE IN GOOD WORKING ORDER............................................................................................. 34
GETTING OTHER INFORMATION AND PUBLICATIONS.............................................................................................34
SICTION 1 -
PREPARING TO INSTALL TURNACB.
A. Literature.
Review this manual. Users’ Information Manual and Parts List. In particular, see User's Information Manual and Parts List for location and identification of furnace com ponents.
After installing furnace, give this Installers' Information Manual, Users' Information Manual, Warranty and Parts List to user. You may have questions as you install the furnace. If you need help on any of the installation in structions or other matters relating to the furnace, contact the office where you bought the furnace. You may also refer to the furnace rating plate for a contact name.
B, Installation Positions.
1. You may install furnace as-shipped in an upflow or horizontal configuration in one of three positions shown in Figure 1.
VENT
OUTLET
VENT
OUTLET
HORiZONTAL
LEFT SIDE DOWN
TVPE 1
UPftOW
TVPE 2
HORIZONTAL
RIGHT SIDE OOWN
TVPE 3
FIGURE 1
2. You may convert furnace quickly and easily from its as-shipped configuration. After conversion, you can install it as a downflow or horizontal furnace In one of three positions shown in Figure 2.
VENT OUTLET
VENT
OUTLET
G. Provide adequate combustion and ventilation air to space
where furnace is being installed. See Section 8 for more information. Connect this furnace to an approved vent system, venting combustion products outdoors. See Sec
tion 9 for more information.
H. Never test for gas leaks with an open flame. Use a com
mercial soap made specifically for leak detection to check
all connections. See Section 11 for more information.
VENT OUTLET
TYPE 4
TYPE 5
TYPE 6
FIGURE 2
SECTION 2 — IMPORTANT SAFETY RULES* WARNING: Read and exactly follow these rules. Fail
ure to do so could cause Improper furnace operation, resulting In damage, injury or death.
A. Signal words.
To alert you to potential hazards, we use the signal words
"WARNING" and "CAUTION" throughout this
manual. "WARNING" alerts you to situations that could cause serious injury or death. "CAUTION” alerts you to situations that could cause minor or moderate injury or property damage. To help you, we use the words "must" and "should" in this manual. "Must" is mandatory, "Should" is advisory.
6. Use only the type of gas approved for this furnace; refer to furnace rating plate.
WARNING: Only use natural gas In furnaces de
signed for natural gas. Only use Propane (LP) gas for furnaces designed for Propane (L.P) gas. Make sure furnace will operate properly on gas type avail able to user. Do not use this furnace with butane. Using wrong gas could create a hazard, resulting In
damage, injury, or death.
C. DO NOT install this furnace outdoors or in a mobile home,
trailer or recreational vehicle. It is not A.G.A. design­certified for these installations. This furnace is suitable for a home built on site or manufactured home completed
at final site.
D. Carefully choose furnace installation site. DO NOT di
rectly expose furnace to drafts, wind or other outdoor conditions. See Section 8 for more information.
E. DO NOT install furnace in a corrosive or contaminated
atmosphere. Make sure all combustion and ventilation
air requirements are adhered to in addition to local codes
and ordinances. See Section 8 for more information.
F. DO NOT use this furnace during construction when ad
hesives, sealers, and/or new carpets are being installed.
If the furnace must be used during construction, provide
clean outdoor air for combustion and ventilation to ^rnace space. See Section 8 for more information.
I. Always install duct system with furnace. Be sure duct
system has external static pressure within allowable fur nace range. See Sections 16 and 25 for more information.
J. Completely seal supply and return air ducts to furnace
casing. Duct work must run to an area outside furnace air space. Seal duct work wherever it runs through walls, ceilings or floors. See Section 16 for more information.
SECTION 3 — MEETING CODES.
Before installing furnace, make sure you know all applicable codes, National, state and local codes may take precedence over any instructions in this manual. Be sure to consult:
— Authorities having jurisdiction over furnaces; — Local code authorities for information on electrical
wiring, gas piping and vent pipe;
— Current National Fuel Gas Code ANSI Z223.1/NFPA
54:
— Current National Electrical Code ANSI/NFPA 70.
See Section 30 for information on getting copies of these codes.
SECTION 4 — DETERMINING BEST FURNACE LOCATION.
You may install this furnace as an upflow or downflow fur nace in an alcove, attic, basement, closet, garage, or utility room. Install furnace so all electrical components are pro tected from water.
You may install it as a horizontal furnace in an alcove, garage, attic, basement or crawl space.
Select furnace location to meet all requirements in this manual, making sure to refer to;
— Section 2 for safety rules; — Section 6 for minimum clearances; — Section 7 for furnace suspension; — Section 8 for combustion and ventilation air; — Section 9 for venting: — Section 11 for gas piping;
— Section 12 for electrical wiring; — Section 16 and 25 for duct work; — Section 17 for filters.
Consult local code authorities for additional location require ments.
Locate the furnace close to the chimney/vent and as near the center of the air distribution system as possible. Install furnace as level as possible.
Provide ample space for servicing and cleaning. Location
must allow 30 inches minimum front clearance for service. Always comply with minimum clearances shown on inside of front door. Do not install furnace directly on carpeting, tile or any combustible material other than wood flooring.
NOTE: A combustible floor base, available from manu
facturer, is required for downflow furnace installation on
wood flooring. HAZARDOUS LOCATIONS. When furnace is in a residential garage, it must be installed
so that burners and ignition source are located no less than fS'inches above the floor. Also, furnace should be protected
from physical damage by vehicles. When furnace is in public garages, airplane hangers, or other
buildings having hazardous atmospheres, install unit in ac cordance with recommended good practice requirements of the National Fire Protection Association, Inc. See Section 30.
SECTION 5 IDENTIFYING FURNACE DI
MENSIONS, SPECIFICATIONS, AND POSITION.
2, Furnace as-shipped position may be converted to a
downflow furnace by following instructions in B. be low. Once conversion is complete, furnace may be installed as a downflow furnace. Furnace may also then be installed as a horizontal on its right or left side. See Figure 2.
WARNING: Do not install furnace on its back. Doing so could cause a fire, resulting In damage, injury or death.
See Figure 3 for dimensional drawings and specification table. B. Converting furnace from as-shipped configuration.
READ ALL INSTRUCTIONS THOROUGHLY BEFORE STARTING CONVERSION.
NOTE: Start conversion with furnace on its back.
A. A unique feature of this furnace is that it may be installed
as an upflow furnace, horizontal furnace, or downflow
furnace (minor conversion required).
1. Furnace as-shipped is an upflow furnace. Furnace may be installed in this position or may be installed as a horizontal on its right or left side without any conversion. See Figure 1.
BTUH* INPUT
40,000 40,000 1/3 3" 60,000 1/4 4"
60.000 1/3 4" 60,000 80,000 80,000 60,000
80,000 3/4 4" 100,000 1/3 4" 100,000 100,000 3/4 4" 120,000 1/2 5" 120,000 140,000 3/4 5" 140,000 3/4
'See Furnace rating plate located on blower door.
MOTOR*
H.P.
1/4
1/2 4“ 1/4 1/3 1/2
1/2
3/4
VENT
DIAMETER
3"
4" 4" 4"
4"
5' 5'
FURNACE
WIDTH
A
14-1/2 14-1/2 14-1/2 14-1/2 12-7/8" 17-1/2 14-1/2 14-1/2 17-1/2 20-1/2 13-7/8" 18-15/16" (2) 10-4 17-1/2 15-7/8" 15-15/16" 17-1/2 20-1/2 20-1/2 18-7/8" 18-15/16" 20-1/2 23-1/2 21-7/8" 21-15/16" 23-1/2
RETURN AIR SIZE
13- 23 /3 2" X B
WARNING: When servicing controls, all wires must be labeled prior to disconnection. Mlswlring can cause improper operation resulting In damage, Injury, or death.
1. Remove front door. Study components described in conversion. See Figure 4.
SUPPLY AIR SIZE
78-1S/16'* X C
12-7/8" 12-15/16" 10-4 50-80 12-7/8* 12-15/16" 10-6
12-7/8" 12-15/16" 15-7/8" 15-15/16" 10-8
12-7/8" 12-15/16* 12-7/8" 12-15/16" 10-6 15-7/8" 15-15/16*
15-7/8" 15-15/16* 10-8 18-7/8"
18-7/8" 18-15/16" (2) 10-4 21-7/8"
12-15/16" 10-6 45-75
18-15/16"
21-15/16*
BLOWER
WHEEL
SIZE
10-4 45-75
10-4
10-8 50-80 10-6 55-85 1245
(2) 10-4
10-8
(2} 10-4 (2) 10-6
TEMP
RISE “F
30-60 1265
35-65 1635 50-80 915 40-70 1235
40-70 1930 50-80 1585
40-70 45-75 1660 45-75 45-75 I860 50-80 2235
CFM
at 0.50“ W.C.
805 850
1260
1645
1950 1965
FURNACE AND DIMENSIONS SPECIRCATIONS
FIGURE 3
AS-SHIPPED CONFIGURATION
FIGURE 4
CONVERTED CONFIGURATION
FIGURE 5
2. Remove two junction box mounting screws from top
plate. Remove four top plate mounting screws. Save all screws. Remove top plate and front duct flange.
3. Disconnect pressure switch wires and inducer motor connector wires.
4. Remove ten screws from the inducer pan; save screws. DO NOT drop screws into heat exchanger openings.
5. Lift inducer pan (with inducer motor and pressure switch stilt in place) about 1/4 inch and tilt left side up to clear casing flanges. Use care not to damage inducer gasket.
NOTE: If possible, decide on direction of gas entry now. Screws to inlet gas valve fitting are accessible. See Section 11.
6. Rotate inducer pan 180 degrees, line up mounting holes and place inducer pan in furnace. Use care not to damage gasket. Replace ten screws in in ducer pan. See Figure 5.
7. Pressure switch wires will no longer reach pressure switch. Remove cable tie around excess length of red/yellow piggyback, blue and purple pressure switch wires.
8. Connect pressure switch wires as follows. Wires are numbered on insulation near terminals.
a. #1 Purple wire to pressure switch, terminal 'C
(Common).
b. #2 Blue wire to pressure switch, terminal 'NC
(Normally Closed).
c. #7 and #8 Red/Yellow piggyback wire to pres
sure switch, terminal 'NO' (Normally Open).
d. Route all pressure switch wires over inducer
motor. e. Reconnect inducer motor connector. f. Replace wire tie in area that prevents wires from
touching hot surfaces.
9. Rgmove four screws that secure bottom plate to cas ing sides. Remove bottom plate; save screws,
10. Install top plate, removed in step 2, where bottom plate was. Secure with four screws. Inducer outlet is now lined up with vent outlet in top plate.
11. Stand up furnace with top plate down. Line front duct
flange up with holes. Place bottom plate on top of duct flange and secure both to casing with four screws.
12. Install junction box on bottom plate using two #6B
screws removed in Step 2. Junction box cover and screw of junction box must face front of furnace.
13. Gasket around flue collar must be in place. If gasket is loose, glue It. If gasket is damaged, replace it.
14. Install a single wall vent pipe section (minimum length 30 inches) (Field-Supplied) to inducer outlet with three
equally spaced screws. This pipe serves as an in ducer outlet extension to which an appropriate vent can be attached. Due to minor variations in vent pipe, available from different manufacturers in the field, and to assure the tightest seal possible, inducer out
let extension is not supplied with furnace. Additional vent pipe sections or Type B1 adapter may then be
added when installing the furnace.
WARNINGS If Inducer outlet extension Is shorter than 30 Inches and chimney or vent becomes blocked, com bustion products may be drawn Into furnace. This could cause nausea or asphyxiation, resulting In Injury or death.
15. Conversion from as-shipped configuration is now complete.
SECTION 6 — ALLOWING FOR CLEARANCES.
WARNING: Do not Install furnace on Its back, doing so could cause a fire, resulting In damage. Injury or death.
Establishing clearances from combustible material.
Locate clearance label on inside of front door. See Figure 6.
WARNINGS Furnace Installation must meet all minimum clearances from combustible material specified In this manual and all applicable codes. Failure to provide re quired clearance between furnace and combustible mate rials could cause a fire, resulting In damage, injury, or death.
WARNINGS This furnace Is A.G.A. design certified for direct Installation on wood flooring for upflow and hori zontal positions.
• Do not install furnace on carpeting, tile or other
combustible material.
• Do not Install furnace In a closet In horizontal
position.
• Do not Install furnace on wood flooring without
special base In downflow position.
MINIMUM INCHES CLEARANCE
CLOSET.
UPFLOW POSITION
• FOR CASING WIDTHS 17 INCHES OR LARGER 0 CLEARANCE MAY BE USED. 18 INCH FRONT CLEARANCE REQUIRED FOR ALCOVE. FOR INSTALLATION ON COMBUSTIBLE FLOORING.
MINIMUM INCHES CLEARANCE CLOSET.
DOWNFLOW POSITJON
• FOR CASING WIDTHS 17 INCHES OR LARGER 0 CLEARANCE MAY BE USED. 18 INCH FRONT CLEARANCE REOUIRED FOR ALCOVE. FOR INSTALLATION ON COMBUSTIBLE FLOORING ONLY WHEN INSTALLED ON SPECIAL BASE PART N0. 4-024400.
MINIMUM INCHES CLEARANCE
• CLEARANCE SHOWN IS FOR AIR INLET AND AIR OUTLET ENDS. VENT MUST MAINTAIN CLEARANCE LISTED ABOVE. FOR INSTALLATION ON COMBUSTIBLE FLOORING.
FOR HORIZONTAL POSITION LINE CONTACT IS ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF TOP AND TWO SIDES OF FURNACE JACKET AND BUILDING JOISTS. STUDS OR FRAMING.
ALL POSITIONS RLOUIRE 30 INCHES FRONT CLEARANCE FOR SERVICE*
TOP SIDES BACK
1 1* 0
1 0 0 2
TOP SIDES BACK
1 1* 0 6 1 0
HORiZONTAL POSmON
TOP SIDES* BACK 1 2* 1
2*
0 COMBUSTIBLE MATERIAL IN ALCOVE OR
FRONT VENT
0 COMBUSTIBLE MATERIAL IN ALCOVE OR
FRONT VENT
0 2
rO COMBUSTIBLE MATERIAL IN ALCOVE.
FRONT VENT 0 18 0 18
6 WHEN USING SINGLE WALL
6
1 WHEN USING B1
6 WHEN USING SINGLE WALL
1 WHEN USING B1
6 WHEN USING SINGLE WALL
1 WHEN USING B1
40ZB№
MINIMUM CLEARANCES
FROM COMBUSTIBLE MATERIALS
FIGURE 6
1. Upflow Installation. Upflow position is approved for installation on
wood flooring. Typical upflow furnace installa tions are an alcove, attic, basement, closet, ga rage, or utility room. See Figure 6 or furnace clearance plate for minimum clearances to com bustible materials.
2. Horizontal Installation
a. Horizontal position is approved for installa
tion on wood flooring. Typical horizontal fur
nace installations are an alcove, garage, at
tic, or crawl space. See Figure 6 or furnace
clearance plate for minimum clearances to combustible materials.
b. Attic Installation.
Line contact is permissible for furnaces installed in horizontal positions. The in
tersection of furnace top and sides forms
a line. This line may be in contact with
combustible material. However, maintain
a 6" clearance to vent connection unless
Type B1 vent is used. See Figure 7.
Doing any of the above could cause a fire resulting in damage, injury, or death.
TYPICAL ATTIC INSTALLATION
FIGURE 7
When using single wall vent pipe in horizon tal installations, horizontal furnaces with
14.50" high casings must be raised 1" to have 6” clearance to combustible material. See Figure 7.
Furnace installation on combustible flooring is permitted with combustible floor base available from manufacturer. Read installation instructions packaged with combustible floor base to correctly install. See Figure 8.
c. Install a platform under furnace that extends
a minimum 30" in front of furnace. This pro vides a work area and keeps insulating ma terials away from combustion air openings.
Secure platform to ioists.
WARNINOs When a furnace Is installed
In an attic or other Insulated space, keep all insulating materials at least 12" away from furnace and all burner combustion air openings. Failure to do so could cause
nausea, asphyxiation or fire, resulting In damage. Injury, or death.
d. Crawl Space Installation.
Furnace can be hung from floor joists or in
stalled on suitable blocks or pad. Pad or
blocks should provide enough height to re duce potential for water damage. See Sec tion 7.
3. Downflow Installation. You must convert furnace from as-shipped con
figuration for downflow furnace installation. See
Section 5.
DOWNFLOW FLOOR OPENING
FIGURE 8
See Figure 9 for installation diagram on com bustible floor.
4. Service Clearance. Allow minimum front clearance of 30 inches for service.
See Figure 6 or inside of front door for minimum service clearance.
SECTION 7 — SUSPENDING FURNACE.
Some installations will require that furnace be suspended from rafters or floor joists.
A common way to do this using threaded rods is shown in
Figure 10. Consider this means when people may walk un derneath furnace. Figure 11 shows another common suspen sion means using pipe strap. Other means that provide ad equate support may be used.
When furnace is not suspended in a crawl space, elevate furnace off ground to avoid water damage and allow for air conditioning coil drain.
Downflow position is approved for installation on non-combustible flooring. Typical downflow fur nace installations are an alcove, attic, closet, basement, garage, or utility room. See Figure 6
or furnace clearance plate for minimum clear
ances to combustible materials.
NOTE: Level furnace from front to back and from left to right within 1M" per four feet.
FURNACE, PLENUM, AND BASE INSTALLED ON A
COMBUSTIBLE FLOOR
FIGURE 9
SICTION S PROVIDING FOR COMBUSTION AND ViNTILATION AIR.
Before you begin installing furnace, pian to provide enough combustion and ventiiation air following:
— Current National Fuel Gas Code ANSI Z223.1/NFPA
54, Section 5;
— Local Code authorities. Refer to Section 31 of this
manual for these codes.
Ventilation is the process of replacing air which is required for furnace operation. The total amount of ventilation air pro vided within structure must equal all requirements of gas ap pliances in the building, plus any air quantities removed by range hoods, exhaust fans, etc.
Another reason to supply fresh outdoor air for combustion and ventilation is that it dilutes contaminants found in indoor air. These contaminants include bleaches, adhesives, clean ing solutions, detergents, solvents, cat litter, spray can pro pellants and most refrigerants.
WARNINDi Furnace and any other fuel-burning appli ances must have enough fresh air for propsr combus tion and ventilation. Lack of adequate combustion and ventilation air could cause nausea or asphyxiation, re
sulting in injury or death.
WARNINOi During construction, do not use air from
inside structure for combustion and ventilation. Vapors
from soma construction adhesives and materials can be come corrosive in the presence of a flame. This could cause failure of heat exchanger or vent system, result
ing in damage. Injury or death.
WARNINO: Combustion and vsntllatlon air that contains
chlorine, fluorine, bromine and Iodine could cause heat exchanger or vent system failure, resulting In damage, Injury or death,
WARNINO: When installing a furnace In an attic or other
insulated space, keep furnace free and clear of all lnsu> lating materials. Make surs all Insulation Is at least 12" away from burner combustion air openings and well away from openings into furnace space that supply air for combustion and ventilation. Failure to do this could causa nausea, asphyxiation or fire, resulting In damage, injury or death.
WARNINGS When Installing furnace in an alcove, attic,
basement, closet, garage, or utility room do not store items in front of furnace or In front of closet or utility door which would block combustion air openings to fur* nace. Failure to do this could cause nausea, asphyxia tion or fire, resulting In damags, Injury or death.
DO NOT install furnace where any combustion or ventilation air openings will allow outside air to blow directly against furnace.
WARNINGS Drafts blowing directly against furnace could
cause improper combustion which could cause heat ex changer failure or fire, resulting In damage, Injury or death.
Sufficient air MUST be provided to insure there wilt not be a negative pressure in furnace room or space. In addition, there MUST be a positive seal between furnace and return air duct to avoid pulling air from burner area.
Provide adequate combustion and ventilation air by consider' ing volume of furnace installation space. Use these instruc tions and current National Fuel Gas Code ANSI Z223.1/NFPA 54 to determine whether furnace is in an unoonfined or con fined space.
If ratio is less than 50, installation space is a con
fined space. If ratio is 50 or greater, installation space
is an unconfined space.
B. Installing furnace In confined space.
WARNING: You must provide permanent air open
ings to a conflned furnace installation space from another area as described below. Failure to do ao could result In Inadéquat# combustion and vsntllatlon air. Thsae could cause nausea, asphyxiation or fire, resulting In damage, injury or death.
1. Combustion and ventilation air openings. a. All combustion and ventilation air from inside the
structure.
1. The furnace space must be provided with two permanent openings to an additional
room(s) of sufficient volume so that the combined volume of all spaces meet the cri
teria above for an unconfined space.
The total input of all gas appliances within
the combined space must be considered in
making this determination. See Figure 12.
2. a. Each opening must have minimum free area of one square Inch per 1,000 Btuh per hour of the total combined input rat
ing of all gas appliances within the con
fined furnace space, but not less than
100 square inches. One opening must be within 12 inches of the top and an other opening within 12 inches of the
bottom of the furnace space. See Fig
ure 12.
A. Determining If your space Is confined or unconflned.
Two factors determine whether a furnace installation space is confined or unconfined:
— Volume of installation space; — Total gas input of appliances to be installed in that
space.
To determine which your space is:
1. First calculate furnace installation space volume in cubic feet.
2. Determine combined input rating (BTUH) of all gas appliances in furnace installation space, including furnace input. This is the total combined input rating.
3. Divide total combined input rating by 1,000. Then divide this number into installation space volume.
Here's the formula:
Space Volume
Ratio
Total lnput/1,000
10
For example:
Total Input
Btuh (square Inches)
40,000-100,000 100
120,000 120 140,000
b. If building is of unusually tight construc
tion, provide a permanent opening di rectly communicating with the outdoors. Opening shall have a minimum free area of one square inch per 4000 Btuh of total input rating for all equipment in the enclosure.
If return air is taken directly from hall way or space next to furnace that com municates with furnace spaces, all air for combustion must come from out doors.
b. All combustion and ventilation air from outdoors.
1. The furnace space must be provided with two permanent air openings directly to the outdoors, or by ducts to the outdoors or spaces (attic or crawl spaces) that freely ac cess the outdoors. These combustion and ventilation openings will give fresh air free access to furnace space for combustion and ventilation. You must also provide air suffi cient for all other gas appliances within fur nace space.
Free Area Per Opening
140
Ducts must freely access outdoors or spaces (attic or crawl spaces) which freely access the outdoors. Well ventilated attics or crawl spaces usually satisfy this requirement.
2. Locate one combustion and ventilation air
operîing within 12" of top of furnace space. Locate another within 12" of bottom of fur nace space.
3. When directly accessing the outdoors, each opening must have a minimum free area of
one square inch per 4,000 Btuh of total combined input rating of all gas appliances within furnace space. See Figure 13A.
4. If combustion air ducts will run vertically, ducts and each opening must have a mini mum free area of one square inch per 4,000 Btuh total combined input rating. You must allow for all gas appliances within the fur nace space. See Figure 13B.
For example:
Required
Total Input
Btuh
40,000 10.0 4
60,000 15.0 5
80,000 100,000 120,000 30.0 7 140,000 35.0
Free Area per Opening
(square inches)
20.0 6
25.0 6
Suggested
Round Pipe
(inches dia.)
7
11
5. if combustion air ducts will run horizontally, ducts and each opening must have a minimum free area of one square inch per 2,000 Btuh total combined input rating. You must allow for all gas appliances within the furnace space. See Figure 14.
CHIMNEY OR CAS vent
NOTE: EACH AIR DUCT OPENINO SHALL HAVE A FREE AREA OF NOT LESS THAN ONE SQUARE INCH PER 2.000 BTU PER HOUR OF THE TOTAL INPUT RATInC OF ALL EQUIPMENT IN THE ENCLOSURE
to 25% free area. Assume metal louvers and grilles have 60 to 75% free area. Refer to current National
Fuel Gas Code ANSI Z223.1/NFPA 54.
Example: Furnace is 100,000 Btuh input and is to be installed in a confined space that contains no other gas appliances. Rectangular combustion and ventila­tion air ducts will run horizontally from outdoors to furnace space.
a. Calculate free area required.
Because combustion and ventilation air ducts run horizontally, allow 2,000 Btuh. See 2b. above.
Furnace Input
Btuh
Free Area Required
2,Q0Q Btuh
per square inch
IF THE EQUIPMENT ROOM IS LOCATED AGAINST AND OUTSIDE WALL ANO THE AIR OPENINGS
COMMUNICATE OIRECTLY WITH THE OUTDOORS. EACH OPENING SHALL HAVE A FREE AfffiA
OF NOT less than one SQUARE INCH PER 4,000 BTU PER HOUR OF THE TOTAL INPUT
RATING OF ALL EQUIPMENT IN THE ENCLOSURE.
EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS.
FIGURE 14
For example:
Total input
Btuh
Free Area per Opening
(square Inches)
Round Pipe
(Inches dia.)
40,000 20 6 60,000 30 80,000 40
100,000
50 8 120,000 60 9 140,000 70
6. Ducts which introduce combustion and ventila tion air from outside structure into furnace space,
must have the same cross sectional area as the free area of openings to which they connect. The minimum dimension of rectangular air ducts
shall not be less than 3 inches.
2. Louvers, grilles, and screens. Sometimes, louvers, grilles, or screens cover com
bustion and ventilation air openings. If so, you must provide larger openings than those calculated above. This is necessary because louvers, grilles and screens block and reduce an opening's free area.
Louver, grille and screen manufacturers supply tech nical data on their products, which usually includes
the Tree area." Sizing the openings with louvers,
grille or screen in place will provide minimum free area to furnace space as calculated above. Do not use screen smaller than 1/4" mesh. If you do not know free area, assume that wood louvers have 20
7 8
10
100,000
50 square inches
2,000
Each opening must have a free area of 50 square inches.
Calculate overall area of openings to give needed
b.
free area once you cover them to keep out rain and other outside elements.
Example: If you will use wood louvers to cover combustion and ventilation air openings and you do not know free area of wood louvers, use 20%, as suggested in ANSI Z223.1/NFPA 54.
100 x Free area
from a) above)
Louver free area
openings expressed
overall area of openings with wood louvers installed
as a percentage
100 x 50
250 square inches
20
Each of the two combustion and ventilation air openings must have a total area of 250 square inches. This is when wood louvers cover openings
for a 100,000 Btuh input furnace and combustion
and ventilation air ducts run horizontally.
c. Calculate minimum rectangular duct size needed.
If you choose a rectangular duct with the mini mum allowed dimension of 3", the other duct dimension must be at least 16-2/3". This is cal culated by dividing the 50 square inches of free area from a) by 3", with equals 16-2/3".
WARNINGi You must fix combustion and ventila
tion air louvers and grilles In open position or Inter
lock them with furnace operation. Furnace operation
12
with louvvrs or grilles closed could cause Inadequate combustion or ventilation air, resulting In Injury or death.
C. Installing furnace in unconfIned space.
Refer to current National Fuel Gas Code ANSI 2223.1/ NFPA 54 for more information. This code does not re
quire that you make special provisions for combustion
and ventilation when furnace is in an unconfined space. However, it is always prudent to arrange for combustion and ventilation air as if installation space is confined space.
In the past, infiltration through loose construction pro
vided enough air for combustion and ventilation when
furnace was in an unconfined space. Current construction
methods may now prevent infiltration of air into unconfined space. These current methods include increased insula tion, vapor barriers, tight fitting doors and windows, and weather-stripping.
D. Allowing for exhauet fan operation.
1, When furnace is in a ventilated attic, crawl space,
residertce garage, or outside the heated space, ex haust fan drafts can adversely affect its operation. These drafts can come from kitchens, bathrooms, clothes dryers or anywhere within the heated space.
WARNING: Exhaust fans that blow against fur
nace could cause heat exchanger failure or fire, resulting In damage, Injury, or death.
2. When furnace is in a repair garage or inside the heated space, exhaust fans can adversely affect its
operation. Exhaust fans in kitchens, bathrooms, clothes dryers or anywhere within heated space in crease combustion and ventilation air requirements. This is because exhaust fans reduce the amount of combustion and ventilation air available to the fur nace. A fireplace also reduces amount of combus tion and ventilation air. You must allow for these reductions.
WARNING: You must allow for reduction of air
available for combustion and ventilation by ex haust fans and fireplaces. Failure to do so could result In Inadequate combustion and ventilation sir. This could cause nausea, asphyxiation, or firs, resulting In damage, Injury, or death.
3. Exhaust fan air may contain compounds of chlorine, fluorine, bromine, and iodine. If used for combus tion, this contaminated air will adversely affect fur nace operation.
WARNING: If used for combustion and ventila
tion, contaminated exhaust fan air could cause heat exchanger or vent system failure resulting In damage, Injury, or death.
SICTION 9
PROVIDING P
Vent furnace using these instructions and Venting Adden dum. Also, meet requirements of local utilities and other local code authorities. You must connect furnace to a vent or fac tory-built chimney or a suitably sized, constructed and lined
masonry chimney. Vent or factory-built chimney must meet a
recognized standard. Chimney lining method and material
must comply with local requirements. Use corrosion-resistant
material meeting nationally recognized standards for vent construction.
INTING.
WARNING: Inadequate vent or chimney could allow
combustion products to collect In structure, resulting In
Injury or death.
WARNING: Vent this furnace separately from any appli
ance designed to burn solid fuel, particularly wood-burn-
Ing or coal burning appliances. Improper venting could
allow combustion products to collect In structure, result
ing In injury or death. A. Venting category.
The furnaces covered by this manual are design-certified as CATEGORY 1 for venting, CATEGORY 1 furnaces
have non-positive vent static pressure and rely on the beat content of combustion products to vent. You may common vent CATEGORY 1 furnaces.
The furnaces covered in this manual are also design­certified as CATEGORY 3 for venting, only when they are installed with manufacturer specified vent system components and installation practices.
Category 3 gas appliances rely on the heat content of combustion products and mechanical or other means to vent. You may not common vent CATEGORY 3 gas ap pliances.
B. Types of vent systems.
These definitions will help you understand the terms we use.
1. "Vent" and "chimney" refer to open passageways.
These passageways convey vent gases from vent connectors to the outside. Gases begin their final ascent at the vent or chimney. Vents and chimneys usually run vertically or nearly vertical. When they serve only one gas appliance, they are called "dedi cated" vents or chimneys. Whan they serve multiple gas appliances, they are called "common" vents or chimneys.
2. A "vent connector" connects a gas appliance to a
vent or chimney. Vent connectors usually run directly from the furnace draft inducer collar to vent or chim ney. Vent connectors may have vertical and horizon tal runs.
3. A "venting system" is a continuous open passage
way from the draft inducer collar to the outside. Venting systems usually have vent connector(s) and a vent or chimney. Venting systems commonly serve
a single furnace or a single furnace and a water
heater. Other multiple-appliance venting systems are
13
less common.
C. Design considerations.
1. General considerations. Avoid oversizing furnace for your application. Se
lect a furnace model with a rated heating output close to the calculated heating toad. This extends
the firing period, decreasing the potential for con densate formation in the vent.
a. Too small a vent cannot carry all combustion
products outdoors. Too large a vent will not vent combustion products rapidly enough to avoid potential for condensation. Refer to Venting Ad dendum for correct size vent.
b. Vent height must be a minimum of five feet.
Minimize vent connector horizontal runs to the extent possible for best performance.
c. The designer must consider the building's ori
entation, answering these questions. Will the vent terminate outside the building where its op
eration could be adversely affected by winds? Could any adjacent buildings adversely affect vent operation? Allowing for these factors can
reduce the possibility of downdraft conditions.
b. Use Type B1 vent connectors in or through at
tics, crawl spaces, or other cold areas. Install thimbles that meet local codes when vent con
nectors pass through walls or partitions of com bustible material.
c. Keep vent connectors as short as possible by
locating furnace as dose as practical to vent or chimney. Avoid unnecessary turns or bends which create resistance to
Adding an elbow adds resistance. For example, adding a 6" 90-degree elbow would be the equivalent of adding 20 feet of horizontal 6" pipe. 45-degree elbows have lower resistance than 90­degree elbows, and can work for most vent runs.
d. You may increase vent connector diameter to
overcome installation limitations and obtain con
nector capacity equal to furnace input. Make this
increase as close as possible to draft inducer collar, allowing for necessary adapters and fit tings.
e. If you join two or more vent connectors before
they enter the vertical vent or chimney, use cau tion. See Venting Addendum.
flow of vent gases.
d. If your local experience indicates possible con
densation problems, provide for draining and disposal of venting system condensate.
2. Vent sizing. a. Sometimes the horizontal distance from the fur
nace to the vent or chimney is already given;
this is known as the horizontal vent connector
run. The vent or chimney height is also usually
given as is the Btuh input of the gas appliances
served by the vent.
Check these parameters to be sure the venting system will work. Use approved engineering practices, Venting Addendum, these instructions, and Part 7 of current National Fuel Gas Code ANSI Z223.1/NFPA 54. Use vent capacity tables in Venting Addendum to check existing or new vent sizes for CATEGORY 1 furnaces.
b. See Venting Addendum for single appliance
venting and multiple appliance (common) vent
ing. For multi-story installations, refer to current
National Fuel Gas Code ANSI Z223.1/NFPA 54.
c. Minimum vent connector diameter from furnace
to vent or chimney is same as draft inducer col lar.
3. Vent connector. a. Vent connectors must be made of noncombus
tible, corrosion resistant material capable of withstanding vent gas temperatures. They must be thick enough to withstand physical damage
and be accessible for inspection, cleaning and replacement.
f. Do not connect this furnace to any portion of a
vent system which operates under positive pres sure. Positive pressure would result with CAT
EGORY 3 and 4 appliances connected to the
vent.
g. Do not connect vent connector to a chimney flue
serving a fireplace unless you permanently seal
fireplace flue opening.
4. Vertical vent or chimney. a. Vents and chimneys usually extend vertically with
offsets not exceeding 45-degrees. Consider vent pipe runs more than 45'degrees as horizontal runs. Include their length in the total horizontal run.
b. Designer and installer must provide an appropri
ately sized common vent for all appliances con nected to it. See Venting Addendum.
c. Connect this CATEGORY 1 furnace only to vent
systems with other CATEGORY 1 appliances.
WARNING: Do not connect this Category 1
furnace to a vent system used by Category 3 and 4 appliances. Do not connect It to vents with mechanical draft systems operating at positive pressure. Improper venting could al
low combustion products to collect in struc
ture during use, resulting In damage, Injury or death.
5. Chimney. Furnace is suitable for venting into a properly sized
and lined masonry chimney. Consult National Fuel
Gas Code ANSI Z223.1/NFPA 54 for construction details. If chimney is oversized, liner is inadequate
14
OT evidence of condensate exists, consider using chimney as a pathway for suitably sized Type B1 vent liner. See Figure 15.
FIGURE 15
WARNIN9I Support Type B1 vent liner in ma
sonry chimney. Maintain at least a 1" clearance on all sides to reduce possibility of condensate in vent. Condensate may cause vent to deterio rate allowing combustion products to collect In structure, which could result In injury or death. See Figure 16.
NOTE; For more information on proper chimney in spection and relining procedures, Gas Research In stitute (GRI) has a topical report entitled "Masonry Chimney Inspection and Reiintng". Obtain copies
through American Gas Association (A.G.A.) at
1-800-841-8400.
6. Vent termination. a. Terminate ail verticai vents with a iisted vent
cap or roof assembly unless local codes require otherwise. See vent cap or roof assembly
manufacturer's instructions. Locate vent termi nation (vent cap or roof assembly) in an area
without positive wind pressures or eddy currents.
Eddy currents occur when air swirls over roof peaks. They can cause down-drafts and ad versely affect vent operation. See Figure 17.
FIGURE 16
WAKNINOi Vent liner muet not block opening
where other epplicncee' vent connector* enter chimney. Blocked opening* could cau»* com bustion products to collact In atructur*, r*sutt-
Ing In damag*, Injury or dssth.
WARNINOt Do not uaa unllnad masonry chlm-
naya. Thasa Incraasa risk of condansats forma tion, which may causa chlmnay to datariorata, allowing combustion products to collact In structura, raaulting In damaga. Injury or death.
Some vent terminations or caps protect against eddy currents and down-drafts, Consult their
manufacturer's instructions. Vent terminations or caps should usually be at least the same size as
the vent. They may be larger if the installation
warrants.
b. Vent systems must end at least five feet above
the highest gas appliance connection. Vent pipe must extend at least three feet above the point where it passes through the roof. Vent termina
tion must be at least two feet higher than any
portion of building within ten feet horizontal and vent termination must be at least two feet higher
than roof peaks within ten feet horizontal. See
Figures 18 and 19. Some vent cap manufactur ers offer vent caps that allow reduced clearances.
Consult their Instructions.
15
D. Installation.
1. Vent connectors. Attach vent connector at draft inducer collar. Make
sure flue gasket is in place providing a seat. Use a minimum of three equally spaced screws around connection. Connect all other vent pipes using three equally spaced screws at each joint. Exception is only when you use Type B1 vent pipe with self locking connections or high temperature plastic pipe.
WARNINGS Unsecured vent pips connections
may loosen. This can allow combustion products
to collact In structura, resulting In Injury or death.
Install vent connectors without any dips or sags. Slope them upward from furnace at least f/4” per foot. To prevent sagging, at each joint support vent connectors and horizontal portions using hinges, straps or equivalent. Seal all connections where vent connectors enter chimney. See Figure 15.
TERMINATION MORE THAN 10 FEET FROM RIDGE
FIGURE 18
TERMINATION 10 FEET OR LESS FROM RIDGE
FIGURE 19
WAftNINGt Failure to properly terminate
vent chimney systems could allow combus tion products to collect In structure, result ing In Injury or death.
c. Terminate venting system at least three feet
above any forced-air building inlet within ten feet. Consider doors, windows and gravity air building inlets. Locate vent termination at least four feet below, four horizontal feet from or one foot above any of these openings.
To avoid blockage, attach vent connector to a ma sonry chimney above the extreme bottom. For in spection ease, use thimble or slip joint to make vent connector removal easy. Firmly attach connector.
Insert all vent connectors into, but not beyond, inside chimney wall.
2. Vertical vent or chimney systems. Install vent materials following their listing terms,
manufacturer's instructions, these instructions and local codes.
A gas vent passing through a roof must extend through roof flashing, jack or thimble. It must termi
nate above roof surface.
E. Existing vent considerations.
Masonry chimneys previously used for venting solid fuel or oil burning equipment should be lined with suitable metal liner. Also provide an accessible clean out per cur rent National Fuel Gas Code ANSI Z223.1/NFPA 54.1.
1. Inspection of vents (chimneys). a. Make sure existing vent or chimney is proper
size and construction for appliances that will use it. The best way to do this is to size as if it were
a new installation. Compare the existing vent to your calculations and make necessary correc tions.
b. Examine vent or chimney cleanouts to make sure
they remain tightly closed when not in use. Make sure vent or chimney passageway is clear and free of obstructions. Look for evidence of con densate or deterioration in vent or chimney. Ei ther of these means an inadequate vent.
c. If you find an inadequate vent or chimney, do
not leave it as is. Repair or replace it. A new vent must meet these instructions and current
16
National Fuel Gas Code ANSI Z223.1/NFPA 54.
Rabuild a chimney to meet national standards.
MCriON 10 —
TOOLS NIIDID rOR INSTALLATION.
WARNINOi An Inadequate vent or chimney
could allow combuatlon products to collect
In structure, resulting In Injury or death.
d. Sometimes you wiii repiace a common vented
appliance. Make sure common vent size is cor rect for aJl appliances connected to it. If you re move a furnace from a common vent without replacing it, the vent will likely be too large for
remaining appliances. See Venting Addendum.
e. The following steps shall be followed with each
appliance remaining connected to common vent ing system placed in operation, while other ap pliances remaining connected to common venting system are not in operation.
1. Seal any unused openings in common vent ing system.
2. Visually inspect venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corro sion and other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between space in which appliances remaining connected to common venting systems are located and other spaces of building. Turn on clothes dryers and any appliances not connected to common venting system. Turn on any ex haust fans, such as range hoods and bath room exhausts so they will operate at maxi mum speed. Do not operate a summer ex haust fan. Close fireplace dampers.
4. Follow Operating Instructions. Place appli ance being inspected in operation. Adjust
thermostat so appliance will operate con tinuously.
5. After it has been determined that each ap pliance remaining connected to common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
6. If improper venting is observed during any of the above tests, common venting systems must be corrected.
NOTE: Follow current National Fuel Gas Code ANSI 2223.1/NFPA 54 to correct im proper common vent operation. Any common vent resizing must approach minimum size
determined by using Venting Addendum.
ITEM
TOOL DESCRIPTION
HAND TOOLS
A.
1. Carton KnHe
1/4" nut driver
2.
5/16" nut driver
3.
4. 3/8” nut driver
1/4" X 8" straight-
5. blade screwdriver
#2 X 8" Phillips
6. screwdriver
7/16" open end or
7. tubing wrench
2-8" to 14" pipe
8.
wrenches
4" adjustable
9. wrench
10. 8” Channel-lock ptiei^
3/16" Allen
11. wrench
12.
9/64" Allen wrench
B.
SUPPLIES
13. Pipe thread sealant suitable for use with
propane (LP) gas
14.
Bottle of soap solutbn
15.
2-1/8” pipe, manual shutoff valves
C.
TEST INSTRUMENTS
16.
Volt meter with 50 and 150 volt ranges
17. Clamp around ammeter with 10 amp and higher ranges
USED FOR
Furnace removal from carton
Control box cover
Casing and blower
Blower and motor mounts
Wire terminals and manifold pressure adjustment
Components in control box
Main burner orifices
Gas pipe installatbn
Blower wheel set screw tightening
Strain reliefs
Inlet and outlet pressure tap plug removal from gas control
Honeywell gas inlet fitting
Gas pipe and controls
Gas leak checking
Gas control inlet and pressure checking
Electrbal chedt of controls and power supply
Amp draw of motors and control check
17
18. 10-turn coil of wire to fit on ammeter
19. "U" Tube Water
Manometer with O.V resolution 0“to 15" W.C. range
20. Slope gauge with
0.01” pressure
measurement taps
and tubing, Oto 1"
W.C. range
Room thermostat heat anticipator setting
Gas pressure
measurement
Duct work static pressure
furnace. A convenient way to do this when you have
reduced bottom clearance, is to make drip leg by using a 1/2" to Г NPT Tee, Then install a 1-1/2" long.l” NPT nipple in Tee with a Г NPT pipe cap to complete drip leg.
3. When using black iron gas pipe, install an A.G.A. listed ground joint union between drip leg (sediment
trap) and furnace gas control. Locate ground joint
union to allow easy servicing of burner assembly and gas control.
4. Install gas pipe to inlet side of furnace gas control.
21. 2 thermometers with 1 -degree
Fahrenheit
resolution, 50
degrees F to 175
degrees F range
22. Stop watch
23. Torque wrench (100 inch-pounds)
Temperature rise measured
through lurnace
Gas input meter timing
Proper screw installation
SICTION 11 — INSTALLING GAS PIPING.
Equipment needed: Save time by getting these tools before you start: Item number(s) 8,12.13 and 14 listed in Section
10.
A. Preparation.
Gas piping must meet requirements of current National
Fuel Gas Code ANSI Z223.1/NFPA 54 and local codes.
Size of pipe running to furnace depends on:
• Length of pipe;
• Number of fittings;
• Specific gravity of gas;
• Input requirements fBtuh) of all gas-fired appli ances attached to same main supply line.
Refer to current National Fuel Gas Code ANSI Z223.1/
NFPA 54 for correct gas pipe sizing information.
Plan furnace gas supply piping so it will not interfere with removal of burner assembly, front door or blower door for servicing.
Always use a pipe thread sealant which is resistant to propane (LP) gas solvent action. Sparingly apply sealant to all joints on male threads only, starting two threads back from end.
B. Installation.
1. Install A.G.A. listed manual shut-off valve in gas supply line immediately upstream of furnace. Install
1/8" NPT plugged tapping accessible for test gauge connection. Omit separate, plugged tapping if local area accepts plugged tapping in gas control inlet.
2. After in-line manual shut-off valve, install a drip leg (sediment trap) at gas supply line inlet connection to
WARNINGS Do not thread gas pipe too far. Do
ing so may cause gas control to split or crack
which could cause a gas leak or distortion or
malfunction of gas control. Thasa could causa a firs or explosion resulting in damage, Injury or death.
5. Isolate gas control from gas supply line pressure during leak check. Gas supply line test pressure de
termines how you isolate gas control.
WARNINGS At gas supply line, test pressure
equal to or less than 14 Inches W.C. (1/2 PSI). Isolate gas control from gas supply line by turning furnace gas control knob clockwise > to off posi
tion. Unexpected surges could damage gas con trol causing gas to leak, resulting In firs or ex plosion.
WARNINGS When test pressure la above 14
Inches W.C. (1/2 PSI), completely disconnect gas
control from gas supply line. Failure to Isolate
gas control from test pressure could damage H,
causing gas to leak, resulting in firs or explosion.
6. Use a commercial soap solution made to detect leaks and check all gas piping connections. Bubbles indi
cate gas leakage. Seat all leaks before proceeding.
WARNINGi Never use an open flams to check
for gas leaks. If a leak doss exist, a firs or explo sion could occur, resulting In damage. Injury or
death.
Furnace Gas Entry Piping.
1. See below for gas entry holes and knockouts.
a. A 1-1/4* X 2-3/4" knockout in top plate.
b. A 1-1/2" diameter hole and a 1-1/4" x 1-15/16"
knockout in right side of casing.
c. Two 1-5/8" diameter knockouts in left side of
casing.
2. Changing Gas Control Inlet. You may want to change direction of gas inlet elbow
on gas control. Gas control is shipped for right side gas entry. If you need top entry, remove the fitting. If you need left side gas entry, rotate the fitting 180 degrees.
18
a. Use 9/64" Hex Allen wrench to remove tour
screws. Check that O-ring is in bottom of gas inlet elbow. Rotate elbow to desired position.
WARNINGi Provide furnace with ita own separate elec
trical circuit, means of circuit protection and electrical disconnect switch. Follow current National Electrical Code ANSI/NFPA 70 and state and local codes. Failure to pro vide these shut-off means could cause electrical shock or fire, resulting In damage, Injury or death.
install proper electrical grounding by attaching grounding source to green wire conductor in furnace junction box. Fol low current National Electrical Code ANSI/NFPA 70 and local codes.
WARNINGS Furnace must have proper electrical ground.
Failure to provide a proper electrical ground could cause electrical shock or fire, resulting In damage. Injury or death.
fICTION 13 — FOLLOWING FIELD WIRING DIAGRAM
HEATING COOUNG
THERMOSTAT MODEL
b. Alternately tighten tour screws to 45 inch pounds
to form a gas tight seal.
c. Use a commercial soap solution made to detect
leaks and check all gas piping connections. Bubbles indicate gas leakage. Seal all leaks be
fore proceeding.
WARNINOi Never use an open flame to
check for gas leaks. If a leak does exist, a
fire or explosion could occur, resulting In
damage, Injury or death.
3. Allowing tor Electronic Air Cleaners.
Some large electronic air cleaners will interfere with incoming gas line. Install air cleaner on opposite fur nace side from gas entry or route gas pipe over top of air cleaner through one of alternate knockouts.
SICTION 12 —
INSTALLING ILICTRICAL WIRING.
Equipment Needed: Save time by getting these tools before
you start: Item number(s) 2 listed in Section 10.
Select a location for room thermostat that is away from sup
ply and return air registers, on draft-free interior wall, and not
near lights, television, direct sunlight, or other heat sources. Install thermostat following field wiring diagram in Section
13. Use electrical wiring that meets current National Electrical Code ANSI/NFPA 70 and local codes. Use Type T (63 de grees C rise) wire or equivalent. See Section 30 for code information.
TO 115V 1 PH 60 H2
POWR SUPPLY PER
LOCAL CODES
FIELD WIRING DIAGRAM
FIGURE 21
NOTE: When replacing original wire, use same type, color, or equivalent wire. Remember to renumber wire ends.
SECTION 14 — ADJUSTING ROOM THERMOSTAT HEAT ANTICIPATOR
Equipment Needed: Save time by getting these tools before you start: Item number(s)5,17 and 18 listed in Section 10.
Wire system using field wiring diagram in Section 13.
19
Loading...
+ 49 hidden pages