3 ISM Radio................................................................................................................................................................6
3.1 ISM Radio Board (Modbus Slave ID 1) ..............................................................................................................................6
3.1.1 DIP Switch Settings for the MultiHop HE5 Board Module.....................................................................................7
3.2 Binding the ISM Radio of a DXM150-Sx Wireless Modbus Slave .................................................................................... 8
4 I/O Base Board for the DXM150-S1 Model.............................................................................................................9
4.1.1 DIP Switches for the I/O Board............................................................................................................................ 10
4.2 Applying Power to the DXM150-Sx Wireless Modbus Slave...........................................................................................10
4.2.1 Supplying Power from a Solar Panel....................................................................................................................10
4.2.2 Connecting a Battery to the DXM Modbus Slave................................................................................................ 11
4.3 Working with Solar Power ...............................................................................................................................................12
4.3.1 Setting the DXM Modbus Slave for Solar Power ................................................................................................ 12
4.3.2 Solar Components .............................................................................................................................................. 12
4.3.3 Recommended Solar
4.3.4 Monitoring Solar Operation ................................................................................................................................. 14
4.4 Connecting the Communication Pins ..............................................................................................................................14
4.5 Inputs and Outputs...........................................................................................................................................................15
4.6 Setting the Modbus Slave ID on the I/O Base Board.......................................................................................................21
5.1.1 DIP Switches for the I/O Board............................................................................................................................ 24
5.2.1 Supplying Power from a Solar Panel....................................................................................................................25
5.2.2 Connecting a Battery to the DXM Modbus Slave................................................................................................ 26
5.3 Working with Solar Power ...............................................................................................................................................26
5.3.1 Setting the DXM Modbus Slave for Solar Power ................................................................................................ 26
5.3.2 Solar Components .............................................................................................................................................. 26
5.3.3 Recommended Solar
5.3.4 Monitoring Solar Operation ................................................................................................................................. 28
5.4 Connecting the Communication Pins ..............................................................................................................................28
5.5 Inputs and Outputs...........................................................................................................................................................29
5.6 Setting the Modbus Slave ID on the I/O Base Board.......................................................................................................35
9 Additional Information .......................................................................................................................................... 40
9.1 DXM150 Documentation List .......................................................................................................................................... 40
9.2 DXM Modbus Slave Support Policy ................................................................................................................................40
9.2.2 Website Information ............................................................................................................................................ 40
1.1 DXM150-Sx Wireless Modbus Slave System Overview
Banner's DXM Logic Controller integrates Banner's wireless radio and local I/O for a remote I/O device.
Inputs/Outputs—On-board universal and programmable I/O
ports connect to local sensors, indicators, and control
equipment.
• Universal Inputs
• Discrete outputs
• Courtesy power
• Switch power
• Battery backup
• Solar controller
Connectivity—The integrated Sure Cross® wireless radio enables Modbus connectivity to remote sensors, indicators, and
control equipment.
Wired Connectivity
Field Bus: Modbus RS-485 Master
Wireless Connectivity
Sure Cross MultiHop 900 MHz, or MultiHop 2.4 GHz
1.2 DXM Configuration Tool Overview
The DXM
creating an XML file that is transferred to the DXM Modbus Slave using
a USB or Ethernet connection. The DXM Modbus Slave can also
receive the XML configurationfile from a Web server using a cellular or
Ethernet connection.
This
operation. The wireless network devices are a separate configurable
system. Use the DX80 User Configuration Tool (UCT) to configure the
internal DX80 wireless Gateway and the attached wireless Nodes. Use
the MultiHop
MultiHop device.
All tools can be connected to the DXM Modbus Slave using a USB
cable or an Ethernet connection.
Configuration Tool configures the DXM Modbus Slave by
configuration file governs all aspects of the DXM Modbus Slave
Configuration Tool (MCT) if the internal radio is a
4www.bannerengineering.com - Tel: +1.763.544.3164
Page 5
DXM150 I/O Board
MultiHop
Radio Board
DXM150-Sx Wireless Modbus Slave
2 DXM150-Sx Hardware Overview
2.1 DXM Hardware
The DXM Modbus Slave can have multiple configurations. The DXM Modbus Slave will have a model number label on the
housing. Use the model number and model table above to identify which boards are included in the controller.
When opening the DXM Modbus Slave, follow proper ESD grounding procedures. Refer to the ESD warning in the
appendix.
Configuration Overview
The DXM Modbus Slave I/O base board provides connections for all inputs, outputs and power. The base board also
contains a 12 V solar controller that accepts connections to a solar panel and SLA battery. The battery connection can also
be used with line power to provide a battery backup in case of line power outages.
The ISM radio
side with the SMA antenna connectors. Connect the U.FL cable from the ISM radio U.FL to the right side U.FL connector.
The ISM radio boards are available with either a 900 MHz radio or a 2.4 GHz radio.
fits on the base board in the parallel sockets. Install the ISM radio so the U.FL antenna connection is to the
www.bannerengineering.com - Tel: +1.763.544.31645
Page 6
1
1
ON
ON
A
D1
B
C
D2
234
234
DXM150-Sx Wireless Modbus Slave
3 ISM Radio
3.1 ISM Radio Board (Modbus Slave ID 1)
The ISM embedded radio boards are available in either DX80 MultiHop or DX80 Performance.
The DX80 MultiHop architecture creates a tree network with a Master radio and one or more Repeater/Slave devices. The
MultiHop architecture is suited for networks requiring repeater devices to provide extended range or obstacle avoidance.
MultiHop ISM radio devices are
• DXMxxx-xxR2 - MultiHop 900 MHz
• DXMxxx-xxR4 - MultiHop 2.4 GHz
• DXMxxx-xxR5 - MultiHop 900 MHz, 100 mW
• DXMxxx-xxR9 - MultiHop 900 MHz, (Australia)
The DX80 Performance architecture is a star-based architecture with one Gateway radio and 1 to 47 Node devices. The
Nodes communicate with the Gateway in a time slot method that is very predictable. DX80 Performance Gateway ISM radio
devices are
The settings outlined below are specific for the DXM Modbus Slave. Not all selections are possible with the DXM Modbus
Slave.
defined with R2, R4, and R5 in the model number.
Plug the ISM radio into the I/O base board with the U.FL
antenna connector closest to the SMA connectors.
A - Antenna connector
B - Button
C - LED
D1 - DIP switches
D2 - DIP Switches
Button Operation
For DXM models without a LCD display, use the button (B) to bind the ISM radio. For models with a LCD display,
use the ISM menu to bind the radio.
LED Operation
The LED located on the ISM radio module indicates power and communications traffic.
• Solid green DX80 ISM radio LED: Indicates power.
• Flashing green MultiHop ISM radio LED indicates operation.
• Red and green combined: Communications traffic and binding.
ISM board LED operations also display on the LED on the right side of the I/O base board.
6www.bannerengineering.com - Tel: +1.763.544.3164
Page 7
DXM150-Sx Wireless Modbus Slave
3.1.1 DIP Switch Settings for the MultiHop HE5 Board Module
D1 SwitchesD2 Switches
Device Settings12341234
Serial line baud rate 19200 OR User defined receiver
slots
Serial line baud rate 38400 OR 32 receiver slotsOFFON
Serial line baud rate 9600 OR 128 receiver slotsONOFF
Serial line baud rate Custom OR 4 receiver slotsONON
Parity: NoneOFF*OFF*
Parity: EvenOFFON
Parity: OddONOFF
Disable serial (low power mode) and enable the receiver
slots select for switches 1-2
Transmit power
900 MHz radios: 1.00 Watt (30 dBm)
2.4 GHz radios: 0.065 Watts (18 dBm) and 60 ms
frame
Transmit power
900 MHz radios: 0.25 Watts (24 dBm)
2.4 GHz radios: 0.065 Watts (18 dBm) and 40 ms
frame
Application mode: ModbusOFF*
Application mode: TransparentON
MultiHop radio setting: RepeaterOFF*OFF*
MultiHop radio setting: MasterOFFON
MultiHop radio setting: SlaveONOFF
MultiHop radio setting: ReservedONON
OFF*OFF*
ONON
OFF*
ON
* Default configuration
Application Mode
The MultiHop radio operates in either Modbus mode or transparent mode. Use the internal DIP switches to select the mode
of operation. All MultiHop radios within a wireless network must be in the same mode.
Modbus mode uses the Modbus protocol for routing packets. In Modbus mode, a routing table is stored in each parent
device to optimize the radio
traffic. This allows for point to point communication in a multiple data radio network and
acknowledgement/retry of radio packets. To access a radio's I/O, the radios must be running in Modbus mode.
In transparent application mode, all incoming packets are stored, then broadcast to all connected data radios. The data
communication is packet based and not
specific to any protocol. The application layer is responsible for data integrity. For
one to one data radios it is possible to enable broadcast acknowledgement of the data packets to provide better
throughput. In transparent mode, there is no access to the radio's I/O.
Baud Rate and Parity
The baud rate (bits per second) is the data transmission rate between the device and whatever it is physically wired to. Set
the parity to match the parity of the device you are wired to.
Disable Serial
If the local serial connection is not needed, disable it to reduce the power consumption of a data radio powered from the
solar assembly or from batteries. All radio communications remain operational.
Transmit Power Levels/Frame Size
The 900 MHz data radios can be operated at 1 watt (30 dBm) or 0.250 watt (24 dBm). For most models, the default transmit
power is 1 watt.
www.bannerengineering.com - Tel: +1.763.544.31647
Page 8
DXM150-Sx Wireless Modbus Slave
For 2.4 GHz radios, the transmit power is fixed at 0.065 watt (18 dBm) and DIP switch 5 is used to set the frame timing. The
default position (OFF) sets the frame timing to 60 milliseconds. To increase throughput, set the frame timing to 40
milliseconds.
Prior to date code 15341 and radio firmware version 3.6, the frame timing was 40 ms (OFF) or 20 ms (ON).
3.2 Binding the ISM Radio of a DXM150-Sx Wireless Modbus Slave
A DXM150-Sx Wireless Modbus Slave (model DXM1x0-S*R2) contains two boards: a MultiHop ISM radio and an I/O base
board. Each board is a separate Modbus device.
• The ISM radio is not required to have a Modbus ID because there are no registers to manage.
• The I/O board must have a Modbus ID to access the I/O register data and
To bind the DXM150-Sx Wireless Modbus Slave (as either a repeater or slave radio) to its master radio, follow the binding
instructions. If the binding instructions are not included in the master radio datasheet, refer to the MultiHop Quick Start
Guide (p/n
The ISM radio board's Modbus ID is assigned from the master radio during binding using the master radio's rotary dials or
the DXM Controller's LCD Binding menu. For example, if the master's binding number is 25, the DXM Slave ISM radio's
Modbus ID is set to 25. To reduce the number of Modbus IDs used, set the ISM radio Modbus ID to 01.
By default, the I/O board's Modbus ID is set to 11. To change the Modbus ID, use the I/O board DIP switches. For
applications requiring Modbus IDs outside the range of the DIP switches, write a Modbus ID to a Modbus register on the I/O
board.
Use the MultiHop
Modbus Slave, only the ISM radio displays on the Network View screen. The Modbus ID of the I/O board is a separate
device that is not a part of the radio network. Although the I/O board does not show up in the Network View, it is accessible
when using the Register View functions.
152653
) or Instruction Manual (p/n
Configuration Tool to display and configure a MultiHop radio network. With the DXM150-Sx Wireless
151317
).
configuration data.
8www.bannerengineering.com - Tel: +1.763.544.3164
Page 9
ON
1
A
B
D
C
E
F
J
L
L
G1
H
G2
G3
1
24
25
48
A
B
K
DXM150-Sx Wireless Modbus Slave
4 I/O Base Board for the DXM150-S1 Model
4.1 Board Connections
Figure 1. Board Connections
1NC17Input 2B33 Analog Output 1 (0 to 10 V)
212 to 30 V dc or solar power in (+)18Ground34 Ground
3Ground19Output 1 Normally Open35 PWR Out - Jumper
Analog Output Characteristics Jumpers
(Jumper 1 sets analog out 1, jumper 2 sets
analog out 2)
B Not UsedFRadio Binding ButtonHISM Radio Connection
C Radio LEDG1 Not UsedJModbus Slave ID DIP Switches
D Radio Module AntennaG2 Not UsedK Rotary Dials
LSAM4 Processor Board Connection
www.bannerengineering.com - Tel: +1.763.544.31649
Page 10
DXM150-Sx Wireless Modbus Slave
4.1.1 DIP Switches for the I/O Board
The DXM150-Sx Wireless Modbus Slave I/O board DIP switches are set from the factory to Modbus Slave ID 11. For more
information, refer to
Setting the Modbus Slave ID on the I/O Base Board
.
4.1.2 I/O Board Jumpers
Hardware jumpers on the DXM I/O board allow the user to select alternative pin operations. Turn the power off to the device
before changing jumper positions.
JumperFunctionPositions
ECourtesy power outputJumper 2 is the power jumper for pin 45. Jumper 1 is the power jumper for pin 35.
• The pin 45 jumper selects 2.7 V when in the "a" position and 12 V battery in the
"b" position.
• The pin 35 jumper selects 4.2 V when in the "a" position and device power on
pin 2 in the "b" position.
G1RS-485 Modbus Slave or
RS-232 Flow Control
G2Generic RS-232 Serial Port or
CAN Serial Port
G3Analog output characteristics
for AO2 (pin 32) and AO1 (pin
33)
Defines the operation of pins 11 and 12. Set the jumpers to use pins 11 and 12 as a
secondary Modbus RS-485 slave port or flow control pins for the RS-232 port. Both
jumpers must be set to the same operation, RS-485 Modbus Slave or Flow control.
The default setting is RS-485.
Defines the operation of pins 9 and 10. Set the jumpers to use pins 9 and 10 as a CAN
serial port or a generic RS-232 serial port. Both jumpers must be set to the same
operation, CAN or RS232.
The default setting is CAN serial port.
Defines current (0–20 mA) or voltage (0–10 V) for analog output 1 and 2.
By default, current (0–20 mA) is selected using jumpers 1 and 2 and registers 4008 and
4028 contain a value of 2.
To select voltage (0–10 V) for output Aout1, set jumper 1 in the voltage position (V) and
set Modbus register 4008 on the I/O board (SID 200) to 3.
To select voltage (0–10 V) for output Aout2, set jumper 2 in the voltage position (V) and
set Modbus register 4028 on the I/O board (SID 200) to 3.
4.2 Applying Power to the DXM150-Sx Wireless Modbus Slave
Apply power to the DXM150-Sx Wireless Modbus Slave using either 12 to 30 V dc or a 12 V dc solar panel and 12 V sealed
lead acid battery.
PinDescription
Pin 1No connection
Pin 212 to 30 V dc input (+) or solar panel connection (+)
Pins 3, 5, 8, 13, 18, 31, 34,
36, 41, 44, 48
Pin 4Solar or backup battery positive input. Battery voltage must be less than 15 V dc. Use only a sealed lead acid (SLA)
Pin 35, Pin 45These outputs are controlled by hardware jumpers.
4.2.1 Supplying Power from a Solar Panel
To power the DXM150-Sx Wireless Modbus Slave from a 12 V dc solar panel, connect the solar panel to power pins 2(+)
and 3(-). Connect a 12 V dc sealed lead acid (SLA) rechargeable battery to pins 4(+) and 5(-).
The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc power to recharge the
battery. If the incoming power is from a solar panel, you must change the charging algorithm.
Main logic ground for the DXM150-Sx Wireless Modbus Slave
battery.
Jumper 2 is the power jumper for pin 45. Jumper 1 is the power jumper for pin 35. Refer to the wiring board for more
information.
•The pin 45 jumper selects 2.7 V when in the "a" position and 12 V battery in the "b" position.
•The pin 35 jumper selects 4.2 V when in the "a" position and device power on pin 2 in the "b" position.
To change the charging algorithm from the menu system:
1. From the DXM Modbus Slave LCD menu, navigate to System Config > I/O Board > Charger.
2. Select Solar for solar panel configurations.
To change the charging algorithm by writing to Modbus register 6071 on the I/O base board (Slave ID 11):
1. Write a 0 to select the solar power charging algorithm.
Modbus Slave IDModbus RegisterDescription
11 *6071Battery backup charging algorithm.
0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)
The following power operating characteristics are stored in Modbus registers.
Battery voltage
If no battery is present, the value in this register is less than 5 V. If the value in this register is greater than the
incoming voltage register, the battery is powering the system.
Battery charging current
The charging algorithm charges the battery when the incoming voltage register value is greater than the battery
voltage register value. This registers shows the charging current in milliamps.
Incoming supply voltage
The incoming power can be from a solar panel or from a power supply. The battery is charging when the incoming
voltage register value is greater than the battery voltage register value. The battery is powering the system when
the incoming voltage register value is less than the battery voltage register value.
On-board thermistor temperature
This register stores the on-board thermistor reading in tenths of degrees C, this is not a calibrated input: divide by
10 to calculate the temperature in degrees C. For calibrated temperature inputs,
define one of the universal inputs
as a temperature input.
Modbus Slave ID
11 *6081Battery voltage (mV)
Modbus RegisterDescription
6082Battery charging current (mA)
6083Incoming supply voltage (mV) (solar or power supply)
6084On-board thermistor temperature (⁰C)
* The Slave ID for the base board is set at the factory. This may be changed using the base board DIP switch settings.
4.2.2 Connecting a Battery to the DXM Modbus Slave
When attaching a battery to the DXM Modbus Slave as a backup battery or as a solar battery, verify the charging algorithm
is set properly. The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc to
recharge the battery.
The charging algorithm is designed to work with a sealed lead acid (SLA) battery only.
• When using 12 to 30 V dc, connect the 12 to 30 V dc + to pin 2 and connect the ground to pin 3.
• When using main dc power with a back up battery (default
(+) and to pin 3 (-). Connect the 12 V sealed lead acid battery to pin 4 (+) and pin 5 (-). The incoming main power
must be 15 to 30 V dc to charge the battery.
• When using a solar panel, connect the solar panel output to pin 2 and connect the ground to pin 3. Connect the 12
V dc SLA battery to pin 4 (+) and pin 5 (-). To change the charging algorithm, refer to
Panel
on page 10.
The battery charging algorithm defaults to a battery backup
the battery charging algorithm.
1. From the DXM Modbus Slave LCD menu navigate to Setting
2. Select Solar for solar panel configurations or DC for battery backup configurations.
configuration), connect the incoming main power pin 2
Supplying Power from a Solar
configuration. To charge the battery from a solar panel, change
0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)
* The Modbus Slave ID for the base board is set at the factory and may be changed using the base board DIP switch
settings.
4.3 Working with Solar Power
A reliable solar system requires careful planning and monitoring to size the components correctly. The recommendations
provided are for the DXM Modbus Slave system as an autonomous system.
Adding extra components increases the power requirements and likely requires increasing the solar system components.
Depending upon the geographical location, the size of the solar panel and battery may vary.
4.3.1 Setting the DXM Modbus Slave for Solar Power
By default, the DXM Modbus Slave is set from the factory to charge a backup battery from a line power source. Use the
LCD menu on the front of the DXM Modbus Slave to change the charging algorithm to solar power.
Go to System
For DXM devices without an LCD, adjust the I/O board Modbus register 6071. Set the register to 0 to select battery
charging from a solar panel, and set to 1 to select battery charging from incoming 12 to 30 V dc supply.
Here are a few DXM configuration tips to help minimize the power consumption (may not apply to all models).
• If Ethernet is not being used, save up to 25% of the consumed power by disabling Ethernet. Set DIP switch 1 to the
• Instead of powering external devices all the time, take advantage of the switched power mechanisms to turn off
• Minimize the number of cellular transactions and the amount of data pushed across the cellular modem.
Config > I/O Board > Charger. Use the up/down arrows to select Solar.
ON position on the processor board then reboot.
devices when possible.
4.3.2 Solar Components
The components of a solar system include the battery and the solar panel.
Battery
The DXM solar controller is designed to use a 12 V lead acid battery. The characteristics of a solar system require the
battery to be of a certain type. There are basically two types of lead acid batteries:
• SLI batteries (Starting Lights Ignition) designed for quick bursts of energy, like starting engines
• Deep Cycle batteries - greater long-term energy delivery. This is the best choice for a solar battery.
Since a solar system charges and discharges daily, a deep cycle battery is the best choice. There are different versions of a
lead acid battery: wet cell
Wet cell batteries are the original type of rechargeable battery and come in two styles, serviceable and maintenance free.
Wet cell batteries typically require special attention to ventilation as well as periodic maintenance but are the lowest cost.
The gel cell and AGM battery are sealed batteries that cost more but store very well and do not tend to sulfate or degrade
as easily as a wet cell. Gel or AGM batteries are the safest lead acid batteries you can use.
Battery Capacity
(flooded), gel cell, and an AGM (absorbed glass mat).
Battery capacity is a function of the ambient temperature and the rate
of discharge. Depending upon the specific battery, a battery operating
at –30 °C can have as much as 40 percent less capacity than a battery
operating at 20 °C. Choose enough battery capacity based on your
geographical location.
A larger capacity battery typically lasts longer for a given solar
application because lead-acid batteries do not like deep cycling
(discharging a large percentage of its capacity). Depending upon the
battery, a battery discharging only 30 percent of its capacity before
recharging will have approximately 1100 charge/discharge cycles. The
same battery discharging 50 percent of its capacity will have
approximately 500 charge/discharge cycles. Discharging 100 percent
leaves the battery with only 200 charge/discharge cycles.
Batteries degrade over time based on discharge/charge cycles and
environmental conditions. Always monitor the battery system to obtain
the best performance of the solar powered system.
Use this as a guide to the approximate state of
charge and in determining when to apply
conservation measures.
Average Voltage Readings Relative to Battery
Change
State of Charge (%)Open Circuit Voltage
10013.0 or higher
7512.6
5012.1
2511.66
011.4 or less
Solar Panel
Banner solar panels come in two common sizes for the DXM Modbus Slave: 5 Watt and 20 Watt. Both panels are designed
to work with the DXM Modbus Slave but provide different charging characteristics. Use the 5 watt panel for light duty
operation and use the 20 watt panel when you require greater charging capabilities.
Solar PanelVoltageCurrentTypical DXM Configurations
5 Watt17 V0.29 ADXM slave controller, ISM radio, I/O base board
20 Watt21 V1 ADXM Controller with ISM radio and Cellular modem
Photovoltaic panels are very sensitive to shading. Unlike solar thermal panels, PV solar panels cannot tolerate shading from
a branch of a leafless tree or small amounts of snow in the corners of the panel. Because all cells are connected in a series
string, the weakest cell will bring down the other cells' power level.
Good quality solar panels will not degrade much from year to year, typically less than 1 percent .
Solar Panel Mounting
To capture the maximum amount of solar radiation throughout the year, mount a fixed solar panel to optimize the sun's
energy throughout the year. For the northern hemisphere, face the panel true south. For the southern hemisphere, face the
panel true north. If you are using a compass to orientate the panels, compensate for the difference between true north and
magnetic north. Magnetic declination varies across the globe.
A solar panel's average tilt from horizontal is at an angle equal to the latitude of the site location. For optimum performance,
adjust the tilt by plus 15 degrees in the winter or minus 15 degrees in the summer. For a
fixed panel with a consistent power
requirement throughout the year, adjust the tilt angle to optimize for the winter months: latitude plus 15 degrees. Although in
the summer months the angle may not be the most
efficient, there are more hours of solar energy available.
For sites with snow in the winter months, the increased angle helps to shed snow. A solar panel covered in snow produces
little or no power.
4.3.3 Recommended Solar
Configurations
These solar panel and battery combinations assume direct sunlight for two to three hours a day. Solar insolation maps
provide approximate sun energy for various locations. The depth of battery discharge is assumed to be 50 percent.
Solar panel and battery combinations for a
Solar PanelBattery Capacity
5 watt10 Ahr10 days25 mADXM Slave Controller - ISM radio and I/O base board
20 watt14 Ahr10 days30 mADXM Controller with ISM radio
DXM Modbus Slave system
1
Days of AutonomyDXM mADXM Controller
1
Battery capacity (amp hour) is standard amp rating taken for 20 hours. Battery capacity should be monitored for reliable system power and may
need to be increased for cold weather locations.
Solar panel and battery combinations for a DXM Modbus Slave system
Solar PanelBattery Capacity
20 watt20 Ahr10 days35 mADXM Controller with ISM radio and Cellular Modem
1
Days of AutonomyDXM mADXM Controller
4.3.4 Monitoring Solar Operation
The DXM solar controller provides Modbus registers that allow the user to monitor the state of the solar panel input voltage,
the battery voltage, the charging current, and the temperature in °C. The DXM Modbus Slave can be
the health of the charging system as well as send an alert message when the battery is too low.
The charts show a typical charging cycle, with each vertical grid representing about eight hours. The chart shows three
days of charging.
configured to monitor
Figure 2. Solar Panel Voltage (mV) -- Cloudy First Day
Figure 3. Battery Voltage (mV) - Cloudy First Day
4.4 Connecting the Communication Pins
The base board communications connection for external Modbus device uses the primary RS-485.
RS-485. The primary RS-485 bus is a common bus shared with the ISM radio board (Modbus Slave ID 1).
RS-232. The RS-232 bus is not currently
PinParameterDescription
Pin 6Primary RS-485 –Running Modbus protocol at 19.2k baud, use this bus to connect to other Modbus Slave devices.
Pin 7Primary RS-485 +
defined.
The DXM150-Sx Wireless Modbus Slave is a Modbus Master device on this RS-485 port.
Modbus Register 6101 = Baud Rate
0 = 19.2k
1 = 9600
2 = 38400
Modbus Register 6103 = Parity
0 = no parity
1 = odd?
2 = even?
1
Battery capacity (amp hour) is standard amp rating taken for 20 hours. Battery capacity should be monitored for reliable system power and may
need to be increased for cold weather locations.
Serial RS-232 connection. This bus must use a ground connection between devices to operate
correctly.
Not used
4.5 Inputs and Outputs
The I/O base board is a Modbus slave device that communicates using Modbus commands. Refer to the Modbus Registers
section for more descriptions of each Modbus register on the DXM150-Sx Wireless Modbus Slave.
4.5.1 Isolated Discrete Inputs
PinInputDescription
Pin 14Input 1A
Pin 15Input 1B
Pin 16Input 2A
Optically isolated AC input type, 0 to 12 to 30 V dc
Input to output isolation of 2.5 kV
Pin 17Input 2B
Synchronous Counters. An isolated input can be programmed to count the input signal transitions. When an input is
enabled as a counter, the counter value is stored into two 16-bit Modbus registers for a total count of 32-bits (unsigned). To
program an input to capture the edge transition counts, follow
Example: Configure Input 1 as a Synchronous Counter
on
page 18.
The counters are synchronous because the inputs are sampled at a 10 ms clock rate. The input logic does not detect rising
or falling edges, it samples the input every 10 ms to
find level changes. The input signals must be high or low for more than
10 ms or the input will not detect transitions. Because most signals are not perfect, a realistic limit for the synchronous
counter would be 30 to 40 Hz.
Universal inputs can also be
configured as a synchronous counter. See the Modbus register map for universal inputs and all
the register definitions. The procedure for creating a synchronous counter is the same as a isolated input with the addition
of changing the input type to PNP or NPN.
ON-State Saturation: Less than 0.7 V at 20 mA
ON Condition: Less than 0.7 V
OFF Condition: Open
4.5.4 Analog Outputs (DAC)
The following characteristics are configurable for each of the analog outputs.
Pin
Pin 33Analog Output 10 to 20 mA or 0 to 10 V dc output (I/O board jumper selectable)
Pin 32Analog Output 2
Parameters for Analog Output 1 start at 4001 through 4008. Parameters for Analog Output 2 start at 4021 through 4028.
Analog Output Type. The analog outputs may be configured as either 0 to 20 mA outputs (default) or 0 to 10 V outputs. To
change the analog output type change the hardware jumper position and write to the Modbus register that defines the
analog output type. For analog output 1, write to Modbus register 4008, for analog output 2 write to Modbus register 4028.
Write a value of 2 (default) to select 0 to 20 mA; write a value of 3 to select 0 to 10 V.
Default Output Conditions. Default output conditions/triggers are the conditions that drive outputs to
Example default output conditions include when radios are out of sync, when a device cycles power, or during a host
communication timeout.
OutputDescription
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
• 2952 Enable Default Communication Timeout. A “communication timeout" refers to the communication between any
Modbus master host and the DXM baseboard. Set this register to 1 to enable the default condition when the host
has not communicated with the DXM baseboard for the period of time defined by the Communication Default IO
Timeout.
• 2953 Communication Default I/O Timeout (100 ms/Count). This parameter
defines the host timeout period in 100
millisecond increments. If a host does not communicate within this timeout period, the device outputs are set to the
default values.
• 2954 Enable Default on Power Up. Setting this parameter to 1 sends the device outputs to their default condition
when the DXM baseboard is powered up. Set to 0 to disable this feature.
Default Output State. The Default Output State parameter represents the default condition of the analog output. When an
error condition exists, the outputs are set to this 16-bit user-defined output state. To define the error conditions for device
outputs, refer to the MultiHop default output parameters 2950-2954.
Enable Register Full Scale. Set to 1 to enable a linear range from 0 to 65535 for
specified input range. For a 4 to 20 mA
output, a value of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store readings in unit-specific
data. For example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA outputs),
values are stored as µA (micro Amps) and voltage values are stored as mV (millivolts).
Hold Last State Enable. Set the Hold Last State to 1 to set the output to its last known value before the error occurred. Set
this parameter to 0 to disable the Hold Last State and use the Default Output State setting during an error condition.
Maximum Analog Value. The Maximum Analog Value register stores the maximum allowed analog value. The specific units
of measure apply to the register value. For example, the register may contain 20000, for 20 mA, or for a voltage output the
register may contain 8000, for 8 volts.
Minimum Analog Value. The Minimum Analog Value register stores the minimum allowed analog value. The
specific units of
measure apply to register value. For example, the register may contain 4000, for 4 mA, or for a voltage output the register
may contain 2000, for 2 volts.
4.5.5 Universal Inputs
The universal inputs can be programmed to accept different types of inputs: discrete NPN/PNP, 0 to 20 mA analog, 0 to 10
V analog, 10k thermistor, potentiometer sense, bridge, and NPN raw fast. Use the DXM Configuration Tool tool to write to
the appropriate Modbus registers in the I/O board to
The universal inputs are treated as analog inputs. When the universal inputs are defined as mA, V, or temperature, use
Modbus registers to configure the operational characteristics of the inputs. These parameters are temperature conversion
type, enable full scale, threshold and hysteresis. See the Modbus register section for the parameter
When a universal input is configured as an NPN or PNP input type, it can be enabled to be a synchronous counter. Enable
the counter function by setting Modbus register 'Enable Rising' or 'Enable Falling' to 1. See
universal input register definitions.
Pin
Pin 47Universal Input 1Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to
Pin 46Universal Input 2
Pin 43Universal Input 3
Pin 42Universal Input 4
Pin 40Universal Input 5
Pin 39Universal Input 6
Pin 38Universal Input 7
Pin 37Universal Input 8
Univ. InputDescription
20 mA, or potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the
following values to the Input Type Modbus registers.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Thermistor Input. A thermistor input must use a 10k thermistor between ground and the universal input. The thermistor must
be a 10k NTC (Banner model number BWA-THERMISTOR-002) or equivalent. Select the temperature conversion of degrees
C (default) or degrees F by writing to the Modbus registers
Potentiometer Sense (DXM150 only). A potentiometer input is created from two inputs: a voltage source (pin 45) that
supplies a voltage to the potentiometer and an input sense (Potentiometer Sense) to read the resistance. Follow
Change Universal Input 8 to Read a Potentiometer Input
potentiometer input.
Potentiometer Input (DXM100 only). A potentiometer input is created from three inputs: a voltage source (pin 30) that
supplies 5 V to the potentiometer and two inputs set to voltage inputs to read the voltage across the potentiometer. See the
DXM technical note for setting up a potentiometer.
configure the input type.
definitions.
Modbus Registers
defined in
I/O Base Board
.
on page 18 to configure the DXM150 Controller for a
Bridge Input. The bridge input is not implemented yet.
NPN vs NPN Raw Fast. The difference between NPN and NPN Raw Fast is the amount of settling time given to the input.
Switch the input type to NPN if the input is not detecting a transition.
Example:
Configure Input 1 as a Synchronous Counter
1. Connect the DXM Modbus Slave to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Modbus Slave by selecting the Device > Connection Settings menu option. You may connect
using either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. In the Write Registers area, write Modbus register 4908 to 1 to enable counting on the rising edge of the input
signal.
8. Read Modbus registers 4910 and 4911 to get the 32-bit value of the count.
Example: Change Universal Input 2 to a 0 to 10 V dc Input
1. Connect the DXM Modbus Slave to the PC.
2. Launch the DXM
3. Connect to the DXM Modbus Slave by selecting the Device > Connection Settings menu option. You may connect
using either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Write a 3 to Modbus register 3326 on Modbus Slave ID 11 (I/O board).
8. Cycle power to the device.
9. Using the Register View tab, read register 3326 to verify it is set to 3.
Configuration Tool software.
Example: Change Analog Output 1 to a 0 to 10 V dc Output
1. Connect the DXM Modbus Slave to the PC.
2. Launch the DXM
Configuration Tool software.
3. Connect to the DXM Modbus Slave by selecting the Device > Connection Settings menu option. You may connect
using either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Set jumper 1 on the I/O base board to the 0 to 10 V position. Refer to the base board image for the analog output
jumper position.
8. Write a 3 to Modbus register 4008 on Modbus Slave ID 11 (I/O board).
9. Cycle power to the device.
10. Using the Register View tab, read register 4008 to verify it is set to 3.
Example: Change Universal Input 8 to Read a Potentiometer Input
Figure 4. Default jumper position
1. Launch the DXM Configuration Tool tool.
2. Click on the Register View tab on the left part of the page.
3. In the upper right part of the window select Modbus Registers using Modbus Slave ID radio button and enter
Modbus Slave ID 11.
4. To set universal input 8 as the sense, write Modbus register 3446 with 5 (Potentiometer Sense).
5. Verify the jumpers are still set to their default position. One jumper should be on pins 1 and 3 to get a 2.7 V source
voltage out pin 45. The default position of the other jumper is on pins 4 and 6.
6. Connect one potentiometer side to power output (pin 45), connect the tap point of the pot to universal input 8 (pin
37), and connect the other end of the pot to ground (pin 36).
4.5.6 Modbus Registers
The DXM MultiHop Modbus Slave device can have two Modbus Slave IDs: one for the MultiHop ISM radio (default 1) and
one for the I/O base (default to 11). All Modbus registers are defined as 16-bit Modbus Holding Registers. When connecting
additional Modbus slave devices, only use Modbus slave IDs 2 through 198.
High Register for Counter49104930495049704990501050305050
Low Register for Counter49114931495149714991501150315051
Enable Full Scale. Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA input, a value
of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store input readings in unit-specific data. For
example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA inputs), values are
stored as µA (micro Amps) and voltage values are stored as mV (millivolts).
Enable Rising/Falling. Use these registers to enable the universal input logic to count on a rising transition or a falling
transition. Write a one (1) to enable; write a zero (0) to disable.
High/Low Register for Counter. The low and high registers for the counter hold the 32-bit counter value. To erase the
counter, write zeroes to both registers. To preset a counter value, write that value to the appropriate register.
Hysteresis and Threshold. Threshold and hysteresis work together to establish the ON and OFF points of an analog input.
The threshold
ON point. Hysteresis
defines a trigger point or reporting threshold (ON point) for a sensor input. Setting a threshold establishes an
defines how far below the threshold the analog input is required to be before the input is considered
OFF. A typical hysteresis value is 10% to 20% of the unit’s range.
In the example shown, the input is considered on at 15 mA. To consider
the input off at 13 mA, set the hysteresis to 2 mA. The input will be
considered off when the value is 2 mA less than the threshold.
Input Type. Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to 20 mA, or
potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the following values to the Input Type
Modbus registers.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Temperature °C/°F. Set to 1 to represent temperature units in degrees Fahrenheit, and set to 0 (default) to represent
temperature units in degrees Celsius.
Universal Input Register Ranges
Register TypesUnitMinimum ValueMaximum Value
Discrete input/output01
Universal input 0 to 10 VmV010000 *
Universal input 0 to 20 mAµA020000 *
Universal input temperature (–40 °C to +85 °C)C or F, signed, in tenths of a degree–400850
* Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.
4.6 Setting the Modbus Slave ID on the I/O Base Board
Only DXM150-Sx and SxR2 Modbus Slave models require that the Modbus Slave ID to be adjusted on the I/O base board.
The DXM150-Sx Wireless Modbus Slave devices use DIP switch J and rotary dial K to set the Modbus slave ID. The device
can use a Modbus register 6804 in the I/O board to access the full range of Modbus Slave IDs.
On the DXM150-Sx Wireless Modbus Slave models, use rotary dial K to select the lower digit of the Modbus Slave ID.
4.6.1 DXM150-Sx Wireless Modbus Slave Models
DIP Switch location J defines the course group of Modbus Slave IDs. DIP Switch 4 must be set to ON for DXM1xx-Sx and
DXM1xx-SxR2 models.
Settings
Modbus Slave ID set to 11 through 19OFFOFF
Modbus Slave ID set to 20 through 29ONOFF
Modbus Slave ID set to 30 through 39OFFON
Modbus Slave ID set to 40 through 49ONON
Not Used-
Modbus Slave Configuration (S1 model only)
I2C Processor CommunicationOFF
2
1234
Location J DIP Switches
Rotary dial location K and DIP Switch location J set the Modbus Slave IDs.
DIP Switches JLocation K Rotary Dials — Position 0 through 9
120123456789
OFFOFFx
ONOFF20212223242526272829
OFFON30313233343536373839
ONON40414243444546474849
3
111213141516171819
ON
DXM150-Sx Wireless Modbus Slave Example
To set the DXM150-Sx Wireless Modbus Slave to a Modbus Slave ID of 25, set the following:
Location J DIP switches set to: 1= ON, 2=OFF
Rotary dial set to 5
The DIP switch sets the upper digit of the slave ID to 2 while the rotary dial sets the lower digit to 5.
4.6.2 Setting the DXM I/O Board Modbus Slave ID using Modbus Registers
Write to the I/O board's Modbus register 6804 to set the Modbus Slave ID to any valid Modbus Slave ID (1 through 245).
• For the DXM150-Sx Wireless Modbus Slave model, rotary dial K should be in the zero position to use the Modbus
register slave ID.
4.6.3 I/O Board Jumpers
Hardware jumpers on the DXM I/O board allow the user to select alternative pin operations. Turn the power off to the device
before you change jumper positions.
ECourtesy power outputJumper 2 is the power jumper for pin 45. Jumper 1 is the power jumper for pin 35.
• The pin 45 jumper selects 2.7 V when in the "a" position and 12 V battery in the
"b" position.
• The pin 35 jumper selects 4.2 V when in the "a" position and device power on
pin 2 in the "b" position.
G1Not UsedNot Used
G2Not UsedNot Used
G3Analog output characteristics
for AO2 (pin 32) and AO1 (pin
33)
Defines current (0–20 mA) or voltage (0–10 V) for analog output 1 and 2.
By default, current (0–20 mA) is selected using jumpers 1 and 2 and registers 4008 and
4028 contain a value of 2.
To select voltage (0–10 V) for output Aout1, set jumper 1 in the voltage position (V) and
set Modbus register 4008 on the I/O board to 3.
To select voltage (0–10 V) for output Aout2, set jumper 2 in the voltage position (V) and
Analog Output Characteristics Jumpers
(Jumper 1 sets analog out 1, jumper 2 sets
analog out 2)
Page 24
DXM150-Sx Wireless Modbus Slave
B Cellular AntennaFRadio Binding ButtonHISM Radio Connection
C Radio LEDG1RS-485 JumpersJModbus Slave ID DIP Switches
D Radio Module AntennaG2RS-232 JumpersKRotary Dials
LSAM4 Processor Board Connection
5.1.1 DIP Switches for the I/O Board
The DXM150-Sx Wireless Modbus Slave I/O board DIP switches are set from the factory to Modbus Slave ID 11. For more
information, refer to
Setting the Modbus Slave ID on the I/O Base Board
.
5.1.2 I/O Board Jumpers
Hardware jumpers on the DXM I/O board allow the user to select alternative pin operations. Turn the power off to the device
before changing jumper positions.
JumperFunctionPositions
ECourtesy power outputJumper 2 is the power jumper for pin 45. Jumper 1 is the power jumper for pin 35.
• The pin 45 jumper selects 2.7 V when in the "a" position and 12 V battery in the
"b" position.
• The pin 35 jumper selects 4.2 V when in the "a" position and device power on
pin 2 in the "b" position.
G1RS-485 Modbus Slave or
RS-232 Flow Control
G2Generic RS-232 Serial Port or
CAN Serial Port
G3Analog output characteristics
for AO2 (pin 32) and AO1 (pin
33)
Defines the operation of pins 11 and 12. Set the jumpers to use pins 11 and 12 as a
secondary Modbus RS-485 slave port or flow control pins for the RS-232 port. Both
jumpers must be set to the same operation, RS-485 Modbus Slave or Flow control.
The default setting is RS-485.
Defines the operation of pins 9 and 10. Set the jumpers to use pins 9 and 10 as a CAN
serial port or a generic RS-232 serial port. Both jumpers must be set to the same
operation, CAN or RS232.
The default setting is CAN serial port.
Defines current (0–20 mA) or voltage (0–10 V) for analog output 1 and 2.
By default, current (0–20 mA) is selected using jumpers 1 and 2 and registers 4008 and
4028 contain a value of 2.
To select voltage (0–10 V) for output Aout1, set jumper 1 in the voltage position (V) and
set Modbus register 4008 on the I/O board (SID 200) to 3.
To select voltage (0–10 V) for output Aout2, set jumper 2 in the voltage position (V) and
set Modbus register 4028 on the I/O board (SID 200) to 3.
5.2 Applying Power
Apply power to the DXM Modbus Slave using either 12 to 30 V dc or a 12 V dc solar panel and 12 V sealed lead acid
battery.
If the incoming voltage drops below 11.2 V dc, the cellular modem does not turn on and will not turn on until the voltage is
above 11.8 V dc. A text
voltage. If cellular operation stops because of voltage, it is logged in this file.
PinDescription
Pin 1No connection
Pin 212 to 30 V dc input (+) or solar panel connection (+)
Pins 3, 5, 8, 13, 18, 24, 25,
31, 34, 36, 41, 44, 48
Pin 4Solar or backup battery positive input. Battery voltage must be less than 15 V dc. Use only a sealed lead acid (SLA)
file (CmVMon.txt) on the internal micro SD card saves the periodic sampling of the incoming
Main logic ground for the DXM Modbus Slave
battery.
Page 25
DXM150-Sx Wireless Modbus Slave
PinDescription
Pin 35, Pin 45These outputs are controlled by hardware jumpers.
Jumper 2 is the power jumper for pin 45. Jumper 1 is the power jumper for pin 35. Refer to the wiring board for more
information.
•The pin 45 jumper selects 2.7 V when in the "a" position and 12 V battery in the "b" position.
•The pin 35 jumper selects 4.2 V when in the "a" position and device power on pin 2 in the "b" position.
Pin 23, Pin 26Courtesy power output from either the input power from pin 2 or the battery power from pin 4.
5.2.1 Supplying Power from a Solar Panel
To power the DXM150-Sx Wireless Modbus Slave from a 12 V dc solar panel, connect the solar panel to power pins 2(+)
and 3(-). Connect a 12 V dc sealed lead acid (SLA) rechargeable battery to pins 4(+) and 5(-).
The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc power to recharge the
battery. If the incoming power is from a solar panel, you must change the charging algorithm.
To change the charging algorithm from the menu system:
1. From the DXM Modbus Slave LCD menu, navigate to System
2. Select Solar for solar panel configurations.
To change the charging algorithm by writing to Modbus register 6071 on the I/O base board (Slave ID 11):
1. Write a 0 to select the solar power charging algorithm.
Modbus Slave IDModbus RegisterDescription
11 *6071Battery backup charging algorithm.
0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)
Config > I/O Board > Charger.
The following power operating characteristics are stored in Modbus registers.
Battery voltage
If no battery is present, the value in this register is less than 5 V. If the value in this register is greater than the
incoming voltage register, the battery is powering the system.
Battery charging current
The charging algorithm charges the battery when the incoming voltage register value is greater than the battery
voltage register value. This registers shows the charging current in milliamps.
Incoming supply voltage
The incoming power can be from a solar panel or from a power supply. The battery is charging when the incoming
voltage register value is greater than the battery voltage register value. The battery is powering the system when
the incoming voltage register value is less than the battery voltage register value.
On-board thermistor temperature
This register stores the on-board thermistor reading in tenths of degrees C, this is not a calibrated input: divide by
10 to calculate the temperature in degrees C. For calibrated temperature inputs,
define one of the universal inputs
as a temperature input.
Modbus Slave ID
11 *6081Battery voltage (mV)
Modbus RegisterDescription
6082Battery charging current (mA)
6083Incoming supply voltage (mV) (solar or power supply)
6084On-board thermistor temperature (⁰C)
* The Slave ID for the base board is set at the factory. This may be changed using the base board DIP switch settings.
5.2.2 Connecting a Battery to the DXM Modbus Slave
When attaching a battery to the DXM Modbus Slave as a backup battery or as a solar battery, verify the charging algorithm
is set properly. The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc to
recharge the battery.
The charging algorithm is designed to work with a sealed lead acid (SLA) battery only.
• When using 12 to 30 V dc, connect the 12 to 30 V dc + to pin 2 and connect the ground to pin 3.
• When using main dc power with a back up battery (default
(+) and to pin 3 (-). Connect the 12 V sealed lead acid battery to pin 4 (+) and pin 5 (-). The incoming main power
must be 15 to 30 V dc to charge the battery.
• When using a solar panel, connect the solar panel output to pin 2 and connect the ground to pin 3. Connect the 12
V dc SLA battery to pin 4 (+) and pin 5 (-). To change the charging algorithm, refer to
Panel
on page 10.
The battery charging algorithm defaults to a battery backup
the battery charging algorithm.
1. From the DXM Modbus Slave LCD menu navigate to Setting
2. Select Solar for solar panel configurations or DC for battery backup configurations.
Modbus Slave IDModbus RegisterDescription
11 *6071Battery backup charging algorithm.
0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)
configuration), connect the incoming main power pin 2
Supplying Power from a Solar
configuration. To charge the battery from a solar panel, change
Config > I/O Board > Charger.
* The Modbus Slave ID for the base board is set at the factory and may be changed using the base board DIP switch
settings.
5.3 Working with Solar Power
A reliable solar system requires careful planning and monitoring to size the components correctly. The recommendations
provided are for the DXM Modbus Slave system as an autonomous system.
Adding extra components increases the power requirements and likely requires increasing the solar system components.
Depending upon the geographical location, the size of the solar panel and battery may vary.
5.3.1 Setting the DXM Modbus Slave for Solar Power
By default, the DXM Modbus Slave is set from the factory to charge a backup battery from a line power source. Use the
LCD menu on the front of the DXM Modbus Slave to change the charging algorithm to solar power.
Go to System
For DXM devices without an LCD, adjust the I/O board Modbus register 6071. Set the register to 0 to select battery
charging from a solar panel, and set to 1 to select battery charging from incoming 12 to 30 V dc supply.
Here are a few DXM configuration tips to help minimize the power consumption (may not apply to all models).
• If Ethernet is not being used, save up to 25% of the consumed power by disabling Ethernet. Set DIP switch 1 to the
• Instead of powering external devices all the time, take advantage of the switched power mechanisms to turn off
• Minimize the number of cellular transactions and the amount of data pushed across the cellular modem.
5.3.2 Solar Components
The components of a solar system include the battery and the solar panel.
Config > I/O Board > Charger. Use the up/down arrows to select Solar.
ON position on the processor board then reboot.
devices when possible.
Battery
The DXM solar controller is designed to use a 12 V lead acid battery. The characteristics of a solar system require the
battery to be of a certain type. There are basically two types of lead acid batteries:
• SLI batteries (Starting Lights Ignition) designed for quick bursts of energy, like starting engines
• Deep Cycle batteries - greater long-term energy delivery. This is the best choice for a solar battery.
Since a solar system charges and discharges daily, a deep cycle battery is the best choice. There are different versions of a
lead acid battery: wet cell
(flooded), gel cell, and an AGM (absorbed glass mat).
Page 27
DXM150-Sx Wireless Modbus Slave
Wet cell batteries are the original type of rechargeable battery and come in two styles, serviceable and maintenance free.
Wet cell batteries typically require special attention to ventilation as well as periodic maintenance but are the lowest cost.
The gel cell and AGM battery are sealed batteries that cost more but store very well and do not tend to sulfate or degrade
as easily as a wet cell. Gel or AGM batteries are the safest lead acid batteries you can use.
Battery Capacity
Battery capacity is a function of the ambient temperature and the rate
of discharge. Depending upon the specific battery, a battery operating
at –30 °C can have as much as 40 percent less capacity than a battery
operating at 20 °C. Choose enough battery capacity based on your
geographical location.
A larger capacity battery typically lasts longer for a given solar
application because lead-acid batteries do not like deep cycling
(discharging a large percentage of its capacity). Depending upon the
battery, a battery discharging only 30 percent of its capacity before
recharging will have approximately 1100 charge/discharge cycles. The
same battery discharging 50 percent of its capacity will have
approximately 500 charge/discharge cycles. Discharging 100 percent
leaves the battery with only 200 charge/discharge cycles.
Batteries degrade over time based on discharge/charge cycles and
environmental conditions. Always monitor the battery system to obtain
the best performance of the solar powered system.
Use this as a guide to the approximate state of
charge and in determining when to apply
conservation measures.
Average Voltage Readings Relative to Battery
Change
State of Charge (%)Open Circuit Voltage
10013.0 or higher
7512.6
5012.1
2511.66
011.4 or less
Solar Panel
Banner solar panels come in two common sizes for the DXM Modbus Slave: 5 Watt and 20 Watt. Both panels are designed
to work with the DXM Modbus Slave but provide different charging characteristics. Use the 5 watt panel for light duty
operation and use the 20 watt panel when you require greater charging capabilities.
Solar PanelVoltageCurrentTypical DXM Configurations
5 Watt17 V0.29 ADXM slave controller, ISM radio, I/O base board
20 Watt21 V1 ADXM Controller with ISM radio and Cellular modem
Photovoltaic panels are very sensitive to shading. Unlike solar thermal panels, PV solar panels cannot tolerate shading from
a branch of a
leafless tree or small amounts of snow in the corners of the panel. Because all cells are connected in a series
string, the weakest cell will bring down the other cells' power level.
Good quality solar panels will not degrade much from year to year, typically less than 1 percent .
Solar Panel Mounting
To capture the maximum amount of solar radiation throughout the year, mount a fixed solar panel to optimize the sun's
energy throughout the year. For the northern hemisphere, face the panel true south. For the southern hemisphere, face the
panel true north. If you are using a compass to orientate the panels, compensate for the difference between true north and
magnetic north. Magnetic declination varies across the globe.
A solar panel's average tilt from horizontal is at an angle equal to the latitude of the site location. For optimum performance,
adjust the tilt by plus 15 degrees in the winter or minus 15 degrees in the summer. For a
fixed panel with a consistent power
requirement throughout the year, adjust the tilt angle to optimize for the winter months: latitude plus 15 degrees. Although in
the summer months the angle may not be the most
efficient, there are more hours of solar energy available.
For sites with snow in the winter months, the increased angle helps to shed snow. A solar panel covered in snow produces
little or no power.
5.3.3 Recommended Solar Configurations
These solar panel and battery combinations assume direct sunlight for two to three hours a day. Solar insolation maps
provide approximate sun energy for various locations. The depth of battery discharge is assumed to be 50 percent.
Solar panel and battery combinations for a DXM Modbus Slave system
Solar PanelBattery Capacity
5 watt10 Ahr10 days25 mADXM Slave Controller - ISM radio and I/O base board
20 watt14 Ahr10 days30 mADXM Controller with ISM radio
20 watt20 Ahr10 days35 mADXM Controller with ISM radio and Cellular Modem
4
Days of AutonomyDXM mADXM Controller
5.3.4 Monitoring Solar Operation
The DXM solar controller provides Modbus registers that allow the user to monitor the state of the solar panel input voltage,
the battery voltage, the charging current, and the temperature in °C. The DXM Modbus Slave can be configured to monitor
the health of the charging system as well as send an alert message when the battery is too low.
The charts show a typical charging cycle, with each vertical grid representing about eight hours. The chart shows three
days of charging.
Figure 6. Solar Panel Voltage (mV) -- Cloudy First Day
Figure 7. Battery Voltage (mV) - Cloudy First Day
5.4 Connecting the Communication Pins
The base board communications connection for external Modbus device uses the primary RS-485.
RS-485. The primary RS-485 bus is a common bus shared with the ISM radio board (Modbus Slave ID 1).
RS-232. The RS-232 bus is not currently
PinParameterDescription
Pin 6Primary RS-485 –Running Modbus protocol at 19.2k baud, use this bus to connect to other Modbus Slave devices.
Pin 7Primary RS-485 +
defined.
The DXM150-Sx Wireless Modbus Slave is a Modbus Master device on this RS-485 port.
Modbus Register 6101 = Baud Rate
0 = 19.2k
1 = 9600
2 = 38400
Modbus Register 6103 = Parity
0 = no parity
1 = odd?
2 = even?
4
Battery capacity (amp hour) is standard amp rating taken for 20 hours. Battery capacity should be monitored for reliable system power and may
need to be increased for cold weather locations.
Serial RS-232 connection. This bus must use a ground connection between devices to operate
correctly.
Not used
5.5 Inputs and Outputs
The I/O base board is a Modbus slave device that communicates using Modbus commands. Refer to the Modbus Registers
section for more descriptions of each Modbus register on the DXM150-Sx Wireless Modbus Slave.
5.5.1 Universal Inputs
The universal inputs can be programmed to accept different types of inputs: discrete NPN/PNP, 0 to 20 mA analog, 0 to 10
V analog, 10k thermistor, potentiometer sense, bridge, and NPN raw fast. Use the DXM
the appropriate Modbus registers in the I/O board to
configure the input type.
The universal inputs are treated as analog inputs. When the universal inputs are defined as mA, V, or temperature, use
Modbus registers to configure the operational characteristics of the inputs. These parameters are temperature conversion
type, enable full scale, threshold and hysteresis. See the Modbus register section for the parameter
When a universal input is configured as an NPN or PNP input type, it can be enabled to be a synchronous counter. Enable
the counter function by setting Modbus register 'Enable Rising' or 'Enable Falling' to 1. See
universal input register
definitions.
Configuration Tool tool to write to
definitions.
Modbus Registers
for the
Pin
Pin 47Universal Input 1Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to
Pin 46Universal Input 2
Pin 43Universal Input 3
Pin 42Universal Input 4
Pin 40Universal Input 5
Pin 39Universal Input 6
Pin 38Universal Input 7
Pin 37Universal Input 8
Univ. InputDescription
20 mA, or potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the
following values to the Input Type Modbus registers.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Thermistor Input. A thermistor input must use a 10k thermistor between ground and the universal input. The thermistor must
be a 10k NTC (Banner model number BWA-THERMISTOR-002) or equivalent. Select the temperature conversion of degrees
C (default) or degrees F by writing to the Modbus registers
defined in
I/O Base Board
.
Potentiometer Sense (DXM150 only). A potentiometer input is created from two inputs: a voltage source (pin 45) that
supplies a voltage to the potentiometer and an input sense (Potentiometer Sense) to read the resistance. Follow
Change Universal Input 8 to Read a Potentiometer Input
on page 18 to configure the DXM150 Controller for a potentiometer
Example:
input.
Potentiometer Input (DXM100 only). A potentiometer input is created from three inputs: a voltage source (pin 30) that
supplies 5 V to the potentiometer and two inputs set to voltage inputs to read the voltage across the potentiometer. See the
DXM technical note for setting up a potentiometer.
Bridge Input. The bridge input is not implemented yet.
NPN vs NPN Raw Fast. The difference between NPN and NPN Raw Fast is the amount of settling time given to the input.
Switch the input type to NPN if the input is not detecting a transition.
Example: Configure Input 1 as a Synchronous Counter
1. Connect the DXM Modbus Slave to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Modbus Slave by selecting the Device > Connection Settings menu option. You may connect
using either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. In the Write Registers area, write Modbus register 4908 to 1 to enable counting on the rising edge of the input
signal.
8. Read Modbus registers 4910 and 4911 to get the 32-bit value of the count.
Example: Change Universal Input 2 to a 0 to 10 V dc Input
1. Connect the DXM Modbus Slave to the PC.
2. Launch the DXM
3. Connect to the DXM Modbus Slave by selecting the Device > Connection Settings menu option. You may connect
using either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Write a 3 to Modbus register 3326 on Modbus Slave ID 11 (I/O board).
8. Cycle power to the device.
9. Using the Register View tab, read register 3326 to verify it is set to 3.
Configuration Tool software.
Example: Change Analog Output 1 to a 0 to 10 V dc Output
1. Connect the DXM Modbus Slave to the PC.
2. Launch the DXM
Configuration Tool software.
3. Connect to the DXM Modbus Slave by selecting the Device > Connection Settings menu option. You may connect
using either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Set jumper 1 on the I/O base board to the 0 to 10 V position. Refer to the base board image for the analog output
jumper position.
8. Write a 3 to Modbus register 4008 on Modbus Slave ID 11 (I/O board).
9. Cycle power to the device.
10. Using the Register View tab, read register 4008 to verify it is set to 3.
Example: Change Universal Input 8 to Read a Potentiometer Input
Figure 8. Default jumper position
1. Launch the DXM Configuration Tool tool.
2. Click on the Register View tab on the left part of the page.
3. In the upper right part of the window select Modbus Registers using Modbus Slave ID radio button and enter
Modbus Slave ID 11.
4. To set universal input 8 as the sense, write Modbus register 3446 with 5 (Potentiometer Sense).
5. Verify the jumpers are still set to their default position. One jumper should be on pins 1 and 3 to get a 2.7 V source
voltage out pin 45. The default position of the other jumper is on pins 4 and 6.
6. Connect one potentiometer side to power output (pin 45), connect the tap point of the pot to universal input 8 (pin
37), and connect the other end of the pot to ground (pin 36).
5.5.2 PNP and NPN Outputs
PinOutputModbus
Register
191501PNP/NPN Output 1
202502PNP/NPN Output 2
213503PNP/NPN Output 3
224504PNP/NPN Output 4
305505PNP/NPN Output 5
296506PNP/NPN Output 6
287507PNP/NPN Output 7
278508PNP/NPN Output 8
DescriptionPNP OUT WiringNPN OUT Wiring
5.5.3 Analog Outputs (DAC)
The following characteristics are
PinOutputDescription
Pin 33Analog Output 10 to 20 mA or 0 to 10 V dc output (I/O board jumper selectable)
Pin 32Analog Output 2
configurable for each of the analog outputs.
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
Parameters for Analog Output 1 start at 4001 through 4008. Parameters for Analog Output 2 start at 4021 through 4028.
OUT 1OUT 2Parameters
40014021Maximum Analog Value
40024022Minimum Analog Value
40034023Enable Register Full Scale
40044024Hold Last State Enable
40054025Default Output State
40084028Analog Output Type
Analog Output Type. The analog outputs may be configured as either 0 to 20 mA outputs (default) or 0 to 10 V outputs. To
change the analog output type change the hardware jumper position and write to the Modbus register that defines the
analog output type. For analog output 1, write to Modbus register 4008, for analog output 2 write to Modbus register 4028.
Write a value of 2 (default) to select 0 to 20 mA; write a value of 3 to select 0 to 10 V.
Default Output Conditions. Default output conditions/triggers are the conditions that drive outputs to
Example default output conditions include when radios are out of sync, when a device cycles power, or during a host
communication timeout.
• 2952 Enable Default Communication Timeout. A “communication timeout" refers to the communication between any
Modbus master host and the DXM baseboard. Set this register to 1 to enable the default condition when the host
has not communicated with the DXM baseboard for the period of time
Timeout.
• 2953 Communication Default I/O Timeout (100 ms/Count). This parameter defines the host timeout period in 100
millisecond increments. If a host does not communicate within this timeout period, the device outputs are set to the
default values.
• 2954 Enable Default on Power Up. Setting this parameter to 1 sends the device outputs to their default condition
when the DXM baseboard is powered up. Set to 0 to disable this feature.
Default Output State. The Default Output State parameter represents the default condition of the analog output. When an
error condition exists, the outputs are set to this 16-bit user-defined output state. To define the error conditions for device
outputs, refer to the MultiHop default output parameters 2950-2954.
Enable Register Full Scale. Set to 1 to enable a linear range from 0 to 65535 for
specified input range. For a 4 to 20 mA
output, a value of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store readings in unit-specific
data. For example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA outputs),
values are stored as µA (micro Amps) and voltage values are stored as mV (millivolts).
Hold Last State Enable. Set the Hold Last State to 1 to set the output to its last known value before the error occurred. Set
this parameter to 0 to disable the Hold Last State and use the Default Output State setting during an error condition.
Maximum Analog Value. The Maximum Analog Value register stores the maximum allowed analog value. The
specific units
of measure apply to the register value. For example, the register may contain 20000, for 20 mA, or for a voltage output the
register may contain 8000, for 8 volts.
Minimum Analog Value. The Minimum Analog Value register stores the minimum allowed analog value. The
specific units of
measure apply to register value. For example, the register may contain 4000, for 4 mA, or for a voltage output the register
may contain 2000, for 2 volts.
5.5.4 Isolated Discrete Inputs
PinInputDescription
Pin 14Input 1A
Pin 15Input 1B
Pin 16Input 2A
Optically isolated AC input type, 0 to 12 to 30 V dc
Input to output isolation of 2.5 kV
Pin 17Input 2B
Synchronous Counters. An isolated input can be programmed to count the input signal transitions. When an input is
enabled as a counter, the counter value is stored into two 16-bit Modbus registers for a total count of 32-bits (unsigned). To
program an input to capture the edge transition counts, follow
Example: Configure Input 1 as a Synchronous Counter
on
page 18.
The counters are synchronous because the inputs are sampled at a 10 ms clock rate. The input logic does not detect rising
or falling edges, it samples the input every 10 ms to
find level changes. The input signals must be high or low for more than
10 ms or the input will not detect transitions. Because most signals are not perfect, a realistic limit for the synchronous
counter would be 30 to 40 Hz.
Universal inputs can also be configured as a synchronous counter. See the Modbus register map for universal inputs and all
the register
definitions. The procedure for creating a synchronous counter is the same as a isolated input with the addition
of changing the input type to PNP or NPN.
Discrete Inputs
Input 1
Input 2
Modbus Registers for Counter
Parameters
3013Enable Rising
3014Enable Falling
3015Counter High
3016Counter Low
3033Enable Rising
3034Enable Falling
3035Counter High
3036Counter Low
Register Definitions
5.5.5 Modbus Registers
The DXM MultiHop Modbus Slave device can have two Modbus Slave IDs: one for the MultiHop ISM radio (default 1) and
one for the I/O base (default to 11). All Modbus registers are defined as 16-bit Modbus Holding Registers. When connecting
additional Modbus slave devices, only use Modbus slave IDs 2 through 198.
The DXM Configuration Tool creates a graphical view of the I/O board parameters. This allows for easy and quick
configuration of the I/O board parameters. Modbus configuration registers are identified below.
RegisterIsolated Input A
3013Enable rising edge counter
3014Enable falling edge counter
3015High register for counter
3016Low register for counter
RegisterIsolated Input A
3033Enable rising edge counter
3034Enable falling edge counter
3035High register for counter
3036Low register for counter
Universal Input Parameter Modbus Registers
Universal Inputs12345678
Enable Full Scale33033323334333633383340334233443
Temperature °C/°F33043324334433643384340434243444
Input Type33063326334633663386340634263446
Threshold33083328334833683388340834283448
Hysteresis33093329334933693389340934293449
Enable Rising49084928494849684988500850285048
Enable Falling49094929494949694989500950295049
High Register for Counter49104930495049704990501050305050
Low Register for Counter49114931495149714991501150315051
Enable Full Scale. Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA input, a value
of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store input readings in
unit-specific data. For
example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA inputs), values are
stored as µA (micro Amps) and voltage values are stored as mV (millivolts).
Enable Rising/Falling. Use these registers to enable the universal input logic to count on a rising transition or a falling
transition. Write a one (1) to enable; write a zero (0) to disable.
High/Low Register for Counter. The low and high registers for the counter hold the 32-bit counter value. To erase the
counter, write zeroes to both registers. To preset a counter value, write that value to the appropriate register.
Hysteresis and Threshold. Threshold and hysteresis work together to establish the ON and OFF points of an analog input.
The threshold
defines a trigger point or reporting threshold (ON point) for a sensor input. Setting a threshold establishes an
ON point. Hysteresis defines how far below the threshold the analog input is required to be before the input is considered
OFF. A typical hysteresis value is 10% to 20% of the unit’s range.
In the example shown, the input is considered on at 15 mA. To consider
the input off at 13 mA, set the hysteresis to 2 mA. The input will be
considered off when the value is 2 mA less than the threshold.
Input Type. Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to 20 mA, or
potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the following values to the Input Type
Modbus registers.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Temperature °C/°F. Set to 1 to represent temperature units in degrees Fahrenheit, and set to 0 (default) to represent
temperature units in degrees Celsius.
Universal Input Register Ranges
Register TypesUnitMinimum ValueMaximum Value
Discrete input/output01
Universal input 0 to 10 VmV010000 *
Universal input 0 to 20 mAµA020000 *
Universal input temperature (–40 °C to +85 °C)C or F, signed, in tenths of a degree–400850
Universal potentiometerunsigned065535
* Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.
5.6 Setting the Modbus Slave ID on the I/O Base Board
Only DXM150-Sx and SxR2 Modbus Slave models require that the Modbus Slave ID to be adjusted on the I/O base board.
The DXM150-Sx Wireless Modbus Slave devices use DIP switch J and rotary dial K to set the Modbus slave ID. The device
can use a Modbus register 6804 in the I/O board to access the full range of Modbus Slave IDs.
On the DXM150-Sx Wireless Modbus Slave models, use rotary dial K to select the lower digit of the Modbus Slave ID.
5.6.1 DXM150-Sx Wireless Modbus Slave Models
DIP Switch location J
DXM1xx-SxR2 models.
defines the course group of Modbus Slave IDs. DIP Switch 4 must be set to ON for DXM1xx-Sx and
Settings
Modbus Slave ID set to 11 through 19OFFOFF
Modbus Slave ID set to 20 through 29ONOFF
Modbus Slave ID set to 30 through 39OFFON
Modbus Slave ID set to 40 through 49ONON
Not Used-
Modbus Slave Configuration (S1 model only)
I2C Processor CommunicationOFF
5
1234
Location J DIP Switches
Rotary dial location K and DIP Switch location J set the Modbus Slave IDs.
DIP Switches JLocation K Rotary Dials — Position 0 through 9
120123456789
OFFOFFx
ONOFF20212223242526272829
OFFON30313233343536373839
ONON40414243444546474849
6
111213141516171819
ON
DXM150-Sx Wireless Modbus Slave Example
To set the DXM150-Sx Wireless Modbus Slave to a Modbus Slave ID of 25, set the following:
Location J DIP switches set to: 1= ON, 2=OFF
Rotary dial set to 5
The DIP switch sets the upper digit of the slave ID to 2 while the rotary dial sets the lower digit to 5.
5.6.2 Setting the DXM I/O Board Modbus Slave ID using Modbus Registers
Write to the I/O board's Modbus register 6804 to set the Modbus Slave ID to any valid Modbus Slave ID (1 through 245).
• For the DXM150-Sx Wireless Modbus Slave model, rotary dial K should be in the zero position to use the Modbus
register slave ID.
5.7 Restoring Factory Default Settings
To reset to factory defaults, write to two Modbus registers in the I/O board. The default slave ID for the I/O board is 11.
To reset the DXM I/O board parameters:
To reset to factory defaults, write to two Modbus registers in the I/O board. The default slave ID for the I/O board is 11.
To reset the DXM I/O board parameters:
1. Write a 1 to Modbus register 4152
2. Write a 10 to Modbus register 4151
To reset only the I/O board:
1. Write a 0 to Modbus register 4152
2. Write a 10 to Modbus register 4151
Modbus RegisterValuesDescription
41510–255Reset/restore trigger. This timer is based in 100 millisecond units. Once written, the timer starts to count down to
41520–11 = Restores factory defaults for I/O parameters.
zero. After the timer expires, the restore factory defaults are applied if register 4152 = 1. If register 4152 is zero, the
I/O board is reset.
For a complete list of all the accessories for the Sure Cross wireless product line, please download the
b_3147091)
Accessories List
(p/n
Cordsets
MQDC1-506—5-pin M12/Euro-style, straight, single ended, 6 ft
MQDC1-530—5-pin M12/Euro-style, straight, single ended, 30 ft
MQDC1-506RA—5-pin M12/Euro-style, right-angle, single ended, 6 ft
MQDC1-530RA—5-pin M12/Euro-style, right-angle, single ended, 30 ft
Static and Surge Suppressor
BWC-LFNBMN-DC—Surge Suppressor, bulkhead, N-Type, dc
Blocking, N-Type Female, N-Type Male
Short-Range Omni Antennas
BWA-2O2-D—Antenna, Dome, 2.4 GHz, 2 dBi, RP-SMA Box Mount
BWA-9O2-D—Antenna, Dome, 900 MHz, 2 dBi, RP-SMA Box Mount
BWA-9O2-RA—Antenna, Rubber Fixed Right Angle, 900 MHz, 2 dBi,
RP-SMA Male Connector
Medium-Range Omni Antennas
BWA-9O5-C—Antenna, Rubber Swivel, 900 MHz 5 dBi, RP-SMA Male
Connector
BWA-2O5-C—Antenna, Rubber Swivel, 2.4 GHz 5 dBi, RP-SMA Male
Connector
—Enclosure, Polycarbonate, with Opaque Cover, 8 × 6 ×
—Enclosure, Polycarbonate, with Opaque Cover, 10 × 8
—Enclosure, Polycarbonate, with Opaque Cover, 12 ×
Misc Accessories
BWA-CG.5-3X5.6-10—Cable Gland Pack: 1/2-inch NPT, Cordgrip for 3
holes of 2.8 to 5.6 mm diam, qty 10
BWA-HW-052— Cable Gland and Vent Plug Pack: includes 1/2-inch
NPT gland, 1/2-inch NPT multi-cable gland, and 1/2-inch NPT vent
plug, qty 1 each
Antenna Cables
BWC-1MRSMN05—LMR100 RP-SMA to N-Type Male, 0.5 m
BWC-2MRSFRS6—LMR200, RP-SMA Male to RP-SMA Female, 6 m
BWC-4MNFN6—LMR400 N-Type Male to N-Type Female, 6 m
• EIP Configuration File for DXM 1xx-BxR1 and R3 models (p/n
• Activating a Cellular Modem (p/n
• Additional technical notes and videos
Technical notes, configuration examples, and ScriptBasic program examples are available at
www.bannerengineering.com
www.bannerengineering.com/wireless
194063
160171
200634
191745
b_4447978
Configurationfile
for Allen-Bradley PLCs
b_4419353
.
)
.
178136
195952
195455
191247
)
158447
190038
194730
)
http://
9.2 DXM Modbus Slave Support Policy
The DXM Wireless Controllers are industrial wireless controllers that facilitate Industrial Internet of Things (IIoT) applications.
As a communications gateway, it interfaces local serial ports, local I/O ports, and local ISM radio devices to the Internet
using either a cellular connection or a wired Ethernet network connection. In a continuing effort to provide the best
operation for the DXM Modbus Slave, stay connected with Banner Engineering Corp to hear about the latest updates
through the Banner website. Create a login today to stay informed of all Banner product releases.
9.2.1 Firmware Updates
The DXM Modbus Slave has been designed to be a robust and secure IOT device. To provide the most reliable and secure
device possible, periodic
Firmware updates and description details are found on the Banner website. Customers with critical update requirements will
get access to pre-released
9.2.2 Website Information
The Banner website is the main method of disseminating DXM Modbus Slave information to customers. The data found on
the website include:
• DXM instruction manuals
•
Configuration manuals
• Firmware downloads
• Firmware release notes
• Errata data, any known issues with a release of
• Possible work-around solutions for known issues
• DXM Solutions Guides
9.2.3 Feature Requests
Our customer is our most valuable resource to improve our DXM Modbus Slave. If you have suggestions for improvements
to the DXM Modbus Slave or configuration tools, please contact Banner Engineering Corp.
firmware updates are released to enhance and expand the capabilities of the DXM Modbus Slave.
firmware from the factory.
firmware
9.2.4 Potential DXM Issues
Potential issues with the DXM Modbus Slave are collected from Banner's support engineers to provide solutions. Users can
get help from the website documentation or by calling Banner Engineering for support help. Solutions are as simple as
configuration adjustments, work-around configuration solutions, or potential new firmware updates.
The DXM Modbus Slave was designed to collect local wireless sensor data, local sensor data, provide simple control, and
send the data to the cloud.
TheDXM Modbus Slave does not run a Linux or Windows based operating system but an embedded RTOS environment. As
a proprietary operating system, the security aspects are easier to manage and minimize.
Security updates are released through the Banner website and New Product Release Announcements (NPRA).
9.3 Contact Us
Corporate Headquarters
Address:
Banner Engineering Corporate
9714 Tenth Avenue North
Minneapolis, Minnesota 55441, USA
Europe
Address:
Banner Engineering EMEA
Park Lane, Culliganlaan 2F, bus 3
1831 Diegem, Belgium
Turkey
Address:
Banner Engineering Elk. San. Ve Tic. Ltd. Şti.Şerifali Mah. Münevver Sok. Ekomed Plaza No:10 Kat:4
Ümraniye / İstanbul, Türkiye
India
Address:
Banner Engineering India Pune Head Quarters
Office No. 1001, 10th Floor Sai Capital, Opp. ICC Senapati Bapat Road
Pune 411016, India
Mexico
Phone: +1 763 544 3164
Website:
www.bannerengineering.com
Phone: +32 (0)2 456 0780
Website:
www.bannerengineering.com
Email: mail@bannerengineering.com
Phone: +90 216 688 8282
Website:
www.bannerengineering.com
Email: turkey@bannerengineering.com.tr
Phone: +91 (0) 206 640 5624
Website:
www.bannerengineering.com
Email: salesindia@bannerengineering.com
Address:
Banner Engineering de Mexico Monterrey Head OfficeEdificio VAO Av. David Alfaro Siqueiros No.103 Col. Valle Oriente C.P.66269
San Pedro Garza Garcia, Nuevo Leon, Mexico
Brazil
Address:
Banner do Brasil
Rua Barão de Teffé nº 1000, sala 54
Campos Elíseos, Jundiaí - SP, CEP.: 13208-761, Brasil
China
Address:
Banner Engineering Shanghai Rep Office
Xinlian Scientific Research Building Level 12, Building 2
1535 Hongmei Road, Shanghai 200233, China
Install and properly ground a qualified surge suppressor when installing a remote antenna system. Remote antenna configurations installed without surge suppressors
invalidate the manufacturer's warranty. Keep the ground wire as short as possible and make all ground connections to a single-point ground system to ensure no ground loops
are created. No surge suppressor can absorb all lightning strikes; do not touch the Sure Cross® device or any equipment connected to the Sure Cross device during a
thunderstorm.
Exporting Sure Cross® Radios. It is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers who want to re-export
this product to a country other than that to which it was sold must ensure the device is approved in the destination country. A list of approved countries appears in the
Certifications
using other antennas, verify you are not exceeding the transmit power levels allowed by local governing agencies. Consult with Banner Engineering Corp. if the destination
country is not on this list.
section of the product manual. The Sure Cross wireless products were certified for use in these countries using the antenna that ships with the product. When
10.1 Banner Engineering Corp. Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will
repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This
warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING
OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE
LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR
SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR
WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product
previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection
applications when the product is