1.5 to 6 Ton (18,300 to 67,000 Btuh)
Left Side Control Panel
The Bard Wall-Mount Air Conditioner with Left Side Control Panel is
designed to provide complete service access (i.e. compressor, electric heat
strip and electrical controls) when two units are mounted side by side with
minimal space between. The left side unit is the ideal product for
telecommunication and over-the-road medical and communication vans
requiring two wall-mount air conditioners be mounted side by side by using
a WL (left side access) unit and a WA (right side access) unit on the same
building. Factory or field installed accessories are also available to meet
specific job requirements.
Engineered Features
Aluminum Finned Copper Coils:
Grooved tubing and enhanced
louvered fin for maximum heat transfer
and energy efficiency.
Twin Blowers:
Move air quietly. Most models feature
multispeed blower motors providing
airflow adjustment for high and low
static operation. Motor overload
protection is standard on all models.
Air Conditioner Compressor:
Reciprocating compressors with
crankcase heater and dual discharge
muffler are standard on 1.5 and 2 ton
models.
Scroll Compressors eliminate need for
crankcase heater. Standard on 2.5 to
5 ton, and available on 2 ton models.
Phase Rotation Monitor:
Standard on all 3 phase scroll
compressors. Protects against reverse
rotation if power supply is not properly
connected. Not required on
reciprocating compressors.
Galvanized 20 Gauge Zinc Coated
Steel Cabinet:
Cleaned, rinsed, sealed and dried
before the polyurethane primer is
applied. The cabinet is handsomely
finished with a baked on textured
enamel, which allows it to withstand
1000 hours of salt spray tests per
ASTM B117-03.
Electrical Components:
Are easily accessible for routine
inspection and maintenance through a
left side, service panel opening.
Features a lockable, hinged access
cover to the circuit breaker or pull
disconnect switch.
Electric Heat Strips:
Features an automatic limit and
thermal cut-off safety control. Heater
packages can be factory installed for
all 1.5 through 6 ton models.
One Inch, Disposable Air Filters:
Are standard equipment. Optional one
inch washable filters available and filter
racks permit the addition of 2" pleated
filter. Factory or field installed.
Built-in Circuit Breakers:
Standard on all single (230/208 volt) and
three phase (230/208 volt) equipment.
Toggle disconnects are standard on all
three phase (460 volt) equipment.
Slope Top:
Standard feature for water run-off.
Top Rain Flashing:
Standard feature on all models.
Full Length Mounting Brackets:
Built into cabinet for improved
appearance and easy installation.
NOTE: Bottom mounting bracket
included to assist in installation.
Auto-Reset High Pressure Switch:
Built-in lock-out circuit resets from the
room thermostat. Provides commercial
quality protection to the compressor.
Auto-Reset Low Pressure Switch:
Built-in lock-out circuit and low pressure
timed bypass circuit. Resets from room
thermostat.
Compressor Control Module:
Built-in off-delay timer adjustable from 30
second to 5-minutes. 2-minute on-delay
if power interrupt. 120-second bypass for
low pressure control, and both soft and
manual lockouts for high and low
pressure controls. Alarm output for alarm
relay.
Low Ambient Control:
Permits cooling operation down to 0°F
outdoor ambient.
Alarm Relay:
Dry contacts for remote alarm capability
on manual high or low pressure controls.
MEA# 357-93-E
Ventilation System Packages
All packages are designed
to meet your specific
ventilation requirements
utilizing one of five
ventilation options for the
product. The ventilation
package is mounted within
the unit eliminating the need
for an exterior mounted
hood or damper assembly
on the unit. All assemblies
can be factory installed,
installed in the field at time
of installation or as a retrofit
system after installation.
Standard - Barometric
Fresh Air Damper
Optional - Motorized
Fresh Air Damper
Optional - Blank off Plate
Optional - Commercial
Room Ventilator with Exhaust
• CRV - Spring Return
• CRVP - Power Return
Optional - Economizer w/Exhaust
• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2004.
• Certified to ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
• Commercial Product - Not intended for Residential application.
1 Capacity is certified in accordance with ARI Standard 390-2003 and tested in accordance with ARI Standard 210/240-2003.
2 EER = Energy Efficiency Ratio and is certified in accordance with ARI Standard 390-2003.
3 SEER = Seasonal Energy Efficiency Ratio and is tested in accordance with ARI Standard 210/240-2003.
All ratings based on fresh air intake being 100% closed (no outside air introduction).
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements.
All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the
factory, or field-installed at a later date.
BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD
The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service
door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the
air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and
closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into
the building and can be easily locked closed if required.
Barometric Fresh Air Damper
Motorized Fresh Air Damper
Commercial Room Ventilator
BLANK OFF PLATE - BOP OPTIONAL
A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any
outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not
required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air,
up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed
with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered
open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower
operation or can be field connected to be managed based on building occupancy.
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require
separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing
dampers in the return air grille may be required to achieve specified amount of outdoor air intake.
COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside
ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings.
It includes a built-in exhaust air damper.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by
providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control
the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field
controlled based on room occupancy. Two versions available (except on 1.5 and 2-ton models). The CRV and
CRVS are power open - spring return on power loss, and CRVP is power open and power return. Complies with
ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.
ECONOMIZER - EIFM OPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be
introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and
settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide
“free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running
the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
Economizer
Standard Features:
• One Piece Construction - Easy to install with no mechanical linkage adjustment required.
• Exhaust Air Damper - Built in with positive closed position. Provides exhaust air capability to prevent
pressurization of tight buildings.
• Actuator Motor - 24 volt, power open, spring return with built in torque limiting switch.
• Proportioning Type Control - for maximum “free cooling” economy and comfort.
• Moisture Eliminator & Prefilter - permanent, washable aluminum construction
• Enthalpy Control - adjustable to monitor outdoor temperature and humidity.
• Minimum Position Potentiometer - adjustable to control minimum damper blade position for ventilation
purposes.
• Mixed Air Sensor - to monitor outside and return air to automatically modulate damper position.
Manufactured under U.S. Patent Nos. 5,485,878; 5,301,744; 5,002,116; 4,924,934; 4,875,520; 4,825,936
Form No.S3279-206
SupersedesS3279-106
Page3 of 12
Electrical Specifications
tiucriCelgniStiucriClauD
detaR
ledoM
Z0A-281LW
50A
80A
01A
Z0A-242LW
50A
80A
01A
Z0B-242LW
60B
Z0A-352LW
50A
80A
01A
Z0B-352LW
60B
Z0A-203LW
50A
80A
01A
51A
Z0B-203LW
90B
51B
Z0C-203LW
90C
51C
Z0A-273LW
50A
01A
51A
Z0B-273LW
90B
51B
Z0C-273LW
90C
51C
Z0A-324LW
50A
01A
51A
Z0B-324LW
90B
51B
Z0C-324LW
90C
51C
Z0A-484LW
50A
01A
51A
Z0B-484LW
90B
51B
Z0C-484LW
90C
51C
Z0A-206LW
50A
01A
51A
Z0B-206LW
90B
51B
Z0C-206LW
90C
51C
Z0A-207LW
50A
01A
51A
Z0B-107LW
90B
51B
Z0C-107LW
90C
51C
stloV
esahPdna
1-802/032
1-802/032
3-802/032
1-802/032
3-802/032
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
3muminiM
dleiF.oN
rewoP
stiucriC
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2ro1
1
1
1
1
1
1
1
1
1
2ro1
1
1
1
1
1
1
1
1
1
2ro1
1
1
1
1
1
1
1
1
1
2ro1
1
1
1
1
1
1
1
1
1
2ro1
1
1
1
1
1
1
1
1
1
2ro1
1
1
1
1
1
1
1mumixaM
tiucriC
yticapmA
61
03
54
65
71
03
54
65
31
22
81
03
54
65
41
22
42
13
74
75
38
71
23
05
01
71
62
82
23
85
48
02
33
15
11
71
62
63
63
95
58
52
43
25
31
71
62
83
83
95
58
42
43
25
21
71
62
44
44
95
58
23
43
25
61
71
62
84
84
95
58
63
63
25
71
71
62
02
03
54
06
02
03
54
06
51
52
52
03
54
06
02
52
53
53
05
06
09
02
53
05
51
02
03
53
53
06
09
52
5
3
06
51
02
03
05
05
06
09
53
53
06
51
02
03
05
05
06
09
53
3
5
06
51
02
03
06
06
06
09
54
54
06
02
02
03
06
06
06
09
05
05
06
52
52
03
2dleiF
esuFlanretxE
.rkrB.tkCro
8
6
8
6
8
6
8
8
8
6
4
8
8
8
8
6
4
8
6
8
8
6
4
8
8
6
8
8
6
4
8
8
6
8
8
6
4
8
8
6
8
8
6
4
8
8
6
2dnuorG
rewoP
eziSeriW
21
01
21
01
41
01
01
01
21
01
21
41
21
01
01
41
01
01
41
21
01
41
21
01
21
21
01
21
21
01
eriW
21
01
01
01
21
01
01
01
21
01
01
01
01
01
21
01
01
01
01
01
8
21
01
01
41
21
01
01
01
01
8756206036010101
01
01
01
41
01
01
01
01
01
8
01
01
01
41
21
01
01
01
01
8956206036010101
01
01
01
41
21
01
01
01
01
8
01
01
01
21
21
01
01
01
01
8
01
01
01
21
21
01
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (lastest version), Article 310
for power conductor sizing.
Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310
regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with
the National Electrical Code and all local codes.
3muminiM
tiucriC
A.tkCB.tkCA.tkCB.tkCA.tkCB.tkCA.tkCB.tkC
756206036010101
956206036010101
956206036010101
956206036010101
1mumixaM
yticapmA
2dleiF
esuFlanretxE
.rkrB.tkCro
rewoP
eziSeriW
2dnuorG
eziSeriW
Form No.S3279-206
Supersedes S3279-106
Page4 of 12
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.